0 ratings0% found this document useful (0 votes) 245 views7 pagesFlat Slab Flexural Design To EC2
Quarry sand as fine aggregate
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
236 Reinforced Concrete Design
Figure 89
‘Continuous pane! spanning
In two directions
EXAMPLE 8.6 _
Moments int 2 continuous two-way slab
‘The panel considered is an edge panel, as shown in figure 89 and the uniformly
distributed load, m = (1.35 gy + 1.Sqy) = 10kN/m*,
som
support
Discontinuous
supported edge
a
y= 625m
support
‘The moment coefficients are taken from table 8.5,
fy _ 628
E2397 13
Positive moments at mid-span
My = Ban? = 0.045 x 10 x
= 11.25KNm in direction ky
Boynl = 0.028 x 10x 5?
=7.0kN m in direction ly
My
Negative moments
Support ad, M, = 0.059 x 10 x $? = 14.75KNm
Supports ab and de, My = 0.037 » 10 x 5? =9.25kNm
‘The moments calculated are for a metre width of slab.
‘The design of reinforcement to resist these moments would follow the usual
procedure. Torsion reinforcement, acvording to rule 4 is required at comers b and c. A
check would also be required on the span-effective depth ratio of the slab. )
8.6 Flat slab floors
AA flat slab floor is a reinforced concrete slab supported directly by conerete columns
without the use of intermediary beams. ‘The slab may be of constant thickness
throughout or in the area of the column it may be thickened as a drop panel. The colurnn
may also be of constant section or it may be flared to form a column head or capital.
‘These vatious forms of construction are illustrated in figure 8.10,Design of reinforced concrete slabs 237 :
N N ‘y
Ly
ns
Floor without drop Floor with column Floor with crop
panel or column head but no drop panel nd column
head panel ead
drop panels are effective in reducing the shearing stresses where the column is,
© punch through the slab, and they also provide an increased moment of
ce where the negative moments are greatest,
lat slab floor has many advantages over the beatn and slab floor. The simplified
rk and the reduced storey heights make it more economical, Windows can
up to the underside of the slab, and there are no beams to obstruct the light and
ulation of air. The absence of sharp comers gives greater fire resistance as there
danger of the concrete spalling and exposing the reinforcement. Deflection
nents will generally govern slab thickness which should not normally be less
0mm for fire resistance as indicated in table 8.6.
analysis of a flat slab structure may be cattied out by dividing the structure into a
f equivalent frames. The moments in these frames may be determined by:
nethod of frame analysis such as monient distribution, or the stiffness method on
omputer;
implified method using the moment and shear coefficients of table 8.1 subject to
: following requirements:
" ; the lateral stability is not dependent on the slab-column connections;
) the conditions for using table 8.1 described on page 217 are satisfied;
}) there are at least three rows of panels of approximately equal span in the
direction being considered;
) the bay size exceeds 30m”
6 Minimum dimensions and axis distance for flat slabs for fire resistance
‘Minimurn dimensions (rmm)
Slab thickness, hy
is distance, a
ee 80 A 15
Ob 200 2B
Se 200 35
40
200 50
cltribution of moments not to exceed 15%,
fre resistance ROO and above, 20% of the total top teinforcemient in éach diecton over
terest supports sould be continuous over fe whole span and placed inthe eon sp,
Figure 8.10
Drop panels and eoluran
headsfe Figure 3.11
Flat slab lived into strips
238 Reinforced Concrete Design
Position of maximum
7 negative morent
\Widih of half column stip = 14 with na drops
‘or= half drop width when drops are used
Interior panels of the flat slab should be divided as shown in, figure 8.11 into column
and middle sttips. Drop panels should be igoored if their smaller dimension is less than
one-third of the smaller panel dimension j. If a panel is not square, strip widths in both
directions are based on /,.
Moments determined from a structural analysis or the coeflicients of table 8.1 are
distributed between the strips as shown in table 8.7 such that the negative and positive
moments resisted by the column and middle strips total 100 per cent in each case.
Reinforcement designed to resist these slab moments may be detailed according to
the simplified rules for slabs, and satisfying normal spacing limits, This should be
spread across the respective strip but, in solid slabs without drops, top steel to resist
negative moments in column strips should have one-half of the area located in the
central quarter-sitip width. If the column strip is narrower because of drops, the
‘moments tesisted by the column and middle strips should be adjusted proportionally as
illustrated in example 8.7.
Column moments can be calculsted from the analysis of the equivalent frame,
Particular care is needed over the transfer of moments to edge columns. This is to ensure
that there is adequate moment capacity within the slab adjacent to the column since
moments will only be able to be transferred to the edge column by a strip of slab
considerably narrower than the normal internal panel column step width. As seen in
table 8.7, a limit is placed on the negative. moment transferred to an edge columa, and
slab reinforcement should be concentrated within width b, as defined in figure 8.12. If
exceeded the moment should be limited to this value and the positive moment increased
to maintain equilibrium,
‘The reinforcement for a flat slab should generally be arranged aeconding to the rules
illustrated in figure 8.2, but at least 2 bottom bars in each orthogonal direction should
pass through internal columns to enhance robustness.
