TFX Ultra Transit Time Flow Meter
Transit Time Ultrasonic Product Family
DESCRIPTION
The TFX Ultra transit time meter measures clean liquids as well as those with small amounts of suspended solids or aeration such as surface water or sewage.
FEATURES
Bi-directional flow measurement system. Totalizer options include forward, reverse and net total Modbus RTU and BACnet MSTP over RS485; Ethernet connections including BACnet/IP, EtherNet/IP, and Modbus TCP/IP protocols Large, easy-to-read digital display Rugged, aluminum enclosure ensures a long service life in harsh environments Certified for hazardous area installation in North America and Europe
APPLICATIONS
TFX Ultra ultrasonic flow and energy meters clamp onto the outside of pipes and do not contact the internal liquid. The technology has inherent advantages over alternate devices including: low-cost installation, no pressure head loss, no moving parts to maintain or replace, no fluid compatibility issue, and a large, bi-directional measuring range that ensures reliable readings even at very low and high flow rates. The TFX Ultra is available in a variety of configurations that permit the user to select a meter with features suitable to meet particular application requirements. The TFX Ultra is available in two versions: a flow meter, and an energy flow meter used in conjunction with dual clamp-on RTDs for temperature measurement. The energy flow meter measures energy usage in Btu, mBtu, mmBtu, tons, kJ, kW, MW and is ideal for retrofit, hydronic process, and HVAC applications. Temperature measurements, when used in conjunction with flow measurement, can yield energy usage readings in the form of heat flow. To find the net heat loss or gain, energy usage is calculated by multiplying the flow rate of the heat transfer fluid by the change of heat content in that fluid after it has done some kind of work. An ultrasonic meter equipped with heat flow capabilities is designed to measure the rate and quantity of heat delivered or removed from devices such as heat exchangers. The instrument measures the volumetric flow rate of the heat exchanger liquid, the temperature at the inlet pipe and the temperature at the outlet pipe.
OPERATION
Transit time flow meters measure the time difference between the travel time of an ultrasound wave going with the fluid flow and then against the fluid flow. This time difference is used to calculate the velocity of the fluid traveling in a closed-pipe system. The transducers used in transit time measurements operate alternately as transmitters and receivers. Transit time measurements are bi-directional and are most effective for fluids that have low concentrations of suspended solids.
Rate of Heat Delivery = Q (Tin Tout) C Where Q = Volumetric flow rate Tin = Temperature at the inlet Tout = Temperature at the outlet C = Heat capacity = Density of fluid
By applying a scaling factor this heat flow measurement can be expressed in the units of your choosing including Btu, Watts, Joules, Kilowatts, and others.
TTM-DS-00085-EN-01 (July 2013)
Product Data Sheet
TFX Ultra Transit Time Flow Meter
SPECIFICATIONS
SYSTEM
Liquid Types Velocity Range Flow Accuracy
Most clean liquids or liquids containing small amounts of suspended solids or gas bubbles Bi-directional to greater than 40 FPS (12 MPS) DTTN/DTTH/DTTL: DTTS/DTTC: DTTS/DTTC: Option A: Option B: Option C: Option D: 1% of reading or 0.01 FPS (0.003 MPS), whichever is greater 1 in. (25 mm) and larger 1% of reading or 0.04 FPS (0.012 MPS), whichever is greater 3/4 in. (19 mm) and smaller 1% of Full Scale (See the Dimensional Specifications page) 32122 F (050 C); 32212 F (0100 C); 40350 F (40177 C); 485 F (2030 C); 0.001 FPS (0.0003 MPS) 0.03 F (0.012 C) 0.05 F (0.025 C) 0.1 F (0.06 C) 0.03 F (0.012 C) Absolute: 0.22 F (0.12 C) Absolute: 0.45 F (0.25 C) Absolute: 1.1 F (0.6 C) Absolute: 0.22 F (0.12 C) Difference: 0.09 F (0.05 C) Difference: 0.18 F (0.1 C) Difference: 0.45 F (0.25 C) Difference: 0.09 F (0.05 C)
