Project:
ETAP
Location:
7.0.0
Page:
Date:
04-10-2015
Contract:
SN:
Engineer:
Study Case: GRD1
12345678
Ground Grid Summary Report
Rg
Ground
Resistanc
e
Ohm
GPR
Ground
Potential Rise
Volts
3.950
Total Fault Current:
81549.6
Touch Potential
Tolerable Calculate Calculate
d
d
Volts
Volts
%
1630.3
20.540 kA Reflection Factor (K):
Maximum Grid Current:
Decrement Factor (Df):
7987.3
Tolerable
Volts
489.9
Step Potential
Calculated
Volts
Calculate
d
%
5855.3
5632.2
-0.724
20.648 kA Surface Layer Derating Factor (Cs):
0.846
1.120
Warnings:
The maximum Touch Voltage exceeds the tolerable limits
Report of Intermediate Constants for IEEE 80 Methods
- Correction factor for grid geometry regarding touch voltage (Kim):
- Correction factor for grid geometry regarding step voltage (Kis):
- Spacing factor for touch voltage (Km):
- Spacing factor for step voltage (Ks):
3.507
3.507
0.526
0.276
- Corrective weighting factor that adjusts for the effects of inner conductors on the corner mesh (Kii):
- Constants 1 related to the geometry of system (K1):
1.340
- Constants 2 related to the geometry of system (K2):
5.652
1.000
015
678
Filename:
96.2
sanjen 42