Hipulse User Manual
Hipulse User Manual
s i n g l e m o d u l e a n d 1 + N e x p a n d a b l e
User Manual
Dear Customer,
Please accept our thanks for giving us the privilege to serve you by choosing a Liebert make UPS. If this is your first Liebert UPS, we hope it is the beginning of a long relationship which delivers value to your organisation. If you already own and use a Liebert product, we are doubly honoured by your decision of continuing this relationship. It is our constant endeavor to partner you for the growth and success of your business. This philosophy is reflected in our Mission statement To deliver value through Air & T Power Quality solutions to achieve customer delight. Please do give us feedback to help us realize our Mission.
IMPORTANT
This manual contains information concerning the installation, operation and maintenance of the Liebert Hipulse Uninterruptible Power System (UPS) for the single module and one plus one Systems. All relevant parts of the manual should be read prior to commencing installation.
The UPS must be commissioned by an engineer approved by the manufacturer (or his agent) before being put into service. Failure to observe this condition will invalidate any implied warranty.
The Hipulse UPS has been designed for Commercial / Industrial use only. The Hipulse UPS has not been designed for direct use in any life support application. If you encounter any problem with the procedures contained in this manual you should seek immediate assistance from Emerson Network Power (India) Pvt. Ltd. Sales Office from whom the equipment was purchased. Alternatively contact the Emerson Network Power (India) Pvt. Ltd Customer Service & Support department at the address shown below:
EMERSON NETWORK POWER (INDIA) PRIVATE LIMITED Plot No. C-20, Road No. 19 Wagle Industrial Estate Thane 400 604, INDIA Phone : (00 91 22) 5807000 5828405 Fax : (00 91 22) 5800829 5828358
Emerson Network Power (India) Private Limited pursues a policy of continual product development and reserves the right to change the equipment without notice.
@ Copyright 1999 by Emerson Network Power Unauthorized reproduction prohibited All rights reserved
BARODA 39 / 2, Arunodaya Society, Alkapuri, BARODA-390 005 Tel : 0265-314296, 330383 Fax: 0265-314296, 330383 CHANDIGARH SCO-198 / 199 / 200, Sector 34A, Near Labour Chowk, CHANDIGARH Phone: 0172-662 873 Mobile: 9814100901 CHENNAI No. 22, First Floor, Gopal Krishna Road, T. Nagar, CHENNAI 600 017 Tel : 044 - 8231742, 8221063, 8228996 Fax: 044 - 8231742 COCHIN Lakshmini No. 36 / 2684, Veluthamma House, Azad Road, Kaloor, COCHIN 682017 Tel : 0484 - 341985 Fax: 0484 - 341986 GOA 622 / A, La Citadel Colony Dona Paula, GOA 403 004 Tel : c/o. 0832 220 723 GUWAHATI South Savania, Ashram Road, Ulubari, GUWAHATI 781 007 Tel : 0361 - 543848 Fax: 0361 - 543270 Mobile: 9864023587
JAMSHEDPUR Kashi kunj, Road no. 2, Gr. Floor Contractors area, Bistupur; JAMSHEDPUR 831 001 Tel : 0657-437549 Fax: 0657-437549 LUCKNOW 206, Sriram Tower, Ashok Marg LUCKNOW Phone : 0522-201467 Pager : 9628-555091 Mobile: 9839025563 NAGPUR 203, Ganga Apts, 13, Giripeth NAGPUR 400 010 Phone / Fax : 0712 540423, 548551 PUNE B-6, Shri Dwarka co-op. Society, 467/ C1, Hare Krishna Mandir Path, Model Colony, Off University Road, PUNE 411006 Tel : 020 - 5676975, 5670709 Fax: 020 - 4004020 SECUNDARABAD Plot no. 4, Sardar Patel Road SECUNDARABAD 500 003 Tel : 040 - 7717263, 7719196 Fax: 040 - 7806502
Safety Procedure
WARNING In a domestic environment, this product may cause radio interface in which case the user may be required to take additional measures.
WARNING HIGH EARTH LEAKAGE CURRENT: EARTH CONNECTIONS IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY. This equipment must be earthed in accordance with local electrical codes.
WARNING THIS UPS DOES NOT INCORPORATE AUTOMATIC BACKFEED PROTECTION. A WARNING LABEL MUST BE FITTED TO ALL EXTERNAL PRIMARY POWER ISOLATIONS STATING. INSULATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON THIS CIRCUIT.
GENERAL As with other types of high power equipment, dangerous voltages are present within the UPS and battery enclosure. The risk of contact with these is minimised as the live component parts are housed behind a hinged, lockable door. Further internal safety screens make the equipment protected to IP20 standards. No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating procedures. All equipment maintenance and servicing procedures involve internal access and should be carried out only by trained personnel.
BATTERIES Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of a large bank of battery cells. These precautions should be followed implicitly at all times. Particular attention should be paid to the recommendations concerning local environmental conditions and the provision of protective clothing, first-aid and fire fighting facilities
TEST EQUIPMENT When the battery is under charge, it is earth-referenced about its mid-point e.g. if the battery s being charged at 460V the battery extremities will be at +230V and 230V with respect to neutral (earth). When using mains-powered test equipment such as oscilloscopes in the UPS voltage area, always use a differential mode of operation to disconnect the oscilloscope frame earth.
PERSONNEL When working inside the UPS (trained personnel only) it is recommended that protection be worn to prevent eye damage, should an electric ware be struck by mishandling or severe electrical fault. Some of the power components are very heavy. If their removal is necessary, ensure that sufficient manpower is available; otherwise use adequate mechanical handling equipment. When working in the general area of the UPS where high voltages are present, a second person should be standing-by to assist and summon help in case of accident.
INDEX
1
1.1 1.2
1.2.1 1.2.2 1.2.3 1.2.4 1.2.5 1.2.6 1.2.7 1.2.8
General Introduction
Introduction Design Concept
Hipulse Module Design Bypass Supplies System control Philosophy ECOMODE (for single UPS) UPS Power Switch Configuration Battery circuit breaker Battery temperature compensation System Expansion
1
1 1
1 2 3 4 5 5 5 5
2
2.1 2.2
2.2.1 2.2.2
Installation Procedure
Introduction Environmental Considerations
UPS location Battery Location
6
6 7
7 7
2.3
2.3.1 2.3.2 2.3.3 2.3.4 2.3.5
Mechanical Considerations
System composition Moving the cabinets Clearances Fixing Magnetic Components Cable entry
8
8 8 8 8 8
2.4 2.5
9 9
3
3.1
3.1.1 3.1.2 3.1.3 3.1.4 3.1.5 3.1.6 3.1.7
Installation (Electrical)
Power Cabling
System Configuration Cable rating General Notes Cable connections Safety earth Protective Devices Cabling procedure
32
32
32 33 33 33 33 34 35
3.2 3.3
3.3.1 3.3.2 3.3.3 3.3.4 3.3.5
39 40
40 41 41 42 42
4
4.1
4.1.1 4.1.2
43
43
44 47
5
5.1
5.1.1 5.1.2
Operating Instructions
Introduction
General Notes Power switches
51
51
51 51
5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 5.10 5.11 5.12 5.13
Procedure for UPS Startup: without interrupting power to the load Procedure for UPS Startup: without power initially supplied to the load Procedure for Switching the UPS into Maintenance Bypass condition from Normal Operation Procedure for Switching the UPS ON from a Maintenance Power condition Procedure for completely Powering down the UPS Procedure for carrying out at Reset after a recognized controlled transfer to Bypass or EPO action Adding a single module to an existing system Procedure to completely switch ON/ OFF the UPS at the UPS Display control panel Procedure to switch ON/ OFF the Inverter at UPS Display control panel Setting the Battery test Language selection Changing the current Date and Time
52 54 56 58 58 59 60 61 63 64 65 65
6
6.1 6.2 6.3 6.4 6.5
6.5.1 6.5.2
Battery Installation
Introduction Safety UPS Batteries Installation Design Considerations Battery Installation and Maintenance
Temperature Considerations Battery Population
66
66 66 67 68 68
68 68
6.6 6.7
6.7.1 6.7.2 6.7.3 6.7.4 6.7.5
69 69
69 69 70 70 70
72 72 74
7
7.1 7.2
75
75 77
8
8.1 8.2 8.3
8.3.1 8.3.2 8.3.3 8.3.4 8.3.5 8.3.6 8.3.7
1 + N System
General Maintenance Cabinet for two modules Installation Procedure
Preliminary Checks Protective Devices Power Cables Control Cables Battery Control Common Battery Box for two UPS in parallel Emergency Stop
82
82 84 85
85 85 85 85 86 87 90
8.4
8.4.1 8.4.2
Operating Instructions
System Start-up and Shutdown procedures (separate batteries) Installation Procedure (common battery)
91
91 95
8.5
98
9
9.1 9.2 9.3 9.4 9.5 9.6 9.7 9.8 9.9
Specification
Conformity and Standard UPS Environmental UPS Mechanical Characteristics UPS Electrical Characteristics UPS Electrical Characteristics (DC Intermediate circuit) UPS Electrical Characteristics (Inverter Output) UPS Electrical Characteristics (Bypass Input Mains) UPS Electrical Characteristics (System Performance) UPS Electrical Characteristics (ECOMODE)
99
99 99 99 100 101 102 103 104 104
General Description
1.1 Introduction
The Hipulse Uninterruptible Power Supply (UPS) System is connected between a critical load, such as a computer, and its three phase mains power supply. Being designed to furnish a well regulated 3 phase output power supply under all rated load and input supply conditions, the system offers the user the following advantages:
1.2
1.2.1
Design Concept
Hipulse Module Design
This section describes an individual module's operating principles. The UPS basically operates as an a.c. - d.c. - a.c. converter (see figure 1 -1 ). This first conversion stage (from a.c. to d.c.) uses a 3 phase, fully-controlled SCR bridge rectifier to convert the incoming mains supply into a regulated d.c. busbar.
Mains Supply
(a.c.)
RECTIFIER
(d.c.)
INVERTER
(a.c.)
STATIC SWITCH
(d.c.)
BATTERY
The d.c. busbar produced by the rectifier provides both battery charging power - being equipped with a temperature compensated battery charging system, to prolong battery life - and power to the inverter section - which utilizes the latest IGBT switching pulse width modulation (PWM) design - and provides the second conversion phase, i.e. reconverting the d.c. busbar voltage back into an a.c. voltage waveform.
During normal operation both the rectifier and inverter sections are active and provide regulated load power whilst simultaneously float charging the battery. In the event of a mains power failure, the rectifier becomes inoperative and the inverter is powered solely from the battery. Critical load power is maintained under these conditions until battery is fully discharged, where upon the UPS shuts down. The end of battery discharge is assumed when the battery voltage falls below a preset value (i.e. 330 V d.c. for a 400 V a.c. system). The period for which the load can be maintained following a mains power failure is known as the Systems Autonomy Time and is dependent upon both the battery A/Hr capacity and the applied percentage load.
The circuit block annotated Static Switch in figure 1-2 contains an electronically controlled switching circuit which enables the critical load to be connected either to the inverter output or to a bypass power source via the static bypass line. During normal system operation the load is connected to the inverter and the inverter -side of the Static Switch is closed; but in the event of a UPS overload, or inverter failure, it is automatically transferred to the static bypass supply line.
RECTIF IER
Input Isolator
INVERTER
Battery Isolator
Output Isolator
BATTERY
Note: The load equipment is not protected from normal supply aberrations when operating on Bypass side or in the maintenance bypass mode
1.2.3
During normal operation, i.e. when the UPS input supply is present and within specification, both the rectifier and inverter sections are active and the static switch is turned on to connect the inverter output to the critical load busbars. The battery circuit breaker is also closed and the battery is therefore permanently float charged at the d.c. busbar voltage level.
Normal Operation
(1+N Parallel UPS System) Note: As the unit outputs are connected in parallel, the System checks that the inverter control circuits are perfectly synchronised with one another and with the Bypass Mains in terms of both frequency and phase and that they have the same output voltages. Current supplied to the load is automatically divided among UPSs. A warning message appears while synchronisation is in progress.
A module's static switch cannot close until these conditions are satisfied.
Mains Failure
If the power mains has a failure or is out of tolerance the rectifier will go off automatically, while the Inverter will continue to operate on power from the battery for a period of time which depends on the load and the capacity of the battery. If the mains supply has not retuned within this time, the Inverter will go off automatically and an alarm message will appear on the UPS operator control panel display. Critical load will not be interrupted in the event of a drop or return of the AC power mains.
Off-Battery
If the battery system only is taken out of service for maintenance, it is disconnected from the rectifier/ charger and inverters by means of (an) external disconnect breaker(s). The UPS shall continue to function and meet all of the specified steady-state performance criteria, except for the power outage back-up time capability. In the event of an Inverter fault, the Static Transfer Switch will automatically transfer the load onto the Bypass Mains with no interruption. In such an event, request qualified technical assistance.
Overload
In the event of an overload at the Inverter output which lasts longer than the typical time/ current (refer to Chapter 9 - Specifications), the Inverter will shut down and the Static Transfer Switch will automatically transfer the load onto the MSS Bypass Mains with no interruption. If the overload falls within the typical time/ current that has been specified, the load will be returned to the inverters when the power drops to a level which can be supported by the number of active units in the system (parallel 1+N). In the event of a short circuit in the output, the load will normally be transferred onto the MSS Bypass Mains, which will cause the Inverter to shut down; this switch is determined above all by the features of the protective devices in use in the system. In either case, an alarm message will appear on the UPS operator control panel display.
Maintenance Bypass
A second bypass circuit contained in the UPS cabinet, identified as the 'Maintenance Bypass' line is included to enable a 'raw' mains supply to be made available to the load while facilitating a safe working environment for carrying out scheduled UPS system maintenance or troubleshooting. The circuit is manually selected by the Maintenance Bypass Isolator which can be padlocked in the OFF position.
WARNING
The internal maintenance bypass must not be used when the UPS system is comprised of more than two UPS modules in parallel.
