0 ratings0% found this document useful (0 votes) 707 views86 pagesCompressed Air Fluor Guide
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
YW FLUOR
PROCESS
UTILITY
MANUALS
1.0.0
1.1.0
1.2.0
‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
COMPRESSED AIR SYSTEMS
TABLE OF CONTENTS
TABLE OF CONTENTS
DESIGN DISCUSSION
1.0 INTRODUCTION
2.0 INSTRUMENT AIR SYSTEM
2.1 GENERAL
2.2 CENTRAL VERSUS UNIT SYSTEMS
2.3 SYSTEM PRESSURE
2.4 AIR QUALITY
2.5 SYSTEM CAPACITY
3.0 PLANT AIR SYSTEM
3.1 GENERAL
3.2 CENTRAL VERSUS UNIT SYSTEMS
3.3 SYSTEM PRESSURE
3.4 AIR QUALITY
3.5 SYSTEM CAPACITY
DESIGN PROCEDURES
1,0 COMPRESSORS
INTRODUCTION
PROCESS SPECIFICATION
CENTRIFUGAL COMPRESSORS
RECIPROCATING COMPRESSORS,
2.0 COMPRESSOR CONTROLS
2.1 CENTRIFUGAL COMPRESSORS
2.2 RECIPROCATING COMPRESSORS
4.0 DRYERS
1 GENERAL
2 DRYER DESIGNS
+3. DESTCCANTS
4 DESICCANT REGENERATION
NUMBER
PAGE
DATE
1.0.0
1of2
12-79VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
FLUOR NUMBER
PROCESS COMPRESSED AIR SYSTEMS PAGE
vont TABLE OF CONTENTS DATE
MANUALS —e——v
1.0.0
2
12-79
1.2.0 DESIGN PROCEDURES (Continued)
5.0 ATR RECEIVERS
6.1 GENERAL
6.2 APPLICATIONS
6.3 OTL REMOVAL
1.3.0 TABLES, GRAPHS, AND FORMS
1.4.0 FLOW DIAGRAMSVOLUME 41 — AIR, FUEL AND WATER SYSTEMS
W FLUOR NUMBER 1.1.0
PROCESS. COMPRBESED ATE SISTERS PAGE lof S
uriuity DESIGN DISCUSSION
wanuats BESIGN DISCUSSION DATE = 12-79
2.0 INTRODUCTION
2.0
All chemical plants and refineries need a source of compressed air as
motive power to operate instruments, controls and pneumatic tools. These
needs are divided into the catagories of plant air and instrument air,
each with its own special design requirements.
This section of the manual gives guidelines for the design of plant air
and instrument air systems. These guidelines represent Fluor practices
and procedures which shall be used where no project specifications exist.
However, early in a project the Process Utility Engineer should agree
with the Client on a job philosophy and its application to the design of
the air systems required.
INSTRUMENT ATR SYSTEM
2.2 General
Instrument air is used throughout process plants as a medium to
transfer control signals and as a power source’ to move positioning
control actuators. The typical instrument air system consists of
one or more compressors, filters, dryer, receiver, and distribution
piping.
2.2 Central Versus Unit Systems
There are two methods of setting up instrument air systems within a
plant. One is a centrally-located operating unit with distribution
piping to supply air to all the users. The instrument air headers
are sized by the Process Utility Engineer, and reviewed by the
Control System Engineer, The design quantity and termination
pressure is specified by the Control system Engineer.
‘The unit system consists of a small compressor and dryer for each
process unit with an emergency make-up from the plant air system or
other external source. This type of installation has higher
installation expense and higher operating costs than a centralized
system. The unit system can be appropriate in plants where
processing units are later added to the original plant.
2.3 System Pressure
If the air pressure level is not set by job or Client specifica~
tions, start with 110 psig at the compressor discharge. Then make
sure that a minimum of 80 psig can be obtained, with reasonableFLUOR
‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
PROCESS
NUMBER 1.1.0
COMPRESSED ATR SYSTEMS pace 2
ut
ILITY DESIGN DISCUSSION pate 12-79
MANUALS
2.3 System Pressure (Continued)
distribution piping sizes, in the most remote instrument circuit.
Check all user pressure levels to determine whether the assumed
pressure of 110 psig at the compressor discharge is high enough.
For example, make certain that there are no process uses that may
require even higher pressures.
control cylinders are normally purchased to operate at a minimum
pressure of 50-60 psig at the user. This minimum pressure
Fequirement should be verified with the Control System Engineer.
systems hydraulics should be periodically checked as the plot plan
develops, to make sure that the assumed compressor discharge
pressure and system line sizing are adequate.
2.4 Air Quality
the moisture content of the instrument air is a function of the
relative humidity of the ambient air and the discharge temperature
and pressure of the compressed air. Engineering standard ST-1-4700
specifies that the dewpoint of the compressed air delivered to the
istribution system shall be at least 5°F below the minimum
ambient temperature. Dewpoint shall be determined at the dryer
outlet pressure. Instrument air must also be free of corrosive
and combustible gases, dirt and oil.
2.5 System Capacity
the quantity of instrument air required is determined by referring
‘to the methods of ST-1-4700 in Control Systems Manual Vol. I. The
computation of instrument air consumption is the responsibility of
the Control System Engineer. The F y Bngineer may, on
Seeasion, be required to estimate the instrument air requirements
Gn order to expedite preparation of equipment specifications.
PLANT ATR SYSTEM
3.1 General
Plant air is normally used during maintenance operations in
pneumatic tools, hoists, spray guns, etc., and sometimes for
process applications.
plant aix systems generally consist of compressor (s), receiver
and distribution piping.yf FLUOR:
PROCESS
UTILITY
MANUALS
VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
NUMBER 1.1.0
COMPRESSED AIR SYSTEMS PAGE 3
DESIGN DISCUSSION DATE 12-79
3.0 PLANT AIR SYSTEM (Continued)
3.2
Central Versus Unit systems
There are two general types of plant air systens.
‘The central system has one or more large compressors located near
the center of a plant. Air is distributed to the various users
from this central location.
Unit systems will have small compressors located at points where
air is needed in individual process units. These unit systems
normally operate independent of each other. Economics generally
favor the central system, so the unit system is seldom used.
Fluor's usual procedure in refineries and chemical plants is to use
the plant air system as an emergency source of supply for the
instrument air system. The emergency connection must be made ahead
of the instrument air dryer as the plant air is usually not dried
except when required because of freezing weather or Client standards.
When the plant air compressor is of the lubricated type, it is very
important that an oil trap furnished by the éryer vendor be
installed in the emergency line to the instrument air system.
‘The plant air system often has a valved connection located so
that a portable air compressor(s) can be used to provide
additional air during maintenance shutdowns and turnarounds.
When instrument air is taken from the plant air system, provisions
should be made to limit the amount of plant air consumption in order
to prevent the instrument air pressure dropping below that systen's
minimum required level.
System Pressure
The recoumended pressure level for the plant air system is a
minimum of 100 psig at the air receiver. When the pressure drop
through the aftercooler and piping is considered, the compressor
ischarge should be approximately 110 psig.
The plant air distribution system must be sized to provide 85-90
psig air at the user most remote from the air receiver. A good rule
of thumb is to allow no more than 108 of the receiver pressure for
Line loss from receiver to point of use.W FLUOR
PROCESS
uTiLiTy
MANUALS
3.4
VOLUME 41 ~ AIR, FUEL AND WATER SYSTEMS
es “ 7 st NUMBER
PAGE 4
DATE 12-79
1.1.0
COMPRESSED AIR SYSTEMS
DESIGN DISCUSSION
system Pressure (Continued)
Process uses and operating devices often require a higher air
pressure than 100 psig. The Process Utility Engineer must check
the process and operating requirements to assure himself that he
has sufficient air pressure to satisfy these conditions.
Air Quality
ven when no particular dewpoint is specified for the plant air, it
is best to supply it as moisture-free as possible. This minimizes
Corrosion and the danger of freezing of tools and other users. The
plant air system should also be free of combustible and corrosive
gases, dirt and excessive oil.
system Capacity,
plant air demands are very difficult to estimate for most refineries
and chemical plants. When no specific information is available on
plant air requirements, a general rule is that plant air capacity
Enould be at least equal to the instrument air requirements. Tt is
conceivable that some plants could require a high amount of plant
Gir and very little instrument air, This is especially true in
plants where regeneration air is a requirement.
the amount of air consumed by various tools is shown in Table T, in
Section 1.3.0 of this Manual. We must provide sufficient capacity
to handle present needs, with some additional capacity for the
future. If plant expansion is expected, allowance must be made in
‘he distribution system and plot space allocated for future
installation of compressors and associated equipment.
increased demand is taken care of by assuming a load rise factor
and spoiving this to the calculated air requirements. This excess
capacity factor may vary from 5 - 50%. To determine a reasonable
factor, the utility engineer should check operating experiences
from similar installations, review future production plans and
schedules, and investigate any other sources of available
information.
. neaks in the air system and tool connections are often assumed by
@plane designers. ‘Tere is no justification for increasing, the
a aeerescor capacity by more than 10% to compensate for leaks-
eeereer piping will hold air just as tightly as any other piping
ioe ies fluid. ‘The excess capacity factor is determined byFLUOR
PROCESS
uriuity
MANUALS
VOLUME 41 ~ AIR, FUEL AND WATER SYSTEMS.
MUNBER 1.1.0
COMPRESSED AIR SYSTEMS PAGE = 5
DESIGN DISCUSSION DATE 12-79
System Capacity (Continued)
comparing CFM for continuous operation to CEM determined by load
factor.
‘This is added to the calculated figure to determine the
total system load. Table II serves as a record for the design of
the air system, and is used as follows:
ke
Set up tabulation as shown on Table IZ.
List names of tools and devices to be operated
by compressed air.
Enter tool location in correct column.
List number of tools of each type.
Enter each tool requirement in CFM, for continuous
operation (see Table I).
Calculate air requirement if tools are running
continuously.
Using load factor adjustment from Table IIT,
calculate actual continuous load requirement.
Add this requirement to the continuous load required
by process or other continuous operating requirements.
‘This total gives the design load for the plant.
Calculate allowance for leads, etc.
Add this to design load to obtain air compressor
capacity.
Plant air systems less than 200 SCFM are uncommon, and if a design
less than 200 SCFM is contemplated, this should be reviewed with
the customer.FLUOR
PROCESS
UTILITY
MANUALS
‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
NUMBER 2.2.0
COMPRESSED AIR SYSTEMS PAGE 1 of 38
DESIGN PROCEDURES DATE 12-79
1.0 COMPRESSORS
La
Introduction
Instrument and plant air compressors are generally of the
reciprocating or centrifugal types, although rotary screw
compressors have been used in these applications. The latter
machines tend to be very noisy and require extensive acoustical
treatment.
For capacities in the range of 200-2000 SCFM, reciprocating
compressors are suitable. Centrifugal compressors can be
considered when system requirements range upwards of 1000 SCFM.
‘The capacity breakpoint for selection of one type of machine over
the other is probably in the range of 1000-1500 CFM. For
installations having combined plants and instrument air
requirements in this range, centrifugal compressors should be
considered.
the requirements for compressed air in most plants can be
satisfactorily met by a packaged compressor unit, complete with
all accessories. On occasion, because of special circumstances,
Fluor may develop design criteria and specifications for the
compressors and related equipment separately. This is sometimes
done to meet Project or Client requirements which require
conformance to API, ASTM or other standards of construction which
may be difficult to obtain in off-the-shelf packaged units.
Process Specification
‘The Process Utility Engineer is responsible for initiating the air
through the use of
compressor specification. This is acct
Form E-537, Compressor Requirements (Section 1.3.0). The Process
Utility Engineer provides data for all itcms which sre marked with
an X. In addition, the following information should be provided
Guring the review of this specification with the responsible
Mechanical Engineer.
a. Suction pressure. whether this includes allowance for
intake filter, valve piping, etc.
b. Discharge pressure. Whether this refers to compressor
discharge flange, aftercooler outlet, or other.VOLUME 41 — AIR, FUEL AND WATER SYSTEMS,
W FLUOR NUMBER 1.2.0
PROCESS COMPRESSED AIR SYSTEMS PGE 2
UTILITY DATE 12-79
MANUALS DESIGN PROCEDURES
1.2 Process Specification (Continued)
©. Summer ambient conditions. Typically, summer maximum
temperatures and coincident relative humidity set the
compressor design head requirement.
4, Winter ambient conditions. ‘Typically, winter minimum
temperatures and coincident relative humidity set driver
horsepower requirements.
e. Method of compressor control required. A Utility system Flow
Diagram (if available) showing the air system is very useful
in defining its functions and determining the appropriate
control method. See Compressor Controls section of this
Manual. ————
Mode of operation of any standby machines, especially when
automatic startup is required. This may involve control of
a complicated, sequential series of events, especially in
the case of a steam turbine-driven standby compressor.
g. Whether the compressor should be lubed or non-lubed.
hh. Whether intercoolers should be machine-mounted (Flucr
usually prefers this).
i. Location. Indoors or outdoors.
Besides electric motor and steam-turbine drivers, air compressors
can also be supplied with natural gas, gasoline, and diesel engine
drivers. The difficulty with the latter drivers is the automatic
start feature required in standby service. These drivers tend to
be used in applications where manual starting is satisfactory.
When the driver is to be a steam turbine, it is the responsibility
of the Process Utility Engineer to provide certain information to
the responsible Mechanical Engineer. Form E-566, General Purpose
Steam Turbine, (Section 1.3.0), is used for this purpose. The
Following guidelines apply to the use of Form E-566.
Steam Conditions
a, Maximum inlet pressure psig should be specified at relief
valve setting on inlet header, usually as set at the boiler
plant.W FLUOR
PROCESS
uTILiTy
MANUALS
1.3
TOE #1 AT, FUEL AND WATER SYSTENS
oun sre NUMBER 1.2.0
cononssap Arn svsneNs mace
DESIGN PROCEDURES DATE = 12-79
Steam Conditions (Continued)
b. Maximum inlet temperature °F. Set same as inlet steam header.
c. Maximum exhaust pressure set at maximum pressure of steam header.
a. Normal pressure at inlet flange should be specified at least
15 psi less than supply header pressure.
e. Normal temperature at inlet flange should be the least superheat
temperature.