Temperature Accuracy
(Energy Meters Only)
Flow:
Sensitivity
Temperature: Option A: Option B: Option C: Option D: 0.5% of reading
Repeatability
Installation Compliance
General Safety (all models): UL 61010-1, CSA C22.2 No. 61010-1; (power options A and D only) EN 61010-1 Hazardous Location (power supply options A and D only): Class I Div. 2 Groups C, D, T4; Class II, Division 2, Groups F, G, T4; Class III Division 2 for US/CAN; ATEX II 2 G Ex nA II T4: UL 1604, CSA 22.2 No. 213, EN 60079-0 and EN 60079-15 Compliant with directives 2004/108/EC, 2006/95/EC and 94/9/EC on meter systems with integral flow transducers, transducers constructed with twinaxial cable (all transducers with cables 100 ft (30 m) and shorter) or remote transducers with conduit AC: DC: Protection: Two line LCD, LED backlit: Icons: Flow rate indication: Flow accumulator (totalizer): Type 4 (IP-65) Construction: Size: Conduit Holes: 40185 F (4085 C) Via optional keypad or PC running ULTRALINK software Flow Meter: Energy Meter: USB 2.0: RS485: 10/100 Base-T: 4-20 mA: Energy Meter Model Only: Flow Meter Model Only: Two Alarm Outputs:
(Note: not all configuration parameters are available from the keypadfor example flow and temperature calibration and advanced filter settings)
TRANSMITTER
Power Requirements
95264 V AC 4763 Hz @ 17 VA max. or 2028 V AC 4763 Hz @ 0.35 A max. 1028 V DC @ 5 W max. Auto re-settable fuse, reverse polarity and transient suppression Top row 0.7 inch (18 mm) height, 7-segment Bottom row 0.35 inch (9 mm) height, 14-segment RUN, PROGRAM, RELAY1, RELAY2 8-digit positive, 7-digit negative max. Auto decimal, lead zero blanking 8-digit positive, 7-digit negative max. Reset via keypad press, ULTRALINK, network command or momentary contact closure powder-coated aluminum, polycarbonate, stainless steel, polyurethane, nickel-plated steel mounting brackets 6.0 in. W x 4.4 in. H x 2.2 in. D (152 mm W x 112 mm H x 56 mm D) (2) 1/2 in. NPT female; (1) 3/4 in. NPT female; Optional Cable Gland Kit
Display
Enclosure
Temperature Configuration Engineering Units
Feet, gallons, cubic feet, million gallons, barrels (liquid and oil), acre-feet, pounds, meters, cubic meters, liters, million liters, kilograms Btu, mBtu, mmBtu, tons, kJ, kW, MW, and the ow Meter list from above For connection of a PC running ULTRALINK configuration utility Modbus RTU command set; optional BACnet MSTP 9600 baud standard, other baud rates are available (consult factory) RJ45, communication via Modbus TCP/IP, EtherNet/IP, or BACnet/IP 12-bit, internal power, can span negative to positive flow/energy rates Total Pulse Option: Opto isolated open collector transistor 01000 Hz: open-collector, 12-bit, can span negative to positive rates; square-wave or turbine meter simulation outputs Open-collector, configure as rate alarm, signal strength alarm or totalizer pulse
Inputs/Outputs
Page 2
July 2013
Product Data Sheet
TRANSDUCERS DTTN/DTTC/DTTL: NEMA 6* (IP-67), CPVC, Ultem, Nylon cord grip, PVC cable jacket; 40250 F (40121 C) DTTN/DTTL: NEMA 6P* (IP-68) option, CPVC, Ultem, Nylon cord grip Polyethylene cable jacket; 40250 F (40121 C)
Construction
DTTH: NEMA 6* (IP-67), PTFE, Vespel, Nickel-plated brass cord grip PFA cable jacket; 40350 F (40176 C) DTTS: NEMA 6* (IP-67), PVC, Ultem, Nylon cord grip, PVC cable jacket; 40185 F (4085 C)
*NEMA 6 units: to a depth of 3 ft (1 m) for 30 days max. NEMA 6P units: to a depth of 100 ft (30 m) seawater equivalent density indefinitely.
