This document contains calculations to determine the earth resistance of a proposed substation earthing system. It provides input data on soil resistivity, conductor type and length, electrode dimensions and spacing. It then shows calculations for (1) the resistance of a single vertical electrode, (2) the total resistance of 14 electrodes, and (3) the resistance of the horizontal earth grid. The final calculation combines the vertical and horizontal resistances to give a total earth resistance of 0.184 ohms, which is less than 1 ohm and considered a safe value for earthing.

Uploaded by

jm.mankavil6230
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
204 views

Larsen & Toubro Limited: Electrical Division, H.Q., Chennai

This document contains calculations to determine the earth resistance of a proposed substation earthing system. It provides input data on soil resistivity, conductor type and length, electrode dimensions and spacing. It then shows calculations for (1) the resistance of a single vertical electrode, (2) the total resistance of 14 electrodes, and (3) the resistance of the horizontal earth grid. The final calculation combines the vertical and horizontal resistances to give a total earth resistance of 0.184 ohms, which is less than 1 ohm and considered a safe value for earthing.

Uploaded by

jm.mankavil6230
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 2

1 OF 2

LARSEN & TOUBRO LIMITED


CONSTRUCTION GROUP

ELECTRICAL DIVISION, H.Q., CHENNAI

PROJECT
Relocation of Riyam Substation and Transformer
Repair Workshop
TITLE
EARTHING CALCULATIONS

REF. NO.

PAGE :

PREPARED

CHECKED

APPROVED

DATE

SSJ

AKR

AKS

22-Feb-16

INPUT DATA

1
2
3
4
5
6
7
8
9
10

Soil resistivity
Type of conductor used
Length of Grid buried in ground
Depth of burial of electrode
Length of Rod or Pipe
Dia of Rod or Pipe
No. of Electrodes
Distance between adjacent rods
P(Ref: Table 5 BS 7430:1991)
Q(Ref: Table 5 BS 7430:1991)

=
=
=
=
=
=
=
=
=
=

L
w
l
d
n
s

26
Copper Flat
275
0.5
3.5
0.016
14
7
2
-1.3

Ohm.m

m
m
m
m
m

CALCULATIONS

Resistance of one vertical Electrode

Net resistance of Electrodes

Re

8l
------------ LOGe -------2*phi*l
d
7.650
ohms

Rr/n

0.546443675 ohms

Resistance of horizontal Buried


Earth grid

Rh

=
=

Net Resistance

=
=

2*L2

------------ x LOGe ---------- -----+ Q2


P x Phi x L
w *d
0.278
ohms
R x Rh
------------R + Rh
0.184

ohms

RESULT

Since the total Resistance is less than 1 ohm, earthing for this area is SAFE.

305260211.xls.xls

- 1

2 OF 2

LARSEN & TOUBRO LIMITED


CONSTRUCTION GROUP

ELECTRICAL DIVISION, H.Q., CHENNAI

PROJECT
Relocation of Riyam Substation and Transformer
Repair Workshop
TITLE
EARTHING CALCULATIONS

REF. NO.

PAGE :

PREPARED

CHECKED

APPROVED

DATE

SSJ

AKR

AKS

22-Feb-16

305260211.xls.xls