CAUTION
If an automatic circuit breaker device is not present in the input distribution panel, there remains a dangerously high voltage at the output busbars of the UPS module that is switched off
1.2.4
In this operating mode the System prefers to put the load on the Bypass Mains, with the Inverter on stand-by. The load is switched over to the Inverter when the mains goes outside of standard frequency and voltage values (or the values as modified using the operator panel when starting up the system). The ECOMODE configuration requires a different setup in the default menu configuration, which may be prepared in the factory before shipment or during installation by personnel trained in the use of the System.
Note: In order to operate in ECOMODE, UPSs must be provided with compatible software versions:
The 'UPS Logic' card must be release 9.0 or later (the S/W release of the cards may be read on the front panel display, referring to Section 4.1.2 - Operating Instructions).
Hipulse UPS Manual Single 1+N UPS System Operating Instructions in ECOMODE are the same as those described in Chapter 5, except that the load is normally on the Bypass mains, the Load LED is normally on Inverter (5), and corresponding alarm message will be replaced with Load on Mains (6).
WARNING
Figure 1-2 illustrates the Hipulse UPS module in what is known as the "Split Bypass" configuration. In the Split Bypass configuration, the static bypass line is connected by a separate power switch to a dedicated 'bypass' power source which also feeds the maintenance bypass line. Where a separate power source is not available the Bypass (Q2) and Rectifier input supply connections would be linked together. With the exception of maintenance bypass isolator, all the isolators shown must be closed during normal UPS operation.
1.2.5
1.2.6
The battery should be connected to the d.c. busbar through a circuit breaker fitted inside the battery cabinet or located adjacent to batteries where a battery cabinet is not used. This circuit breaker is closed manually, but it contains an undervoltage release coil which enables it to be tripped from the UPS control electronics following certain detected faults. It also has a magnetic trip facility for overload protection.
1.2.7
Hipulse UPS System offers a battery temperature compensation circuit. As the temperature inside the battery cabinet area rises, the d.c. busbar voltage reduces in order to sustain the battery at its optimum charge voltage. This must be used in conjunction with the battery sensor board.
1.2.8
System Expansion
If necessary, a single -module system can be expanded to cater for an increased load requirement by adding additional modules - upto a maximum of six UPS modules can be connected in parallel. System expansion requires change in the SETUP of the display panel.
Note: System expansion should be carried out only by trained service personal. The individual modules connected to the system must be of the same power rating
CHAPTER 2
Installation Procedure
2.1 Introduction
WARNING
Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.
WARNING
The UPS equipment should be installed by a qualified engineer in accordance with the information contained in this chapter and all equipment not referred to this manual is shipped with the details its own mechanical and electrical installation.
Special care should be taken when working with the batteries associated with this equipment. When connected together, the battery terminal voltage will exceed 400V DC, and is potential lethal. Eye protection should be worn to prevent injury from accidental electrical arcs. Remove rings, watches and all metal objects. Only use tools with insulated handles. Wear rubber gloves. If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in container resistant to sulfuric acid and disposed of in accordance with local regulations. If electrolyte comes into contact with the skin, the affected area should be washed immediately with water.
NOTE
Because every site has its peculiarities, it is not the aim of this chapter to provide step-by-step installation instructions, but to act as a guide as to the general procedures and practices that should be observed by the installing engineer.
2.2
2.2.1
Environmental considerations
UPS location
The UPS module should be located in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range (see Chapter 9 - Specifications). All models in the Hipulse UPS range are cooled with the aid of internal fans. Cooling air enters the module through ventilation grills located at various parts of the cabinet and exhausted through grills located in the cabinet roof. When the cabinet is located on a raised floor, and bottom cable entry is used, additional cooling air also enters the UPS via the floor void. If necessary, a system of extractor fans should be installed to aid cooling air-flow, and a suitable air filtration system used where the UPS is to operate in a dirty environment.
Note 1: When batteries are cabinet-mounted adjacent to the UPS module, it is the battery which dictates the designed maximum ambient temperature, not the UPS. Note 2: Power losses from the System which may be used in an air conditioning system are intended for operation using the Inverter, as in the ECOMODE configuration they would be undersized. 2.2.2 Battery location
Temperature is a major factor in determining the battery life and capacity. Battery manufacturers quote figures for an operating temperature of 20oC. Operating above this temperature will reduce the battery life, operation below this temperature will reduce the battery capacity. On a normal installation the battery temperature is maintained between 15oC and 25oC. Batteries should be mounted in an environment where the temperature is consistent and even over the whole battery. Keep batteries away from main heat sources or main air inlets etc. The batteries can be mounted in purpose-built battery cabinet, which is positioned adjacent to the UPS module. Pedestals are required for the battery cabinets when they are located on raised floors, in the same way as for the UPS cabinets. If the batteries are rack-mounted, or otherwise located remote to the main UPS cabinet, a battery circuit breaker must be mounted as close as possible to the batteries themselves, and connected using the most direct route possible. A customized remote battery circuit breaker box, containing the circuit breaker and its necessary control board, is also available as a standard option.
2.3
2.3.1
Mechanical Considerations
System composition
A UPS system can comprise a number of equipment cabinets, depending on the individual system design requirements - e.g. UPS cabinet, Battery cabinet. In general, all the cabinets used in a particular installation are of the same height and designed to be positioned side-by-side to form an aesthetically appealing equipment unit.
2.3.2
Ensure that any lifting equipment that used in moving the UPS cabinet has sufficient lifting capacity.
Ensure that the UPS weight is within the designated surface weight loading (Kg/sq.cm.) of any handling equipment. See the UPS specification for weight details. The UPS cabinets can be moved by fork lift or crane. For operations with fork lift, it is necessary to remove both the front, rear (or side) grille panels located on the base of the cabinet. To enable the cabinet to be lifted by a crane, removable lifting bars, are fitted to the top of the cabinet. In the eventuality that the equipment cannot be moved by fork lift or crane, then rollers should be used.
2.3.3
Clearances
As Hipulse has no ventilation grills at either the sides or the rear, no clearances are required. Back -access is not an essential requirement for maintenance; however, where space permits, a clearance of approximately 600mm will ease access to magnetic component parts. Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully opened.
2.3.4
After the equipment is in place, remove the transportation restraints that hold the output transformer in place.
Cables can enter for Hipulse UPS and battery cabinet either from below or through either side. Side entry is made possible by removing blanking pieces fitted in the side panel to reveal the cable entry holes. This cable entry method allows the equipment to be positioned on a solid floor without the need for cable trenching and allows cables to pass from one module to the other when positioned side-by-side.
2.3.5
Cable entry
Note: When selecting the power cables for side entry to a module located on a solid floor, consideration must be given to the minimum permissible bending radius of the proposed cables to ensure that they can be fashioned to reach the UPS connection busbars.
2.4
Preliminary Checks
Before you install the UPS hardware you should carry out the following preliminary checks: 1. Verify that the UPS room satisfies the environmental conditions stipulated in the equipment specification, paying particular attention to the ambient temperature and air exchange system. 2. Remove any packaging debris, then visually examine the UPS and battery equipment for transit damage, both internally and externally. Report any such damage to the shipper immediately.
2.5
Installation Drawings
The following diagrams illustrate the key mechanical characteristics of the various UPS system cabinets 2.1 2.3 2.5 2.7 2.9 2.11 2.13 2.15 2.17 2.19 2.20 2.22 80kVA UPS with 6 pulse rectifier Single module and 1+N 80kVA UPS with 12 pulse rectifier Single module and 1+N 120kVA UPS with 6 pulse rectifier Single module and 1+N 120kVA UPS with 12 pulse rectifier Single module and 1+N 160kVA UPS with 6 pulse rectifier Single module and 1+N 160kVA UPS with 12 pulse rectifier Single module and 1+N 200kVA UPS with 6 pulse rectifier Single module and 1+N 200kVA UPS with 12 pulse rectifier Single module and 1+N 80kVA UPS with 6 pulse rectifier with Top cable entry option 80kVA UPS with 12 pulse rectifier with Top cable entry option 120/ 160/ 200kVA UPS with 6 pulse rectifier with Top cable entry option 120/ 160/ 200kVA UPS with 12 pulse rectifier with Top cable entry option
875 4
F R O N T
............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................
1900
900 842
1900
1 1100 900
REAR VIEW
1680
TOP VIEW
all dimensions are in mm
1. 2. 3. 4. 5.
Removable grill for lifting with fork-lift truck (200 x 100mm) Air inlet grill Removable grill if using side cable entry (630 X 105 mm) Top lifting bars (removable) Air outlet grill Fig 2-1 : 80 kVA UPS with 6 pulse rectifier
10
BASE VIEW
1
25.5 15 20 860 100 45 100 45 78.5 25.5 25.5 27 800 20
749
F ront D o o r
25.5
809
1. 2. 3. 4.
N.4 holes dia. 14 for securing unit to floor (if required) Surface loading of UPS N4 x 70 sq.cm, 2.7 Kg/sq.cm. Grill for air entry from the bottom Cable access
11
875
F R O N T
....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... .......................
............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................
1900 2 1
1300 842
1 1400
REAR VIEW
1680
TOP VIEW
all dimensions are in mm
12
BASE VIEW
1
15 25.5 349 25.5 860 100 45 100 45 78.5 100 45 25.5 27 800 45 20
F ront D o o r
400 25.5 809
20
1. 2. 3. 4.
N.4 holes dia. 14 for securing unit to floor (if required) Surface loading of UPS N8 x 70 sq.cm, 2 Kg /sq.cm. Grill for air entry from the bottom Cable access
13
875
F R O N T
............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................
....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... .......................
1900
1250 842
1 1450
REAR VIEW
1680
TOP VIEW
all dimensions are in mm
1. 2. 3. 4. 5.
Removable grill for lifting with fork-lift truck ( 455 x 100mm). Air inlet grill. Removable grill if using side cable entry (630 X 105 mm). Top lifting bars (removable). Air outlet grill
1
20
BASE VIEW
1210 100 45 20 15 100 100 45 4 5 1 0 3 .5 25.5 27 800 50 50 25.5 45
749
25.5
F ront D o o r
F ront D o o r
1159
25.5
1. 2. 3. 4.
N.4 holes dia. 14 for securing unit to floor (if required) Surface loading of UPS N4 x 70 & 2 x 45 sq.cm, 2.7 Kg /sq.cm. Grill for air entry from the bottom Cable access
Fig 2-6 : Base view for 120 kVA UPS with 6 pulse rectifier
15
F R O N T
............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ...............................
............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................
....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... .......................
1900
1890 842
REAR VIEW
1. 2. 3. 4.
Removable grill for lifting with fork-lift truck (440 x 110mm). Air inlet grill. Removable grill if using side cable entry (630 X 105 mm). Top lifting bars (removable).
Fig 2-7 : 120 kVA UPS with 12 pulse rectifier
16
TOP VIEW
2
1680
2090
BASE VIEW
1
20 2 5 .5 589 2 5 .5 1850 100 20 15 45 100 45 103.5 27 800 45 45 50 45 100
100 45
F ront D o o r
640 2 5 .5
F ront D o o r
1159 2 5 .5
2
20
1. 2. 3. 4.
N.4 holes dia. 14 for securing unit to floor (if required) Surface loading of UPS N8 x 70 & 2 x 45 sq.cm, 2.6 Kg /sq.cm. Grill for air entry from the bottom Cable access
Fig 2-8 : Base and Top view for 120 kVA UPS with 12 pulse rectifier
17
875
F R O N T
............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................
....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... .......................
1900
1250 842
1 1450
REAR VIEW
1680
TOP VIEW
all dimensions are in mm
1. 2. 3. 4. 5.
Removable grill for lifting with fork-lift truck ( 455 x 100mm). Air inlet grill. Removable grill if using side cable entry (630 X 105 mm). Top lifting bars (removable). Air outlet grill
1
20
BASE VIEW
1210 100 45 20 15 100 100 45 4 5 1 0 3 .5 25.5 27 800 50 50 25.5 45
749
25.5
F ront D o o r
F ront D o o r
1159
25.5
1. 2. 3. 4.
N.4 holes dia. 14 for securing unit to floor (if required) Surface loading of UPS N4 x 70 & 2 x 45 sq.cm, 3.2 Kg /sq.cm. Grill for air entry from the bottom Cable access
Fig 2-10 : Base view for 160 kVA UPS with 6 pulse rectifier
19
875
F R O N T
............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ...............................
............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................
....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... .......................
1900
1890 842
1. 2. 3. 4.
Removable grill for lifting with fork-lift truck. Air inlet grill. Removable grill if using side cable entry (630 X 105 mm). Top lifting bars (removable).
REAR VIEW
all dimensions are in mm
TOP VIEW
2
1680
2090
BASE VIEW
1
20 2 5 .5 589 2 5 .5 1850 100 20 15 45 100 45 103.5 27 800 45 45 50 45 100
100 45
F ront D o o r
640 2 5 .5
F ront D o o r
1159 2 5 .5
2
20
1. 2. 3. 4.
N.4 holes dia. 14 for securing unit to floor (if required) Surface loading of UPS N8 x 70 & 2 x 45 sq.cm, 2.6 Kg /sq.cm. Grill for air entry from the bottom Cable access
Fig 2-12 : Top and Base view for 160 kVA UPS with 12 pulse rectifier
21
875
F R O N T
............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................
....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... .......................
1900
1250 842
1 1450
REAR VIEW
1680
TOP VIEW
all dimensions are in mm
1. 2. 3. 4. 5.
Removable grill for lifting with fork-lift truck. Air inlet grill. Removable grill if using side cable entry (630 X 105 mm). Top lifting bars (removable). Air outlet grill.
Fig 2-13 : 200 kVA UPS with 6pulse rectifier
22
1
20
BASE VIEW
1210 100 45 20 15 45 100 50 45 103.5 25.5 27 800 50 1110 50 25.5 45
100
749
25.5
F ront D o o r
F ront D o o r
1159
25.5
1. 2. 3. 4.
N.4 holes dia. 14 for securing unit to floor (if required) Surface loading of UPS N4 x 70 & 2 x 45 sq.cm, 3.6 Kg /sq.cm. Grill for air entry from the bottom Cable access
Fig 2-14 : Base view of 200 kVA UPS with 6pulse rectifier
23
875
F R O N T
............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ...............................
