BOILER
PROTECTION
AND
INTERLOCKS
CONCEPT OF BOILETR
PROTECTION AND
INTERLOCKS
PROTECTION
Whenever the boiler safety is
threatened cutting off all fuel
supply to boiler to avoid damage
to boiler
INTERLOCKS
Ensure safe sequential
operation of
various
systems and components
Trip individual equipment incase
of abnormalities
BOILER PROTECTION
ABNORMA
L
OPERATIN
G
ENERGISE
MASTER
FUEL
TRIP
RELAY
CLOSE ALL
OIL TRIP
VALVES AND
NOZZLE
VALVES
TRIP ALL R.C
FEEDERS AND
MILLS
TRIP ALL
P.A.FANS
CONDITIO
N
03/05/15
S.VISWANATHAN
ABNORMAL OPERATING
CONDTIONS CAUSING BOILER
TRIP
Loss of power supply to BMS / FSSS
Less than fire ball and loss of A.C. at
any elevation in service
Loss of all fuel trip
Flame failure trip
Very very low drum water level
Very very high drum water level
Furnace pressure very very high
Furnace vacuum very very high
03/05/15
S.VISWANATHAN
ABNORMAL OPERATING
CONDTIONS CAUSING BOILER
TRIP
Both I.D. fans tripped
Both F.D. fans tripped
Airflow less than 30% and boiler load
less than 30%
Re heater protection
Both trip push buttons on console
pressed simultaneously
Generator tripping on electrical
protection
Excessive turbine axial shift
Very very low turbine L.O pressure
03/05/15
S.VISWANATHAN
LOSS OF ALL FUEL TRIP
This protection shall act only
after once a minimum of 3
ignitors have been put on at
any elevation and if all the
following conditions occur
All R.C.feeders are off
Either IOTV is not open or
more than one of IONVs are
not open at all oil elevations
Either HOTV is not open or
more than one of HONV s are
not open at all oil elevations
Either LOTV is not open or
more than one of LONV s are
not open at ab elevation
AC supply to FSSS is available
03/05/15
S.VISWANATHAN
INTERLOCKS COVERED UNDER FSSS
LOGIC
PURGE INTERLOCKS
INTERLOCKS FOR FUEL OIL VALVES
IGNITOR OIL TRIP VALVE
WARMUP OIL TRIP VALVE
HEAVY OIL TRIP VALVE
HEAVY OIL RE-CIRCULATION VALVE
INTERLOCKS FOR PULVERISERS
INTERLOCKS FOR R.C. FEEDERS
INTERLOCKS FOR SY. AIR CONTROL
AUXILIARY AIR DAMPERS
FUEL AIR DAMPERS
INTERLOCKS FOR SCANNER AIR FANS
INTERLOCKS FOR IGNITOR AIR FANS
------------------------------------------------------------
03/05/15
S.VISWANATHAN
03/05/15
S.VISWANATHAN
PURGE INTERLOCKS
FURNACE PURGING CAN BE STARTED
ONLY IF THE FOLLOWING PERMISSIVES
ARE SATISFIED
ALL OIL TRIP VALVES AND NOZZLE
VALVES ARE PROVEN CLOSED
ALL THE PULVERISERS AND FEEDERS
ARE OFF