Frequency Cables Cable Length RTDs
(Energy Meters Only)
DTTS/DTTC: DTTN/DTTH: DTTL:
2 MHz 1 MHz 500 KHz
RG59 Coaxial, 75 ohm or Twinaxial, 78 ohm (optional armored conduit) 990 ft (300 meter) max. in. 10 ft (3 m) increments; Submersible Conduit limited to 100 ft (30 m) Platinum 385, 1000 ohm, 3-wire; PVC jacket cable DTTN (-N option) /DTTS/DTTH/DTTC: DTTN Transducer and IS Barrier (-F option): General and Hazardous Location (see Installation Compliance above) Class I Div. 1, Groups C&D T5 Intrinsically Safe Ex ia; CSA C22.2 No. 142 & 157; UL 913 & 916
Installation
SOFTWARE UTILITIES
ULTRALINK EnergyLink
Used to configure, calibrate and troubleshoot flow and energy meters. Connection via USB A/B cable; software is compatible with Windows 2000, Windows XP, Windows Vista and Windows 7 Used to monitor a network of flow and energy meters. Connection via RS485. Operates within Microsoft Excel 2003, Microsoft Excel 2007, Microsoft Excel 2010. (32-bit O.S. only)
ULTRALINK SOFTWARE UTILITY
In addition to, or as a replacement for, the keypad entry programming, the flow meter can be used with the ULTRALINK software utility. The software is used to configure, calibrate and communicate with TFX Ultra flow meters. Additionally, it has numerous troubleshooting tools to make diagnosing and correcting installation problems easier. A PC can be hard-wired to the TFX Ultra through a standard USB connection found on most current computers.
U
UltraLINK Device Addr 127 Edit View Communications Window Help Errors
File
Con guration
U
Strategy
Calibration
Print
Print Preview
About
Stop Go Step Stop
View
Device Addr 127
Time:
60 Min
Scale:
2000
Historical Data
Flow: Totalizer Net: Pos: Neg: Sig. Strength: Margin: Delta T: Last Update: 135 Gal/Min 237 Gal 237 Gal 0 Gal 15.6% 100% 2.50 ns 12:17:20
2000 1600
1200
800
Signal Strength too Low!
400
Reset Totalizers
Flow Rate
-400
-800
-1200
-1600
-2000
-1.00:00
-50:00
-40:00
-30:00 Time (mm:ss)
-20:00
-10:00
-0:00
Data Display For Help, press F1
Diagnostics 13:26:33 COMM:
Exit OK
July 2013
Page 3
TFX Ultra Transit Time Flow Meter
METER WITH INTEGRAL FLOW TRANSDUCER
For pipe/tubing sizes of 2 in. (50 mm) and smaller, Ultra is available with a clamp-on transducer mounted and wired directly to the flow meter display/electronics enclosure. This design provides a convenient installation in areas where the user requires local indication. PVC constructed transducers are rated to 185 F (85 C) and CPVC are rated to 250 F (121 C).
Bottom View
Common Features:
Rate-Total Backlit Display 420 mA Output 01000 Hz Rate Pulse and Dual Alarm Outputs (Flow Meter Model Only) USB Programming Port RS485 Modbus Network Connection
Integral Flow Transducer
Front View
Supply
Temperature Transducers (Energy Meter Only)
Remote Totalizer Reset
Return
PART NUMBER CONSTRUCTION
DTFX a
Model
Pipe Size Measurement Range
Transducer Material/ Temperature
d
Power
e
Keypad
f
Advanced Communications
Energy Temperature Range
j
Language
Approvals Options
B) Flow Meter E) Energy Meter
P) PVC
40185 F ( 4085 C) C) CPVC 40250 F ( 40121 C)
B) BACnet MSTP C) BACnet MSTP; 10/100 Base-T E) 10/100 Base-T
(Ethernet/IP, Bacnet/IP, Modbus TCP/IP) (Ethernet/IP, Bacnet/IP, Modbus TCP/IP)
H) BACnet MSTP; 76800 Baud N) None P) Total Pulse Output
(Energy Meter Model Only)
F) General Safety, Hazardous Locations, and CE N) General Safety, (Power Supply C Only)
A) 1/2 in. ANSI Pipe (DN 15) B) 3/4 in. ANSI Pipe (DN 20) C) 1 in. ANSI Pipe (DN 25) D) 1-1/4 in. ANSI Pipe (DN 32) E) 1-1/2 in. ANSI Pipe (DN 40) F) 2 in. ANSI Pipe (DN 50) G) 1/2 in. Copper Tube H) 3/4 in. Copper Tube I) 1 in. Copper Tube J) 1-1/4 in. Copper Tube K) 1-1/2 in. Copper Tube L) 2 in. Copper Tube M) 1/2 in. OD Standard Tube N) 3/4 in. OD Standard Tube P) 1 in. OD Standard Tube Q) 1-1/4 in. OD Standard Tube K) 1-1/2 in. OD Standard Tube S) 2 in. OD Standard Tube
A) A/C (95264 V AC) C) A/C (2028 V AC) D) D/C (1028 V DC) K) Keypad N) No Keypad
N) None A) 32122 F (050 C) B) 32212 F (0100 C) C) 40350 F ( 40177 C) D) 485 F ( 2030 C)
(Leave Blank for English F) French S) Spanish N) None C) 4-Pin (male); Brad Harrison Micro Change
(Available for DC Power Only
A) Cable Gland Kit
Page 4
July 2013
Product Data Sheet
METER WITH REMOTE FLOW TRANSDUCER
The TFX Ultra is available with remote mounted transducers that permit separation of up to 990 feet (300 m). This design is used on larger pipes or when pipes are located in areas that are not convenient for viewing, or on piping systems with severe vibration. PVC constructed transducers are rated to 185 F (85 C), CPVC are rated to 250 F (121 C) and PTFE are rated to 350 F (176 C).
