100% found this document useful (1 vote)
2K views1 page

Anchor Bolt Design

The document summarizes calculations to check the safety of M24 anchor bolts used to connect a column. It provides the maximum uplift and horizontal forces on the column, details of the 4 anchor bolts used including their length of embedment. It then checks that the bolts are safe based on tension, shear, and pull out capacity according to industry standards, and finds that all criteria are satisfied.

Uploaded by

nishant131
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
2K views1 page

Anchor Bolt Design

The document summarizes calculations to check the safety of M24 anchor bolts used to connect a column. It provides the maximum uplift and horizontal forces on the column, details of the 4 anchor bolts used including their length of embedment. It then checks that the bolts are safe based on tension, shear, and pull out capacity according to industry standards, and finds that all criteria are satisfied.

Uploaded by

nishant131
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

JB0803- ISOLUX

BOLT CALCULATION FOR M24 ANCHOR BOLT


MAXIMUM UPLIFT FORCE ( COLUMN C'-2') = DESIGN DIAMETER = Nos. OF BOLTS PROVIDED = MAXIMUM HORIZONTAL FORCE (COLUMN C'-3') = UPLIFT PER BOLT = LENGTH OF EMBEDMENT PROVIDED = CHECK FOR EMBEDED LENGTH As per AISC guidelines L= Apsf/3.14 mm Tu 4tf'c ( sq. mm) 4.6 27 4 16.4 1.15 950 KN ( DUE TO WIND ALONG -Z AXIS ) mm Nos KN ( DUE TO SEISMIC ALONG X AXIS ) KN ( DUE TO WIND ALONG -Z AXIS ) mm

Apsf (required surface area) = where Tu = force in N = 1150 t = resistant factor = 0.75 f'c = compressive strength of concrete = Apsf = L= Minimum length of embedment = 12 d =

32 67.76 4.65 324.00

N/sq.mm mm mm mm HENCE SAFE

PROVIDED LENGTH > 4.65 mm or 324 mm CHECK FOR TENSION As per ACI-318 Nsa = n Ase,N futa where Nsa = nominal stregth in tension in Newton n = nos. of bolts in a group. = 4 Ase,N = effective x-sectional area of a single bolt =

d2 4 = 572.265 ( sq. mm) futa = not greater than 1.9 fya or 861.845 N/sq.mm(125000 psi) whichever is less fya = yield strenth of anchor steel in N/sq.mm = 250 Nsa = 1087.3035 KN > 4.6 KN HENCE SAFE CHECK FOR SHEAR As per ACI-318 Vsa = n 0.6 Ase,V futa where Vsa = nominal stregth in shear in pounds n = nos. of bolts in a group. = 4 Ase,V = effective x-sectional area of a single bolt =

d2 4 = 572.265 ( sq. mm) futa = not greater than 1.9 fya or 861.845 N/sq.mm(125000 psi) whichever is less fya = yield strenth of anchor steel in N/sq.mm = 250 Vsa = 652.3821 KN > 16.4 KN HENCE SAFE CHECK FOR PULL OUT As per ACI-318 Npn = c,p Np where Npn = nominal pull out stregth in pounds c,p = modification factor = 1.4 and Np = 8 Abrg f'c where Abrg = net bearing area of bolt head(dia 2d) = = 32

f'c = compressive strength of concrete = Np = now Npn =

d2 4 2289.06 N/sq.mm

( sq. mm)

585999.4 Newton 820.3991 KN > 1.15 KN HENCE SAFE