............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................
....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... .......................
1900
1890 842
REAR VIEW
1. 2. 3. 4.
Removable grill for lifting with fork-lift truck (440 x 100mm). Air inlet grill. Removable grill if using side cable entry (630 X 105 mm). Top lifting bars (removable).
Fig 2-15 : 200 kVA UPS with 12 pulse rectifier
24
TOP VIEW
2
1680
2090
BASE VIEW
1
20 2 5 .5 589 2 5 .5 1850 100 45 20 15 100 100 45 45 103.5 27 800 45 45 50 45 100
F ront D o o r
640 2 5 .5
F ront D o o r
1159 2 5 .5
2
20
1. 2. 3. 4.
N.4 holes dia. 14 for securing unit to floor (if required) Surface loading of UPS N8 x 70 & 2 x 45 sq.cm, 3.1 Kg /sq.cm. Grill for air entry from the bottom Cable access
Fig 2-16 : Top and Base view of 200 kVA UPS with 12 pulse rectifier
25
875
F R O N T
............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................
....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... .......................
1900
1300 842
REAR VIEW
1. 2. 3. 4.
Removable grill for lifting with fork-lift truck. Air inlet grill. Removable grill if using side cable entry (630 X 105 mm). Top lifting bars (removable).
Fig 2-17 : 80 kVA 6 pulse rectifier UPS with Top cable entry option
26
TOP VIEW
1
1680
1400
BASE VIEW
15 20 880 380 100 100 20
45
45
800
F ront D o o r
25.5 809 25.5
1. 2. 3. 4.
N.4 holes dia. 14 for securing unit to floor (if required) Surface loading of UPS N8 x 70 sq.cm Grill for air entry from the bottom Cable access
Fig 2-18 : Top and Base view of 80 kVA 6 pulse rectifier UPS with Top cable entry option
27
27
875 4
F R O N T
............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ...............................
............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................
....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... .......................
1900
1700 842
REAR VIEW
1. 2. 3. 4.
Removable grill for lifting with fork-lift truck (180 x 100mm) Air inlet grill. Removable grill if using side cable entry (630 X 105 mm). Top lifting bars (removable).
Fig 2-19 : 80 kVA 12 pulse rectifier UPS with Top cable entry option
28
875 4
F R O N T
............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................
....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... .......................
............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ...............................
1900
1890
842
REAR VIEW
1. 2. 3. 4.
Removable grill for lifting with fork-lift truck (440 x 100mm). Air inlet grill. Removable grill if using side cable entry (630 X 105 mm). Top lifting bars (removable).
Fig 2-20 : 120/ 160/ 200 kVA 6 pulse rectifier UPS with Top cable entry option
29
TOP VIEW
1680
2090
BASE VIEW
20 1210 100 100 680 20 100 15
45
45
100
50
1110
50 45 50
45
45
800
F ront D o o r
25.5 1159 25.5
25.5
F ront D o o r
589 25.5
1. 2. 3. 4.
N.4 holes dia. 14 for securing unit to floor (if required) Surface loading of UPS N8 x 70 & 2 x 45 sq.cm. Grill for air entry from the bottom Cable access
Fig 2-21 : Top and Base view of 120/ 160/ 200 kVA 6 pulse rectifier UPS with Top cable entry option
30
27
875 4
F R O N T
............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ...............................
............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................
....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... ....................... .......................
............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ............................... ...............................
1900
2530
842
REAR VIEW
1. 2. 3. 4.
Removable grill for lifting with fork-lift truck (440 x 100 mm). Air inlet grill. Removable grill if using side cable entry (630 X 105 mm). Top lifting bars (removable).
Fig 2-22 : Top and Base view of 120/ 160/ 200 kVA 6 pulse rectifier UPS with Top cable entry option
31
Installation (Electrical)
The UPS requires both Power and Control cabling once it has been mechanically installed. All Control cables, whether screened or not, should be run separate from the Power cables in metal conduits or metal ducts which are electrically bonded to the metalwork of the cabinets to which they are connected.
3.1
Power Cabling
WARNING
Before cabling-up the UPS, ensure that you are aware of the location and operation of the external isolators that connect the UPS input/ bypass supply to the mains distribution panel. Check that these supplies are electrically isolated, and post any necessary warning signs to prevent their inadvertent operation.
3.1.1
System Configuration
The power cables of the system must be size with respect to the following description: The module input cables must be sized for the maximum input current, including the maximum battery recharge current, given in the table 3-1, with respect to the module rating and the input a.c. voltage.
The Bypass and Output cables must be sized for the nominal output current, given in the table 3.1, with respect to the module rating and the output a.c. voltage.
Battery cables
Each UPS module has its own battery, which is connected using two cables, one positive and one negative. The battery cables must be sized for the battery discharge current at the end-of-discharge voltage, as given in the table 3-1, with respect to the module rating.
32
3.1.2
Cable rating
NOMINAL CURRENT (Amps) BUSBAR STUD SIZE Battery at minimum battery voltage (400Vac) 208 309 414 517 Input / Output Cables Bolt M8 M10 M10 M10 dia 8.2 11 11 11 M8 Bolt M10 Bolt M10 Bolt M10 Bolt 13 26 26 26 Torque Load (Nm)
Input Mains with full battery re-charge (less 5% for 12 pulse) 380V 400V 157 233 310 388 415V 151 225 299 374
Output at full load 380V 121 182 243 304 400V 115 173 231 289 415V 111 167 222 278
Battery Cables
Table 3-1 UPS Module cabinet power cable rating 3.1.3 General Notes
The following are guidelines only and superseded by local regulations and codes of practice where applicable: 1. The neutral conductor should be sized for 1.5 times the output/ bypass current. 2. The earth conductor should be sized at 2 times the output/ bypass conductor ( this is dependent on the fault rating, cable lengths, type of protection etc.) 3. Consideration should be given to the use of paralleled smaller cables for heavy currents, as this can ease installation considerably. 4. When sizing battery cables, a maximum volt drop of 3V d.c. is permissible at the current ratings given in Table 3-1.
The rectifier input, bypass, output and battery power cables (all require lug type terminations) and are connected to busbars situated below the power isolator switches as shown in figure 3.1 for 80kVA and fig 3.2 for 120 /160/ 200kVA. A terminal block X3 is used for connecting the control cables to the battery circuit breaker and a second terminal block X4 is used for the external emergency stop facility, external OFF inverter, ext. Bypass, etc. these are female spade type connections (Fast-on 6.3 x 0.8) and are described later in Section 3.3
3.1.4
Cable Connections
3.1.5
Safety earth
The safety earth busbar is located near the input and output power supply connections as shown in the figure 3.1 and 3.2. The safety earth cable must be connected to the earth busbar and bonded to each cabinet in the system. All cabinets and cable trunking should be earthed in accordance with local regulations.
WARNING
Failure to follow adequate earthing procedures can result in electric shock hazard to personnel, or the risk of fire, should an earth fault occur.
33
For safety reasons, it is necessary to install, external to the UPS, circuit breaking protective devices in the input a.c. supply and towards the battery. Given that every installation has its own characteristics, this chapter provides general useful information engineers, with knowledge of operating practices, of regulatory standards, and of the equipment to be installed. Rectifier and bypass inputs: Protection against excessive over currents and short circuits These inputs must be protected, installing suitable protective devices at the distribution panel of the incoming main supply, considering that the protection should discriminate with overload capacity of the system (see Chapter 9: Specification - Electrical Characteristics).
3.1.6
Protective devices
Split Bypass : In the case of a split bypass being used, separate protective devices should be installed in the incoming mains distribution panel.
The protective devices must be selected for the nominal input current, with respect to the UPS rating and the input a.c. supply voltage as given in table 3-1.
These isolators must have an average sensitivity, possible adjustable between 0.3 and 1A. It is recommended that the selectivity with every differential switch be verified both upstream of the input distribution board and downstream (towards the load). Use of differential circuit breakers on UPS unit inputs in a configuration with separate inputs and one battery for each unit requires installation of a common device only on the System Bypass Mains. Use of differential circuit breakers on UPS unit inputs sharing a common battery requires installation of device common to all the input lines. If inputs are configured for separate mains, a common device will also be required for all System bypass mains.
Parallel 1+N:
34
The UPS Battery is protected by means of a control circuit that operates the tripping mechanism of an automatic circuit breaking device (having a variable trip setting). The tripping mechanism using an undervoltage release coil that operates on a present minimum voltage level. The circuit breaker is essential for maintenance of the battery and is normally located near to the battery installation. The characteristics and operation of the automatic circuit breaker are given in Chapter 6. Output of the System: In the eventuality that an external distribution panel is used for load distribution, the selection of protective device must proved discrimination with those that are use at the input to the UPS module.
UPS Battery:
3.1.7
Cabling procedure
Once the equipment has been finally positioned and secured, connect the power cables as described in the following procedure. Study the connection diagram in the figures below. 1. Verify that the UPS equipment is totally isolated from its external power source and all the UPS power isolators are open. Check that these supplies are electrically isolated, and post any necessary warning signs to prevent their inadvertent operation. 2. Open the door(s) to the UPS cabinet and remove the lower protective cover to gain access to the connections bars. 3. Connect the safety earth and any necessary bonding earth cables to the copper earth bus busbar located on the floor of the equipment below the power connections.
Note: The earthing and neutral bonding arrangement must be in accordance with local and national codes practice Common Input Connections:
4. For common bypass and rectifier inputs, connect the a.c. input supply cables between the mains distribution panel and the UPS bypass input supply busbars (U3-V3W3-N3 terminals) and tighten the connections to 13 Nm (M8 bolt), and to 26 Nm (M10 bolts).
Note: When the Class 'A' EMC filter is fitted and a common input supply is used for the bypass and rectifier, the input busbars ( ) should be removed.
ENSURE CORRECT PHASE ROTATION 5. If a 'Split Bypass' configuration is used, connect the a.c. input supply cables to the input busbars (U1-V1-W1 terminals) and the bypass a.c. supply cables to the bypass busbars (U3-V3-W3-N3 terminals) and tighten the connections to 13 Nm (M8 bolt), and to 26 Nm (M10 bolts) WARNING
Ensure that any links ( ) fitted between Rectifier input and Bypass busbars are removed (see figures 3-1 & 3-2).
ENSURE CORRECT PHASE ROTATION
35
If the load equipment will not be ready to accept power on the arrival of the commissioning engineer then ensure that the system output cables are safely isolated at their ends.
7. Connect the Battery cables between the UPS terminals (+/ -) and its associated battery circuit breaker. Connect screened auxiliary cables from each battery circuit breaker control board to the auxiliary terminal block (X3) of their metal frame of the battery cabinet (if used) or Battery circuit breaker box (if used). As a safety precaution remove the battery fuse in the module until the arrival of commissioning engineer. OBSERVE THE BATTERY CABLE POLARITY WARNING
Do not close the battery circuit breaker before the equipment has been commissioned.
8. 1+N Parallel UPS System: Inside the module there is an Parallel Connectors Board mounted on the left hand side. Connect one end of the interconnecting ribbon cables to interface connector (X1) of the first UPS module and the other end to connector (X2) of the second module, and so to the next module until a closed loop is formed. (see fig 8-3).
Auxiliary Connections:
9. Connect the auxiliary cables of any external interface/ signals to the respective connections of the output auxiliary terminal block (X4). 10. Refit the lower protective cover.
36
Note 1: For Split Bypass operation, ensure the bubars (*) between Bypass and Rectifier input are removed. Note 2: These bar () are only present when the Class 'A' EMC Filter is fitted. Note 3: When the Class 'A' EMC filter is fitted and a common input supply is used for the bypass and rectifier, the input bars (U1, V1, W1) should be removed.
X3
1 2 1
Q1
Q2
Q4
X4
1 2
Q3
U1 V 1 W 1 U3 V 3 W 3 N3 N2 U2 V 2 W 2
Q1
1
Q2
Q4
12
12
Q3
U1 V 1 W 1 U3 V 3 W 3 N3 N2 U2 V 2 W 2
BYPASS CONNECTIONS
EARTH
OUTPUT CONNECTIONS
Note 1: For Split Bypass operation, ensure the bubars (*) between Bypass and Rectifier input are removed. Note 2: These bar () are only present when the Class 'A' EMC Filter is fitted. Note 3: When the Class 'A' EMC filter is fitted and a common input supply is used for the bypass and rectifier, the input bars (U1, V1, W1) should be removed.
X3
12 1
Q1
Q2
Q4
X4
12
Q3
U1 V 1 W 1
U3 V 3 W 3 N3
N2 U2 V 2 W 2
X3
Q1
Q2
Q4
12
X4
12
Q3
U1 V 1 W 1
U3 V 3 W 3 N3
N2 U2 V 2 W 2
BATTERY CONNECTIONS
INPUT CONNECTIONS
BYPASS CONNECTIONS
EARTH
OUTPUT CONNECTIONS
Fig 3-2 : Cable connections for 120/ 160/ 200 kVA UPS
38
3.2
UPS
Rectifier a.c. input supply Bypass a.c. input supply UPS a.c. output supply Battery Power Auxiliary Cables: Battery Control / Temperature compensation. Communications to AS400/ External Alarm monitor Remote Emergency Power OFF (EPO) Ground
Table 3 - 2
39
3.3
3.3.1
Control cables
Battery Control
The battery circuit breaker is controlled by the Battery Circuit Breaker Controller Board which is located within the Battery Cabinet - or adjacent to the Battery Circuit Breaker when the batteries are rack-mounted. This board controls the circuit breakers undervolts release coil and also provides a path for the circuit breaker auxiliary contacts to signal the circuit breaker status back to the UPS control logic. All the connections between the controller board and the UPS module are made via the Auxiliary Terminal Block which is located in the base of the UPS cabinet.
B AT T E RY B R E A K ER
C IR C U IT
C O NT R O L L E R
BOARD
X1
X3
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12
AUXILIAR Y TERMINAL BLOCK LO CATED IN Ext OFF Inv. Ext Sw. Out Ext EPO Ext BYP Back feed Int EPO UPS CABINET
LINKS
X4
Connect the battery circuit breaker control and temperature compensation cables between the UPS auxiliary terminal block and battery circuit breaker controller board as shown in figure 3-3. These cable must be shielded, shield should be connected at protective earth of battery cabinet or battery breaker, not of UPS.