Common Features: Rate-Total Backlit Display 420 mA Output 01000 Hz Rate Pulse and Dual Alarm Outputs (Flow Meter Model Only) USB Programming Port RS485 Modbus Network Connection Remote Totalizer Reset
Remote Flow Transducers
Supply
Temperature Transducers (Energy Meters Only)
Return
PART NUMBER CONSTRUCTION
DTFX
a
Transmitter Type
ZN
Remote Transmitter
c
Power Supply
d
Keypad
e
Advanced Communications
Energy Temperature Range
g
Approvals
h
Options
i
Language
B) Flow Meter E) Energy Meter
A) A/C (95264 V AC) C) A/C (2028 V AC) D) D/C (1028 V DC) K) Keypad N) No Keypad
B) BACnet MSTP C) BACnet MSTP; 10/100 Base-T E) 10/100 Base-T
(Ethernet/IP, Bacnet/IP, Modbus TCP/IP) (Ethernet/IP, Bacnet/IP, Modbus TCP/IP)
Use with DTTN/DTTH/DTTL Large Pipe Transducers (pipes larger than 2 in.) or DTTS/DTTC Small Pipe Transducers (pipes 1/22 in.)
H) BACnet MSTP; 76800 Baud N) None P) Total Pulse Output
(Energy Meter Model Only)
F) General Safety, Hazardous Locations, and CE N) General Safety, (Power Supply C Only)
(Leave Blank for English F) French S) Spanish
N) None A) 32122 F (050 C) B) 32212 F (0100 C) C) 40350 F ( 40177 C) D) 485 F ( 2030 C)
N) None C) 4-Pin (male); Brad Harrison Micro Change
(Available for DC Power Only
A) Cable Gland Kit
FLOW TRANSDUCER PIPES LARGER THAN 2 in. (DN 50 mm)
DTT
a
Type
N) Standard 250 F (121 C) CPVC, Ultem H) High Temp 350 F (176 C) PTFE, Vespel L) Large 250 F (121 C) CPVC, Ultem*
bbb
Cable Length
020) 20 ft (6 m) 050) 50 ft (15 m) 100) 100 ft (30 m)1
c
Conduit Type
ddd
Conduit Length
e
Installation
N) None A) Flexible Armored
000) None 020) 20 ft (6 m) 050) 50 ft (15 m) 100) 100 ft (30 m)1
N) General Purpose F) ClassI, Div. 1, Groups C & D (DTTN Only)
FLOW TRANSDUCERS - SMALL PIPES 1/22 in. (12 MM50 mm)
DTT
a
Type
S) Standard 185 F (85 C) PVC, Ultem C) High Temp 250 F (121 C) CPVC, Ultem
b
Nominal Pipe Size
D) 1/2 in. F) 3/4 in. G) 1 in. H) 1-1/4 in J)1-1/2 in L) 2 in.
c
Pipe Type
ddd
Cable Length
e
Conduit Type
f
Conduit Length
P) ANSI Pipe 020) 20 ft (6 m) C) Copper Pipe 050) 50 ft (15 m) T) Rigid Tubing 100) 100 ft (30 m)1
N) None A) Flexible Armored
000) None 020) 20 ft (6 m) 050) 50 ft (15 m) 100) 100 ft (30 m)1
Maximum length: 990 ft (300 m) in 10 ft (3 m) increments
* Recommended for pipe sizes larger than 24 in. (610 mm)
July 2013
Page 5
TFX Ultra Transit Time Flow Meter
NETWORK OPTIONS
RS485 NETWORK All TFX Ultra meters come equipped with RS485 drivers and use a Modbus RTU command set (data can be returned in single-precision, doubleprecision, integer or floating point values) or an optional BACnet MSTP protocol. Up to 126 Ultra products can be run on a single daisy-chain network and be individually queried for flow rate, positive flow accumulator, negative flow accumulator, supply temperature, return temperature and signal strength. Flow accumulators can be cleared at discrete addresses or globally. The RS485 network is also compatible with the EnergyLink, direct to Excel, application. (EnergyLink compatible with Modbus RTU only.)