ALL THE HOT AIR GATES ARE FULLY
CLOSED AND THE COLD AIR DAMPERS
ARE LESS THAN 5% OPEN
ALL THE ELEVATION FLAME SCANNERS
SHOW NO FLAME
ATLEAST ONE ID&FDFANS ARE IN
SERVICE AND THE AIR FLOW IS 30% OF
FULL LOAD AIR FLOW
ALL AUXILIARY AIR DAMPERS ARE
MODULATING TO MAINTAIN AN
ADEQUATE WIND BOX TO FURNACE
DIFFERENTIAL PRESSURE
NONE OF THE BOILER TRIP CONDITIONS
EXIT
--------------------------------
03/05/15
S.VISWANATHAN
PURGE
PUSH TO
READY
PURGE
PURGE
PURGE
ON
COMPLETE
IGNITOR OIL TRIP VALVE
OPENING PERMISSIVES
IGNITOR OIL SUPPLY PRESSURE IS ADEQUATE
(12.5KSC)
ALL THE I.O. NOZZLE VALES ARE PROVEN CLOSED
NONE OF THE BOILER TRIP COMMANDS IS PRESENT
PURGE IS COMPLETED
THIS VALVE WILL CLOSE AUTOMATICALLY UNDER
ANY OF THE FOLLOWING CONDITIONS
BOILER TRIPS
IGNITOR OIL HEADER PRESSURE IS LOW (9.1 KSC) FOR
MORE THAN 2 SEC. AND ANY I.0 N.V. IS NOT CLOSED
-----------------------------------------------------------------------------
03/05/15
S.VISWANATHAN
10
03/05/15
S.VISWANATHAN
11
WARMUP OIL TRIP VALVE
OPENING PERMISSIVES
W.O. SUPPLY PRESURRE IS ADQUATE (5.6KSC)
ALL W.O NOZZLE VALVES ARE CLOSED
NO BOILER TRIP IMPULSE IS PRESENT
PURGE IS COMPLETED
THIS VALVE WILL CLOSE AUTOMATICALLY UNDER
ANY OF THE FOLLOWING CONDITIONS.
BOILER TRIP OCCURS
W.O. HEADER PRESSURE IS LOW(1.5KSC) FOR MORE
THAN 2 SEC. AND ANY W.O.N.V. IS NOT CLOSED
D.P. BETWEEN W.O. AND ATOMISING AIR IS LOW
(O.4KSC) FOR MORE THAN 2 SEC., WHEN NO PAIR OF
W.O. GUNS ARE IN START UP OR SHUT DOWN AND
ANY W.O. N.V. IS NOT CLOSED.
03/05/15
S.VISWANATHAN
12
HEAVY OIL TRIP VALVE
OPENING PERMISSIVES
HEAVY OIL HEADER PRESSURE IS ADEQUATE(9.8KSC)
ALL HEAVY OIL NOZZLE VALVES ARE CLOSED
NO BOILER TRIP CONDITION EXISTS
PURGE COMPLETE
THIS VALVE WILL CLOSE AUTOMATICALLY UNDER
ANY ONE OF THE FOLLOWING CONDITIONS
BOILER TRIP OCCURS
H.O. HEADER PRESSURE IS LOW (1.5KSC) FOR MORE
THAN 2SEC. WHEN ANY H.O. NOZZLE VALVE IS NOT
CLOSED.
D.P. BETWEEN H.O. AND ATOMIS ING STEAM IS
LOW (0.4KSC) FOR MORE THAN 2 SEC. WHEN ANY
H.O. NOZZLE VALVE IS NOT CLOSED, AND NO H.O.
GUN IN START/STOP CONDITION.
H.O. TEMP. LOW (105oC) FOR MORE THAN 2 SEC.
WHEN ANY H.O. NOZZLE VALVE IS NOT CLOSED.
03/05/15
S.VISWANATHAN
13
HEAVY OIL RE-CIRCULATION
VALVE
THIS VALVE CAN BE OPENED PROVIDED
THE H.O. TRIP VALVE AND ALL H.O.
NOZZLE VALVES ARE CLOSED. THIS VALVE
WILL CLOSE AUTOMATICALLY WHEN ANY
OF THE H.O. NOZZLE VALVE IS NOT
CLOSED.
