The document provides specifications for an AMF panel. It will be metal clad, cubical type, single front, and flush mounted. It will have IP-54 degree of protection and be fabricated from 14/16 SWG thick CRCA sheet steel. Internal wiring will use suitable sized PVC insulated copper cable and cable entry will be at the bottom.

Uploaded by

Hari Krishna.M
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
53 views1 page

Specifications of EMRV Contol Panel

The document provides specifications for an AMF panel. It will be metal clad, cubical type, single front, and flush mounted. It will have IP-54 degree of protection and be fabricated from 14/16 SWG thick CRCA sheet steel. Internal wiring will use suitable sized PVC insulated copper cable and cable entry will be at the bottom.

Uploaded by

Hari Krishna.M
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 1

SPECIFICATION FOR AMF PANEL :

GENERAL:
1. DESIGN FEATURES: Metal clad, Cubical type, Single Front, Flush Type,
2. Floor mounted, Dust & Vermin proof as per IS 2147 & 8623
3. OPEPERATION OF PANEL: Single Front operation
4. PAINTING DETAILS: Through chemical treatment for degreasing, derusting and phosphate of sheet
metal work with 7 tank process, powder coated, shade IS-635
5. DEGREE OF PROTECTION: IP-54,
6. FABRICATION DETAILS: 14/16 SWG thick CRCA (cold rold cold annealed)
Sheet steel metal
7. WIRING: Suitable sized PVC insulated single core flexible multistrand copper
Cable for internal wiring of the components .Metering is done with 1.5sqmm single core multi stand
PVC insulated flexible copper cable. 2.5sq-mm single Core, multistand, PVC insulated flexible copper
cable for C.T wiring.
8. CABLE ENTRY: At the bottom.
9. MISCALLENIOUS: Good quality of natural rubber gasket to be provided, Panel locks for the cubical
doors, Engrave name plates with white letters on black back ground, Door earthing with flexible cable,
Earthing bus bar to be provided, Ferrules for easy identification of control circuit, Labels for identification
of internal components.