Address 1
Address 2
Address 126
RS485 converter
3-wire + shield 4000 feet (1220 m) max. without repeaters
10/100 BASE-T NETWORK If equipped with the optional Ethernet communications module, the TFX Ultra can be plugged into a LAN and queried for flow rate, positive flow accumulator, negative flow accumulator, supply temperature, return temperature, and signal strength. The module contains Modbus TCP/IP, EtherNet/IP, and BACnet/IP network compatibility.
Device 1
Device 2
Device 3
Device N
LAN
RTD KITS FOR INTEGRAL AND REMOTE ENERGY MEASUREMENT METERS
D010-3000-120 D010-3000-121 D010-3000-122 D010-3000-123 D010-3000-124 D010-3000-125 RTD Kit1, clamp on, 130 C, 1000 Ohm, 20 ft RTD Kit1, clamp on, 130 C, 1000 Ohm, 50 ft RTD Kit1, clamp on, 130 C, 1000 Ohm, 100 ft RTD Kit1, clamp on, 200 C, 1000 Ohm, 25 ft RTD Kit1, clamp on, 200 C, 1000 Ohm, 50 ft RTD Kit1, clamp on, 200 C, 1000 Ohm, 100 ft
1 2
D010-3000-200 D010-3000-201 D010-3000-202
Insertion RTD Kit2, 3", 1/4" O.D., 260 C, 1000 Ohm, 20 ft Insertion RTD Kit2, 3", 1/4" O.D., 260 C, 1000 Ohm, 50 ft Insertion RTD Kit2, 3", 1/4" O.D., 260 C, 1000 Ohm, 100 ft
2 RTDs, heat sink compound and installation tape A set of 2 RTD
RTD Kits include: Insertion RTD Kits include:
Page 6
July 2013
Product Data Sheet
DIMENSIONS
Remote System
B A
Wall mount
A
Pipe mount
A
C C DIA Mounting holes (2)
ELECTRONICS ENCLOSURE
Enclosure A B C D 6.00 in. (132.4 mm) 4.20 in. (106.7 mm) 4.32 in. (110 mm) 2.12 in. (53.8 mm) Wall Mount 6.50 in. (165.1 mm) 2.30 in. (58.4 mm) 0.19 in. (4.8 mm) Pipe Mount 1.38 in. (35.1 mm) 2.90 in. (73.7 mm) 1.20 in. (30.5 mm)
(Min Clearance)
B
TOP VIEW OF PIPE
DTTN/DTTH/DTTL
Pipes Larger Than 2" (50 mm) DTTN A B C 2.95 in. (74.9 mm) 2.75 in. (69.8 mm) 3.00 in. (76.2 mm) DTTH 2.95 in. (74.9 mm) 2.75 in. (69.8 mm) 3.00 in. (76.2 mm) DTTL 3.40 in. (86.4 mm) 2.94 in. (74.7 mm) 3.20 in. (81.3 mm)
July 2013
Page 7
TFX Ultra Transit Time Flow Meter
DIMENSIONS
Integral System
B C
D A
DTTS/DTTC TRANSDUCERS
Pipe Size 1/2 in. Pipe Material
ANSI/DN Copper Tubing ANSI/DN
A
2.46 in. (62.5 mm) 2.46 in. (62.5 mm) 2.46 in. (62.5 mm) 2.46 in. (62.5 mm) 2.46 in. (62.5 mm) 2.46 in. (62.5 mm) 2.46 in. (62.5 mm) 2.46 in. (62.5 mm) 2.46 in. (62.5 mm) 2.80 in. (71.0 mm) 2.46 in. (62.5 mm) 2.46 in. (62.5 mm) 3.02 in. (76.7 mm) 2.71 in. (68.8 mm) 2.71 in. (68.8 mm) 3.70 in. (94.0 mm) 3.70 in. (94.0 mm) 3.21 in. (81.5 mm)
B
2.36 in. (59.9 mm) 2.36 in. (59.9 mm) 2.28 in. (57.9 mm) 2.57 in. (65.3 mm) 2.50 in. (63.5 mm) 2.50 in. (63.5 mm) 2.92 in. (74.2 mm) 2.87 in. (72.9 mm) 2.75 in. (69.9 mm) 3.18 in. (80.8 mm) 3.00 in. (76.2 mm) 3.00 in. (76.2 mm) 3.40 in. (86.9 mm) 2.86 in. (72.6 mm) 3.31 in. (84.1 mm) 3.42 in. (86.9 mm)* 3.38 in. (85.9 mm)* 3.85 in. (98.0 mm)