HOTV
R.C.VALVE
NRV
03/05/15
S.VISWANATHAN
14
WARMUP FUEL ON-OFF CONTROL &
SUPERVISION
START-STOP CONTROL
SELECTION OF WARMUP OIL/HEAVY OIL
PERMISSIVES
ALL THE W.U. OIL ANDH.O. NOZZLE VALVES ARE
PROVEN CLOSED IN AB ELEVATION
BOTH PAIR AT THAT ELEVATION HAVE BEEN
SHUT DOWN
STARTING THE ELEVATION
PERMISSIVES
D.C. POWER AVAILABLE
IGNITOR OIL TRIP VALVE FULLY OPEN
WARMUP, OIL TRIP VALVE FULLY OPEN
ANY FEEDER ON OR NOZZLE TILT HORIZONTAL
WITH AIR FLOW ADJUSTED BETWEEN 30 TO 40%
03/05/15
S.VISWANATHAN
15
WARMUP FUEL ON-OFF CONTROL &
SUPERVISION (CONTD.)
IF PERMISSIVES ARE
SATISFIED ELEVATION IS
STARTED IN PAIR BASIS
BY PUSH BUTTONS
INITIATE 90SEC. TRIAL
TIME.
CORNER RECEIVES START
COMMAND
STOPPING THE
ELEVATION
INITIATED BY A STOP
SIGNAL
03/05/15
INDIVIDUAL CORNER
RECEIVES A STOP
COMMAND WITH A TRIAL
TIME OF 375 SEC. 16
S.VISWANATHAN
WARMUP FUEL ON-OFF CONTROL &
SUPERVISION (CONTD.)
CORNER MONITORING
INDIVIDUAL CORNER WILL
BE PUT INTO SERVICE
PERMISSIVES
THE CORNER START
IMPULSE IS GIVEN
LOCAL MAINTENANCE
SWITCH IN REMOTE
POSITION
MANUAL ISOLATION VALVES
OF OIL AND ATOMISING
MEDIUM ARE OPEN
SCAVANGE VALVE CLOSED
GUN IS ENGAGED
RESPECTIVE IGNITOR IS IN
SERVICE*
03/05/15
S.VISWANATHAN
17
WARMUP FUEL ON-OFF CONTROL &
SUPERVISION
INDIVIDUAL CORNER WILL TRIP UNDER
CONDITIONS
ASSOCIATED LOCAL MAINTENANCE CONTROL
SWITCH TURNED OFF
CLOSING THE W.U. OIL OR ATM. MEDIUM
MANUAL ISOLATION VALVES
ASSOCIATED IGNITOR IS OFF*
W.U.OIL GUN NOT ADVANCED*
*IGNITOR TRIP VALVE CLOSURE*
*W.U. TRIP VALVE CLOSURE
*LOSS OF UNIT D.C. POWER (2 SEC. TIME DELAY)
*BOILER TRIP
03/05/15
S.VISWANATHAN
18
OIL ELEVATION STARTING SEQUENCE
(WITH EDDYPLATE IGNITORS)
STARTED IN PAIRS (1,3), (2,4)
DEPRESSING ONE PAIR START PUSH BUTTON WILL
INITIATE 90 SEC. START TIME TRIAL IF PERMISSIVES
ARE SATISFIED.
IN THE FIRST 10 SEC. ASSOCIATED ELEVATION
IGNITORS ARE STARTED*
WHEN 3 OUT OF 4 IGNITORS ARE PROVEN ON START
COMMAND IS GIVEN TO FIRST CORNER
WHEN THE CORNER GETS START COMMAND AND IF
ITS ASSOCIATED IGNITOR IS PROVEN ON THE
CORNER IS PLACED IN SERVICE BY
GUN ADVANCES TO FIRING POSITION.
WHEN GUN IS FULLY ADVANCED ATOMISING VALVE OPEN
WHEN ATOMISING MEDIUM VALVE IS PROVEN FULLY
OPEN OIL NOZZLE VALVE OPENS PLACING THE GUN IN
SERVICE.
03/05/15
S.VISWANATHAN
19
OIL ELEVATION STARTING
SEQUENCE(CONTD.)