£. Normal pressure at exhaust flange for non-condensing service
should be 5 psi above exhaust header pressure.
g- Normal pressure at exhaust flange for condensing service usually
2" Hg above the saturation pressure of the condensate.
Note: I£ the air compressor is the reciprocating type, Fluor
prefers not to use steam turbine drivers because of
Compressor train torsional and gear reducer design problems.
Centrifugal Compressors
a. Equipment Selection
In present-day design of plant and instrument air systems, the
trend is towards providing package-type installations, consisting
of a base plate-mounted, multi-stage, oil-free centrifugal
compressor provided with intercoolers and built-in automatic
control. A pre-piped integral lube system is also included.
{ntake air filters are always required and these are normally
furnished with the compressor.
‘This type of unit is available with motor or steam turbine driver,
mounted on the same base plate.
the centrifugal compressor-based package unit offers some
attractive advantages over systems using reciprocating compressors:
@ Delivers oil-free air.
© ‘ower maintenance costs.
¢ Easier and less expensive installation.
@ Requires a small floor space.¥ FLUOR
PROCESS
UTILITY
MANUALS
LUME 47 — AIR, FUEL AND WATER SYSTEM
vo AIR, FUEL s NUMBER = 1.2.0
COMPRESSED AIR SYSTEMS PAGE 4g
DESIGN PROCEDURES DATE 12-79
Equipment Selection (Continued)
Most of the smaller units in the 1000 to 2100 CFM range are
capable of design pressures between 95 to 125 psig, which
makes them specially suited for plant and instrument air
applications. Units in this capacity range are usually
three-stage machines.
Computations
In the early stages of a job, before vendor information is
available, the Process Utility Engineer may have to calculate
preliminary values for driver horsepower and cooling water
requirements. These can be determined in the following
manner.
Cooling Water Requirements
The cooling water rates for intercoolers and aftercoolers can
be estimated, based on a calculated temperature rise through
each compression stage. A procedure for calculating the
discharge temperature for centrifugal compressors is outlined
in the Compressors section of Process Volume IT.
In addition, the requirements of the lube oi} cooler have to
be considered. As a general rule, 15% of the intercooler and
aftercooler cooling water rates should be added in order to
obtain a preliminary estimate.
Driver Horsepower
Approximate values for driver horsepower versus centrifugal
compressor capacity are shown in Graph I. This plot reflects
data for package units offered by: several vendors.
Additional methods for estimating these and other compressor
characteristics include those described in:
© Compressor Performance Calculations and Selection, Elliott Co.
Compressor Performance Calculations and Selection,
Bulletin P-11A.
© Quick Method for Centrifugal Compressor Estimates.
Hydrocarbon Processing, October 1965, Vol. 44, N. 10.C)
YW FLUOR
PROCESS
uTiLiTy
MANUALS:
VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
NUMBER 1.2.0
COMPRESSED AIR SYSTEM PAGE = 5
12-79
DESIGN PROCEDURES DATE
1.4 Reciprocating Compressors
Equipment Selection
gnall system capacities (less than 1000 Scr) or other project
design criteria may dictate the use of a reciprocating
compressor. In this case, a decision must be made between
lubricated and non-lubricated designs.
instrument air must be dry and oil-free. Desiccant dryers
are normally used for drying the air. Oil-free air is almost
{npossible to obtain from a lubricated reciprocating compressor -
There are various patented oil removal devices, but these never
‘seem to do the complete job over a long period of operation.
When these separators are new and maintained correctly, they
will remove most of the oil, but after a few years of
operation, oil tends to build up in the instrument air
distribution system.
the presence of oil in compressed air can also be hazardous.
API Standard 618, Reciprocating Compressors for General
Refinery Services, recommends a high discharge temperature
Giarm or shutdown for air compressors which are lubricated by
hydrocarbons. This is intended to prevent fire and possible
explosion resulting from combustion of the lubricant.
‘he non-Lubricated reciprocating compressor is designed to
provide oil-free air. This compressor is constructed so thas
ee oil is present in the cylinder where the air is compressed.
The distance piece between the compressor cylinder and the
crankcase is made into two compartments. This prevents oil
from the crankcase leaking along the piston rod into the
compression cylinder.
Many manufacturers use carbon piston rings with cast iron
cylinders and some use teflon rings with stainless steel
Gylinder liners. the big problen with carbon rings and cast
{ron cylinders is that the piston must be moving continuously
go that no rust can form in the cylinder. Even after a short
Shutdown period, rust can be a problem. This means that the
spare compressor can't vse carbon rings and cast iron
cylinders.
Fluor's experience shows that the economic advantage of using
lubricated compressors is usually outweighed by the problems
with the compressors and downstream equipment.VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
Virilor NUMER 1.2.0
Process COMPRESSED AIK s¥STEus PACE 6
uriuity SOWPRESSED AIR SYSTENS
wana DESIGN PROCEDURES DATE aze79
1.4 Reciprocating Compressors (Continued)
Computations
Preliminary values for driver horsepower and cooling water
requirements are frequently required before vendor data are
available. ‘These can be determined in the following manner.
Gooling Water Requirements
Reciprocating air compressors in the smaller sizes, to about
100 Horsepower, can be air-cooled.
However, most plants usually have compressors large enough to
require cooling water. This is water from the plant cooling
water circulation system. Cooling water to compressor
jackets removes 15-40% of the total heat of compression
depending upon cylinder size, rpm, compression ratio and
other factors, Intercoolers on two-stage units will remove
30-35% of the total heat of compression plus the latent heat
from moisture condensation. It is desirable that the water
enter the cylinder jackets at a temperature at least 10° to
1S°F higher than the air intake temperature. This prevents
initial condensation of moisture from the air on the heads
and walls of the compressor cylinders. For single-stage
units, the cooling water can pass first through the oil.
cooler and then into the cylinder jackets. On two-stage
units, the problem is solved by passing the cold water through
the intercooler first then through the cylinder jackets. The
water temperature rise across the compressor cylinder jacket
should be a maximum of 15°r,
The cooling water rates given in Table IV can be used for
preparing the first draft of the utility system flow diagram
and the initial plant cooling water balance. Cylinder jacket
cooling water requirements can also be estimated by means of
heat rejection calculations (See Graph II, Section 1.3.0).
The design pressure for the cooling water system usually
depends on the shut-off pressure of the cooling water pump.
This is usually 100 to 115 psig. The water jackets of the
compressor cylinders are frequently designed for 60-75 psig.
The Process Utility Engineer must provide a relief valve on
the outlet piping if the water returns to a closed system.
The relief valve can be omitted if the water from the cylinderW FLUOR
PROCESS
UTILITY
MANUALS:
VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
NUMBER 1.2.0
COMPRESSED AIR SYSTEMS PAGE = 7
DESIGN PROCEDURES DATE 12-79
Cooling Water Requirements (Continued)
jacket goes to the sewer. The amount (and destination) of
Zooling tower blowdown required will usually decide where the
return line should go.
Driver Horsepower
Approximate brake horsepower requirenents can be obtained by
reference to Table VI. Driver horsepower can also be
ictimatea by use of charts found in the Compressors section
of Process Manual Vol. II.FLUOR
PROCESS
uTiLity
MANUALS
VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
NUMBER 1.2.0
COMPRESSED ATR SYSTEMS PAGE 8
DESIGN PROCEDURES DATE = 12-79
2.0 COMPRESSOR CONTROLS
2a
Centrifugal Compressors
Most compressed air systems-that the Process Utility Engineer will
encounter involve the use of package units, which are supplied
complete with all the necessary controls. However, the Engineer
should have an understanding of the principles involved so that he
and the responsible Control System and Mechanical Engineers can
work together to assure that the compressor vendor provides the
proper controls for each particular application.
A basic requirement of instrument and plant air systems is that
they be able to continuously supply air at constant pressures, or
over reasonably small pressure ranges, despite variations in
demand. The compressor control system must be designed to meet
these requirements, while at the same time protecting the
compressor and its accessories from maloperation and damage.
‘Two typical control methods are illustrated in Figures 2.1.1 and
2.1.2. Each scheme has its place, depending upon the magnitude
of fluctuations in the plant demand for compressed air. Both are
based on the use of a constant speed driver, such as an electric
motor. The following paragraphs describe the essential features
of these two schemes.
a. Constant Pressure Control (Pigure 2.1.1)
General
The compressor is supplied with a pneumatically-activated constant
pressure and surge control system. The purpose of the control is
to provide a constant discharge pressure and also provide automatic
surge control to protect the equipment during periods of low demand.
Constant Pressure Control
The pressure control system is of the constant speed inlet throttle
valve type. As the system demand falls off, the compressor will
tend to establish a new operating point at the reduced flow but at
a higher pressure on its constant speed characteristic curve. A
remotely-located pressure transmitter will sense the increase in
pressure and send a 3 to 15 psig signal to a panel mounted pressure
controller. This controller will in turn transmit a signal to close
the butterfly valve located in the compressor suction line. ‘TheVOLUME 41 — AIR, FUEL AND WATER SYSTEMS
FLUOR NUMBER 2.2.0
PROCESS COMPRESSED AIR SYSTEMS PAGE 9
, OTILITy DESIGN PROCEDURE:
MANUALS. DESIGN PROCEDURES. DATE 12-79
FIGURE 2.1.1
CONSTANT PRESSURE CONTROL SCHEMATIC
ORIFICE
DISCHARGE an TO PROCESS
r ary
1 \ \
1 i \
oO INDICATING DIFFERENTIAL
PRESSURE PRESSURE
DRIVER TRANSMITTER | [TRANSMITTER
7 T
\ SUCTION | 1
1 1
\ '
1 1
1 FLOW
) ' CONTROLLER
\ \ ———
\ ' 1
1 1 \
1 \
\ 1 1
' 1
' FILTERED pypAss
i suppiy VALVE
' 20 PSIG
1 1
' TO ATMOSPHERE
PRESSURE
CONTROLLER
F
1
'
BUTTERFLY \ MANUAL
CONTROL 77] OVERRIDE
VALVE
1
1
FILTERED
) AIR
SUPPLY
20 PSIGVOLUME 41 — AIR, FUEL AND WATER SYSTEMS
FLUOR NUMBER 1.2.0
PROCESS COMPRESSED AIR SYSTEMS PAGE 20
uTiuiry DESIGN PROCEDURES DATE 12-79
MANUALS
Constant Pressure Control (Continued)
valve will close to a position where the compressor flow has
decreased to a point that satisfies the system demand and
equilibrium is again established.
Surge Control
‘The compressor surge control is the blow-off type with the controls
arranged in a closed loop. The actual compressor flow is measured
by an orifice plate in the compressor discharge and compared with a
minimum stable flow in the flow controller. A differential pressure
transmitter takes the orifice differential reading and transmits a
3 to 15 psig signal to the flow controller. This controller in turn
transmits a signal to a blow-off valve to maintain the flow of the
compressor above the surge limit. As long as the system requirement
is above the surge limit, the blow-off valve is closed. The sum of
the flow to process and the flow through the blow-off valve will
always be equal to or greater than the minimum stable compressor
flow. The differential pressure transmitter is located at the
orifice while the flow receiver controller is panel mounted. Since
the discharge temperature will. experience minor variations, no
expensive density compensation equipment is required.
Start-up
A manual over-ride is included on the system for start-up operation.
In order to relieve the duty of the motor during the starting period,
it is desirable to have the butterfly valve closed. The loss of
instrument air will cause the butterfly valve on the compressor
suction to close and the bypass valve to open. This is the desired
position of the valve for unloading the motor during start-up. After
start-up, instrument air is required to open the inlet butterfly
valve and close the blow-off valve in order to load the compressor.
Total Closure Control (Figure 2.1.2)
General
‘The Total Closure Control System allows efficient operation of the
compressor for applications where the air demand is a normal base
load but does have intermittent fluctuations much below the base
load.(UME a1 ~ AIR, FUEL AND WATER SYSTEMS
~~ ‘ TER NUMBER =1.2.0
PAGE aL
DATE 12-79
COMPRESSED AIR SYSTEMS
DESIGN PROCEDURES
Base Load
with air demand between 75¢ capacity and 100% capacity, the
compressor operates on its normal performance curve delivering air
continuously at the required rate and at the system pressure. The
compressor suction throttle valve is open and the bypass valve is
closed during this operation. During operation at air inlet
‘temperatures less than the rated air temperature, the compressor
operating as base load can deliver over 100% capacity. This adds
capability to the total air system and can be a major advantage.
Motor overloading is prevented during this excess capacity
operation by the motor overload control. This control senses the
motor amperes and translates the amperes to a pneumatic signal.
‘his signal in turn regulates the position of the suction throttle
valve limiting the compressor capacity to a desired motor load.
Load Fluctuations
‘The compressor is allowed to operate between two pre-determined
pressures on its operating curve. The compressor air system and/or
the receiver provide the storage capacity for the compressed air.
‘The system is pumped up to a pre-set maximum pressure. This
unloading pressure is so determined that it will fall just inside
the stable operating range of the compressor. when the system
reaches this pressure, the air to the compressor is shut off by
closing the inlet or total closure valve. At the same time, the
discharge side of the compressor, before the check valve, is
completely unloaded to atmosphere by a bypass valve. The compressed
air system then supplies the air to fulfill the system demands until
‘the pre-set minimum pressure on the compressor operating curve is
reached. When the system falls to this pressure, the inlet
butterfly valve is opened and the bypass valve is closed,
automatically loading the compressor.
Start:
A manval override is included in the above system for start-up
operation. In order to relieve the duty of the motor during the
starting period, it is desirable to have the butterfly valve
closed. Th loss of instrument air will cause the butterfly valve
fon the compcessor suction to close and the bypass valve to open.
‘ais is the desired position of the valve for unloading the motor
during start-up. After start-up, instrument air is required to
open the inlet butterfly valve and close the blow-off vaive in
order to load the compressor.VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
W FLUOR NUMBER 1.2.0
PROCESS COMPRESSED AIR SYSTEMS PAGE 12
utiuity yesrGN PROCEDURES
TE
Nas DESIGN PROCEDURES DATE 12-79
PIGURE 2.1.2
TOTAL CLOSURE CONTROL SCHEMATIC
DISCHARGE, \} *_TREceiver!