Table 8.7 Division of moments between strips
Column strip idle strip
Negative moment at edge column 100% but not more 0
than 0.17 bd
Negative moment at internal column 60-80% 40-20%
Positive moment in span 50-70% 50-30%
y= Width of ecige stip.Design of reinforced concrete slabs 239
Figure 3.12
Definition of
Yy i ide
ane fc of clin aE
i
coy beazeye 2
‘Note: Al slab reinforcement perpendicular to a free edge transferring moment to the column
should be concentrated within the width be
(@) Edge column (©) Comer column
sn eige// sh edge
i
+
i
‘Important features in the design of the slabs are the calculations for punching sheat at
the head of the columns and at the change in depth of the stab, if drop panels are used,
The design for shear should follow the procedure described in the previous section on
punching shear except that EC2 requires that the design shear force be increased above
the calculated value by 15 per cent for intemal columns, up to 40 per cent for edge
columns and 50 per cent for comer columns, to allow for the effects of moment transfer.
‘These simplified rules only apply to braced structures where adjacent spans do not differ
| by more than 25%,
In considering punching shear, C2 places additional requirements on the amount
| shear capacity is developed.
‘The usual basic span-effective depth ratios may be used but where the greater span
exceeds 8.5m the basic ratio should be multiplied by 8.S/span, For flat slabs the span-
_effetive depth calculation shouldbe based on the longer span.
‘esetibing the eguemen' forthe analysis and design of fat slabs, including the ws of
wide punching shear resistance,
- columns are at 6.5m centres in each direction and the slab supports a variable load
KN/m”. The characteristic material strengths are fo, = 25N/mm? for the concrete,
500N/mm? for the reinforcement,
Weight of drop = 0.1 x 25 x 2.5? = 15.6kN
Total = 279.7kN240
Reinforced Conerete Design
Figure 6.3 2.5m square drops
Fat slab example
4
a 0 +
Too |
column centres each way
Variable load
i Total = 5 x 6.5% = 211.3kN
‘Therefore
ultimate load on the floor, F = 1.35 x 279.7 41.5 x 211.3,
= 69SIN per panel
and. equivalent distributed Joad, n = & = 16.4 kNim?
‘The effective span,
= clear spam between cofumn heads 418 Wickmess 6 eng
il . = (65-12) +92 x 2% 107 =5.65m
A concrete cover of 25mm has been allowed, and where there are two equel layers of
reinforcement the effective depth has been taken as the mean depth of the two layers in
o calculating the reinforcement areas. (d= 205mm in span and 305 mm at supports.)
‘The drop dimension is greater than one-third of the panel dimension, therefore the
column strip is taken as the width of the drop panel (2.5 m).
Bar spacing and size tits o
As the slab thickness is greater than 200 mm the spacing limits given in section 8,3(c) do
not apply. Use the spacing or bar size limits from tables 6,7 and 6.9 for the bending
reinforcement, In both cases the steel siress under the quasi-permanent loads can be
estimated from equation 6.1 assuming 20% redisuibution (the maximum applicable to
table 8.1 used below) as:
Six, +030, 1 Aa
FATIS* (35, +150) “5 * Ager |
500 (279.7 4.0.3 x 211.3)
14500,
1s 695
= 268N/mm*
asstuming that As, pov = As eg-
Hence from table 6.7 the maximum spacing « 165 mm
or from table 6.9 the maximum bar size ~ 12mmDesign of reinforced concrete slabs
¢ the. variable load is less than the permanent load and bay size = 6.5 x 65 =
sm? ( > 30m*), from table 8.1:
063 x 695 x 5.65 = 247kNm.
th OF the middle stip is (6.5— 2.5) = 4m which is greater than half the
{ dimension, therefore the proportion of this moment taken by the middle strip
stake as 0.45 from table 8.7 adjusted as shown:
dle strip positive moment = 0.55 x 247 = 136kNm,
strip positive moment = (1 ~ 0.55) x 247 = 111kNm,
Foo ape ge = 00032
00 x 2057 x a5 = 8
“sixteen H12 bars (4s = 1809mm?) each way in the span,
levenly. across the 4m width of the middie strip (spacing = 250mm).
ss the maximum fimit of 165 mm but bar size of 12 mn is
MH stip'moments will require 1310mm bottom steel which can be
twelve H12 bars (A, = 1356mm?) in the span disttibuted evenly
‘Width of the column strip (spacing approx 210mm),
= 0.0631
4
25 x =
* Gyg 8247 = 0.31 x 247
TKN m
10.31) x 247 = 0.69 x 247 = 170kNm242
Reinforced Concrete Design
From the lever-armn curve, figure 4.5, I, = 0.98 (> 0.95), therefore
4 =i TI x 108
© O87. O87 x 300 x 0.95 % 005
= 909mm?
Provide eleven evenly spaced HI2 bars as top steel (4, =
1243 msm?) spacing
400mm, which exceeds 165mm maximum. Jimit but the bar size of 12 mm is
satisfactory.
(©) For the column strip
Mo 170 x 108
bij, ~ 2500 x 305? x 35 9-979
From the lever-arm curve, figure 4.5, [, = 0.97 (> 0.95), therefore
A M 170 x 108
eon ae O8Tfuz O87 500% 0.95 x 305
= 1349 mm?
Provide F112 bars as top steel at 200 centres. This is equivalent to fourteen bars
(4, = 1582 mm?) over the full 2.51m width of the column strip. The bending
reinforcement requirements are summarised in figure 8.14,
Punching shear
1. Atthe column head
Perimeter up = 1r x diameter of column head
x 1200 = 370mm
shear force Vag = F ~
Glen
695 —F1.2 x 16.4 = 6764 kN
Figure 8.14 4 cohen € column
Deas of bending
renorement 2 ~400 2 | jiit2-400
= Z =
168112 “250 each way
(@) Middle stip 4.0m wide
| i2—200 exe
wa
= =
a a
1212-210
14}112-200 ew
(©) Column strip 2.5m wide