AFTER 10 SECONDS START COMMAND IS GIVEN
TO OTHER CORNER AND PLACED IN SERVICE
AFTER 90 SEC. START TIME TRIAL OF THE PAIR
IS COMPLETED, A CORNER TRIP IS INITIATED
FOR ANY CORNER WHERE THE NOZZLE VALVE IS
NOT PROVEN FULLY OPEN OR ASSOCIATED
IGNITOR IS NOT PROVEN ON.
90 SEC. AFTER SECOND PAIR START, A MINIMUM
OF 3 OUT OF 4 NOZZLE VALVES MUST BE
PROVEN FULLY OPEN IN THAT ELEVATION
OTHERWISE
UNSUCCESSFUL ELEVATION START ALARM IS
INITIATED AT THAT ELEVATION AND OIL GUNS OF
THAT ELEVATION ARE SHUT DOWN IN AN ORDERLY
FASHION.
03/05/15
S.VISWANATHAN
20
OIL ELEVATION STARTING SEQUENCE
(WITH HEA IGNITORS)
STARTED IN PAIRS (1,3), (2,4)
DEPRESSING ONE PAIR START PUSH BUTTON WILL
INITIATE 90 SEC. START TIME TRIAL IF PERMISSIVES
ARE SATISFIED.
ON RECEIVING PAIR START COMMAND
IGNITOR ADVANCES
IGNITOR TRANSFORMER ENERGISES
ATOMISING NOZZLE VALVE OPENS
OIL NOZZLE VALVE OPENS
IGNITOR TRANSFORMER DE ENERGISES
IGNITOR RETRACTS
DISCRIMINATING SCANNAR PICKS FLAME
---------------------------------------------------------------
03/05/15
S.VISWANATHAN
21
PULVERISER INTERLOCK
03/05/15
S.VISWANATHAN
22
PULVERISER INTERLOCK
START PERMISSIVES
MILL DISCHARGE VALVES ARE OPEN
SEAL AIR VALVE IS OPEN
COLD AIR DAMPER IS OPEN
R.C.FEEDER INLET DAMPERS ARE
OPEN
TRAMP IRON HOPPER VALVE IS
OPEN
D.C.POWER TO FSSS IS AVAILABLE
BURNER TILT IN HORIZONTAL
POSITION AND BOILER AIR FLOW
ADJUSTED BETWEEN 30 TO 40% OF
FULL LOAD AIR FLOW
MILLOUTLET TEMP. IS LESS THAN
930C
P.A.PRESSURE IS ADEQUATE
EITHER A MINIMUM OF 3 NEXT
IMMEDIATE HO/LO NOZZLE VALVES
ARE OPEN OR NEXT IMMEDIATE
ELEVATION MILL IS WORKING AT
GREATER THAN 50% LOAD AND
BOILER LOAD IS GREATER THAN
30%
03/05/15
S.VISWANATHAN
23
PULVERISER INTERLOCK
WHEN MILL IS STARTED IMPULSE SHALL
BE GIVEN FOR
PERMISSION TO OPEN HOT AIR GATE
PERMISSION TO START R.C. FEEDER
PERMISSION FOR REGULATORS IMPULSE TO
ACT ON HOT AIR DAMPER
03/05/15
S.VISWANATHAN
24
PULVERISER INTERLOCK
PULVERISER WILL TRIP AUTOMATICALLY UNDER
ANY OF THE FOLLOWING
BOILER TRIPS
LOSS OF UNIT D.C.SUPPLY FOR MORE THAN 2 SEC.