—_ | AND/OR
CHECK | PIPING
VALVE |system |__>
TO
O = T—~ DEMAND
DRIVER 5)
1 1 SUCTION
|
BUTTERFLY
TYPE THROTTLE
VALVE
TO ATMOSPHERE
VA
a ISWITCHES
1
1
H
1
1
'
BYPASS '
'
1
'
1
1
.LVE.
1
FLOW
ICONTROL
VALVE
MANUAL
OVERRIDE
--TL-
Il
FILTERED
AIR
SUPPLY
20 PSIGWV FLUOR
PROCESS
UTILITY
MANUALS
VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
NUMBER 1.2.0
COMPRESSED AIR SYSTEMS PAGE = 13,
DESIGN PROCEDURES DATE 12-79
2.0 COMPRESSOR CONTROLS (Continued)
2.2
Reciprocating Compressors
In reciprocating machines, air flow and pressure may be controlled
in four ways:
a. Manually
b. Automatic start-stop
¢. Constant running control (unloaders), or
@. Automatic stert-stop with constant running control
Manual control is seldom used in refineries or chemical plants.
Automatic start-stop control is used when the demand for air is
infrequent. When using start-stop control, the compressor should
be designed to operate less than 50 percent of the time. This
control works best with an electric motor driven compressor because
of the ease with which the machine can be started and stopped. The
control signal normally comes from a pressure switch located on the /
air receiver. For a 100 psig air, system, the pressure switch should /
be set to start the compressor at™{10 psig and stop it at 125 psig
depending upon the upper range of the compressor discharge. One
should never design a start-stop control system in which the motor
cycles more than 4 times per hour. In these instances, the receiver
size should be increased or a different method of control installed.
‘The constant running control is recommended where compressed air
requirements are steady or where the receiver is so small that the
‘compressor has to operate more than SO percent of the time. The
motor driver runs continuously, but the compressor actually compresses
air only between pre-determined limits. Some type of pilot unloader
is used and upper and lower limits of pressure are set at a 10 to 15
pei differential. This pilot type unloader will operate in one of
three ways, ie., (1) by throttling the compressor intake line, (2) by
Lifting the suction valves, or (3) by opening clearance pockets in
the cylinders. Inlet valve unloading is the preferred method on
the smaller and medium sized units. This type of control is used
for most plant and instrument air systems.
yor larger units, clearance control and a combination of inlet valve
unloading and clearance is used. Inlet valve unloading involves
holding the inlet valve plate or plates off their seats, preventing
the compression of air in the unloaded cylinder. Clearance control
involves the opening of volume chambers into the cylinder in a
preset order. The air is compressed into the chamber or chanbersVOLUME 41 — AIR, FUEL AND WATER SYSTEMS
W FLUOR NUMBER 1.2.0
PROCESS COMPRESSED AIR SYSTEMS PAGE 14
uritity
32-7
waNUALS DESIGN PROCEDURES DATE 9
2.2 Reciprocating Compressors (Continued)
y. \ instead of being discharged. On the suction stroke, the air in the
chamber expands behind the piston, returning the power previously
required for compression.
‘A dual control system is used when the spare compressor for the
instrument air system is the plant air compressor. For the
instrument air system, this spare would be on constant running
control, but when operating only as a plant air compressor it
would be on start-stop control.
Various steps of capacity output may be obtained with these
controls. The usual type is the three-step control. This means
the compressor has a capacity of 0, 50, or 100 percent. When the
compressors are quite large, say over 500 SCFM, the five-step
control may be more favorable. This gives capacities of 0, 25,
50, 75 and 100 percent.
Regulator and control operating air should be taken directly
from a point near the top of the receiver. This is done in
order to obtain clean, dry air at a more constant pressure.
For initial start-up, the Process Utility Engineer has to make
sure the unloading controls can be by-passed for start-up
without requiring instrument air.
Compressors bought for 110 psig discharge usually have the relief
valve set at 125 psig to give adequate range for unloading
control. The Process Utility Engineer should always check the
Successful vendor's quotation to make sure that there is indeed
adequate range for control.FLUOR
PROCESS
UTILITY
MANUALS:
‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
HUMBER 1.2.0
COMPRESSED AIR SYSTEMS PAGE 15,
DESIGN PROCEDURES DATE = 12-79
3.0 EXCHANGERS
3.
Intercoolers
a. General
‘he exchanger between stages of a compressor is called an
intercooler. Intercoolers are normally furnished with the
compressor and are an integral part of the compressor assembly.
Special circumstances may require that Fluor obtain the
intercoolers from another source. In this case, the Process
Utility Engineer must prepare Exchanger Specification Sheets,
Form E-S63A/B (Section 1.3.0) to define the intercooler duties;
design temperatures and pressures must be obtained from the
compressor vendor for each such service.
b. Design
Cooling Water Requirements. Table IV can be used to estimate
Zooling water requirements for reciprocating aiz compressors,
for use in plant water balances prior to the time that vendor
information is available. Water requirements may also be
determined by the use of Graph III, which gives air discharge
temperatures for each stage of compression as a function of
that stage's compression ratio. The compression ratio may be
calculated from the following formula:
n= Number of stages
Compressor Discharge Pressure (psia)
= Compressor Suction Pressure (psia)
Discharge Pressure of the first stage
R = Compression Ratio (assume equal for all stages)VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
FLUOR NUMBER 1.2.0
PROCESS COMPRESSED AIR SYSTEMS PAGE 1s
UTILITY
NANUALS DESIGN PROCEDURES DATE 12-79
Cooling Water Requirements. (Continued)
Assuming a 15 to 20 approach between the cooled air and the
inlet water, and using the allowable cooling water temperature
rise specified for each particular project, the duty and cooling
water requirements for the intercooler can be calculated.
Other Criteria. The following criteria should generally apply
to the design of these exchangers, whether supplied by the
compressor vendor or others.
© Intercoolers are usually designed with air flow in the shell
side and cooling water in the tubes.
© Water condensed in the intercooler is trapped and drained
from the exchanger to prevent damage to the following
cylinder or stage.
© Water velocity through the intercooler generally ranges from
5 to 10 feet per second.
© Airside pressure drop usually runs 3 to 5 psi.
© Waterside pressure drop usually runs 5 to 15 psi.
© Each 10°F reduction in air temperature between stages
reduces power input by approximately 1%.
* When the vendor supplies the intercooler, he usually
furnishes the required instrumentation, including temperature
and pressure indicators, pressure safety valves, traps, and
high water level alarms. when the exchanger’ is supplied
from another source, the Process Utility Engineer must make
certain that adequate instrumentation is provided to protect
the equipment and measure its performance.
© Even when the compressor vendor supplies the intercoolers,
the Process Utility Engineer is responsible for specifying
any special conditions that apply to the intercooler design.
For example, vendors cormonly use Admiralty tubes. Because
of water quality or other reasons, project standards
sometimes call for use of steel tubes. This requirement
must be made known to the responsible Mechanical Engineer,
along with any other factors that will influence the
exchanger design. Cooling water fouling factor is a good
example of the latter‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
FLUOR NUMBER 1.2.0
PROCESS COMPRESSED AIR SYSTEMS PAGE = 17
UTILITY gn EES
TE -
aANUALS DESIGN PROCEDURES Da 12-79
3.2. Aftercoolers
General,
‘an aftercooler is an exchanger installed on the discharge of an air
Conpressor to reduce the air temperature prior to drying or other
use of this stream.
the aftercooler may be furnished by the compressor vendor or others.
Fluor's usual practice is to have the compressor vendor quote the
aftercooler ag a separate item. This should be noted in the
senarke column of the Compressor Requirements Specification Sheet,
Form E-537.
ime Process Utility Engineer should also prepare @ separate
exchanger specification sheet which can be submitted to exchanger
vendors for quotation.
b>. Design
cooling Water Requirements. For use in preliminary plant
EStances, cooling water requirements can be estimated by the
methods described in Paragraph 3.1.
Piping. Typical piping arrangements are shown on the flow
Zingrans presented in the back of this Manual. It is
preferable to have an aftercooler on each compressor, with 2
Block valve placed downstream of the aftercooler so that it
fan be inspected each time the compressor is down for repairs.
This is especially true in the case of aftercoolers operating
{n the discharge of reciprocating compressors, which have &
history of leakage due to loosening of the tubes from the
pulsating flow.
Other Criteria.
e the air leaving the aftercooler should be approximately
10°F.
e water velocity through the aftercooler should range from
5 to 10 feet per second.
@ Airside pressure Grop usually runs 2 to 3 psi.
Waterside pressure dzop usually runs 5 to 10 psi-‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
NUMBER 1.2.0
PAGE = ag
COMPRESSED ATR SYSTEMS
DATE = 12-79
DESIGN PROCEDURES
Other Criteria, (Continued)
© The design pressure and temperature for the shell side of
the aftercooler are the same as for the compressor. For
example, for a two-stage, reciprocating compressor
discharging at a maximum of 125 psig, the design pressure
is usually set at 150 psig while the design temperature
is 350°F. Check with the compressor vendor to obtain the
design figures for his particular machine.
© If the aftercooler is to operate on the discharge of a
reciprocating compressor, and it is supplied by other
than the compressor vendor, the Process Utility Engineer
should point out in the remarks section of the exchanger
specification sheet that it will be subjected to pulsating
flows and pressures.
© The aftercooler is usually furnished with a boot and
trap if it is supplied by the compressor vendor. If the
aftercooler is purchased from the exchanger vendor, it is
usually without the added expense of the boot and trap.
The aftercooler should be elevated above the air receiver
inlet when not provided with a boot and trap. The air
receiver serves as a boot in this instance.
© The aftercooler should be located inside a building
whenever the plant location has a design ambient
temperature below 32°F. In the event that it becomes
necessary to locate the air system outside in a freezing
climate, steam tracing with insulation should be provided
on the outlet piping, boot and lower portion of the air
receiver.“VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
WFLUOR MuMBeR 1.2.0
PROCESS COMPRESSED AIR SYSTEMS PAGE 1s.
UTILITY DESIGN PROCEDURES DATE 12-79
MANUALS: za——
4.0 DRYERS
4.1 General
compressed air used in instrumentation, for automatic controls, and
in many process applications must be free of excess moisture. A
variety of air drying systems are available, ranging from simple
Yn-line, desiccant-£illed cartridges to elaborate, automatically-
controlled package units.
ithe selection of appropriate drying equipment for a given
application should be based upon the dewpoint required, the
quantity of air to be dried, and the temperature and pressure at
Ghich the air is available to the dryer from the compressor unit.
‘To compare the relative economics of alternative systens, the
costs of electricity, steam, and water must also be known.
he Process Utility Engineer is responsible for issuing the dryer
process requirements to the responsible Mechanical Engineex, This
is accomplished by means of the Dryers Specification Sheet,
Form E-550 (Section 1.3.0). While the Mechanical Engineer is
responsible for completing mechanical details of the specification
and securing quotations for appropriate equipment, the Utility
Process Engineer should have an understanding of what systems are
available, how they work, and how they should be applied.
4.2 Dryer Design
Figure 4.1.1 presents a comparison of the major characteristics of
Several different drying systems. In addition, there is the
ical or absorbent system which is based on the use of @
Geliquescent desiccant. The following paragraphs describe these
systems in more detail.
. Deliguescent_ Dryer
this type of dryer is filled with absorbents composed of chemical
gaits which have an affinity for moisture. The absorbent
(deliquescent) desiccant is slowly dissolved by the moisture it
removes and is periodically drained away. Tne required desiccant
jevel is maintained by manual additions of fresh, solid
deliquescent.\ FLUOR
PROCESS
UTILITY
MANUALS
VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
NUMBER 1.2.0
COMPRESSED AIR SYSTEMS PAGE — 20
DESIGN PROCEDURES DATE 12-79
FIGURE 4.1.1
Drying Systens
PRESSURE SWE ON WOT REGEN WaT ACGENERATED TPE coo
me TPE PL TRA
nae TA | nce | ay Slate | micunessune | cow racssune | PER
amtaShathe | rolwcuum | YOatwosevene | "Kin'funee’ | wethie posce | Werk Nee
DRYING SYSTEM
»
CONDITIONS
ne
r
Te | Oly
Usk
fi
{ay inagy rlow mance)
| _soru (00*F'@ Too PSIG
(0=5.000 | 200-20,000 | 0-1,000 | 300-5,000 | 300—30,000 | 100—10.000 | 01.000
ily EFTEIP] —go—ia9 | eomi20 | eo-is0 | 60-130 | eomig0 | eoniso | somis0 |
| TRREPBSURE|“eos,000 | 60-8000 | so-s.o00 | 20-soo0 | so-i,coo | sso | 50-300
| DUTT ee POTN S 5 = = .
LP SRE | <0 oetov|—sonsetow| “cou vr | ~eoa ur | coeur | ~eoaur | saseur
wuectaic| “Rate at"| “Ructirawe’ | YES YES Yes ves ORE ee
ott, | Pongo utd
cream] none | oma’ | ves | ves | ves | ves [none
FREES AR OF S| YES YES Yes oo ves ves TONE
[EXTERNAL AIR OR GAS] __NO NO NO YES, NO NO. aa
RECATTVECOHTRRISON Low Low MEDIUM MEDIUM ‘MEDIUM MEDIUM Low
(OF MAINTENANCE
| uses ee é a
| Sie ae
a oe
| / Ges £7 #
a. Deliguescent Dryer (Continued)
1B deliquescent dryer has only one tower and does not require
regeneration or power. Tt has no moving parts. This simplicity
makes it far less costly than either the regenerative or
refrigerant dryer. Its operating cost is also much less, in some
cases one-half to one-third the operating cost of the other types.
A deliquescent dryer also benefits from a prefilter to remove the
dirt and oil. This provision keeps the entire desiccant bed
clean and permits it to effectively remove moisture. An
afterfilter prevents desiccant carryover.‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
v NUMBER 1.2.0
PROCESS COMPRESSED AIR SYSTEMS pace | 2
uTiuity :
NANUALS DESIGN PROCEDURES DATE 12-79
a. Deliquescent Dryer (Continued)
Hygroscopic ingredients are usually blended with other
ingredients to control the pH of the effluent; other material
additions prevent corrosion, caking and channeling. Desiccants
may be formed into tablets at high pressure.
