For the voltmeter, when VPOL = VH - VX the transformer functions with subtractive
polarity and terminals A and B would be labeled X1 to X2, respectively. Conversely,
when VPOL = VH + VX the transformer has additive polarity and terminals B and A would
be labeled X1 to X2, respectively as polarity terminals are diagonally opposite each
other.
The AC Polarity test method can be conveniently made during the Transformer Ratio
test. The methodology used to check ratio include the Voltage method and the
Transformer Turns Ratio (TTR) test set. The test is used to check nameplate voltage
values for the range of taps on the transformer.
8.8.4 RATIO AND POLARITY VOLTMETER TEST OF TWO-WINDING
TRANSFORMERS
The circuit for making ratio and polarity tests of a two-winding transformer is shown in
Fig. 50.