CAUTION
If battery temperature compensation is not used the system must be de-activated by commissioning engineer.
40
3.3.2
Note:
The auxiliary cables of the battery must be screened and double insulated. The screen is connected to the earth of the battery cabinet or supporting rack. Use multiple-core shielded cables with a section of 0.5 to 1mm2 Connect the cables with the Fast-on 6.3 x 0.8 mm terminals (female)
3.3.3
3-4
5-6
Ext. EPO
7-8
Ext. BYP
9-10 11-12
Note:
All auxiliary cables of terminal block X4 must be double insulated. The cross-sectional area of the auxiliary cables is from 0.5 to 1 mm2 Connect the cables with the Fast-on 6.3 x 0.8 mm terminals (female) Maximum contact rating on auxiliary terminals: 50 Vdc @ 1 Amp.
41
To Battery
+
Sensor Temperature (Optional) 3 2 1
X3 X4 X5 X6 X7
V<
X8 X9
X2 X10 1 2 3 4 5 X1
UPS CABINET
X3
1 2 3 4 5 6 7 8 9 10 11 12
3.3.4
Emergency Stop
Note: The Emergency Stop action within the UPS shuts down the rectifier, inverter and static bypass and trips the battery circuit breaker. It does not however internally disconnect the input mains supply. If required, this additional action can be facilitated by feeding the UPS input via a circuit breaker which can be tripped by a second contact of the Emergency Stop switch. Note: Terminals I1 and I2 of the Auxiliary Terminal Block (X4) are connected to a normally closed contact of the UPS Display Panel Emergency Stop button and go open circuit when the button is pressed. This output can be used as part of a wider Emergency Stop system to initiate an external action (such as tripping an external supply breaker) 3.3.5 Back Feed Protection
Using an auxiliary terminal (pins 9-10 of connector X4) the UPS provides a normally open contact to be used for opening of an external circuit protection device, to protect the operator against back feed of energy resulting from a short-circuit fault of the Bypass line SCRs. This auxiliary contact can be used, for example, in series with an external low voltage source, in order to supply the trip coil of an automatic circuit breaking device, located upstream of the UPS Bypass mains input. In the vent of energy being backfeed the auxiliary circuit will activate closing the normally open contact and as a result opening of the external circuit-breaking device; the UPS is disconnected from the Bypass mains supply. The electrical characteristics of the auxiliary contact are 50V (a.c. or d.c.) @ 1 Amp.
42
CHAPTER 4
HIPULSE
%
43
4.1.1
The control and display panel LEd indications are illustrated in figure 4-2 and described in the following text:
6
DISPLAY
%
ENTER
10
11
12
13
14
15
16
17
18
19
Mimic indications
Six LEDs mounted on a single line diagram represents the various UPS power paths and show the current UPS operation status: 1. Bypass supply healthy This led illuminates when the bypass a.c. input power switch is closed and the input supply is within of set value nominal voltage (default 10%) 2. Input supply healthy and Rectifier is operative. 3. Battery voltage healthy (i.e. between under - voltage cut-off and over - voltage trip levels). 4. Inverter output healthy. 5. Load on Inverter status This led illuminates when the output power switch is closed and the load is connected to the inverter. 6. Load on Bypass status. This led illuminates when the output power switch is closed and the load is connected to the bypass a.c. supply via the static switch.
7. Inverter ON - Manual inverter selection switch. 8. Inverter LED - inverter status indicator contained within the switch icon. The Inverter LED (yellow) indicates when the Inverter is switched OFF.
44
Note: In addition to entering the day-to-day operating functions, the menu system is also used to set-up various UPS operating parameters during commissioning. A system of password protection is therefor used to limit the control functions accessible to the operator, whilst allowing full access to maintenance personnel. A full description of the available menus is provided in the appropriate User and Commissioning manuals. Note: From the Display panel menu it is possible to select one of the following languages: English, French, Italian, Spanish, German, Dutch. The sequence is Default window > FUNCTION > ENTER PASSWORD > PANEL SETUP > LANGUAGE
9. ESC Pressing the ESCAPE cancels the most recent actions; i.e. when selecting options it returns the prvious window to the LCD. when setting parameters, it exits the window without saving the new settings. 10. MENU The DOWN push button moves a cursor down the LCD over the options offered on certain windows, and changes the highlighted parameter values in others. 11. MENU The UP push button moves a cursor up the LCD over the options offered on certain windows, and move a rectangular cursor to the next digit on the right when changing parameter values in others; 12 ENTER Pressing ENTER, when selecting options, displays the next window; The next window is determined by the option which has been selected in the present window. When selecting new parameters its saves the new parameters. 13 Warning indicator - The red LED with the Alarm Silence switch illuminates when a WARNING alarm is displayed on the LCD message screen, and is normally accompanied by an audible alarm. 14. Alarm Silence Switch - Pressing the Alarm Silence switch cancels the audible alarm but leaves the warning message display until the inappropriate condition is rectified.
45
Hipulse UPS Manual Single 1+N UPS System Pressing the ENTER button [12] from the Default Screen gives the operator access to the Measurements menu which facilitates access to the following measurements:
Output Parameters
Output Output Output Output Voltage (L-L or L-N for all three phases) Current (all three phase currents displayed in Amperes or as a % Load) Power (for all three phases displayed in kW or kVA) Frequency (of inverter and bypass mains)
Input Parameters
- Input Voltage (L-L for all three phases)
Battery Parameters
- Battery Voltage - Battery Current - Battery Charge (in %)
Temperature
- Temperature (C) at critical points
Bargraph Selection
This following functional area shows the various UPS load and battery charging conditions. 16. Load Battery The amber led situated at the beginning of the % Autonomy bargraph illuminates when the battery voltage has discharged to 1.8V /cell and indicates that the battery is approaching its low voltage cut-off point and the UPS will shortly shutdown. 17. % Battery state Autonomy time bargraph When the battery is being charged (normal) the six leds illuminate progressively to indicate the state of battery charge as a percentage of a charge. When the battery is discharging (battery on-load) the bargraph function changes to provide an indication of the remaining battery autonomy time, each step indicate approximately 2 minutes. With a fully charged battery all five LEDs are illuminated indicating greater than 10 minutes remaining, as the autonomy falls below this time the LEDs will extinguish in steps starting from the right-hand end. 18. % Load bargraph The six leds illuminate progressively to indicate the applied load as a percentage of the rated maximum current increasing in 20% steps to 100% of full load when all five are illuminated. 19. Overload The amber LED situated at the end of the % Load bargraph illuminates if the applied load exceeds 100% of modules rated output current. This indication will be accompanied by an audible alarm a alarm message.
46
............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................ ............................................
4.1.2
A map of the routes to the options offered by the menu is provided in figure below. Options include windows which show status information and windows which permit data to be entered, or parameters for equipment control to be set. The menu map shows that the route pass from the main menu through different intermediate windows to reach the option targeted. The diagram shows each of the windows in the format in which it appears on the LCD screen. The initializing, default & main menu windows are described below.
47
V 07.0 V 07.0
<
<
<
OUTPUT : [ Vrms] VOLTAGE [Vrms] L1-L2 L 2-L3 L3-L4 XXX XXX XXX
L3-N XXX
[ %] L3 XXX
[KW] L3 XXXX
[ KVA] L3 XXXX
FUNCTION
MAINTENANCE
SETUP
PRESS ESCAPE KE Y
After first connecting power to the UPS and closing the bypass A.C. input power switch, the INITIALIZATION message will appear on the LCD screen. It persists for about five seconds while the control firmware is loaded and the unit performs a self-test. It is followed by a window showing various messages with the time and date on the bottom line. When the power switches and battery circuit breaker have been closed and the inverter has stabilized the window will change to the default window.
RECTIF. SWITCH OPEN BATTERY C.B. OPEN OUTPUT SWITCH OPEN hh.mm.ss dd.mm.yy
Default Window
NORMAL OPERATION
The message shown below, will be seen on the default window whenever the UPS is operating normally. The top lines display the UPS operational status and indicates alarm conditions when they occur; and line four normally shows the time and date.
hh.mm.ss
dd.mm.yy
Info Window
From Default Window, pressing the ESC key, information about the modem programmed in memory and its connection are shown on display. Pressing again the ESC key, software release are shown, both on UPS board and on Panel board; this feature is useful upgrading SW for next versions and to know exactly features of present release. Pressing again ESC key it goes back to Default Window.
The MEASUREMENT option gives access to windows which show the present values of parameters such as input & output voltages and current, load, etc. These parameters are useful when determining the state of UPS or the cause of alarms, and are described in more detail below.
49
Hipulse UPS Manual Single 1+N UPS System The FUNCTION, MAINTENANCE and SETUP options all require a password which is set by the commissioning engineer. This manual does not provide servicing instructions and the options accessed from theses windows are therefore not shown on the menu map in figure 4-4. Only trained service engineers should be authorized with a password. In any case FUNCTION, MAINTENANCE and SETUP options can be read but is not possible to change them without password.
The Alarm and Warning messages are shown on the three upper lines of the display. The ALARM indicator (red) and audible warning accompany all Alarm messages. There is a default selection for every message and corresponding mode of red indicator (OFF, ON, FLASHING) and buzzer sound (OFF, ON INTERMITTENT, SINGLE SOUND) The default mode can be changed according to particular needs of the plant, a PC and communication program are needed. The Alarm and Warning messages Interpretations of this manual. are detailed in Chapter 7Display Panel
50
CHAPTER 5
Operating Instructions
5.1 Introduction
The UPS can be considered to be in one of three operating conditions: All relevant power switches and circuit breakers closed, the load is powered by the UPS.
Normal operation
Shutdown
All power switches and circuit breakers open - no load power.
The load power is supplied through the mains static bypass line. This may be considered as an intermediate operating condition being utilized for the purpose of load transfers between inverter and maintenance bypass or supply under abnormal operating conditions.
On Static Bypass
ECOMODE
All the relevant power supply switches and the battery switch are off, and the load is fed by the Bypass Mains through the UPS Static Transfer Switch, while the Inverter remains on stand-by. This chapter contains instructions which enable you to switch between the three above conditions, to carry out a RESET after a fault transfer and how to switch OFF the inverter.
5.1.1 General notes Note1: All the user controls and indicators mentioned in these procedures are identified in chapter 1. Some of diagrams are repeated here to assist in understanding the procedures. Note2: The audible alarm may annunciate at various points in these procedures. It can be cancelled at any time by pressing the Alarm Reset push-button. Note3: The Hipulse UPS System incorporates an optional automatic boost charge facility which can be used in systems containing conventional flooded lead-acid batteries. If this type of battery is used in your installation you may notice that the battery charger voltage may be greater than its nominal (432V d.c. for 380V a.c., 446V d.c. for 400V a.c. and 459V d.c. for 415V a.c. system) when the mains supply returns from a prolonged outage. This is the normal response of the boost charge facility; the charger voltage should return to normal after a few hours. 5.1.2 Power Switches
The UPS can be separated by means of power switches, mounted inside the cabinet and accessible after opening the front door, which has a key. The location of the UPS power switches is shown in Figure 5-1. The UPS module power switches are: o Q1 - Input Isolator: connects the UPS with he mains supply. o Q2 - Bypass Isolator: connects the UPS with the bypass supply. o Q3 - Maintenance Bypass Isolator (Padlocked) permits supply of the load directly by the bypass line for maintenance of the UPS module.
The internal maintenance bypass must not be used when the UPS system is comprised of more than two UPS modules in parallel.
o Q4 - Output Isolator: connects the output of the UPS to the load.
Note: The battery interrupter is not expected inside of the UPS and should be installed in the proximity of the respective battery bank.
51
5.2 Procedure for UPS Start-up: without interrupting power to the load
This procedure will describe how to start the UPS and the how to transfer the load from the external maintenance bypass to the UPS inverter. It is assumed that the installation is complete, the system has been commissioned by authorized personnel and the external power isolators are closed. Refer to Fig 5-1 for corresponding isolators Q1 to Q4, and Fig 5-2 Operator Control Panel for various LEDs and Display indications.
Q1 R ECTIFIER ISOLATOR
Q4 OUTPUT ISOLATOR
1 2
DISPLAY
%
10
11
12
13
14
15
16
17
18
19
Initializing Window:
LIEBERT UPS
After first connecting power to the UPS and closing the isolator, this message will appear on the LCD screen. It persists for about five seconds while the control firmware is loaded by a screen showing various messages with the time and date on the bottom line. The Module Mimic indicators Bypass supply healthy (1) and after 20 seconds Load on Bypass (6) will flash and red led (13) will illuminate.
52
The Display window will show the present status of the UPS
Note: In ECOMODE the Load on Mains led (6) stays on while the Load on inverter led (5) is off.
NORMAL OPERATION
The message shown below, will be seen on the Default screen whenever the UPS is operating normally.
hh.mm.ss
dd.mm.yy
The UPS is operating normally with its Inverter supplying the load
ECOMODE: The following message will appear in the default screen whenever the UPS is operating on ECOMODE. The load is supplied by the Bypass Mains.
The UPS is operating in ECOMODE with the Bypass Mains supplying the load.
53
5.3 Procedure for UPS Startup without power initially supplied to the load
This procedure should be followed when turning on the UPS from fully powered down condition i.e. where the load is not being initially supplied at all. It is assumed that the installation is complete, the system has been commissioned by authorized personnel and the external power isolators are closed. Refer to Fig 5-1 & 5-2 for corresponding isolators Q1 to Q4, and Operator control Panel respectively. 1. Open the UPS doors to gain access to the main power switches. 2. Close the Rectifier Power Switch (Q1). The Module Mimic LEDs will indicate input supply a.c. present (2 -steady green) and after approximately 20 seconds the Inverter output healthy (4- steady green) and Battery unavailable (3) will light and also red led (13) will illuminate. The Display screen will show the following:
Initializing Window:
LIEBERT UPS
After first connecting power to the UPS and closing the Q1 isolator, this message will appear on the LCD screen. It persists for about five seconds while the control firmware is loaded. It is followed by a screen showing various messages with the time and date on the bottom line.