‘This type of dryer can be applied to compressed air systems with
flows ranging from 0-5000 acfm (100°F and 100 psig), temperatures
from 50 - 100°F, and pressures from 0 - 150 psig. These dryers
fare useful when product air dewpoints of 30°F or more are
satisfactory. It is the least expensive of the dryer types
discussed here. Fluor has used deliquescent dryers to achieve
15 - 20°F freeze point depressions in plant air systems.
b. Regenerative Dryer
‘This type of dryer is filled with regenerative desiccant which
absorbs water vapor from the air. Adsorption involves a physical
adhesion between the surface of the desiccant and the water vapor
which condenses as a very thin film on the desiccant's surface;
there are no chemical interactions. Adsorption is a reversible
and selective phenomenon. As long as contact between the adsorbent
and the water vapor is maintained, adsorption proceeds until the
water vapor pressure on the desiccants is equal to the vapor
pressure of the water vapor in the air being éried. Then,
equilibrium has been reached.
Nearly ail régenerative dryers consist of two or more adsorbent
chambers. One chamber is on operation while the other is being
regenerated.
tn some designs, the wet influent air flows in the upwazd direction,
in others, downwardly. When the upward direction is chosen, care
must be taken to prevent the force exerted by the fluid from
moving or fluidizing the desiccant because this material is hard
ana abrasive. If agitated, the beads, granules or pellets break,
creating smaller particles that cause further attrition. Since
these fines pass through bed supports and exit screens, loss of
capacity occurs.
‘the dryer is normally preceded by a prefilter if the compressor is
of the lubricated type. Even if the air compressor is of the
non-lubricated type, prefilter/separators should be provided to
Tenove any liguid water present in the feed air stream.WV FLUOR
PROCESS
UTILITY
MANUALS
VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
NUMBER 1.2.0
PAGE = 22
DATE 12-79
COMPRESSED AIR SYSTEMS
DESIGN PROCEDURES
c. Refrigerated Dryer
This type of dryer removes moisture by chilling the compressed air
below its dewpoint, causing water to condense out. Chiller air
outlet temperatures commonly range between 35 and 50°F, depending
on the needs of the user system. The cooled air is frequently
reheated in exchange with the incoming air, to reduce its relative
humidity and eliminate sweating of downstream air piping.
The refrigerated dryer has the following advantages, when compared
to other drying systems:
No consumable chemicals required.
Less piping than the regenerative types.
No heat input required.
Moisture removal is continuous, by means of automatic
@rainer on condensate separator.
Disadvantages include:
© ‘The dewpoint, at pressure, cannot be reduced below the
freezing point of water.
© ‘Tis system has more moving parts than the others, i-e., in
the refrigeration unit.
There are two basic designs for refrigerated drying systems.
Pigures 4.1.2 and 4.1.3 show their general flowschemes. The
principle difference between them is the cooling medium used to
chill the air. In one case (Figure 4.1.2), the refrigerant is
circulated through the air chiller, producing air with dewpoints
as low as 35°F, at pressure. “his is equivalent to an atmospheric
-dewpoint of -12°F. ‘The other design (Figure 4.1.3) uses the
refrigerant to chill water which is then circulated through the
air chiller. The later system is normally used to produce air
with dewpoints of 50°F and up, at pressure, corresponding to
atmospheric dewpoints of 4°F and up.
Control Mode
In the past, Fluor has recommended installation of semi-automatic
units, feeling that this would force plant operators to visit the
@ryer at least once a shift and cause them to be aware of any
system maloperation. However, the modern trend is towards
package dryer units supplied with automatic controls. Properly
designed, these dryers are quite reliable and capable of
unattended operation.OO
PIGURE 4.1.3
Refrigerated/Chiller Dryer
W FLUOR
PROCESS
UTILITY
MANUALS:
‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
MUNBER 2.2.0
PAGE = 23
DATE = 12-79
COMPRESSED AIR SYSTEMS
DESIGN PROCEDURES
emotuant CONDDEEYW FLUOR
PROCESS
UTILITY
MANUALS
‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
NUMBER 1.2.0
COMPRESSED AIR SYSTEMS PAGE 24
DESIGN PROCEDURES, DATE 12-79
e. Design Conditions
The dryer design pressure is set by the air receiver design
pressure. The design temperature is established by the dryer
vendor and is based on temperature limitations for his particular
desiccant.
Desiccants
A nunber of types of regenerative desiccants are commercially
available, with special grades formulated and manufactured to
meet specific adsorption tasks. All have extremely high
surface-to-mass ratios, in the range of 3 million ft?/1b
desiccant. Of the following desiccants, silica gels are mst
commonly supplied. Fluor sometimes insists on other materials,
notably alumina. Silica gels are less expensive than alumina,
but they tend to be degraded by liquid water whereas alumina
is not.
a. Granular Silica Gel (99% + SiO,). This material is of
irregular shape, amorphous, and extfemely porous. It is highly
compatible and inert with most fluids that need drying, but is
not reconmended for strong alkalies or hydrofluoric acid.
Manufacturers normally recommend regeneration temperatures of
350°F. Various grades exist for specific purposes, such as for
static dehumidification, selective adsorption, chromatography.
b, Bead~Type Modified Silica Gels. These are spherical in shape
and also extremely porous. They have a high degree of compati-
bility but should not be used with strong alkalies or HF. The
recommended regeneration temperature range is 300 to 500°F, the
latter being a maximum value.
c. Activated Alumina. These porous aluminum oxides are very
inert. Several grades and shapes are available (granular,
spherical). Regeneration temperature range is 350 to 600°F. the
spheroid shape is most often used for dynamic adsorption purposes.
4. Molecular Sieves. These substances are synthesized and are
available in rodlike pellets or spherical beads. Regeneration
temperatures of from 400 to 600°F are recommended for all types‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
Vr FLUOR NUMBER 1.2.0
PROCESS COMPRESSED AIR SYSTEMS PAGE = 25
UTILITY DESIGN PROCEDURES TE 12-79
MANUALS ———— pa
4.4 Desiccant Regeneration
a. General
Heat is liberated as the adsorbate attaches itself to the surface
of the desiccant. If this heat -- equal to the heat of wetting
Gné the heat of condensation -- is not carried away by either the
carrier fluid or by means of heat sinks or cooling coils, the
temperature of the desiccant bed will rise. As the temperature
rises, the relative humidity in the fluid decreases, and the
removal effectiveness of the desiccant decreases.
As already stated, the adsorptive process is reversible, the
driving force being the concentration differential (vapor pressure)
between the adsorbate on the desiccant surface and in the carrier
fluid. Therefore, to regenerate the adsorbent and to remove the
adsorbate, the desiccant should be purged with hot and/or dry gas.
Most often, the regeneration mode starts when the bed drying the
fluid reaches an equilibriun condition equal to the maximum
adsorbate concentration acceptable. In dual-chamber systems, a
@iversion valve -- or a series of valves -~ switches the wet
inlet to the already reactivated bed. Hot and/or dry gas then
passes countercurrent over the just-used wetted bed, until the
water is stripped and purged off. If heat is used, each
Qdsorbent has a maximum regeneration temperature specified by the
manufacturer. However, within this limit, the hotter or dryer the
regeneration fluid, the more thorough the regeneration and the
lower the effluent dewpoint.
One desiccant man onship between
regeneration temperature and effluent's dewpoint (assumed to be at
atmospheric pressure!
Temperature, °F Effluent Dewpoint, °F
280 -2
350 ~65
450 -108
Although solid adsorbents can withstand many cycles (alternate
‘adsorption and regeneration periods), there is an irreversible
(though moderate) reduction in capacity that should be taken into
consideration when systems are designed. This decay in dynamic
Sapacity is sometimes referred to as aging. The lower the
regeneration temperature, the less extensive the degree of aging.
When regeneration occurs without external heating sources, aging
is negligible.[UME 41 — AIR, FUEL AND WATER SYSTEMS
Vf FLUOR VOLUME 41 ~ AIR, NUMBER 1.2.0
PROCESS COMPRESSED AIR SYSTEMS PAGE 26
uTiuity DESIGN PROCEDURES DATE 12-79
MANUALS oo
a. General (Continued)
Aging should not be confused with contamination due to chemical
impurities -- e.g., oily tars that cover portions of the active
surface of the adsorbent. In some instances, contaminants can be
heated off, but it is always better to prevent these impurities
from reaching the desiccant. This can be accomplished by
scrubbing the gas inlet to the compressor or by using adequate
coalescing prefiltration to remove oil mists.
b. Regeneration Methods
Drying techniques are quite similar in all designs. It is really
the regeneration that varies, of which there are basically two
Kinds: heated and heatless. The various methods of regeneration
are described in the following paragraphs.
Internal Heat Regeneration. The heated method is the older one,
with the internal-heated type being the most common for smaller
units, up to 1,000 standard cfm (scfm) at 100 psig. ‘Two chambers
are usually involved, each containing a heater within the desiccant.
While one chamber is in operation, the desiccant in the other one
is being regenerated. This usually takes 4, 6 or 12 hours.
For small and medium-size units, up to about 15,000 scfm, the
two-chamber system is commonly recommended. For larger flows,
three or -- on occasion -- four chambers or towers are preferable.
When more than two chambers are needed, one chanber dries the
process fluid, one is being heated (regenerated), while the third
is being cooled. There are also occasions when single-chamber
systems are used. In such instances, however, drying is not
required on a continuous basis, and there is time to reactivate the
desiccant. However, since continuous flow of dry fluid is generally
needed, the dual-chamber design is preferred.
Desiccant dryers are equipped with switching or diversion valves
that alternate the flow between the two chambers. Although some
dryers have the heater-element sheath in direct contact with the
desiccant, this is not desirable because overheating the desiccant
reduces its usable life.
Internal heat-regenerated dryers rely upon condition and
radiation to transfer the heat to the desiccant. Because of this,
the size of the dryer is somewhat limited. There is also a small
flow of air or gas that passes over the heated desiccant to purgeW FLUOR
PROCESS
UTILITY
MANUALS
VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
NUMBER 1.2.0
COMPRESSED AIR SYSTEMS PAGE 27
DESIGN PROCEDURES DATE 12-79
Internal Heat Regeneration. (Continued)
moisture from the chamber. Figure 4.4.1 shows the flow circuit of
one such dryer, where wet gas enters through four-way Switching
Valve A to Desiccant Bed B ~~ through the stainless-steel,
cleanable Outlet Filter C and Outlet Check-Valve D -- to the
ary-gas outlet.
FIGURE 4.4.1
Dual Chamber, Internally-Heated,
Regenerative Desiccant Bed
“Let cinmber drying —— Wet ine 38353
A small portion of dried gas passes through Purge-Throttling-Valve
, Purge-Indicator F and Purge-Flow Orifice G, which controls the
s ges passes through Flow-Check Valve H. up
through Heater-Tube I and over Electric Heater J, after which it
enters the plenum area of Chamber K, flowing downvard tlrcugh the
wet-desiccant bed, countercurrent to the drying flow. Now
carrying previously adsorbed moisture, the gas exits to the
atmosphere through Exhaust Valve L.
Shortly before the end of the cooling period, the exhaust valve
closes to repressurize the reactivated chamber. Switchover takes
place with both chambers at line pressure, which eliminates
desiccant-bed attrition, displacement of switching-valve lubricant,
and line surges. As the left chamber is exhausted to the atmosphere
and its regeneration cycle started, the fully regenerated right
chanber dries gas at line pressure. Figure 4.4.2 shows chamber
internals for an internally-heated dryer.W FLUOR
PROCESS
UTILITY
MANUALS
7 SYSTEMS
VOLUME 41 — AIR, FUEL AND WATER NUMBER 2.2.0
COMPRESSED AIR SYSTEMS PAGE = 28
DESIGN PROCEDURES DATE = 12-79
FIGURE 4.4.2
Blectrically-Heated
Desiccant Bed
External Heat Regeneration. Another regeneration method -- which
has an atmospheric purge blower and a heater external to the
desiccant chambers -- does not draw upon the process stream for
purging needs. Atmospheric air is pulled into the regeneration loop
by means of a blower, which compresses the purge gas to compensate
for the pressure drop through the dryer piping and desiccant bed.
This technique should not be used if the environment from which the
purge air is drawn is heavily contaminated with corrosive or
desiccan* soisoning vapors.
Figure 4.4.3 shows a flow diagram for this dryer, where wet gas
enters four-way Switching Valve A and then passes down through
Desiccant Bed B and Outlet Check-Valve C to the dry-gas outlet. To
vegenerate simultaneously, ambient air is drawn through Blower~
Suction Filter-Silencer D, by means of Purge-Blower E. It then =VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
WW FLUOR
PROCESS COMPRESSED AIR SYSTEMS Pace
UTILITY DESIGN PROCEDURES
MANUALS: pate
external Heat Regeneration. (Continued)
NUMBER
1.2.0
29
12-79
goes through Heater F and Purge-Check Valve G, up through Desiccant
Sos teaching Valve A, and then through the open Exhaust Valve I
we ne atmosphere. The heated purge air then desorbs the water
seed h. During the drying cycle, a small portion of dry ai*
fron Pthrough Repressurization Valve J. Shortly before switchover,
Epmet valve 1 is closed, to allow the right chamber to be
pressurized through this line.
Repressurization prevents a sudden jolt to the desiccant when the
Stmosphere downwardly through Depressurization Valve
Protects the desiccant from fluidization during sis period.
rreee first cones onstrean. ‘The left chamber vents to Se
once
Brotecrenber is fully depressurized, Exhaust Valve T opens, and
Eegeneration begins. Switching back to the original chamber occurs
in the same manner.
Closed:
ircuit Regeneration. Closed-cireuit regeneration methods
cae reed for large flows of gases, when the atmospheric
are ortetpe ig undesirable, or when the venting of purge gas is
eam ceptable because of its value or toxicity. Closed-toop
Geyers are divided into three types: splitestream, ne convection
cetings split-stream, with convection cooling: and captive Bose
soch a pressurized blower. Good operation of the first Fo of
wets @ Wicems depends on the proportioning, differential-flow
control valve.‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
V FLUOR NUMBER 1.2.0
PROCESS COMPRESSED AIR SYSTEMS PAGE 30
UTILITY
MANUALS. DESL FROCEDES. DATE 12-79
Closed-Circuit Regeneration. (Continued)
To operate continuously and to have enough purge flow to carry
sensible heat for regeneration, these systems require about 208 of
rated flow. Regeneration flow is countercurrent to the direction
of process flow.
