Grid1 - GRID1 - Results

This 3 sentence summary provides the key details from the given document: The document is a ground grid summary report for project ETAP located analyzing a study case called GRD1, which found that the maximum touch voltage of 5855.3 volts exceeds the tolerable limit of 489.9 volts. It provides details of the total fault current of 20.548 kA, maximum grid current of 7987.3 amps, and reports various correction factors used in the IEEE 80 grounding analysis.

Uploaded by

subasratna
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
15 views2 pages

Grid1 - GRID1 - Results

This 3 sentence summary provides the key details from the given document: The document is a ground grid summary report for project ETAP located analyzing a study case called GRD1, which found that the maximum touch voltage of 5855.3 volts exceeds the tolerable limit of 489.9 volts. It provides details of the total fault current of 20.548 kA, maximum grid current of 7987.3 amps, and reports various correction factors used in the IEEE 80 grounding analysis.

Uploaded by

subasratna
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 2

Project:

ETAP

Location:

7.0.0

Page:

Date:

04-10-2015

Contract:

SN:

Engineer:

Study Case: GRD1

12345678

Ground Grid Summary Report


Rg
Ground
Resistanc
e
Ohm

GPR
Ground
Potential Rise
Volts

3.950

Total Fault Current:

81549.6

Touch Potential
Tolerable Calculate Calculate
d
d
Volts
Volts
%

1630.3

20.540 kA Reflection Factor (K):

Maximum Grid Current:


Decrement Factor (Df):

7987.3

Tolerable
Volts
489.9

Step Potential
Calculated
Volts

Calculate
d
%

5855.3

5632.2

-0.724

20.648 kA Surface Layer Derating Factor (Cs):

0.846

1.120

Warnings:
The maximum Touch Voltage exceeds the tolerable limits

Report of Intermediate Constants for IEEE 80 Methods


- Correction factor for grid geometry regarding touch voltage (Kim):

- Correction factor for grid geometry regarding step voltage (Kis):


- Spacing factor for touch voltage (Km):
- Spacing factor for step voltage (Ks):

3.507
3.507

0.526
0.276

- Corrective weighting factor that adjusts for the effects of inner conductors on the corner mesh (Kii):
- Constants 1 related to the geometry of system (K1):

1.340

- Constants 2 related to the geometry of system (K2):

5.652

1.000

015

678
Filename:

96.2

sanjen 42