MILL DISCHARGE VALVES ARE NOT OPEN
IF IGNITION ENERGY PERMISSIVE DISAPPEARS BEFORE 180
SEC. FROM FEEDER START
PRIMARY AIR TRIP
WHEN BOTH P.A.FANS TRIP
P.A.DUCT PRESSURE FALL BELOW LOW SET POINT FOR 5 SEC
P.A.DUCT PRESSURE FALL BELOW VERY LOW SET POINT
WHEN ONE P.A. FAN TRIPS AND THREE OTHER TOP ELEVATION
MILLS ARE IN SERVICE
03/05/15
S.VISWANATHAN
25
PULVERISER INTERLOCK
WHEN A MILL IS TRIPPED IMPULSE SHALL
BE GIVEN FOR
TO TRIP THE R.C. FEEDER MOTOR
TO CLOSE THE HOT AIR GATE
TO DISCONNECT THE REGULATORS IMPULSE
AND CLOSE HOT AIR DAMPER
TO PERMIT CLOSING OF MILL DISCHARGE
VALVES
TO BRING COLD AIR DAMPER TO MINIMUM
03/05/15
S.VISWANATHAN
26
PULVERISER INTERLOCK
HOT AIR GATE
HOT AIR GATE WILL OPEN ONLY IF MILL IS ON
IF THE HOT AIR GATE IS OPEN IMPULSE SHALL BE GIVEN TO
RELEASE HOT AND COLD AIR DAMPER CONTROL TO REGULATE
HOT AIR GATE WILL CLOSE AUTOMATICALLY AFTER 30 SEC.
UNDER ANY OF THE FOLLOWING CONDITIONS
MILL IS TRIPPED
MILLOUTLET TEMP. IS VERY HIGH
R.C. FEEDER STOPS WITHIN 5SEC. OF ITS START
WHEN HOT AIR GATE IS CLOSED IMPULSE SHALL BE GIVEN
FOR OPENING THE COLD AIR DAMPER PROVIDED IF THE MILL
IS ON
03/05/15
S.VISWANATHAN
27
R.C. FEEDER INTERLOCK
START PERMISSIVES
NO BOILER TRIP CONDITION PREVAILS
ELEVATION A.C. AND D.C. ARE AVAILABLE
IGNITION ENERGY IS AVAILABLE
MILL IS ON
HOT AIR GATE IS OPEN
FUEL AIR DAMPERS ARE CLOSED
NO STOP SIGNAL
03/05/15
S.VISWANATHAN
28
R.C. FEEDER INTERLOCK
ON STARTING R.C. FEEDER IMPULSE
SHALL BE GIVEN FOR
TO INCLUDE FEEDER OUTLET IN TOTALISING
CIRCUIT AFTER 15 SEC.
TO RELEASE FEEDER SPEED CONTROL TO AUTO
AFTER 50 SEC.
TO MODULATE FUEL AIR DAMPERS ACCORDING
TO FEEDER SPEED AFTER 50 SEC.
TO PERMIT FEEDER SPEED VARIATOR TO MOVE
03/05/15
S.VISWANATHAN
29
R.C. FEEDER INTERLOCK
R.C. FEEDER SHALL TRIP AUTOMATICALLY
UNDER ANY ONE OF THE FOLLOWING
CONDITIONS
BOILER TRIPS
ELEVATION A.C. / D.C. FAILS
IGNITION ENERGY DISAPPEARS BEFORE 180
SEC FROM THE STARTING OF FEEDER
MILL TRIPS
LOSS OF COAL FLOW AND MILL AMP.
LOW{ONLY AFTER 5 SEC FROM FEEDER START}
03/05/15
S.VISWANATHAN
30
R.C. FEEDER INTERLOCK
WHEN R.C. FEEDER TRIPS IMPULSE SHALL
BE GIVEN FOR
CLOSING HOT AIR GATE
IF EITHER MILL AMP. IS ABOVE MAXIMUM
SET POINT OR BOWL D.P. IS HIGH
IMPULSE SHALL BE GIVEN FOR
BRINGING R.C.FEEDER SPEED TO MINIMUM
03/05/15
S.VISWANATHAN
31
03/05/15
S.VISWANATHAN
32
INTERLOCKS FOR SY. AIR
CONTROL
AUXILIARY AIR DAMPERS
DURING PURGING AND UPTO 30% LOAD ALL THE
AUXILIARY AIR DAMPERS MODULATE TO MAINTAIN
WIND BOX TO FURNACE DIFFERENTIAL PRESSURE
OF APPROX. 40 MM WCL. (LOW SET PT.)