Split-Stream, No-Convection Cooling. Shown in Figure 4.4.4, this
system has wet gas piped directly to the intake of the
Digferential-Flow Control Valve A. It then passes to four-way
Switching Valve B, where it is directed downward through either
Chamber C or Chamber G. Dried gas exits at the chamber's bottom
to Switching Valve D, which directs it to point of use.
FIGURE 4.4.4
Split-stream, No Convection-Cooli!
Regeneration of one chamber is cocurrent with tlie ‘onstream time of
the other. A portion of the wet, incoming gas is tapped off -~
just ahead of the difgerential-flow control valve -~ as purge gas,
for removal of moisture from the chamber is being regenerated.
‘Thais purge stream first passes through Purge Metering Orifice E
to Heater F, and is then diverted through Valve D to the bottom
of the regenerating chamber. Passing upward through the bed, the
hot gas exits to Valve B, which directs it through Cooler H, where
moisture condenses. Coalescing Separator I then removes the
moisture, and the purge gas is returned to the system-input line
via Valve A.‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
NUMBER 1.2.0
W FLUOR
PROCESS COMPRESSED AIR SYSTEMS
uTiLity
MANUALS DESIGN PROCEDURES.
PAGE = 31
DATE = 12-79
split-Stream, With Convection Cooling. Sometimes, convection
secling is used to eliminate temperature bumps during chamber
seceches. ‘The difference between this system (Figure 4.4.5) and
the previous one is that after the purge stream passes throvsh
orifice E to Heater F, the heated gas is diverted through Purge
Switching Valve K to Switching Valve D, and then to the
Segenerating chanber's bottom. Also, the regeneration cycle has
a gesiceant convection-cooling phase. When moisture removal is
Gomplete (determined by timing or temperature devices), Heater F
fares off, and Purge Valve K is cycled to divert cool, purge gas
fhrough Valve B. This gas exits through Valves D and K -> passitg
through Cooler # and Separator I -- to rejoin the system input vis
valve A for further drying.
PIGURE 4.4.5
split-Stream Dryer With Convection Coolins
captive Purge with Pressurized Blower. This third type of closed
Toop system has a pressure blower and a captive volume of
qegtneration fluid. The technique uses cocurrent flow, i.e. the
regeneration gas flows in the same direction as the process stream,
This method of regeneration is not generally recommended by
Gosiceent manufacturers because it is an inefficient means of
Gecomplishing thorough renoval of moisture from the desiccant.
Heatiess Regeneration. A small portion of the dry effluent air at
working pressure is expanded to atmospheric pressure oF below
‘eacuun source), and passed countercurrently over the desiccant £0
A@fegenerated. The drying period for heaterless dryers is much
Shorter, § of 10 minutes, as opposed to 4 or 6 hours for the‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
WV FLUOR NUMBER 1.2.0
process COMPRESSED AIR SYSTEMS PAGE 32
UTILITY DESIGN PROCEDURES 2-79
MANUALS pate ,
Heatless Regeneration. (Continued)
heat-regenerated types. Yet, the general configuration and chamber
size are nearly comparable (Figure 4.4.6). ‘Therefore, the moisture
load per pound of desiccant is far less with the heaterless dryer,
where only 2 to 38 of the total bed-dynamic-capacity is utilized.
The remainder of the bed extracts the last traces of water vapor.
Similarly, much less energy is needed to regenerate the desiccant.
Since the cycle time is very short, the residual heat of
adsorption -- coupled with the super-dry, low-pressure purge -~ is
sufficient to yield very low effluent dewpoints: -40°F and lower
for the 5 minute period, and -100°F and lower for the 10 minute
period. The heaterless dryer has been widely accepted for drying
aix and for selective separation of gases.
FIGURE 4.4.6
Heaterless Dryer
TL TE A‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
v NUMBER 1.2.0
any COMPRESSED AIR SYSTEMS PAGE 33
i uTiuity
MANUALS DESIGN PROCEDURES paTE 12-79
5.0 AIR RECEIVERS
5.1 General
Air receivers perform four functions in utility and instrument
air systems:
a. Dampen pulsating effects, if used with reciprocating
compressors.
b. Provide a reservoir for the system.
c. Remove moisture droplets from the air leaving the aftercooler.
d. Limit the frequency of compressor loading and unloading.
Air receivers are classed as unfired pressure vessels by the ASME
and should be built to its standards.
Most compressor vendors will quote the receiver along with the
Aetercooler and the compressor. The difference in first cost
) betreen the receiver quoted by the compressor vendor and the one
Quoted by a vessel vendor is normally not significant enough to
Justify the difficulty experienced in obtaining dzawings from
the compressor vendor. The Process Utility Engineer usually
Sizes the air receiver and prepares a process vessel sketch.
This enables the responsible Vessel Engineer to design the
receiver and prepare quotation drawings. In this manner,
Piotplan layout can also proceed without waiting for vendor
information.
5.2 Design
a. Receiver Sizing. Minimum reconmended receiver sizes for
@ifferent system capacities are listed in Table V. Receiver
Volumes can also be calculated, to provide air over a
specified pressure range and time period.
the following formula can be used for this purpose:
y= 14.7) (e)_ (CPN)
PL PpW FLUOR
PROCESS
uTILiTy
MANUALS
- JEL AND WATE Ms,
VOLUME 41 — AIR, FU WATER SYSTEI NUMBER 2.2.0
PAGE
DATE
34
COMPRESSED AIR SYSTEMS
DESIGN PROCEDURES 22-79
(Continued)
Receiver Sizing.
V = Receiver volume cubic feet.
& = Time in minutes.
P, = Upper set pressure of the pressure controller, psia. [(()#
sor
P.
Lowest pressure at which system will operate, psia
(pressure at which the emergency air cuts in).
SCFM = Normal air consumption in standard cubic feet per
minute.
‘
Design Conditions. The design pressure and temperature are
‘the same as the ones used for the compressor and aftercooler.
For 110 psig compressor discharge, the design receiver
pressure is 150 psig and the design temperature 350°F.
Mechanical Details. The following guidelines should be
observed in the design of the air receiver.
© te air receiver can be either horizontal or vertical. A
vertical vessel is usually preferable as it requires less
plot area.
The receiver inlet nozzle should be located at least 30"
above the bottom tangent line. The outlet nozzle is located
on the top head. ‘The drain nozzle is located on the bottom
head.
the corrosion allowance is norsially 1/8".
The vessel support is usually a skirt. Pulsations from
reciprocating compressor tend to weaken any other type.
Instrumentation. ‘The following instruments are the minimum
required for the proper operation of the air receiver:
Pressure indicator and pressure switch located in the top
portion of the vessel.
‘Trap located at the bottom.
A level gage located in the lower portion of the vessel.
Safety valve located at the top or on the outlet pipe. (This
valve is a minimum size based on fire conditions since the
full compressor output is relieved at the compressor
discharge by a pressure safety valve at that location).FLUOR
PROCESS
uTiiTy
MANUALS:
VOLUME 41 AIR, FUEL AND WATER SYSTEMS
foun " NUMBER 1.2.0
COMPRESSED ATR SYSTEMS PAGE 35
DESIGN PROCEDURES DATE 12-79
6.0 FILTERS
6.
General
Filters are used in compressed air systems to protect the
compressors, dryers and air users from damage and maloperation.
Applications
a. Compressor Intake Filters
‘An intake filter is essential. ‘The usual filters are
oil-wetted, dry cloth, or oil-bath types. The lubricated air
compressor may use any one of the three types. If intake air
is unusually dirty, an oil bath filter should be used on
lubricated machines. The dry-cloth filter is more efficient
than the oil-wetted, but will load up faster and must be
cleaned more often.
A filter which contains oil should not be used with the
non-lubricated compressor. If the compressor vendor doesn't
furnish the filter, then the circular dry type may be used.
Usually, the vendor locates the intake filter directly on
the compressor intake nozzle. Where practical, we should
locate the filter outside where cool air is available. The
Filter should be located at least 10' above grade. For every
10" higher, the suction line should be increased one size
larger than the compressor intake nozzle. The final
arrangement must be reviewed with the compressor vendor to
make sure that the performance of his machine is not
adversely affected and the pressure drop allowed for the
inlet piping and filter is not exceeded.
b. Dryer Prefilter
A prefilter is not required when non-lubricated compressors
are used. However, when lubricated instrument air
compressors are used, or when lubricated plant air
compressors provide an emergency source of instrument air, a
prefilter is required. Oil contamination in compressed air
may catise such problems as erratic operation of pneumatic
controllers, valves and other instrumentation; contamination
of intermediate or end products when the air is used for
agitating a liquid or conveying solids; softening of hoses,W FLUOR
PROCESS
UTILITY
MANUALS
VOLUME 41 — AIR, FUEL AND WATER SYSTEMS vauer Tao
COMPRESSED AIR SYSTEMS PAGE = 36
DESIGN PROCEDURES DATE 12-79
Dryer Prefilter (Continued)
causing leaks and decreasing service life and contamination
of paint spraying equipment. Oil removal also protects air
drying equipment, keeping adsorbents at a high level of
activity, and prevents oil fouling of heat exchangers in
refrigerated dryers.
When the prefilter is required for dryer protection, it
should always be supplied by the dryer vendor and should be
part of the equipment covered by his guarantee. The Process
Utility Engineer is responsible for providing the dryer vendor
with a description of the quality and source of the air to be
dried. The Engineer should be familiar with the criteria
applying to the design of oil elimination devices; these are
discussed in Paragraph 6.3.
Dryer Afterfilter
This filter is a mechanical device designed to trap particles
of desiccant which may be carried over by air flow through
the dryer. This helps prevent maloperation of controls and
instruments serviced by the dried air system.
‘The afterfilter should always be provided by the dryer vendor
and should be a part of the equipment covered by his
guarantee.
6-3 O11 Removal,
General
During the compression cycle of the typical compressor, the
air temperature climbs to between 400°F and 700°F. Some of
‘the lubricating oil is vaporized and a portion may react with
the compressed air to form partially oxygenated carbon and
nitrogen compounds. Upon cooling, part of the vaporized oil
and these newly formed compounds condense to various size
droplets, which can be classified in two distinct phases:
one a vapor and the other a liquid. ‘The liquid phase can be
considered in two particle size ranges: 0.01 to 5 microns as
a mist, and above 5 microns as a spray. Particles larger
than 0.01 micron can be removed by filtration; smaller
particles can be removed by adsorption on a suitable medium.©
W FLUOR
PROCESS
UTILITY
MANUALS
‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS.
NUMBER 1.2.0
COMPRESSED AIR SYSTEMS PAGE = 37
DESIGN PROCEDURES DATE 12-79
General (Continued)
vany process air applications and certain instrument uses
require an oil vapor content lower than 10 ppm.
in choosing the most efficient oil vapor removal equipment,
it is first necessary to determine the actual or, if not
available, the theoretical content of oil vapor in the air.
This requires knowledge of the temperature of the air after
lit leaves the aftercooler, vapor pressure of the oil at the
air temperature, molecular weight of the oil and pressure of
the system. All this pertinent data is readily available
from locally mounted instruments, handbooks and lubricant
vendors.
he relationship between these factors can be expressed by
the following equation:
Weight of oil vapor in air =
vapor pressure) (oil molecular
(air pressure) (air molecular weight)
Water vapor partial pressure has been neglected since it is
very small compared to the total system pressure.
Oil Removal by Filtration
over 99 percent of the liguid oil in compressed air consists
of droplets in the size range of 0.05 microns to 0.1 micron.
Therefore, many types of mechanical filters or separators can
te omittea since gravitational, inertial impingement and other
such type separators do not effectively remove dropieis smaller
than 3 microns. But certain coalescing filters designed for
Submicronie aerosols will also remove larger sized droplets
Guthout clogging or even causing appreciable pressure drop.
These filters will also remove the sub-micron and larger
suspended solid contaminants, such as pipe scale and piping
compounds -
one example of the filters with fine pores are those made
from epoxy impregnated cellulose combined with inorganic
bese materials, Others are on the market as well. This type
of liquid of] removal equipment must precede vapor adsorbers
§é low oil effluents and long service is to be achieved.YW FLUOR
PROCESS
UTILITY
MANUALS
‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS:
NUMBER 1.2.0
COMPRESSED AIR SYSTEMS PAGE = 3
DESIGN PROCEDURES DATE 12-79
Oil Removal by Adsorption
041 droplets smaller than 0.01 micron can be considered as
“oil vapor", and as such can not be removed by using a
mechanical filter. However, oil vapor can be effectively
removed by adsorption. Efficiency for oil vapor adsorption
can be as high as 99.9 percent with proper selection of
contact time, vapor velocity, bed depth and type of
adsorbent -- assuming prior liquid-droplet removal.
Adsorbents. Normally, 8 x 12 or 6 x 16 mesh charcoal is used
for a carbon bed adsorber. Alumina, with its much greater
inherent strength, can be used in coarser meshes, 1/4 x 8
usually. The finer size particles are more efficient, require
shorter contact times, but produce higher pressure drops.
Because of the different strengths, carbon has a much greater
tendency to dust than does alumina.
For compressed air systems containing hydrogen sulfide,
carbon is not recommended since it will oxidize the sulfide
to free sulfur which will foul the adsorbent. In general,
carbon is more efficient for oil vapor than alumina,
especially when the air contains water vapor. Carbon is
more expensive than alumina but its greater oil capacity or
effective on-stream life often offsets the cost differential.
Adsorbent Bed Sizing. Generally, a deep narrow bed is
preferred within the range of maximum allowable velocity and
allowable pressure drop. The oil capacity of the adsorbents
vary but for activated carbon the deeper the bed, the
greater the oil vapor capacity (on a weight basis) before the
effluent oil content rises above the desired level. For
example, a 12-inch bed depth yields an approximated 15 percent
capacity, whereas a 36-inch bed will allow for a 20 percent
capacity.
Por a required removal efficiency, a specific contact time
can be selected on a basis of influent oil vapor content.
Increasing contact time means higher efficiencies (at constant
flow), but this in turn means larger vessels and larger
amounts of adsorbent and higher first cost. Longer contact
time may also mean greater pressure drop unless even larger
diameter vessels are used for reduced linear velocities.
As a case in point, using alumina, a contact time of 12
seconds will result in an efficiency of 99 percent.