BYPASS SWITCH OPEN BATTERY C.B. OPEN OUTPUT SWITCH OPEN hh.mm.ss dd.mm.yy
Note: If input power is present but the display remains blank, then the Micro Controller is not working, please contact your dealer for advice.
WARNING
The following action will apply power to load the equipment - Ensure that it is safe do so
3. Close the UPS output power switch Q4. The Module Mimic LEDs will change so that the Load on Inverter (5 - steady green) and Battery unavailable (3) will light and also red led (13) will illuminate.
BATTERY C.B. OPEN BYPASS SWITCH OPEN hh.mm.ss dd.mm.yy
hh.mm.ss
dd.mm.yy
54
<
The Main Menu Window will display: Select MEASUREMENT and press ENTER key.
If the voltage indicated is satisfactory (432V d.c. for 380V a.c. system, 446VV d.c. for 400V a.c. system and 459V d.c. for a 415V a.c. system) press the Escape key repeatedly until the display returns to the original window. 6. Manually close the battery circuit breaker. This is located inside the battery cabinet (if used) or is otherwise located adjacent to the battery racks. The Module Mimic indicator (3) Battery unavailable should extinguish. Several LEDs on the Battery state of charge bargraph (17) will illuminate showing the battery state of charge When the battery circuit breaker has been closed and the inverter has stabilized the screen will change to the default window.
Default window:
NORMAL OPERATION
The message shown below, will be seen on the default screen whenever the UPS is operating normally: The top lines display the UPS operational status and indicates alarm conditions when they occur; and line four normally shows the time and date.
hh.mm.ss
dd.mm.yy
The UPS is operating normally with its Inverter supplying the load.
ECOMODE: The following message will appear in the default screen whenever the UPS is operating in ECOMODE. The load is supplied through Bypass Mains.
The UPS is operating in ECOMODE with the Bypass Mains supplying the load.
55
5.4 Procedure for Switching the UPS into a Maintenance Bypass condition from normal operation
The first part of this procedure details how to select the Inverter OFF and power the load from the bypass mains via the Static Switch. This procedure should be followed to transfer the load from the UPS inverter output to the maintenance bypass system. This may be required during UPS maintenance procedures. NORMAL OPERATION: Follow the procedure below to transfer the load from the output to the Maintenance Bypass of UPS. ECOMODE: Follow the procedure below to transfer the load from the output Maintenance Bypass of the UPS.
CAUTION
The following window alls the operator to select the UPS inverter ON or OFF Before making this operation, read messages on display to be sure that bypass supply is regular and the inverter is synchronous with it, not to risk a short interruption in powering the load. IF YOUR ARE NOT SURE OF WHAT YOU ARE DOING - THEN DO NOT DO IT
1. Press the INV switch on the left side of the operator control panel.
WARNING! STOP INVERTER REQUESTED ENTER TO CONTINUE ESC TO CANCEL
2. Confirm this operation as instructed at the display: Press ENTER for 1 second to confirm INV OFF Press ESC for 1 second. 3. If ENTER is pressed: The Module Mimic indicator Load on Inverter (5) will extinguish and the Load on Bypass indicator (6) will flash amber, and also the red led (13) will flash and normally will accompanied by an audible alarm. Pressing the Alarm Silence Switch cancels the audible alarm but leaves the warning message displayed until the appropriate condition is rectified. 4a) NORMAL OPERATION: The UPS inverter will not shut down and the load will transfer to the Bypass supply. The Module Mimic indicator Load on Bypass (6) will flash amber and the Load on Inverter (5) indicator will extinguish.
56
Hipulse UPS Manual Single 1+N UPS System 4b) ECOMODE: At this point the UPS inverter stops but the load continues to be supplied by the bypass mains. The Load on Mains indicator light (6) on the unit's synoptic panel flashes yellow, and the Load on Inverter indicator light (5) goes off.
5. Unfasten the lock, release the internal safety bar and close the maintenance bypass power switch Q3. Open the Rectifier input power switch Q1, the Output power switch Q4, the bypass power switch Q2 and the Battery circuit breaker. This is located inside the battery cabinet (if used) or is otherwise located adjacent to the battery racks. The unit will power down but the load will continue to be supplied by the manual bypass.
WARNING
WARNING
The following points will be live within the UPS: - Bypass a.c. input supply terminals. - Maintenance Bypass power switch. - Static Bypass power switch. - UPS output terminals. Input and Output terminals remain protected by a metallic cover.
Your load is now powered from the maintenance bypass system and the UPS is completely shut down.
57
5.5 Procedure for Switching the UPS ON from a Maintenance Power condition.
Follow the procedure for 'UPS startup: without interrupting power to the load' referring to the paragraph 5.2, start from point number 2.
5.6
This procedure should be followed to completely power down the UPS and LOAD. All power switches, isolators and circuit breakers will be opened and there will be no load power.
CAUTION
The following procedure will switch off all power to the load equipment.
1. Open the Battery circuit breaker and the Rectifier input power switch Q1. The Module Mimic indicator Load on Inverter (5) will extinguish and the Load on Bypass indicator (6) will flash amber. The Battery not available indicator (3) will light amber and the battery bargraph LEDs will all extinguish.
LOAD ON BYPASS BATTERY C.B. OPEN RECTIF. SWITCH OPEN hh.mm.ss dd.mm.yy
The display window will show messages reflecting the actions taken (i.e. Load on Bypass; Battery Breaker open; Rect. Switch open; etc).
On the primary input distribution panel, which is often located distant from the UPS area, a label should be posted advising service personnel that the UPS circuit is under maintenance.
58
WARNING
IMPORTANT
The Maintenance Bypass Power switch may be operated at any time when the UPS is powered down to connect the load to the maintenance bypass supply if required. The load equipment is not protected from normal supply aberrations when operating in the maintenance bypass mode.
5.7 Procedure for carrying out a RESET after a recognized controlled transfer to bypass or EPO action.
When the necessary action to correct the problem has been taken, this procedure should be followed to restore the UPS back to its normal operating condition following, a controlled transfer to bypass or when the Remote Emergency Power Off has been activated. A recognized controlled transfer to bypass is activated by the following problems: Inverter Overtemperature, Cut-off Overload, Battery Over voltage, when configured for manual return from bypass operation (only for system test).
EMERGENCY STOP LOAD ON BYPASS INV: UNSYNCHRONISED hh.mm.ss dd.mm.yy
<
59
<
Return the Display window to normal by repeatedly pressing the ESCAPE key back through the various windows until the default screen is displayed. These operations resets the logic circuitry to enable the rectifier, inverter and static switch to operate normally.
Note: When the remote EPO switch has been activated it is necessary to manually close the battery circuit breaker.
CAUTION
When the EPO system incorporates a trip facility of the external input a.c. power supply circuit breaker, the RESET switch would have no affect on it. First close the external input a.c. supply circuit breaker, the UPS can be started in the normal manner, as the logic circuits will automatically reset on return of the power supplies.
5.8
60
5.9 Procedure to completely switch ON/ OFF the UPS at the UPS Display Control Panel:
MEASUREMENT >FUNCTION MAINTENANCE SETUP
1. From the Default window, press the ENTER key: the Main Menu window will display:
<
2. Select FUNCTION and press ENTER key: Before being allowed into the FUNCTION windows you are requested to enter a password. This is achieved by pressing the UP arrow key repeatedly until the first digit displays the character required, you then press the DOWN arrow key once to move on to the second digit. This action is repeated for all eight digits. When the PASSWORD has been completed press the ENTER key. CAUTION
This operation gives the operator access to modify UPS's operating mode, it is advised that only trained qualified personnel should attempt to do that.
3. You have now access to all function windows.
BATTERY TEST GENERATOR PANEL SETUP >NEXT PAGE
Press the DOWN arrow key until the cursors have selected NEXT PAGE press the enter key.
<
MODEM CONNECTION >ON/OFF UPS CONTROL < RELOAD UPS DATA RESET BUFFERS
4. Press the DOWN arrow key until the cursors have selected ON/OFF UPS CONTROL. Press the enter key.
CAUTION
< ON ON MAN
The following window allows the operator to select the UPS inverter ON or OFF, select the rectifier ON or OFF, select the rectifier to manual or float voltage and a switch OFF the line (bypass) voltage to the load. IF YOU ARE NOT SURE WHAT YOU ARE DOING, THEN DO NOT DO IT.
ROTATE INVERTER
NORMAL OPERATION: 5a. Ensure INVERTER is selected by the cursors and press the ENTER key.
61
The OFF selection will be highlighted, using the UP arrow key, rotate between the selections offered (in this case it will be ON or OFF) select ON. Press the ENTER key to execute your order. After approximately 20 seconds, the Module Mimic will change so that the Load on Inverter (5) will light steady green and the Load on Bypass (6) will extinguish. 6a. Return the Display window to normal by repeatedly pressing ESCAPE key back through the various windows until the default screen is displayed.
The UPS is operating normally with its Inverter supplying the load.
< ON ON MAN
ECOMODE: 5b. Ensure BYPASS is selected by the cursor and press the ENTER key: The OFF selection will be highlighted, using the UP arrow key, rotate between the selection offered (in this case it will be On or OFF) Select ON. Press the ENTER key to execute your order. The Module Mimic LEDs will change: Load on Mains (6) will come on and Load on Inverter (5) will go out. 6b. Return the Display window to normal by repeatedly pressing ESCAPE key back through the various windows until the default screen is displayed.
ROTATE INVERTER
The UPS is operating in ECOMODE with Bypass Mains supplying the load.
62
5.10 Procedure to switch ON/OFF the inverter at UPS display control panel
CAUTION
This operation gives the operator access to modify UPSs operating mode, it is advised that only trained qualified personnel should attempt to do that.
NORMAL OPERATION
The display window will show the present status of the UPS for normal operation.
hh.mm.ss
dd.mm.yy
The display window will show the following screen for the UPS running in ECOMODE. 1. Press the INV switch on the left side of the operator control panel. 2. Confirm this operation as instructed at the display: Press ENTER for 1 second to confirm INV OFF Press ESCAPE for 1 second to exit. 3. If ENTER is pressed: The Module Mimic indicator Load on Inverter (5) will extinguish and the load on bypass indicator (6) will flash amber, and also the red led (13) will light and normally will be accompanied by audible alarm. Pressing the Alarm Silence Switch cancels the audible alarm. Pressing the Alarm Silence Switch cancels the audible, but leaves the warning message displayed until the appropriate condition is rectified.
NORMAL OPERATION
hh.mm.ss
dd.mm.yy
63
CAUTION
Do not continue with this procedure if the battery is not yet charged.
1. 2. 3. 4. 5. 6. 7. 8.
From the default window press the ENTER key: the Main Menu window will display. Select FUNCTION and press ENTER key. When the password has been completed press the ENTER key. Select the BATTERY TEST and press ENTER key. Verify that the parameters entered in the battery test set up menu are appropriate. If not then enter the correct set up parameters (FUNCTION BATTERY TEST SET UP) Press ESC key to return to the battery test menu screen. Using the UP menu button, select YES (Y), then press enter to initiate an immediate battery test. Step back to default screen, by continuously pressing the ESC button and verify that the message: BATTERY UNDER TEST is displayed. The green LED battery bargraph will indicate the remaining battery time.
Note: If the UPS is allowed to run in this condition the battery bargraph LEDs will progressively turn off the indicating the remaining autonomy time. 9.
The battery will be tested for the selected DURATION time after which the UPS will revert to normal operation.
Note: If the battery fails the test, the rectifier will immediately return to the float mode and the BATTERY: TEST FAILED alarm will be displayed on the default screen.
64
<
From Default window, press ENTER key. Select the FUNCTION and press the enter key.
A password must be entered to gain a further access to next menu. The initial default password of 00000000 need not be changed at this point of time. Press the enter key.
>LANGUAGE ENG < TYPE 0000 MASTER GROUP 1 UPS 1 PASSWORD 00000000
Use the UP push button to rotate through the available options and select the required default language. The options are: English, Italian, German, French , Dutch & Spanish. Press ENTER to accept and store the language selection, then step back to the default window by repeatedly pressing ESC as required; the current alarms should now be stored in the selected language.
Note: Ensure the data entered during the following procedures are r3cordded in the appropriate commissioning documentation.
65
Battery Installation
6.1 Introduction
The UPS battery consists of battery blocks connected in series to provide a nominal d.c. input voltage for the UPS inverter. The required Autonomy time (the time that battery can maintain supply to the load in the event of a mains failure) is limited by the ampere hour size of the individual battery blocks and in some cases it could mean several strings are connected in parallel. Usually, with UPS installations in the power range covered by the Hipulse equipment, the batteries are contained in a purpose built battery cabinet which sits alongside the main UPS and the Battery Circuit Breaker Controller Board ( for all sizes). The battery cabinet can be installed in one of the following forms: Complete installation comprising the battery cabinet, batteries and the circuit breaker. Battery cabinets and battery circuit breaker - with no batteries. Battery cabinet only with no batteries or circuit breaker. It is possible to install batteries of various types and capacity in the cabinet to obtain he required autonomy characteristics. It must be possible to disconnect the battery from the UPS module when undertaking maintenance or service procedures. This is facilitated by means of a suitably rated circuit breaker which must be located as close as possible to the battery terminals, and the power and control cables connected to the UPS using the most direct route possible. The circuit breaker can be switched off manually ON or OFF, but should also contain an under voltage release mechanism (to be energized by the UPS control electronics) and a magnetic trip facility for overload protection which is used in conjunction with battery circuit breaker controller module. If multiple sets of batteries connected in parallel are used to increase battery autonomy, the extension must be fitted with a sectioning device to permit work to be performed on one set of batteries wile the others remain in service. For external battery assembly, a customized Battery Circuit Breaker (the features of which depend on the sizes of the UPS) including a Battery Circuit Controller Board (the same for all sizes) can be provided. This box is designed to be either wall mounted or assembled on a frame, and is connected between the UPS and the battery. Refer to section 6.9 for more information. A common battery circuit breaker is available for systems incorporating two parallel UPS with a common battery. It comprises two switches, which may be used to section one UPS while the other remains active. Refer to section 8.3 for more information.