WHEN LOAD EXCEEDS 30% THE D.P SET POINT IS
CHANGED TO APPROX. 100 MMWC (HIGHER SET
PT.) SIMULTANEOUSLY THE AUX. AIR DAMPERS
ASSOCIATED WITH COAL OR OIL ELEVATION NOT IN
SERVICE CLOSE IN TIMED SEQUENCE STARTING
FROM UPPER ELEVATIONS.
ALL THE AUX. AIR DAMPERS MAINTAIN STATUS
QUO UPON BOILER TRIP AND OPEN FULLY WHEN
BOTH F.D. FANS ARE OFF.
03/05/15
S.VISWANATHAN
33
INTERLOCKS FOR SY. AIR CONTROL
(CONTD.)
THE AUX. AIR DAMPERS ASSOCIATED WITH OIL
ELEVATIONS MODULATE AS A FUNCTION OF OIL
HEADER PRESSURE WHEN OIL IS BEING FIRED AT
THAT ELEVATION. OTHERWISE THEY OPEN OR
CLOSE WITH THE BALANCE OF THE AUX. AIR
DAMPERS.
FUEL AIR DAMPERS
FUEL AIR DAMPERS OPEN 50 SEC. AFTER THE
ASSOCIATED FEEDER IS STARTED AND
MODULATE AS A FUNCTION OF FEEDER SPEED.
FUEL AIR DAMPERS CLOSE, 50 SEC. AFTER THE
TRIPPING OF ASSOCIATED R.C. FEEDER
ALL THE FUEL AIR DAMPERS OPEN FULLY WHEN
BOTH F.D. FANS ARE OFF.
03/05/15
S.VISWANATHAN
34
INTERLOCKS FOR SCANNER AIR
FANS
SCANNER AIR FAN WILL START
WHEN THE START PUSH BUTTON IS PRESSED
WHEN THE SCANNER DUCT TO FURNACE
DIFF.PR. IS LESS THAN 115MM OF WC AND THE
OTHER SCANNER AIR FAN IS RUNNING
IF THE OTHER FAN FAILS TO START WITHIN 5
SE. OF ITS START.
WHEN SCANNER AIR FAN IS STARTED
IMPULSES SHALL BE GIVEN FOR
OPENING ITS DISCHARGE DAMPER
CLOSING THE DISCHARGE DAMPER OF THE
OTHER FAN WITH A TIME DELAY OF 5 SEC.
PROVIDED THAT FAN IS OFF.
03/05/15
S.VISWANATHAN
35
INTERLOCKS FOR SCANNER AIR FANS
(CONTD.)
SCANNER AIR FAN CAN BE TRIPPED BY
PRESSING THE STOP PUSH BUTTON
PROVIDED THE SCANNER DUCT TO
FURNACE P IS MORE THAN 115 MMWC
WHEN SCANNER AIR FAN IS TRIPPED,
IMPULSE SHALL BE GIVEN TO CLOSE ITS
DISCH. DAMEPR PROVIDED THE OTHER
FAN IS IN SERVICE WITH A TIME DELAY 5
SEC.
03/05/15
S.VISWANATHAN
36
INTERLOCKS FOR IGNITOR
AIR FANS
IGNITOR AIR FAN (SELECTED) CAN BE
STARTED BY PRESSING THE PUSH
BUTTON
IGNITOR AIR FAN (SELECTED) SHALL
START AUTOMATICALLY WHEN ANY
OIL ELEVATION START IS INITIATED
IGNITOR AIR FAN CAN BE TRIPPED BY
PRESSING THE PUSH BUTTON
PROVIDED ALL THE IGNITOR VALVES
ARE IN CLOSED CONDITION.