Accessory Equipment. It is advisable to install an afterfilter
following the adsorber, to protect the air dryer or other
equipment and control systems.(s
W FLUOR
PROCESS
UTILITY
MANUALS.
TableI...
Table IT. .
Table IIT. .
Table IV. .
Table Vv. .
Table VI.
Graph...
Graph It. .
Graph TIT. .
Graph IV.
Graph Vo.
Form 6-537.
Form E-550
Form E-563A/B
Form 5-566
‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
MUNBER 1.3.0
PAGE 1 of 22
DATE = 12-79
COMPRESSED AIR SYSTEMS
TABLES, GRAPHS, AND FORMS
TABLES, GRAPHS, AND FORMS
Aix Requirements of Various Tools, U1-A02-1168
Compressed Air Consumption Computation, U1-A03-1168
Typical Tool Load Factor, Ul-A04-1168
Cooling Water Requirements for Reciprocating
Compressors, Ul-A05-1168
Data for Selection of Air Receiver, Ul-A06-1168
Reciprocating Compressor, Approximate Brake Horsepower
Requirements, U1-A07-1168
centrifugal Compressors, Motor Hoksepower Vs. Capacity
Heat Rejection from Compressor Cylinder Jacket,
U1-a09~1168
Gas Compression Temperatures for Various Values "K" or
“R," UL-A10-1168
Dew Point Conversion, U1-R08-1168
Moisture Content of Dry Air, UL-A12-1168
Compressor Requirements Specification sheet
Dryers Specification sheet
Shell and Tube Heat Exchanger Specification Sheets
(Two Cases)
General Purpose Steam Turbine Specification SheetVOLUME 41 — AIR, FUEL AND WATER SYSTEMS
W FLUOR NUMBER 1.3.0
PROCESS COMPRESSED AIR SYSTEMS PAGE 2
utiuiry ABLES, GRAPHS, AND FORE
Tues TABLES, GRAPHS, AND FORMS DATE 12-79
TABLE 1
AIR REQUIREMENTS OF VARIOUS TOOLS
Free Air, cfm at
© psig,
Tool 100% Load Factor
Grinders 6" and 8" Wheels... 0. ee ee eee ee OD ;
Grinders, 2" and 23" Wheels 2... ee eee ee ee ee HHO
File and Burr Mechines . 2s ett t ees 28
Rotary Sanders, 9" Pads). ee ee 8B
Rotary Sanders, 7" Pads... wiv antes 30
Sand Rammers and Tampers
"xh" cylinder se ee
Ag" x 5" Cylinder 6. ee ee ee ee ee OB
ab" x 6" cylinder ve
Chipping Hammers, Weighing 10-13 lbs 2.21) 1.0. 28-30
HOY vee ee eee ee eee eee
Weighing 2-4 lbs. 1... eee ee eee ee ee ee
Mut Setters to 5/16" Weighing 8 its... ........ 20
Mut Setters 2" to 3/k" Weighing 18 tbs 111222221 30
Sump Pumps, 145 Gals. (a 50 foot head) ......... 70
Paint Spray, Average we ee ee eee 7
Varies from os ee ee ee ee ee ee ee 220
Bushing foots (woninental)’ .) 1... ho
2" Diameter Weighing 26 Lbs 2.1... .22242+ 80
Steel Drills, Rotary Motors
Capacity up to i” Weighing 1-4 Ibs ......... 18-20
Capacity +" to 3/8" Weighing 6-8 Ibs | 1). 1.1) 20-k0
Capacity 4" to 3/4" Weighing 9-14 Ibs... LL. 70
Capacity 7/8" to 1" Weighing 25 Ibs... 2.2... 80
Capacity 14" Weighing 30 Lbs... 2.6 eee ee ee 95
Stee) Drills, Piston Type
capacity 4" to 3/k” Weighing 13-15 Lbs... . 2... M5
Capacity 7/8" to 12" Weighing 25-30 Ibs 1.2... 75-80
Capacity 1" to 2" Weighing 40-50 Ibs . 1) 1222) 80-90
Capacity 2" to 3" Weighing 55-75 Ibs... 22... 2 200-110FLUOR
PROCESS
UTILITY
MANUALS.
VOLUME 41 —AIR, FUEL AND WATER SYSTEMS
COMPRESSED AIR SYSTEMS
TABLES, GRAPHS, AND FORMS
NUMBER 1.3.0
PAGE «3
DATE 12-79
TABLE I (Continued)
CUBIC FEET OF AIR PER MINUTE REQUIRED BY SAND BLAST
Compressed Air Gege Pressure
Wozzle
Diameter
60 tes. | To Les. | 60 tbs. | 100 Lbs.
aie" 4 5 5.5 6.5 |
3/32" 9 a ue 15
1/8" aud 19 an 2
3/16" #8 43 4uT 5
aun 67 % 8 103
5/16" 105 ng 333 161
3/8" as. in ash 232
a/2" 268 30h 3h0 ue |VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
COMPRESSED AIR SYSTEMS
TABLES, GRAPHS, AND FORMS
+xeuuew owes 213 uy poanduco
9ae spest xe} “ATUO soURUDRUTeU pue ‘aTedex ‘uoTZonpoad 103 SesN ZTE SMOUS eTqeI STUL :930N
ugg = uesoup Aazoedep woasis . = z0q9eg esTy-AayoedeD
39, x9 Teron
820308,
sxoputa9
sxoputa9
sejeary pueH
aseta pues
Aeads urea
asete pues
sxoj0aTy pueH
STUTaa Areacy
szeputz5
sx0a395 30N
sxeayaa nez0s
3STOH Uor-aubra
sxaddyyo
1) wo @ a) ty Te @ w
tsa wz ‘speeN -3030%4_— STOOL, JO Joo, «= STOO, ~—MOTaEOOT Toon,
papeon aTe 20ra peor —uor3ezedo ea yo
eanssora =9 “100 snonuFauog =u zOqUMN
XS “TOO Os uso
NOTIVENEHOD NOTLANNSNOD BIW GaSSaWaNOD
TT atau‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
FLUOR NUNBER 1.3.0
PROCESS COMPRESSED ATR SYSTEMS PAGE 5
uTILity cope
eats ‘TABLES, GRAPHS, AND FORMS DATE 12-79
TABLE III
TYPICAL TOOL LOAD FACTOR
ood Factor”
Grinders. eee 0.5-0.8
Chipper. nee ee eee ene O05
Hoist cc ee eee eee ee Ord O03
Serew Drivers see ee ee ee ee 018505
Mat Setters oe ee ee ee O4B5O5
Wood Borer se cee ee ees 0485
Rotary Drills see ee ee eee 0422005
Riveters oss e eee ee eee eee ees O20
a
Paint Spray ee ee ee ee eee OBL
Motors sees ween 021.0
*xote:
Factors vary appreciably from one refinery to
another, depending on age, tool condition,
number of maintenance and production jobs, etc.WW FLUOR VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
NUMBER 1.3.0
Process COMPRESSED AIR SYSTEMS. PAOEL &
UTILITY TABLES, GRAPHS, AND FORMS -
oa TABLES, GRAPHS, AND FORMS. DATE 12-79
IRBLE_IV
COOLING WATER REQUIREMENTS
RECIPROCATING COMPRESSORS,
(in Gallons Per 100 Cubic Feet Intake Air)
COOLING WATER
INLET TEMPERATURE, °F
60 70 80 90
Intercooler and Cylinder Jackets in Series,
‘Two-Stage Compression 2.9 34 4.0 4.5
Aftercoolers or Intercoolers:
‘Two-Stage Compression 28 3 3500 4
Single-stage Compression 4.0 45 5.2 6
Two-Stage Jackets
(L. P. and H. P. in Series) 0.85 1.0 1.2 1.4
Single Stage Jackets:
40 psig 0.5 0.6 0.7 0.9
60 psig 0.6 0.7 0.8 1.0
80 psig 0.7 0.8 0.9 1a
100 psig 0.8 0.9 1.0 1.2
Notes:
a. The above cooling water quantities are based on the air leaving the
aftercooler or intercooler within 20°F of the temperature of the
water entering the cooler.
b. ‘The cooling water temperature rise at these flowrates for the
cylinder jackets is about 15°F. If not more than 10°F rise is
contemplated in the design, the values given should be increased
by at least 50 percent.FLUOR
PROCESS
uTiLiry
MANUALS
VOLUME 41 ~ AIR, FUEL AND WATER SYSTEMS
COMPRESSED AIR SYSTEMS
TABLES, GRAPHS, AND FORMS
TABLE ¥
DATA FOR SELECTION OF AIR RECEIVER
NUMBER
PAGE
DATE
Minimum Based on One Minute at Actual Compressor Capacity And
100 psig System
1.3.0
7
12-79
ASME Sta. ASME Sté. Calculated Compressor
Dia. (I.D.) Length Capacity chet
Inches Feet 1) (2)
us 4 35 18 4s
16 6 85 43 n
ak 6 250 B 1g
7 260 130 3h
8) 450 < 22> 57
be 10 750 373 6
48 12 1,200 600 as
5h uy 1,750 75 223
60 16 2,500 1,250 pe
66 18 3,400 1,700 428
* CFM of Free Air at Compressor Inlet
(2) For Constant-Speed Regulation
(2) For Automatic Start and Stop ServiceYFLUOR VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
NUMBER 1.3.0
process COMPRESSED AIR SYSTEMS PAGE 8
MANUALS TABLES, GRAPHS, AND FORMS DATE = 12-79
TABLE VI.
RECIPROCATING COMPRESSOR
APPROXIMATE BRAKE HORSEPOWER REQUIREMENTS
(In BHP Per 100 Cubic Feet of Intake Air Per Minute Actually Delivered)
Single Stage ‘Two-Stage
_—~ ——Bi_ en |
Altitude 60 8 100 60 8 100 125
° 16.3 19.5 22.2 U7 17-1 19.2 21.3
1,000 16.1 19.2 21.7 W.5 16.8 18.7 20.9
2,000 15.9 16.9 21.3 W.3 16.5 18.4 20.5
3,000 15.7 18.6 20.9 14.0 16.1 18,0 20.0
4,000 15.4 18.2 20.6 13.8 15.8 17.7 19.6
5,000 15.2 17.9 20.3 13.5 15.5 17.3 19.2
6,000 15.0 17.6 20.0 13.3. 15.3 17.0 18.8
7,000 b.7 17.3 19.6 13.0 1k.g 16.6 18.4
8,000 W572 19.3 12.7 W.6 16.2 16.0
9,000 14.3 16.8 18.9 12.5 1.3 15.9 17.6
20,000 U1 16.5 16.6 12.3 Wl 15.6 17.2
Reference: Compressed Air and Ges Institute‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
YW FLUOR WUMBER 1.3.0
PROCESS COMPRESSED AIR SYSTEMS PAGE 9
UTILITY
MANUALS TABLES, GRAPHS, AND FORMS DATE 12-79
GRAPH I.
CENTRIFUGAL COMPRESSORS
MOTOR HORSEPOWER VS. CAPACITY
2400
2200
2000
1800
1600
1400
1200
MOTOR HORSEPOWER (CONNECTED)
800
600
400
200
1000 3000 5000 7000 ‘9000 11000
COMPRESSOR CAPACITY - INLET CFM
NOTES: 1, USE THIS GRAPH FOR PRELIMINARY ESTIMATES ONLY;
‘COMPRESSOR VENDOR TO CONFIRM.
2, GRAPH IS COMPOSITE OF DATA FROM SEVERAL PACKAGE
COMPRESSOR VENDORS, FOR SEA LEVEL OPERATION AT 80-125 psig.VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
ovus A . sr NUMBER 1.3.0
FLUOR
PROCESS COMPRESSED ATR SYSTEMS PAGE 10
uTIuity eo
DATE -
as, TABLES, GRAPHS, AND FORKS 32-79
gear or
HEAT REJECTION CALCULATIONS _
Cooling water quantities for cylinder jackets may be calculated
using Graph II to determine cylinder heat dissipation. This
graph is used for cylinders having a gas discharge temperature
of 250°F or greater, or for gas temperature rise greater than
170°F. The water inlet temperature should not be below 90°F, "
and should not exceed the inlet gas suction temperature by more
than 10°F except when the gas suction temperature is below 80°F. ;
A sample calculation to find the amount of cooling water
required is as follows:
rt, = 90°F
Inlet Water Temp, t, ,
Outlet Water Temp, t,,= 100°F
Inlet Gas Temp, t, 80°F
Outlet Gas Temp, t, 250°F (Minimum)
taverage=t,+ t, = 0+ 250 = 165
“asa +
z j
ty 165 - 90= 75 eb YO
From Graph II, the heat rejection is equal to 490 BTU/BHP/tour.
‘The approximate BHP per 100 cubic feet of intake air can be
obtained from Table VI at the desired working pressure. For a
100 psig pressure using a 2-stage compressor, the required BHP
per 100 cubic feet intake air is 19.1 at sea level.