6.2
Safety
Special care should be taken while working on batteries associated with Hi-pulse UPS system equipment. When all the cells are connected together, the battery terminal voltage will exceed 400 V DC and is potentially lethal. A primary safety consideration is to physically isolate the battery installation from all but appropriately qualified maintenance personnel, which is best achieved by locating in a key locatable cabinet or a purpose designed, dedicated battery room.
66
Hipulse UPS Manual Single 1+N UPS System The following general battery safety precautions and WARINGS should be observed all the time.
CAUTION
A battery can present risk of electric shock or burn from high short circuit currents. When connected in a string the voltage could be 460 V d.c. this voltage is potentially lethal always observe high voltage precautions. Only qualified personnel should install or service batteries. Eye protection should be worked to prevent from accidental electrical arcs. Only use tools with insulated handles. Wear rubber gloves and a rubber apron when handling batteries. If a battery leaks electrolyte, or is otherwise physically damaged, it should be placed in a container resistant to sulphuric acid and disposed of in accordance with legal regulations. If electrolyte comes into contact with the skin the affected area should be washed with plenty of clean water immediately. Batteries must be always disposed of according to local environmental laws.
67
6.4
Note: Full safety instructions concerning the use and maintenance of UPS batteries are provided in the appropriate battery manufacturers manuals. The battery safety information contained in this section relates to the key considerations, which must be taken into account during the installation design process and might affect the design outcome depending on localized conditions.
6.5
6.5.1
Battery performance depends on the ambient battery temperature. Capacity and autonomy are quoted for a new battery operating at 20o C. Battery capacity is increased by 1% for every 1o C increase in temperature up to 25o C. If a battery is used at a temperature above 25o C, its life is reduced; consequently, its capacity and UPS autonomy time will reduce more rapidly over a period of time. Operating below 20o C will reduce the battery capacity by approximately 1% -1.5% per 1o C. For example if a battery discharge test is attempted during the middle of winter when the ambient temperature is 5o C the battery capacity will be only 77.5% of its design value and will not satisfy its specified autonomy time. Ambient temperature, ventilation, spacing, float voltage and ripple current all affect the battery temperature. Uneven temperature distribution through the battery string will cause the voltage distribution to be uneven which can also lead to problems- it is therefore very important to maintain an even temperature across the whole battery chain. Valve regulated cells are very sensitive to temperature and should be operated at a temperature between 15o C and 25o C. To help sustain this operating temperature range the battery is normally float charged at 2.25V/cell. When batteries are cabinet mounted adjacent to the UPS module, it is the battery which dictates the designed maximum ambient temperature, not the UPS. i.e. in the case of valve regulated cells the ambient regulated cells the ambient room temperature should be kept between 15oC and 25oC, and not between 0oC and 40oC (which is the specified main equipment operating temperature range) Temperature excursions are permissible for short periods of time provided the ambient temperature does not exceed 25oC.
The nominal DC bus voltage, and therefore battery float voltage, is set according to the modules rated input/output voltage and usually set top 432Vdc (380Vac) 446 Vdc (440Vac) or 459Vdc (415Vac). Given that the desired cell float voltage is 2.25V, this means that a different number of cells are required in each case. (See Table 6-1).
6.5.2
Battery population
Parameter
Number of cells used (Standard) End-of-discharge voltage Float voltage
380V
192 320 432
400V
198 330 446
415V
204 340 459
68
6.6
Battery protection
The battery is connected to the UPS through a circuit breaker which is manually closed and electronically tripped via the UPS control circuitry. If the cells are cabinet mounted this circuit breaker is fitted within the cabinet, however, if they are rack mounted (or located remote from the main UPS cabinet) then the battery circuit breaker must be mounted as near as possible to the batteries themselves, and the power and control cables connected to the UPS using the most direct route possible. The UPS electronic circuitry will trip the circuit breaker if any of the following conditions occur:1. If the d.c. busbar drops below 330Vd.c. (this would normally occur during a mains failure when the battery autonomy time has been exceeded. 2. If there is a rectifier problem and the d.c. bus rises above (2.45 V/cell exceeded on the battery). 3. If the emergency stop is operated. To achieve the required autonomy time, it may be necessary to parallel the battery strings. In which case, the battery circuit breaker should be placed downstream of all parallel battery strings.
Note: All equipment servicing procedures should be carried out by trained personnel only.
6.7
6.7.1
The Battery cabinet is designed to house a range of standard manufactured batteries for use within Hipulse UPS system module. This cabinet can also be used in conjunction with other cabinets, to provide the necessary accommodation required by the large cells associated with system having a long autonomy time. Where two (or more) cabinets are used they are positioned alongside each other and secured and bonded together. If the cabinet(s) is/are located immediately adjacent to the main UPS section, the two units are bolted together through the holes already drilled in the cabinet side struts.
Circuit breaker
A circuit breaker is fitted together with the circuit breaker controller board, which interfaces the circuit breaker to the UPS modules control system. The circuit breaker is manually closed once the module establishes that the DC busbar is above the low battery trip voltage. Once closed, the circuit breaker can be opened manually at any time and will be tripped automatically by the UPS module following certain fault occurrences or a detected low/high DC busbar voltage.
69
Hipulse UPS Manual Single 1+N UPS System This circuit breaker has the following features: Cabinet isolated for safety Short-circuit protection Circuit breaker automatic opening when the inverter is locked out due to battery under voltage, thus avoiding damaging discharges to the battery. Circuit breaker remote breaking action using the emergency stop button, if installed Protection against operating errors (closing the circuit breaker with the rectifier disables) Protection against battery cabinet and UPS connection errors (polarity reversal +/-)
6.7.3
Battery Racks
These are custom build fabricated racks for keeping the batteries. These are similar in construction to Battery cabinets except for the external covers. There are no covers and batteries are allowed to cool naturally.
6.7.4
1. In general, a minimum space of 10 mm must be left on all vertical sides of the battery block to permit free air movement around cells. 2. Clearance should be allowed between the top of the cells and the underside of the shelf above (this is necessary for monitoring and servicing cells. 3. When installing the batteries, please always work from the bottom shelf upwards to prevent raining the center of gravity.
1. All the cabinets/ racks must be earthed and bonded together. 2. When the cabinet/ rack is installed on a raised floor, the battery power cables and circuit breaker control cables can be routed to the UPS cabinet via the floor of the cabinets. If the cabinets are located adjacent to each other located on a solid floor these cables can be passed between the cabinets via the lifting apertures located in the lower sides of the cabinets 3. In general, it is recommended that the inter-connecting cables are fitted to the batteries within their particular level before fitting the inter-level connecting cables, followed finally by the cables to the circuit breakers. 4. An insulating shroud should be fitted cables, followed finally by the cables to the circuitbreaker. 5. When connecting the cables between the battery extremities to the circuit breaker always connect the circuit breaker end of the cable first .
6.7.5
70
The battery cabinet also indicates the power and auxiliary connection cables (3 meters in length) between the cabinet and the UPS. Refer to section 3.3.1 to identify connections.
71
6.8
Battery Installation
Whatever the type of mounting system selected, following conditions should be noted: Whatever battery mounting system is used, the batteries should be laid out in such a manner as to make simultaneous contact with two exposed live parts having a potential greater than 150V impossible. Where this is not possible, insulated terminal shields must be installed and insulated cable must be used for connection.
Service platform:
The service platform (or duckboard) must be slip-proof, insulated from the floor and be at least one meter wide.
Connections:
All connections must be as short as possible.
6.9
A battery circuit breaker box houses the battery circuit breaker and its control board and is used to connect the battery to the UPS in installations where the batteries are not contained in the standard battery cabinet. There are two boxes available which are similar in their design and content. These are listed below: 100 Amp C/B Part No. 746410270210120206014 160 Amp C/B Part No. 746410280310120206015 Usually the 'box' is fitted as close as possible to the batteries. Battery circuit breaker boxes must be earthed. The connections are similar to the connections made to the battery cabinet. Figure 6-2 shows details of the power and control cable connections between the circuit breaker box or battery cabinet and the UPS itself. Two methods of connecting the three pole battery circuit breaker are illustrated. Method A shows the spare pole being used to divide the battery bank in half, thereby reducing the battery total voltage to half when the circuit breaker is open during servicing etc. Method B connects the spare pole in series with the positive connection, thereby providing two sets of contacts in the positive line as an added safety precaution. When installing the battery cabinet remove the battery fuse In the UPS before making the battery circuit breaker power connections.
+
96 Cells
+
96 Cells
+
96 Cells
+
96 Cells
72
3 2 1
X3 X4 X5 X6 X7 X8 X9
X2 X10 1 2 3 4 5 X1
UPS CABINET
X3
1 2 3 4 5 6 7 8 9 10 11 12
F13
3 2 1
X3 X4 X5 X6 X7 X8 X9
X2 X10 1 2 3 4 5 X1
UPS CABINET
X3
1 2 3 4 5 6 7 8 9 10 11 12
F13
74
The LED item number refers to details shown in the figure 7.1 below.
6
DISPLAY
%
ENTER
10
11
12
13
14
15
16
17
18
19
2.
ON
3.
OFF
75
4.
ON
If this green led is OFF, it signifies that the inverter is not producing its correct output voltage. Check the following 1. If [OVERTEMPERATURE] or [OVERLOAD] alarm messages are active then (after allowing the UPS to cool / checking that the load current on the Bypass line is not excessive) use the procedure to carry out the reset (see Chapter 5 Operating Instructions). 2. Check that the conditions for led(2) are satisfied. 3. Check that the Inverter led(8)- yellow is OFF, otherwise follow Inverter switch ON procedure. 4. Check that no conditions exist which will prevent switching the INV ON (e.g. PC command). 5. Verify that condition leading to an emergency stop has not happened, in which case a Reset must be carried out. If this green led is OFF, then it signifies that the load has been transferred to the Static bypass supply. If this is an automatic change over it will be accompanied by a fault warning on the display panel. Take the appropriate actions for the display indication (see Display alarm message table 7-2). This led is mutually exclusive to led(5). If this amber led is ON, the load has been transferred to the Bypass mains supply. Verify the cause by following the alarm indications at the LCD display panel. If the above checks prove unsatisfactory then seek qualified assistance. This red led will flash ON and OFF and indicates that the UPS has detected fault, it will be accompanied by a message on the display panel, take the required actions for the display panel message (see Display alarm message table 7-2). This will be accompanied by an audible warning. Pressing the Alarm silence switch (14) stops the audible alarm, but leaves the warning message displayed until the appropriate condition is rectified. If this yellow led is ON it signifies that the battery voltage is low and that the end of battery discharge is near. This will be accompanied by audible warning. This is a bargraph indicating the battery charge state and would normally have four or five of the leds ON. When the unit runs on battery, this bargraph changes to give an indication of the time remaining on the battery. This is a bargraph indicating the % of the total load that is being applied to the system. If this yellow led is ON it signifies that the applied load has exceeded the maximum. It will be accompanied by all five load bargraph leds being ON (item 18), the Alarm warning indication flashing RED (item 13) and an OVERLOAD messages on the visual display. This will be accompanied by an audible warning. Reduce the load immediately.
5. 6. 13.
ON OFF OFF
76
7.2
The message displayed on Hipulse can be categorized into types:(a) ALARM messages - these are messages which needed urgent attention and warn of a UPS shutdown or imminent shutdown the load would normally transfer to the bypass supply if it is available. All alarm messages are accompanied by an audible warning. (b) WARNING messages - these are the messages generated to warn or confirm to the operator of action taken (i.e. if the rectifier a.c. input supply power switch was opened the Warning message would read RECTIF. SWITCH OPEN). The following table lists the various messages displayed on the operator panel together with a description of their interpretation.
Sr. No. 1.
Interpretation This alarm indicates that the UPS was shut down by means of the local or remote (if fitted) Emergency Power Off push button (EPO) which is normally due to operation action investigate the cause for pressing the button. If this button was not pressed then check the continuity of the circuit to the Remote switch, Customer connections, Auxiliary terminal block X4; pin 5 and 6; normally closed. The INV. OFF alarm is active whenever the inverter is not producing its correct output voltage, either because it has been switched OFF or due to an internal fault, it will normally be accompanied by one or more of the other inverter fault conditions.
2.
INV. OFF
3.
Most of the inverter fault messages are self explanatory, however the WAVEFORM ERR informs the operator that the output voltage peak has flattened caused by an internal inverter problem and therefore the output will be out of limits.
4.
INV. OVERTEMPER.
Over temperature is sensed by a normally-closed thermostat (90C operating) fitted to each inverter heat sink. If an over temperature condition arises, the audible alarm will accompany this message; the inverter stops and load transfers to Bypass after 3 minutes.
5.
OVERTEMP. SHUTDOWN
This message informs the operator that the inverter has been switched OFF and that the load has been transferred ot Bypass due to an Inverter over temperature.
77
6.
OVERLOAD PRESENT
7.
OVERLOAD SHUTDOWN
The inverter overload has an inverse load/ time characteristic i.e. it will accept 125% overload for 10 minutes and 150% overload for 60 seconds. If this characteristic is exceeded the load transfers to the bypass supply, the inverter stops and the overload alarm annunciates. The [OVERLOAD PRESENT] alarm will annunciate as soon as the load exceeds 100% of the UPS rating, and the load will transfer to Bypass some time later, depending on the degree of overload present. This message informs the operator that the load has been transferred to bypass due to an inverter overload.
8.
This is a status alarm. The output switch must be selected CLOSED at all times except when operating on the Maintenance bypass supply.
9.
This is a status alarm. The bypass input switch must be closed all the times.
10.
This is a status indication only. Note that if the UPS is operating with the Battery circuit breaker open, and the mains power fails, then the UPS output will also fail together with load power, since the inverter has no battery backup.
11.
This problem should be rectified as soon as possible. If the mains power fails then the UPS output will also fail together with load power, since there is no battery backup.