03/05/15
S.VISWANATHAN
37
INTERLOCKS NOT COVERED
UNDER BMS/FSSS
I.D. FAN INTERLOCKS
F.D. FAN INTERLOCKS
P.A. FAN INTERLOCKS
SEAL AIR FAN INTERLOCKS
AIR HEATER INTERLOCKS
EMERGENCY BLOWDOWN VALVES
SCANNER FAN OUTLET DAMPERS
IGNITOR FAN OUTLET DAMPERS
INTERLOCKS FOR LUB.OIL SYSTEMS OF FANS
FURNACE TEMP. PROBE
03/05/15
S.VISWANATHAN
38
FAN INTERLOCKS PROVIDE
FAN START PERMISSIVES
SYSTEM RESPONSE ON STARTING A
FAN
ONE IS STARTED OTHER IS NOT IN
SERVICE
ONE IS STARTED OTHER IS IN SERVICE
FAN TRIPPING CONDITIONS
SYSTEM RESPONSE ON TRIPPING
OF A FAN
ONE IS TRIPPED OTHER IS IN SERVICE
ONE IS TRIPPED OTHER IS NOT IN
SERVICE
03/05/15
S.VISWANATHAN
39
FAN START
PERMISSIVES
SUCTION AND DISCHARGE
DAMPERS ARE CLOSED
FAN CONTROL DEVICE AT
MINIMUM POSITION
BEARING TEMP. NOT HIGH
LUB. OIL PRESSURE ADEQUATE
FOR F.D. FAN IN ADDITION TO
ABOVE
SELECTED I.D. FAN IS IN SERVICE
03/05/15
S.VISWANATHAN
40
03/05/15
S.VISWANATHAN
41
SYSTEM RESPONSE ON
STARTING A FAN
ONE IS STARTED OTHER IS NOT
INSERVICE
SUCTION AND DISCHARGE DAMPERS OF
STARTED FAN OPENS AFTER A TIME DELAY
OF 60 SEC.
REGULATOR TO FAN CONTROL DEVISE IS
CONNECTED
CLOSE THE SUCTION AND DISCHARGE
DAMPERS OF OTHER I.D.FAN
GIVE PERMISSIVE TO START THE
CORRESPONDING F.D.FAN
OPEN THE INTER CONNECTING DAMPER IF
AVAILABLE S.VISWANATHAN
03/05/15
42
03/05/15
S.VISWANATHAN
43
SYSTEM RESPONSE ON
STARTING A FAN
ONE IS STARTED OTHER IS INSERVICE
SUCTION AND DISCHARGE DAMPERS OF
STARTED FAN OPENS AFTER A TIME DELAY
OF 60 SEC.