490 x 19.1
300 x 1.88 GPM/CEM Free Air
Cooling Water Rate
With the above calculated cooling water, it may be expected that
the water outlet temperature should not be 10°F higher than the
water inlet temperature.3 * 008
eg | ACP IvaTy = M0 van ono “e400 vavess38 34009 38 ,
of S| 4 ‘13NOVP OL W3LVA 40 aUmvuaaraL = "5
a
« DSTO > HOTT, *
gue 4 “HUMLNIBAVGL YD 3BNURAY
|
a4
AND FORMS
COMPRESSED AIR SYSTEMS
GRAPHS ,
TABLES,
VOLUME 41 — AIR, FUEL ANO WATER SYSTEMS
002
Joon
008
8 ar3 srove wn Yssane va
af Bez “,AUVHO NOLLOIPIY LVaH
> iia A Haveo
= ~ ~
AH wad Wa u34 Me “WOLLOSNRH L¥3H1.3.0
-79
12
NUMBER
PAGE
DATE
|
2
a
ae
5 Gla
2 ae
Ss 43
= fa
ge
3
|
UTILITY
MANUALS
W FLUOR
PROCESS
No1ss3¥noo 40 O1L¥Y
“woLive3iswoo ¥30KN G36¥9 40 UMM 31K ONLLAL LISHED SNOILOVH 3HL_40 110134 BTOIION 39VLAGOURE HO ALIAYO
‘21419345 G31VHILS3 YO ‘ORLY INOW ‘HKONN 3IL NOUI O3NIVIGO 38 MVD SVD FHL JO BMWA .X, 3HL “ZL WONs OOH LOVMLANS
Jo ‘7 ONIA OL “3NIsnr 338030 ‘SZHnUVABeL sLmiosoy sv anssa¥oxd so Lowy % sua ** wth = 2 vino)
3 WOWS S35V0 40 SSUMLMYAUNEL HOISSIVANGD OLLVEVIOY Yo WOLLOHIL 3H JO NOLWNMEIL3O SLURS L4¥H0 3AoaY KL
S¥9 JO 3NWA WX,
e z
008 008 009 005 oh 0E ‘02 01 °
4g ‘L !3UMLV¥3aNsL J0¥vIOSIO
Yn YO wu SINTWA SNOIVA HOS
SIYNLVUIdHAL NOISSTYdHOD s¥O
sv49
z‘VOLUME 41 ~ AIR, FUEL AND WATER SYSTEMS
¥ mor MUNBER 1.3.0,
PROCESS COMPRESSED ATR SYSTEMS PAGE le
UTILITY TABLES, GRAPHS, AND FORMS DATE ~
MANUALS 22-79
SPeeLsVEATION SHEET
DRYERS seer vo. ro,
ome
ore,
roeno, _— sence 9,
*. a
eos TS
am surouine Ea] ne “paw wroarie Cel
1 TPE oF tema STON
=e
aE oF aT
teint) x
27 GLECTRICITY CONTMOLE seco . ¢ Te] ars —__rvase oat
A yeu panarornein weiner poor arr
So ne tui nim fe] mamem eS] amet
: x 7
TUIEMOAS trace wou agate fon tctioe Sa wee
whewVOLUME 41 ~ AIR, FUEL AND WATER SYSTEMS
W FLUOR
PROCESS
UTILITY
MANUALS
COMPRESSED AIR SYSTEMS
TABLES, GRAPHS, AND FORMS
GRAPH IV
DEW POINT CONVERSION
10
120
100
20
= 60
2 x
zo
2
z=
5 nn
“80
-80
“80
100
sioo a0 8002S
DEW POINT AT ATMOSPHERIC PRESSURE. °F
60
pate
a0
NUMBER 1.3.0
PAGE
13
12-79
100PROCESS
uTiuity
MANUALS
W FLUOR
COMPRESSED AIR SYSTEMS
TABLES, GRAPHS, AND FORMS
VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
NUMBER
PAGE
DaTE
saTueaTion TowreearuRe,
0
0
60
i ore
= MOISTURE CONTEXT
320 OF DRY AIR AT
VARIOUS SATURATION
‘TEMPERATURES
00
wo
0
20
00
0
00
0
x
00
20
260
no
20
0
a
TOTAL WORKING PRESSURE, PSIA
1.3.0
14
12-79VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
¥ ° . NUMBER =1.3.0
PROCESS COMPRESSED AIR sySTEMS PAGE «15.
utitity COMPRESSED ATR SYSTEMS
MANUALS TABLES, GRAPHS, AND FORMS DATE 12-79
‘FLUOR a
mockss seciFicaTion one.ey x exon
care x a
‘COMPRESSOR REQUIREMENTS.
x [are CPR ERY ORLY CEG ESTE RET OAR
* x oe x
si" ence Xn rece
x [ree Gleentmrvoat Dntornocarine Closer conecrzo Clatanso Loman
» Guoron nos ievnes oven
x [oniven: Clereas rnveine cance pmtss) (con
GASANALYSIE—MOLX | MW [RATED NORM. [ OTHER CONDITIONS [START ‘eNERAL
Soe oe te or
fimomn x ‘aN STEAM SONETON
ona Tne re =
ATER VAPOR Clexrnacrion rs
unin a Tan
Dwain onive, waxy a
ty reLosune
on
a
(Clsanoweren
(Dloesion renrenas
‘Dann vent
x Y
x
ores vauvesroucvanae—o [YT a9 ae enteren Be
eouPnesniniTy ar sverion 27 pe non
coueness at onewanoe ti x Te
neLaTive suwarTy Sat See a ae
mass rcon neni canons [XTX
east reow werr=cenn cay Ty = aaa aaa
[orcnating conoiTions = =u
ucron nessun ria aL
isouance rnestune. reins [xT
X ) capacrrv or excnmacnmers Cas ex 0 om 0.VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
W FLUOR NUMBER = 1.3.0
process COMPRESSED AIR SYSTEMS pace 17
unity TTRBLES, GRAPHS, AND FORMS pate 12-79
MANUALS
waqnet es
ea
rior en
SPECIFICATION SHEET ee
moe ae
SHELL AND TUBE oun ts
HEAT EXCHANGER
a
2 Silas
yy Sar ar
$n Se Sota ne
: FERGRIRRET OF OTETRT
1 eet crn
Sa TS Dyswem
i Cee
3 [astern
3 [tet wean
3 [Fetennemmae Teer iorrewW FLUOR
PROCESS
uTiLity
MANUALS
SQRSESEDSEEG RESELL ERE REELED
VOLUME 41 — AIR, FUEL AND WATER SYSTEMS.
NUMBER 1.3.0
COMPRESSED AIR SYSTEMS. PAGE = 18
TABLES, GRAPHS, AND FORMS DATE «12-79
¥FWWoR
tciricanion SHEET
SHELL AND TUBE HEAT
EXCHANGER (Continued)
‘Sai se
Fert =a
Te et (OV? Wer
BE OO (roensn eine ‘Wesel OV? Bune
sarc ro [eeoeston
Tet [tot Tar
TATERIALS (Manx STRESS REL EVED ~ SR RADIOGRAPREDRRT
SoCo
oo
Ban oe “Waee se
ROT SHE [nating a PAGNS RATING FANEYW FLUOR
PROCESS
UTILITY
MANUALS
1.4.0
‘VOLUME 41 — AIR, FUEL AND WATER SYSTEMS
NUMBER 1.4.0
PAGE =. of 3
DATE
COMPRESSED AIR SYSTEMS
FLOW DIAGRAMS
12-79
FLOW DIAGRAMS
‘The Standard System Plow Diagrams (1) included in this section were
drawn to be used as guides in setting up instrument and plant air
systens. The Process Utility Engineer should obtain copies and add or
delete information to fit these diagrams to his project's particular
process requirements or Client preferences.
these standard flow diagrams reflect the basic arrangement used on the
majority of Fluor jobs. ‘The instrument and plant air systems operate
lat the same pressure level. The compressors are usually the non-lubri-
cated type and are identical in size and mechanical design. One air
receiver is used for both systems, with the plant air take-off ahead of
the dryer.
the main advantage of the standard flow diagrams is that detailed system
flow diagrams can be completed early in the job. This expedites the
selection of the equipment and promotes early layout of the air systems.
(1) USPDO2 Instrument and Utility Air, Centrifugal Compressors
USFDO4 Instrument and Utility Air, Reciprocating CompressorsPIP Tse
Calenlating pressure drop
First, refer to Table L, "Fucturs for Caleulsting Pressure Loss Caused by
Five Crictton," Aypendia A ef this sectiva, For all finear rons of
iu difterert sections of the system, select a ballpark pipe si the
appropriate icfm for that seetion, ALL cables are based on tefm at PL
fsoe Section 1, “Systems Standards"). The calculation will determine
sresatrs drop in psi for specific conditions, If the pressure deop is
tow great, you shuld recalculate, using the next size of pipe. Here's
the formula co use wich the table:
ros
Faclor intersecting on table with selected ictm and pipe diumecer.
Prl ~ atmospheric pressure, peti
Pr2 = Desired pressure after compression, psig & Pri (psia).
[= Length of pipe in fee, as determined for the specific o.
culation,
prrection factor .vr valves, fittings, ete. (LE yew were to
calculate cach valve, elbow, fiteing, etc., the job would never
end, A correction factor of 1.2 will generally adjust the formula
for these ailded losses.)
easure Luss, psi.
Formilat
‘Too
Example: 1000 icfm, 14.6 psia atmospheric pressuce, 385’ pipe, 100 paix.
Example A--3" pipe:
2094 14.6,
oan 7
1.2 = 4.296 pst pressure loss
elsExample B--4" pipe:
Te
Wat 16
1.3 pst presse
In the examples above, 4" would likely be the appropriate size, especially
Lf this calculation were for a header. Rating for maximum capacity would
storage capacity in the header, st pare load, to reduce
+ in che system,
s of the
branches, and drops, The only purpose of these pa
piping system is to transport air from P4 to PS (again, see "Systems
Stundards"). There is no practical reason for storage unless you have a
ader with a single large user of air or user with a
yh instantanecus
Examples would be a bag house, sandilaut operation, paint spray
application, very Large cylinder, o¢ ether arpiicutyan that blo
a large
euaitity oF air to atmosphere, Lf you have such an appiica
Lion, storage
is necessary to prevent a considerable pressure fluctuation in the system.
Example
400-gal.
ae Cheek va storage vesse:
Cheek valve toray a Baghouse
Header 20 cfm for a
S-sec. cycle,
1 cycle.
per min.
Control valve
Subheader or dump valve
Subheas
Figu tit feeds baghouse.
Iu this example, keep in mind that the bag house uses 20 cuble feet in 3
Expanding this to cubic feet
+ you would have a flow
eouivalent to 12 x 20 cubic feet, because 5 sceonds is 1/12 of a minute andall ratings are in cubic fect per minute. With the check valve upstream
of the storage vessel to prevent stored air from going to other demand in
the system, the pipe upstream of the recedver should be sized to transport
20 cfm to rer'ace what is taken out of the storage vessel in that S-s.cond
demand. The Line size downstream of the storage vessel must be sized to
handle 29 cfm in 5 seconds, or the equivalent of 249 cfm. Tf contamiaant-
renoval equipment is used for this application, tt should be placed down-
stream of the check valve and upstream of the storage vess
1. No other
users, branches, or drops should be planned on this sublhe:
With normal selection of pipe size fur subheadors, branches, an!
drops, you should determine the high average demand on any subheader,
branch line, or drop at the lower average pressure fur the longest rv
all sections of that type in the system. Do not include bigh single demint
users in this calculation, Calculations for such high demand users should
be evaluated on an individual basis. Exampli
‘Branch Line
3 cfm
}————a——— 4
Figure 2, Subheaders, tranches, and drops.
Now let's Look at the subheader. Total dvinand is U3 tefm at 95 psig,
length ts 60", atnoepher nsuve is 14.6 psta, Calculation for Us" pipe
(95 + 14.6)
6.8 Se
a8 = 16 psi pressure lossThis confirms that the selection of subucader piping is 1". Heaviest
usage for brauch lines 1s 40 icfm at 95 psig, Length is 40’ long,
atmospherle pre
a. Calculation for 1" pipe:
x 40 x 1.2
22 psi pressure loss
Although 1" Is the indicated selection, 3/4" would also be acceptable
with only .8 pst pressure loss. But because the difference in installed
cost between 3/4" and 1" 1s so insignificant, the selection of 1" is
really in your best interest in terms of flexibil{ty, storage, and growth.
Drop legs. The same calculations used for subheaders and branches are
also used when determining drop leg size. It is advisable to select the
same size for all subheaders, for all branches, and for all drops. In the
example Just calculated, all eubhcaders would be I's", all branch lines 1",
etc. This will cut down the cost of installation and allow for navenent
of equipment and expansion of the total system. Having used the high
average derand, sections with lower demand will have lower pressure drops
and help provide stoi
e for other sections of the system. (This, of course,
does not apply to the high single deniand users, as previously tention:
izing the header. The header section has two essential funct ons:
transport and storage. (Without storege, you can't have a system free of
pressure fluctuatson.)
Selection of size is only one consideration in header design. It's
also important to consider geometry, balance, entry, flevibiliey, valvin
location of the header relative to the distribution of P5 locarfons, and
grouth of the system.
You should size the header for no more than 1 psi of pressure loss
at anticipated maxinum demand at least two years from initial startup of
=45the system. Rven better, plan header size and design for your auticipated
Hemant five years
from tottial startup. Oversizing the header is the best
investment you can make fn the tetal system.
In order to calculate higher demand, try to estimate not only increases
in equipment, but also inereases in production as a percentage of what
your inftial demand will be. fach perceat of increase in production with
the same equipment will net a proportionate percentage in increased demand
Tor te volume. Examples
Current demand at 23 1080.0 etm
20% increase over initial planned
rate of production (.20 x 1080) 216.0
ew equipment added over two years
4 = 20 hp printers, 70 cfm @ 502
use factor’ per min, 140.0
8 - blowguns, 18 cfm @ 10% use
factor 40.0
s, 20 efm a 40% use
Factor 40.0
1 ~ hag house, 52 cfm, @ 100%
se factor 52.0
Total new equipment 246.4
Total air desand two years from startup 1542.4 cha
in calculating actual air usage, take the rated cfm of an air-operated device
and multiply by the percentage of time in any minute it may operate. fw not
average. Tines in the week or day are unimportant. Note that the two:
eat
actual cfm.method applies only to the healer and riser sizing.
The next step is to determine what type of header vou Lave and the m thad
of determining length for sizing calculations. Types ace Loop, unic loop,
erid, and unit grid, as shown below.
A
Compressor Dees Glo,
OD ¢ g 1 ¢ oto
Figure 3. Loop. L = a2 + B2,
gore
Unie loop. Also L = a2 + 8°,
Compressor
Figure
cone) t
Figure 5. Grid system. Use the entire length of the header. Step
sizing ad air is taken off will not provide for storage or expansion.
oO
O+—0
Compressor Compressor
1 é . |
Compressor _4 L__- .
Eiyure 6. Unit grid. Two or mre conpressors at various lucations
or calculation is one-half the distance between comFigures 1 aud 3 are better designs, but 2 and 4 may be necessary because
of existing piping or in special applications for new systems to balance
potential pressure fluctuations. (sample: a mine or very long system.)
And whore an already existing header is too small, ur where there Is no
Foon to ald a compressor at the original location, 2 and 4 may also apply.
But be aware that those systems are really not desirable from an energy
cost point uf view, because when pressure fur the compressors is sensed
at multiple locations there Is always more connected blip on Line than
necessary when the system is at part load.
Gnee the length te be used in your calculation is determined, proceed
with the formula as previously indicated.