12.
The system has carried out a test of the battery. If this alarm is not accompanied by a [BATTERY C.B. OPEN] or [BATTERY: FUSE FAIL] message then a full check of the Battery bank is required.
78
13.
DC BUS: UNDERVOLTAGE
When the inverter is operating on the battery this message is displayed on the condition when battery voltage has fallen below a preset value. If the input a.c. power cannot be restored, you should shut down your loads. Battery discharge has continued beyond a preset value. The inverter will shut down, the system will attempt a transfer to bypass. If Bypass is not available, any load connected to the UPS will be without power.
14.
BATTERY: E.O.D.
15.
RECT. OFF
The RECT. OFF alarm is active whenever the battery charger (rectifier) is not producing its correct output voltage. This can be caused by an operator selection to OFF, an Input supply failure, an open rectifier a.c. input power switch or an internal fault which may be accompanied by one of the fault conditions. Most of the rectifier fault messages are self explanatory however, the DC BUS: FAST OVERVOLTAGE message informs the operator the d.c. busbar voltage is too high.
16.
RECT. SWITCH OPEN RECT. CURRENT LIMIT BATTERY: FUSE FAIL DC BUS: FAST OVERVOL
17.
INPUT FAILURE: input a.c. supply failed or out of specified acceptable range. Do not switch OFF the inverter while this indication is active or the load will lose its power.
18.
One or more of the static switch SCRs has developed a fault. The bypass would not support the load in the event of a UPS failure, immediate action is required. Seek qualified assistance.
19.
This message informs the operator that the input power lines have been cross-connected and the phases sequence is incorrect.
20.
This is a status warning that the load is being powered through the maintenance bypass line and is unprotected from mains supply aberrations.
79
21.
INV. UNSYNCHRONIZED
This warns that the inverter is not synchronized with the bypass supply, which is normally due to a problem with the bypass supply being outside an acceptable frequency window. Do not switch OFF the inverter when this alarm is active or the load will experience a 200 millisecond power break. This is a status warning that the battery is discharging. It normally accompanies a [BYP: ABSENT] or [RECT: OFF] message.
22.
BATTERY ON LOAD
23.
The micro monitors the battery percentage capacity while on charge and the battery time remaining while on discharge. It calculates the time remaining as function of the discharge current against the programmed ampere-hour capacity of the battery. It will update the time remaining as the load is change. This message informs the operator that the system is carrying out a periodic battery test.
24.
25.
This message is only applicable to systems which include the boost charge option, boost time charge elapsed set value, battery should be controlled by service personnel.
26.
LOAD ON BYPASS
This is a status warning that the load is being powered through the static bypass line and is unprotected from mains supply aberrations. This action is either selected by the operator or a fault condition, check for other fault messages.
27.
This is a status message confirming that the rectifier has been selected off by the operator from either the front panel display or an external PC or by a switch on UPS microprocessor PCB.
28.
This is a status message confirming that the bypass has been inhibited by the operator from either an external PC or by a switch on UPS microprocessor PCB.
80
29.
This is a status message confirming that the inverter has been selected off by the operator from either the front panel display or an external PC or by a switch on UPS micro controller PCB.
30.
This message informs the operator that the load has been transferred to the bypass more than eight times in one minute. After eight transfers the load will remain on bypass. This message could be initiated by a load causing the UPS to overload, it requires investigation. This message informs the operator that the battery is not longer isolated from ground and there is danger of electrocution.
31.
32.
BACKFEED FAULT
This message informs the operator that the failure of the bypass static devices has resulted in voltage being fed back to the bypass supply input.
In addition to the above message there are a number of software alarms (i.e. BAD EEPROM, BACK-UP, BATTERY LOW etc.) that will require attention from a qualified service engineer.
81
1 + N System
8.1 General
The system can comprise of up to 6 UPS modules of the same power rating and connected in parallel without the need for a centralized mains static bypass. Instead the bypass static switches of each UPS share the load when the system transfers to the main bypass supply. From a power viewpoint, each module is internally identical to the single module configuration. A 1+N parallel system requires inverter and bypass supplies, inter-module control signals to manage current sharing, synchronizing and bypass switching between the module. In the figure 8-1, this is shown as the inter-module control bus, which is facilitated through the use of multi-way ribbon cables connected between the units of the system. When three or more modules are to be connected in parallel it is recommended that inductance should be inserted in the static bypass line. This can be installed internal to the UPS as an option. For each module it is necessary to program the display panel with the correct rating and to identify that the internal static switch is being used.
82
Bypass Isolator Q2
RECTIFIER
Input Isolator Q1
DC Bus
INVERTER
STATIC SWITCH 3
UPS MODULE 1
Battery C.B. 1 Inter Module Control Bus
X4
Ext. Sw . Out
BATTERY 1
Bypass Isolator Q2
RECTIFIER
Input Isolator Q1
DC Bus
INVERTER
STATIC SWITCH 3
UPS MODULE 2
Battery C.B. 12 Inter Module Control Bus
X4
Ext. Sw . Out
BATTERY 2
UPS MODULE 6
Ext. Sw . Out
DISTRIBUTION PANEL
83
8.2
For a two-module UPS system, an optional maintenance bypass cabinet is available. This is rated to meet the capacity requirements of the system. For each module, it is necessary to program their display panel with the correct rating and identify that the internal Static Switch is being used. It is important that isolation in the bypass cabinet be identified at the module. For this purpose auxiliary contacts must be fed back to the connector X4 in relevant UPS module (Refer figure 8-2)
7
Ext. Bypass Maintenance Bypass Line
X4
Bypass Isolator Q2
RECTIFIER
Input Isolator Q1
DC Bus
INVERTER
STATIC SWITCH
UPS MODULE 1
Battery C.B. 1 Inter Module Control Bus
X4
Ext. Sw . Out
BATTERY 1
7
Maintenance Bypass Isolator Q3 Ext. Bypass Maintenance Bypass Line
X4
Output to Load
Bypass Isolator Q2
RECTIFIER
Input Isolator Q1
DC Bus
INVERTER
STATIC SWITCH 3
UPS MODULE 2
Battery C.B. 12 Inter Module Control Bus
X4
Ext. Sw . Out
BATTERY 2
84
8.3
8.3.1
Installation procedure
Preliminary Checks
Be sure that a parallel kit is present and fitted in each of the modules, and that the modules are of the same rating and with the same software and hardware release (see section 4.1.2 Info window)
WARNING
Fitting of the parallel kits and board setting required to convert from Single Module to 1+N must be made by qualified and trained personnel. This operation involves also setting of system with separate batteries or common batteries.
8.3.2
Protective Devices
8.3.3
Power Cables
UPS Module 1
To Parallel PCB
UPS Module 2
To Parallel PCB
UPS Module 3
To Parallel PCB
UPS Module 4
To Parallel PCB
UPS Module 5
To Parallel PCB
UPS Module 6
To Parallel PCB
85
8.3.5
Battery Control
Note: The Common Battery configuration is possible with 6 pulse rectifier only, not within 12 pulse rectifiers.
UPS MODULE 1
Maintenance Bypass Line
Bypass Isolator Q2
RECTIFIER
Input Isolator Q1
DC Bus
INVERTER
STATIC SWITCH 3
X3
X4
Ext. Sw . Out
2
BATTERY
C.B. C.B.1
Cable 1 5 w ires
X1 X2
X1
Cable 5 w ires
X3
1
Ext. Sw . Out
T O
3
Input Isolator Q1
X3
3 STATIC SWITCH
X4
L O A D
RECTIFIER
DC Bus
INVERTER
Output Isolator Q4
Bypass Isolator Q2
UPS MODULE 2
D I S T R I B U TI O N PANEL
86
8.3.6
A common battery box is available to permit a common battery to be shared between two modules (see fig 8-4). The box, which is used to connect the DC busbar of the two modules to a common battery, should be fitted as close as possible to the UPS modules, with cabling preferably of the same length.
WARNING
There is no protection to prevent closing a modules battery isolation switch when its rectifier is shut down. Such operation will trip the battery circuit breaker and rupture the battery fuse in that module.
Before operating the modules battery isolation switch, the operator must first check that the battery voltage and rectifier voltage different by less than 10% - this may be easily achieved by reading the Battery Voltage on the Display Panels of both the modules. Control cable connections are required as shown in Fig 8-5, this includes an extension of the inter-module cables described in Section 8.3.3. In addition there are other auxiliary connections that are identified in this figure and which are referred to in table 8-1.
Note: The Common Battery configuration is possible with 6-Pulse Rectifiers only, not with 12 Pulse Rectifiers. Cable A: 5 Wires + Screen Common Battery Box Connector X3 (Female) Pin 1 not connected Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 Cable B: 2 Wires + Screen Connector X3 (Female) Pin 12 Screen Pin 11 Pin 10 Cables C: 5 Wires + Screen Connector X3 on UPS1 cabinet Pin 1 not connected Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 Connector X1 on Common Battery Box Pin 1 screen Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 2nd Temperature Sensor in Battery (screws) Pin 1 not connected Pin 2 Pin 3
Battery Cabinet Connector X1 on 4520046T PCB (screws) Screen Pin 5 Pin 4 Pin 3 Pin 2 Pin 1
87
Cables D: 5 Wires + Screen Connector X3 on UPS 2 cabinet Pin 1 not connected Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 Flat Cables ( 34 way + screen ) X2 4590060U on UPS1 X1 4590060U on UPS2 X1 4590060U on UPS1 X1 4590060U on Common Battery Box X2 4590060U on Common Battery Box X2 4590060U on UPS2 Connector X2 on Common Battery Box Pin 1 screen Pin 2 Pin 3 Pin 4 Pin 5 Pin 6
Table 8-1 : Control cables of Common Battery Box (see fig 8-5)
88
Battery
Cabinet
or
Battery
Break er
Box
3 2 1
a b
3 2 1
X10 X2
1 2 X1
Cable A
- 3 M1
5 5
F1 F2
C1
3 3 4 4
+ X6 +
1 3 2 1
X7 X2 X1
a b c d e
1 2 3 4 5 6 7 8 9 10 11 12
a b c d e
1 2 3 4 5 6 7 8 9 10 11 12
+
Aux. Terminal Cable C X3 1 2 3 4 5 6 7 8 9 10 11 12 Cable D UPS 1 Cabinet
a b c d e
a b c d e
DC Bus bar
DC Bus bar
Paral. Conn.
X2 X1
X3
Paral. Conn.
X3
X2
X1
Fig 8-5: Common Battery Box - connection details (refer to Table 8-1)
89
Cable B
The external emergency stop facility is identical to that described for the single modules installation that an individual Emergency Stop button is provided for each module.
8.3.7
Emergency Stop
X4
X4
Module 1
Module 2
90
Starting and stopping the 1+N system is the same as a single module, however the modules response depends on whether it is configured on the menu of the Operator Control Panel.
8.4
Operating Instruction
8.4.1
If differential circuit breakers are used on UPS unit inputs, use a common device only on the systems bypass mains. At the instant of electrical connection, the current may not be split instantaneously and this may cause the residual current circuit-breakers to trip separately.
These operations must be performed one at a time, progressing to the next step only after having completed the previous step on both UPS modules.
8.4.1.1 System Start-up StartThis procedure should be followed when tuning on the UPS from a fully powered down condition i.e. where the load is not being initially supplied at all. It is assumed that the installation is complete, the system has been commissioned by authorized personnel and the external power isolators are closed. 1.Open the UPS door(s) to gain access to the main power switches. WARNING
The following action will apply power to the load equipment, ensure it is safe to do.
2. Close the Bypass power switch Q2 The Module Mimic LEDs will indicate Bypass supply healthy (1-steady green) and the Load on bypass (6 flashing amber). The display screen will show the following:
Initializing Window:
LIEBERT UPS
After first connecting power to the UPS and closing the Q2 isolator, this message will appear on the LCD screen. It persists for about five seconds while the control firmware is loaded. It is followed by a screen showing various messages with the time and date on the bottom line.
RECTIF. SWITCH OPEN BATTERY C.B. OPEN OUTPUT SWITCH OPEN hh.mm.ss dd.mm.yy
Note: If input power is present but the display remains blank, then the Micro controller is not working, pleas contact your dealer for advice.
91
Hipulse UPS Manual Single 1+N UPS System 3. Close the Rectifier input power switch Q1 and UPS output power switch Q4.
BATTERY C.B. OPEN
hh.mm.ss
dd.mm.yy
After approximately 20 seconds the Module Mimic leds will change so that the Load on inverter will light (5-steady green) and the Load on bypass (6) will extinguish. The display window will show: 4. Before closing the battery circuit breaker check the d.c. bus-bar voltage. From the above window press the ENTER key. The Main menu will display:
<
BATTERY VOLTAGE CURRENT CHARGE 446 [V] 001 [A] 000 [%]
If the voltage indicated is satisfactory (432V d.c. for 380V a.c. system, 446V d.c. for 400V a.c. system, and 459V d.c. for a 415V a.c. system ) press the escape key repeatedly until the display returns to the original window. 5. Manually close the battery circuit breaker. The Module Mimic inidicator (3) Battery unavailable should extinguish. Several leds on the Battery state of charge bargraph (17) will illuminate showing battery state of charge. When the battery circuit breaker has been closed and the inverter has stabilized the screen will change to the default window. Default window: The message shown below, will be seen on the default screen whenever the UPS is operating normally. The top lines display the UPS operational status and indicates alarm conditions when they occur; and the bottom line shows the time and day. The UPS is operating normally with its inverter supplying the load. Follow the foregoing procedure for the other UPS. For a system configured in the 1+N system, the N UPS modules will simultaneously change from load on bypass to load on inverter provided that a sufficient number of modules are running, and on-line, to satisfy the power load requirements.
NORMAL OPERATION
hh.mm.ss
dd.mm.yy
92
The internal maintenance bypass must not be used when the UPS system is comprised of more than two UPS modules in parallel.
Follow the procedure for the single UPS by referring to Chapter 5 Operating Instructions: Paragraph 5.4. For a system configured in the 1+N system, the changeover from load on inverter to load on bypass will occur only when the operation described in point 3 has been completed on both UPS modules.