REGULATOR TO FAN CONTROL DEVISE IS
CONNECTED
CLOSE THE INTER CONNECTING DAMPER
IF AVAILABLE
GIVE PERMISSIVE TO START THE
CORRESPONDING F.D.FAN
03/05/15
S.VISWANATHAN
44
03/05/15
S.VISWANATHAN
45
FAN TRIPPING
CONDITIONS
BEARING TEMP. TOO HIGH
LUB. OIL PRESSURE TOO LOW
INADDITION TO ABOVE
FOR I.D. FAN
CORRESPONDING AIR HEATER TRIPS
FOR F.D. FAN
CORRESPONDING I.D.FAN TRIPS
FOR P.A. FAN
CORRESPONDING F.D.FAN TRIPS
BOILER TRIPS
03/05/15
S.VISWANATHAN
46
SYSTEM RESPONSE ON
TRIPPING A FAN
ONE IS TRIPPED OTHER IS INSERVICE
SUCTION AND DISCHARGE DAMPERS OF
TRIPPED FAN CLOSES IMMEDIATELY
FAN COTROL DEVISE IS BROUGHT TO
MINIMUM AND REGULATOR TO FAN
CONTROL DEVISE IS DISCONNECTED
OPEN THE INTER CONNECTING DAMPER IF
AVAILABLE
TRIP THE CORRESPONDING F.D.FAN
ENERGISE PART LOAD RELAY
03/05/15
S.VISWANATHAN
47
SYSTEM RESPONSE ON
TRIPPING A FAN
ONE IS TRIPPED OTHER IS NOT INSERVICE
SUCTION AND DISCHARGE DAMPERS OF
TRIPPED FAN REMAINS OPEN
FAN COTROL DEVISE IS BROUGHT TO
MAXIMUM
TRIP THE CORRESPONDING F.D.FAN
OPEN THE SUCTION&DISCHARGE DAMPERS
ANDFAN REGULATING DEVISE OF OTHER FAN
OPEN ALL DAMPERS IN F.G.PATH
03/05/15
S.VISWANATHAN
48
INTERLOCKS FOR SEAL AIR
FANS
SEAL AIR FAN IS IS
PROHIBITED FROM
STARTING UNLESS ONE
OF THE P.A. FAN IS
RUNNING
A RUNNING SEAL AIR
FAN CAN BE TRIPPED
ONLY IF ALL THE MILLS
ARE TRIPPED OR OTHER
SEAL AIR FAN IS
RUNNING
SEAL AIR FAN WILL BE
TRIPPED
AUTOMATICALLY WITH
ATIME DELAY OF 60
SEC. IF BOTH P.A. FANS
TRIP
03/05/15
S.VISWANATHAN
49
AIR HEATER INTERLOCKS
AIR HEATER ELECTRIC MOTOR/AIR
MOTOR WILL TRIP WHEN THE
SUPPORT/GUIDE BEARING TEMP.IS VERY
HIGH
WHENEVER AIRHEATER ELECTIC MOTOR
TRIPS IMPULSE SHALL BE GIVEN FOR
STARTING AIR HEATER AIR MOTOR
PROVIDED THE SUPPORT AND GUIDE
BEARINGS TEMP. IS LESS THAN 700C
03/05/15
S.VISWANATHAN
50
03/05/15
S.VISWANATHAN
51
AIR HEATER INTERLOCKS
WHENEVER BOTH ELECTIC MOTOR AND
AIR MOTOR TRIP IMPULSE SHALL BE
GIVEN FOR
CLOSING INLET AND OUTLET DAMPERS IN
FLUE GAS, SY.AIR, P.A. LINES TO AIR
HEATER
TRIPPING OF CORRESPONDING I.D.FAN IF
OTHER I.D. AND A.H. ARE IN SERVICE
TRIP BOTH I.D. FANS IF OTHER A.H. IS NOT
IN SERVICE
OPEN INTER CONNECTING DAMPER IN HOT
S.A.LINE IF OTHER A.H. IS IN SERVICE
03/05/15
S.VISWANATHAN
52
INTERLOCKS FOR EBD VALVE
THIS VALVE WILL
OPEN WHEN THE
DRUM LEVEL
REACHES VERY HIGH
LIMIT
DRUM
THIS VALVE WILL
CLOSE ONLY WHEN
THE DRUM LEVEL
REACHES NORMAL
LEVEL
03/05/15
S.VISWANATHAN
EBD LINE
IBD
EXPANDER
53
FURNACE TEMP. PROBE
THE PROBE IS PROHIBITED FROM
ADVANCING INTO THE FURNACE IF THE
FURNACE OUTLET TEMP.IS MORE THAN
5400C
IF THE PROBE IS INSIDE THE FURNACE
AND IF THE FOT INCREASES ABOVE
5400C THE PROBE RETRACTS
AUTOMATICALLY
03/05/15
S.VISWANATHAN
54