Riser
izing. The riser is the ripe between the Last piece o:
cquipneat (including veers, fileers, ete.) and the entry point in che
overhead piping where header distribution begins. (The riser Saciudes
horizontal as well as vertical runs between these points.)
The riser has to transpert air to the header and furnish the pressure
signal from the header through accessories to the coupressor. tc also
must reduce the veluetty of compressed air to minimize contanfaants being
carried to the header. That's why a drip leg should be used in the riser.
It's adviseable to pitch the overhead horizontal runs of the riser away
from the header towards the drip leg and enter the header from the side or
bottam.
The riser should de the next aominal pipe size larger than the hea
er the intercos
ect piping va the cengr:
eal air-eauipment, whichever i$
larger, to facilitate contaminant drop out in the drip leg. ExampleSonpressor Entry. a"
Dryer
Use larger pipe size for riser
The place at which the riser connects to the header is the entry, a ver
design point in the systen. The best intentions are frequent ly
destroyed by a poorly selected entry, as in Figure 8 below.
4" to 3"
bell reducer
1” tee
Entry
Figure 8 Poorly designed entry uses 3" tee.
In the example above the entry is 3". Use of a 4” tee, with reducers
ter the tee as In Figure 9 below, vi
1 increase the entrv--and sys
capacity by 25%. Example 8:
toa"
tee
to 3"
Use of 4" tee increas
es capacity ty 25%.
rowth in the system, we'll suvest"
Tt
W" riser
4" co 3"
4
Planning fur geowth,
loubling the growth of this system is a sinple muteer of sizing the
riser and eatry for 6" and the crossover for 5", with a 4" mating te
at the far end of the crossover, The system also requires 4" tees
centered en the north and south side of the header. As the distribution
grows, the system would eventually lock Like this:
4" @ 600
How to plan for twice as much capacity.
This layout makes it possible to install the system at the lowest initial
cost for 1200 cfm and gradually add twice as much air with a minimum
investment at each point of growth, while maintaining balance
and storage
during growth. The only other altornatie is to install a 6" t
arler
system co start with, witch would double the initial expense.
Tf you have an
about piping, please contact your lecal
Sullair office.APPENDIX A
Table 1. Factors for calculating loss of air caused by pipe friction.
for any initial pressure.
2 ¥ee98 83982 asezs
SEES 885)APPENDIX A.
(Continued)
Table 1.
An?COMPRESSED AIR RECEIVER CAPACITY
Capacity | Capacity in cu, ft, of free air at gauge pressure shown
Tank in - oe
Dimensions | Gallons 0 50 100 125 150 175 200
re] 20 2.7 12.0 20.8 25,3 30.0 34.4 38.9)
le" x 36" 30 4.0 18.0 31.2 38,0 45.0 51.6 58.4
aoe" 60 8.0 36.0 62.4 76,0 90.0 103.2
20 x 63" 80 10,7 48.0 83.2, 101.3 120.0 137.6
2" x 68" | 120 16.0 72,0 124.8 152.0 180.0 206.4
|
30" « 84" 240 L 32.0 144.0 249.6 304.0 360.0 412.8 467.2VARIUUS ORIFICES
xpressed in cubic feet per minute, and is assuned to take place from a receiver
1, in which atr 4e contained under pressure, into the atmosphere at sea level.
‘Temperature of air in receiver is assumed at 60 degrees Fahrenheit. This table is ony
correct for orifices wich narrow edges; flow through even a short length of pipe would be less
than that given below.
Flow of Free Alr (Ca.Fe. Per Min.) Through Orifices of Various Diameters
1/64" v3" yea" Vie"
027 107 242 +430
038 153 “3a +607
“ove 1188 van 750
“059 1242 “505 ' 1965
‘086 342 ” | 136
5 103 “38 T 167
2» hus 107 193
25 | 1333 uz 216
30 156 140 2.52
8 13 156 2.80
%0 at) La 3.07
“5 1208 19 3.36
0 "25 2.05 3.66
60 126 2.35 az |
70 | 2295 es 476
0 3 2.97 | 52
90 368 3.28 | 587
100 40 3.66 66s
ne | rf) 3.98 7:00
120 a a27 | 758
130 457 3
140 als 8.68
150 3:20 9.20
175 5.96 10-6
200 6:90 122
| | 3716 ve |
la 172 3.86 6.85
, 3 | 263 5.42 9.74
3 2.98 en ww
5 3.86 a7 15.4
20 5.45 23 28 |
15 6.65 15.0 eT
20 ; nn | ya 30-8
25 495 8.6 19-4 34.5
30 56 10.0 22:5 woo |
6 62 m2 25.0 4a.7
“0 6.8 23 25 wi
45 76 | 134 30°3 33.8
| 50 8.2 1435 22.8 38.2
| 6 | 3.4 : 37.5 | 7
\_70 | 10.7 43.0 | 16 i
ie n3 ws ye i
90 Bi 525 %4 |
| 100 165 | 58.3 1 wins
110 \ 13.7 | , “ae
120 {ro | a
130 2
140 5 |
150 7
us 8 |
200 23 |CHART IT - FOR TOOLS HAVING A CONTINUOUS
CONSUMPTION OF COMPRESSED ATR
| Tools Size Number CFM Each Total
| io
y 12.90
| tet Nozzle 1/16" Dia. 2 6.45 Exarple
190 psigTate ‘Avg. Free Normal
| press. Air Cons. Load
| Range Equipment CPM Factor***
L = =
| | i
30-100 | ##Bench Rammer 5.0 sox
| 90 - 100 **Ploor Rammer 7.0 40%
(90 = 100 | **Back£111 Tamp [15.0 402
350 ~ 100 | **Compression
| gaBtveter 1.0
Fon - 100 | ##automatte Drills 6.0
y= 100) #AALE Motor, LBP | 10.0 '
~ Lot tate Motor, 2 j 13.0
- 190 **Air Motor, 3 HP 20.0 | 1
3) - 100) *#A‘r Motor Hoist, i |
| | 10008 1 s.0 10%
90-100 | **A‘e Motor Hotst, i |
' 20008 5. 10% |
190-100 | Cylinder Type |
| \ joist [1. 16%
| | Hamers !
| 90 - 100 | **Scaling Hanmer | 4.0 39%
| 99 = 190 | *&Chipping Harmer 7.0 35%
95 = 100 | #*Riveting Harmer | 15.0 | 35% i
1 Spray 5
(90 - 100 | *xPaint Spray Gun | |
| (Production) | 85 | sox |
40-100) *APaine Spray
(Touch-Up) 35 25%
* Always check with tocl manufacturers for actual consumpticn of tools being
used, The above are based on averages and should net be considered accurate
for any particular make of tools. The free air consuuptions Listed herein
are based on the use of the normal load factors shown in the adjacent column.
Load factor is a percentage that exoresses the normal actual usage of air
as compared to the maximum usage that will occur if the tool's throttle valve
is turned fully open and the tool is operated continuously at maximum capacity.
(Load factors should be adjusted based on your own individual operating
conditions.)
4*# These devices are to be considered as continuously operating devices when
operating normally. All other devices listed are to be considered as inter-
mittently operated when operating normally. When the devices consist of a
large number of the continuously eperating type, and if only a few are to be
used at one tine, the compressor should have a Capacity at least equal to the
total consumption of all those tocls used simultaneously, in addition to the
consumption of al! Ly of tools, if any. 7
sae Sormal load fact ci thus the throteze valve ds open dur
normal usageie ‘Ava. Free Normal
becss Air Cons. Load
Range aipnent crue Factor##*
| kane [ Equip | -
190 = t99 | Bench Raumer 5.0 | sox
[90 = 100 | *#FLoor Rane 70 soz
a9 = 100 | A*packetit Tan 15.0 40%
50 = 100 | **Conpression
| |. Riveter 1.0 10%
V0 - ssqutomatic Drills 6.0 25%
ne stair Motor, 1 HP 19.0 25%
7 s*Air Motor, 2 UP 15.0 25%
- Hair Motor, 3} HP 20.0 i 35x \
= 100) #Raie Motor Hotst, |
10008 5.0 ton
99-100, | ARAL Motor aise, |
20008 5.0 10% |
| 90 - 100 Cylinder Type
| Hoist Ls 10%
f Hamers
99 - 100 | *#Scaiing Hanmer 4.0 35%
90 = 100 | *Achipping Hammer To 352
| FARIvet ing Hanmer 150 35% |
{ Spray Gane ~ 1
0 | seraine Spray Gun | |
| @reduet ion) 8.5 son
) | M#Paine Spray Gun
| (Touch-Up) 3.5 2st
ae
Always
eck with tool manufacturers for actual consumption of tools being
used. The above are based on averages and should not be considered accurate
for any particular make of tools. The free air consumptions listed herein
ate based on the use of the normal load factors shown in the adjacent column.
Load fac a percentage that expresses the normal actual usage of air
4 compared to the maximum usage that will occur if the tool's throttle valve
is turned fully open and the tool is operated continuously at maximum capacity.
(Load factors should be adjusted based on your own individual operating
conditions.)
These devices are to be considered as continuously operating devices when
operating normally. All other devices Listed are to be considered as inter-
mittently operated when operating normally. When the devices consist of a
large number of the continuously operating type, and if only a few are to be
nsed at one tine, the compressor should have a capacity at least ecual to the
total consumption of all those tools used simultaneously, in addition to the
consumption of all tie {ntermitrently operated tools, {F aay. °
1 load fact
normal usage.
the percentage of time the throttle valve Ls open duringFRICTION OF ATA IN Hose
no 12 430
100
+
as
2INDUSTRIAL TOOLS
AND EQUIPMENT
\ ate Ave. Free Normal |
| Press. Ar Cons. | Load
| ange Equipment cFM* Factock™® |
E ~ 1
| oo - 100 | *Abuseing Gun |
| (Blow Gun) 3.0 10%
| 90 - 100 | *aDrtii, 1/16" co 3/8" 40 25%
uw **Drd11, 3/18" to 5/8" 7.0 25%,
WScrendriver, 02
: to #6 Screw
- 109 | *AScrendriver, #6
| to 5/16" Screw 3.0 1st
| oo - 190 | **Tapper, to 3/8" 3.0 1st
[90 - 100 | *Autsetters, to 3/8 3.0 15%
| 90 - 100 *kNutsetters, to 3/4" 5.0 15%
, 90 - 100 **Impact Wrench,
1 3/8" sq. dr. 2.0 20%
00 - 100 | **Impact Wrench, 1 1 |
4" sq. dr. {3.5 20%
90 - 100 | *AImpact Wrench, |
| 5/8" sq. dr. 5.0 20%
a9 - 100 | tt Wreach,
ag. dr. 15 j 208
96 - 100 *#Impact wrench,
L''sq. dr. 10.0 20%
**Die Grinder, Small 4.0 (30%
‘**Die Grinder,
Medium 5.0 30%
90 ~ 100 | *#Horlzontal
Grinder, 2" ‘10.0 | 30%
| 90 - 100 ‘*eHorizontal |
1 Grinder, 4" 14.0 30%
90 - 100 **Horizontal
Grinder, 6" 16.0 30%
90 - 100 | *#Horizontal |
Grinder, 8" 20.0 30%
90-100 | *AVereical Grinders
& Sanders, 5" Pad 10.0 30%
90-100 | *4Vertical Grinders |
& Sanders, 7" Pad | 14.0 30%
90 - 100 | *4Vereical Grinders |
* Sanders, 9" Pad |
90-100 | *A*Filing & Sawing
Machine, Sitall
90-100 | **PLLing & Sawing
| Machine, Large
j 90-199 | **Eurring Tool, |
| small
| 90 - 100 | **Burring Tool,
I [largeINDUSTRIAL TOOLS
AND EQUIPMENT
Avg. Free Normal
Air Cons. | Load
Equipment crm | Factors#*
xrDusting Gun |
(Blow Gun) 3.0 10% |
**Drill, 1/16" to 3/ 4.0 25%
waprill, 3/18" to 5/ 7.3 |
‘Screwdriver, #2 | i
to #6 Screw | 1.0 jist
‘AScreudriver, #6 j
to 5/16" Screw 3.0 1st [
**Tapper, to 3/8" 3.0 15%
*aNutsetters, to 3/8 3.0 |
*sNutsetters, to 3/4" 5.0 | iss
xeImpact Wrench,
3/8" sq. dr. 2.0 20%
**Impact Wrench, | |
Wr" sq. dr. 3.5 20%
*AImpact Wrench, | i
5/8" sq. dr. 5.0 20% !
*sImpact Wrench, i
3/4" sq. dr. j 75 20%
jo - tno | #eImpact Reench, |
L"'sa. dr. 16.0 20%
90 - 100 | *ADie Grinder, Small 4.0 30%
9G - 100 | *D1e Grinder,
Medium ~ 5.0 30% |
59-100 | *AHortzontat |
Grinder, 2" 10.0 30%
96 = 10 stHortzontal |
| Grinder, 4" | e.0 30% i
| *Hlorizontal | |
| Grinder, 6” 16.0 30%
| *#Horizontal
Grinder, 8" 20.0 30% j
| 90 - 100 | ‘Vertical Grinders |
| | @ Sanders, 5" Pad 10.0 30% |
40 - 1c) *AVertical Grinders |
| | sanders, 7" Pad 14.0 | 30x |
90 - 100 | *#Vertical Grinders
[90 - 100 | *AFiling & Sawing |
| Machine, Small 3.0 15% |
| 90-100 | AMFLLing & Sawing
Machinz, Large 5.0 | asx
-1 saBurring Tool, |
| Small | 40 | 30% |
| 90 - 109 | **Burring Tool, | |
I Large 5.0 30% JSAND BLASTING NOZZLES
CAGE PRESSURE
DIAMETER 60 70 80 100 |
|
1/16 4 5 1 5.5 | 6.5 |
| 3/32 9 i | 2 i wy |
1/8 VW 19 21 26 |
3/16 38 43 47 58
4 67 76 85 103
5/16 105 119 133 161
3/8 151 vi 191 232
ue 268 304 340 412 |
|
|YOUR OWN PLANT ATR ESTIMATE
CHART 1 ~ FOR TOOLS HAVING AN INTERMITTENT
CONSUMPTION OF COMPRESSED AIR
Your Teale ory
Number Use Estimated Air
Type Size Each Total Factor Req. CFM
15-3/4
Impact s 3 ws 105 30% Example
Wrench Capacity
TOTAL