8.4.1.4 Switching OFF and isolating one UPS while the other remains in service.
1. In sequence, open the UPS isolators Q4 (output), Q1 (rectifier input), Q2 (bypass input). 2. Open the circuit-breaker inside the battery cabinet. To completely isolate the UPS, open the a.c. power supply circuit-breaker (both circuit breakers if separate supplies are provided for the rectifier and the bypass supply) and thee output circuit breaker on the power distribution switchboard. If individual UPS output isolation circuit-breaker (and its auxiliary contacts) are not installed on the power distribution switchboard, remember that voltage supplied by the others UPS which remains in service still will be present on the output terminals of the shutdown UPS.
WARNING
If individual UPS output isolation circuit-breaker are not installed on the power distribution switchboard, remember that voltage supplied by the others UPS remains in service will still be present on the output terminals of the shutdown UPS. Warning : Wait 5 minutes for the internal d.c. busbar capacitors to discharge.
93
8.4.1.5 Switching ON a UPS that was previously switched OFF and isolated from the system. previously
1. Close the circuit-breakers relative to the shutdown UPS that were previously opened on the power distribution switchboard. 2. Close the switches Q1 (rectifier input) and Q2 (bypass input) of the UPS. 3. Select the MEASUREMENT function from the display on the main menu, then press ENTER and select BATTTERY. Press ENTER and check that the voltage level has reached the rated value (432V or 446 or 459 in accordance with no. of battery blocks). 4. Close the battery circuit-breaker. 5. Close the UPS switch Q4 (output), wait about 20 seconds and check the message NORMAL OPERATION appearing on the display operator panel.
94
8.4.2
WARNING
If differential circuit breakers are used on UPS inputs, be sure to use a common device for all input lines. If the configuration has inputs from separate mains, a common device will also be required for all the System's bypass mains. At the instant of electrical connection, the current may not be split instantaneously and this may cause the residual current circuit-breakers to trip separately.
Refer to the general diagram shown in figure 8-4. The 1+N parallel system with common batteries (only for two units) also uses the "Common Battery Box" optional kit (box type depends on UPS dimensions). This box uses two isolators to connect the battery to the UPS modules, and thus individually isolate the two modules from the system. The box is also designed to supply the two UPS modules with a battery current measurement (charge or discharge). The Common Battery includes protection fuses of the DC power supply (F1 & 2): type GL = size 10 x 38 - 1A / 500V.
95
The isolators Q1 and Q2, located in the "Common Battery Box", must be operated following the procedures described below. Incorrect operation of these isolators might cause the circuit-breaker located in the battery cabinet to open or blow the battery fuse located in the UPS.
In the system start-up and maintenance bypass configuration procedures, the operations must be performed one at a time, going to the next one only after having completed the previous one on both UPS modules.
8.4.2.3 System start-up startFollow the procedure for the single UPS by referring to paragraph 8.4 - System startup. After completing the operations described in point 4, close isolators Q1 and Q2 located inside "Common Battery Box". For a system configured in the "1+N system", the two UPS modules will simultaneously change the state from "Load on Bypass" to "Load on Inverter" (turning on and off the relative LEDs on the mimic panel), after the voltage level has reached the rated value (432V or 446V or 459V in accordance with the number of Battery blocks).
The internal maintenance bypass must not be used when the UPS system is comprised of more than two UPS modules in parallel.
Follow the procedure for the single UPS by referring to Chapter 5 - Operating Instructions: paragraph 5.4. After completing the operation, open isolators Q1 and Q2 located inside the Common box for common battery. For a system configured in the "1+N system", the changeover from "Load on Inverter" to "Load on Bypass" will take place only when the operation described in point 3 has been completed on UPS modules.
8.4.2.5 Procedure to switch the system from the Maintenance Bypass mode to the Normal operating condition the
Follow the procedure for the single UPS by referring to Chapter 5 - Operating Instructions: paragraph 5.2. After completing the operations described in point 4, and before going to point 5, close the isolators Q1 and Q2 located inside the "Common Battery Box".
96
8.4.2.6 Switching OFF and isolating isolation one UPS while the other remains in service
1. In sequence, open the UPS switches Q4 (output), Q1 (rectifier input), Q2 (bypass input). 2. Open the isolator located inside the Common Battery Box, relative to the UPS that is being excluded.
WARNING
If individual UPS output isolation circuit-breaker are not installed on the power distribution switchboard, remember that voltage supplied by the other UPS which remains in service will still be present on the output terminals of the shutdown UPS. WARNING: Wait 5 minutes for the internal d.c. busbar capacitors to discharge.
8.4.2.7 Switching ON a UPS that was previously switched OFF and isolated from the system. switched
1. Close the circuit-breakers relative to the shutdown UPS that were previously opened on the power distribution switchboard. 2. Close the switches Q1 (rectifier input) and Q2 (bypass input). 3. Select the MEASUREMENT function from the display on the main menu, then press ENTER and select BATTERY. Press ENTER and check that the voltage level has reached the rated value (432V or 446V or 459V in accordance with the number of battery blocks). If this occurs, proceed the next step. If this does not occur and a voltage close to 0V is measured, this means that the active UPS is operating under the battery charge current limiting condition. In this case, open Q1 (rectifier input) then open the circuit breaker located inside the battery cabinet, close Q1 again and check the voltage level on the display. The battery circuit breaker must be closed again after completing the operation described in point 4. 4. Close the isolator located inside the Common Battery Box, for to the UPS which has been switched ON. 5. Close UPS switch Q4 (output), wait about 20 seconds and check that the message NORMAL OPERATION appears on the display operator panel.
97
8.5
The alarms are the same as for the single module, as given in the previous paragraph, with the additional alarms: CODE 44 46 DISPLAY ALARM MESSAGE INV: PARALLEL ERROR NR: INVERTERS NOT OK. INTERPRETATION The parallel board has detected a wrong sharing of the load and has blocked its inverter. Seek qualified assistance. The number of active inverters is below the preset capacity value.
98
Specification
This specification describe requirements for an Uninterruptible Power System (UPS).
9.1
9.2
UPS Environmental
The UPS shall be able to operate under the following environmental conditions without damage or degradation in electrical operating characteristics:
Environmental Characteristics Characteristics Rated Power Operating Temperature Maximal temp. for 8hr day Mean temp. for 24 hr Relative Humidity Altitude of operation Storage/ transport temperature
Units kVA C C C m C
160 200 0 to 40 40 C (de-rate power by 1, 5% per C between +40 C & +50 C 90% at 20 C 1000m asl (de-rate power by 1% per 100m between 1000m & 2000m) -25 to 70 C
80
120
9.3
Mechanical Characteristics Height Width Depth Weight Ventilation Airflow Cable entry
99
9.4
I/P Ratings Ratings Rated power Rated Mains Voltage j Supply Input voltage tolerance k Frequency Input frequency tol. Rated input power l Rated input current l Maximum input power m Maximum input current m Duration of progressive power walk-in n
80 kVA 6 pulse 80
80 kVA 12 pulse
120 kVA 120 kVA 160 Kva 160 kVA 6 pulse 12 pulse 6 pulse 12 pulse 120 160 380 400 415 V Three phase without neutral
% Hz % kVA A kVA A sec 87 125 109 157 83 120 104 152 129 186 162 233 124 181 157 228
15 50 or 60 5 173 259 215 310 168 254 210 305 216 310 269 388 211 305 264 383
2 to 10
j = 380V or 415V set changing taps on auxiliary supply transformer k = With mains at 15% and suggested battery elements the UPS maintains the output rated voltage at rated load bu
cannot guarantee float charge to battery; the battery does not discharge. l = EN 50091-3 (1.4.39): UPS, rated load, input rated voltage 400V, no current to battery m = EN 50091-3 (1.4.40): UPS, rated load or overload, input rated voltage 400V, battery on boost charge with maximum allowed current. n = set with jumper on Rectifier control board.
100
9.5
Rated Power Power Voltage range for Inverter operation Recommended number of Leadacid cells j-k Recommended float charge voltage 2.25 V/cell j Recommended boost charge voltage 2.40 V/cell j Recommended end of discharge voltage 1.67 V/cell j Recommended test voltage j Maximum voltage of manual charge 2.47 V/cell j Battery boost charge cycle l Maximum boost charge duration l Boost-float threshold current l Ripple voltage superimposed m
kVA Vdc
190 (380 Vac) 198 (400 Vac) 204 (415 Vac) 432 (380 Vac) 446 (400 Vac) 459 (415 Vac) 460 (380 Vac) 475 (400 Vac) 490 (415 Vac) 320 (380 Vac) 330 (400 Vac) 340 (415 Vac) 365 (380 Vac) 376 (400 Vac) Vac) 388 (415 Vac) 480 (380 Vac) 495 (400 Vac) 500 (415 Vac) Characteristics to DIN 41772I-U, boost to floating charge switching, with current measuring criterion plus control of charging time. 0-999 0-99
Note: j = (According to rated voltage) k = factory set for rated 400V, different cells number and voltage per cell may be set by software and / or trimmers on Rectifier control board. l = Set by software m = Battery disconnected, RMS percentage value referred to DC voltage.
101
9.6
kVA Vac
80
320 - 400 - 415 Three phase with neutral Hz 50 to 60 Rated Power at cos = 0.8 Rated Power at cos = 1 Three-phase transient overload l Single phase transient overload Maximum non linear load allowed m Voltage stability, steady state test
n
80 64 60 1.10
160 128
% 5 Hz /sec 0.1
Note: j = Factory set 400V 380V or 415V voltages with software setting k = Factory set at 50Hz ; 60Hz with software setting. l = EN50091-3 (1.4.50). m = EN50091-3 (1.4.58) crest factor 3. n = EN50091-3 (4.3.4). o = EN50091-3 (4.3.7) also for 0-100% load transient, restore time 20ms to 1%. p = Factory set at 0.1Hz/ sec; upto 2 Hz/sec with software setting.
102
9.7
Rated Power Power Rated mains voltage j Supply Rated Current: 380 Vac 400 Vac 415 Vac Bypass voltage tolerance k Delay time to recognize bypass voltage returned to window Inverter output voltage window Frequency l Input frequency tolerance m Maximum frequency slew rate Current rating of neutral cable
kVA Vac
80
Three phase with neutral A 121 115 111 % sec % Hz % 2 Hz /sec 0.1 1.5 x In 182 173 167 10 10 10 50 or 60 243 231 222 304 289 278
To avoid series fuses, the bypass line should be protected using an external device should be sized to discriminate with the load protection. ms I / In 10 14.3 20 12.6 50 11.0 100 10.0 200 9.0 500 8.0 1000 7.1 2000 6.6 5000 5.7
Transient overload
Note: j = Factory set 400V 380V or 415V set changing taps on auxiliary supply transformer and with software setting. k = Other values 0-15% with software setting. l = Factory set at 50Hz ; 60Hz with software setting. m = Other values 1-9% with software setting.
103
9.8
SYSTEM I/P Ratings Rated power No load losses Full load losses (100%) Units kVA KW KW 1.75 5.57 80 kVA 6 pulse 80 2.20 6.72 80 kVA 12 pulse
PERFORMANCE 160 Kva 160 kVA 6 pulse 12 pulse 160 2.75 9.63 3.30 11.89 200 kVA 200 kVA 6 pulse 12 pulse pulse 200 3.5 11.12 4.15 13.91
120 kVA 120 kVA 6 pulse 12 pulse 120 2.50 7.45 2.95 8.58
9.9
Units kVA KW
80 kVA 12 pulse
2.3
104
105
Hipulse UPS Manual Single 1+N UPS System 10.1 Remote Alarm Monitor The Remote Alarm Monitor (RAM) Board can be used in conjunction with the AS400 Alarms Interface Board to display the UPS alarm and status information at a remote station to 100 meters from the UPS. The RAM, which can be mounted either horizontally or vertically contains a mains-driven power supply for alarm LED annunciation and displays the following warnings: Panel
Inverter ON Utility failure Battery low Bypass ON Maintenance Alarm
Colour
Green Red Red Red Red Red
Normal state
ON OFF OFF OFF OFF OFF
Interpretation
Normal operating condition indicating that the load is being supplied by the inverter. This is not an 'alarm indicator. When lit, it indicates that the input bypass is out of tolerance or missing. When lit, it indicates that the battery voltage is below minimum or that the battery circuit breaker is open. When lit, it indicates that the load is being fed from the bypass supply, possibly due to a UPS failure. When lit, it indicates that the UPS has been selected to operate on the maintenance bypass and load is unprotected. This is a common alarm and is lit when any of the red leds described above are lit
Table A An audible warning accompanies any of the above alarm conditions. This is, however, subject to a short time delay when activated in conjunction with the 'Utility Failure' and 'Bypass ON' alarms, to prevent the warning being activated by transient conditions. Pressing the 'reset' push-button cancels the audible warning but the alarm indications remain until the conditions is rectified.
Power Supply The RAM contains a single-phase 220-240 V AC mains-driven power supply. Power is applied through a standard three-pin mains connector located in the RAM back panel (plug provided) -use 3-core 0.5 mm cable (minimum). The supply is rated at approximately 4 Watts and fused at 1 A. It is advised that the power supply is taken from the UPS output, otherwise in the event of a mains failure the RAM may be inoperative. Alarm connections A 9 pin D-type connector with solder points is provided with the RAM. This connector fits into the 9 pin socket on the back of the RAM and should be cabled to the Interface Board # 10020112003 fitted to the UPS, using 9 core, 0.22 mm. (minimum) shielded cable as shown. The maximum recommended distance is 100 meters.
Note: Operation of the RAM indicators, is achieved by feeding a voltage across the module Alarm Board relay contacts. No other connections should be made across the relay contacts used.
106
# 100201120003
15
X4
Bypass Failure
RL K1
14 13 12 11 10 9
RL K2
RL K3
8 7 6
RL K4
5 4 3
RL K5
2 1
220/240V AC 50 Hz
5 9
4 8
3 7
2 6
UPS Monitor
INVERTER ON UTILITY FAILURE BATTERY LOW
Liebert
ALARM
ON
BYPASS MAINTENACE
107