C
2.66 in. (67.6 mm) 3.33 in. (84.6 mm) 3.72 in. (94.5 mm) 2.66 in. (67.6 mm) 3.56 in. (90.4 mm) 3.56 in. (90.4 mm) 2.86 in. (72.6 mm) 3.80 in. (96.5 mm) 3.80 in. (96.5 mm) 3.14 in. (79.8 mm) 4.04 in. (102.6 mm) 4.04 in. (102.6 mm) 3.33 in. (84.6 mm) 4.28 in. (108.7 mm) 4.28 in. (108.7 mm) 5.50 in. (139.7 mm) 5.50 in. (139.7 mm) 4.75 in. (120.7 mm)
D
0.84 in. (21.3 mm) 0.63 in. (15.9 mm) 0.50 in. (12.7 mm) 1.05 in. (26.7 mm) 0.88 in. (22.2 mm) 0.75 in. (19.0 mm) 1.32 in. (33.4 mm) 1.13 in. (28.6 mm) 1.00 in. (25.4 mm) 1.66 in. (42.2 mm) 1.38 in. (34.9 mm) 1.25 in. (31.8 mm) 1.90 in. (48.3 mm) 1.63 in. (41.3 mm) 1.50 in. (38.1 mm) 2.38 in. (60.3 mm)* 2.13 in. (54.0 mm)* 2.00 in. (50.8 mm)
E
2.12 in. (53.8 mm) 2.12 in. (53.8 mm) 2.12 in. (53.8 mm) 2.12 in. (53.8 mm) 2.12 in. (53.8 mm) 2.12 in. (53.8 mm) 2.12 in. (53.8 mm) 2.12 in. (53.8 mm) 2.12 in. (53.8 mm) 2.12 in. (53.8 mm) 2.12 in. (53.8 mm) 2.12 in. (53.8 mm) 2.12 in. (53.8 mm) 2.12 in. (53.8 mm) 2.12 in. (53.8 mm) 2.12 in. (53.8 mm) 2.12 in. (53.8 mm) 2.12 in. (53.8 mm)
Measuring Range
2.038 gpm (8144 lpm) 1.827 gpm (7102 lpm) 1.518 gpm (668 lpm) 2.7566 gpm (10250 lpm) 2.554 gpm (10204 lpm) 2.545 gpm (10170 lpm) 3.5108 gpm (13409 lpm) 3.595 gpm (13320 lpm) 3.585 gpm (13320 lpm) 5.0186 gpm (19704 lpm) 4.5152 gpm (17575 lpm) 4.0136 gpm (15514 lpm) 6.0250 gpm (23946 lpm) 5.0215 gpm (19814 lpm) 5.0 200 gpm (19757 lpm) 8.0420 gpm (301590 lpm) 8.0375 gpm (301419 lpm) 8.0365 gpm (301381 lpm)
3/4 in.
Copper Tubing ANSI/DN
1 in.
Copper Tubing ANSI/DN
1-1/4 in.
Copper Tubing ANSI/DN
1-1/2 in.
Copper Tubing ANSI/DN
2 in.
Copper Tubing
* Varies due to U-bolt configuration
DTTS/DTTC
Pipes and Tubing 1/2" to 2" (12 mm to 50 mm)
DTTS/DTTC U-BOLT CONNECTIONS
ANSI/DN and Copper 2" (50 mm) Models
D A C
D A C
TFX Ultra and ULTRALINK are registered trademarks of Badger Meter, Inc. Other trademarks appearing in this document are the property of their respective entities. Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specifications without notice, except to the extent an outstanding contractual obligation exists. 2013 Badger Meter, Inc. All rights reserved.
www.badgermeter.com
The Americas | Badger Meter | 4545 West Brown Deer Rd | PO Box 245036 | Milwaukee, WI 53224-9536 | 800-876-3837 | 414-355-0400 Mxico | Badger Meter de las Americas, S.A. de C.V. | Pedro Luis Ogazn N32 | Esq. Angelina N24 | Colonia Guadalupe Inn | CP 01050 | Mxico, DF | Mxico | +52-55-5662-0882 Europe, Middle East and Africa | Badger Meter Europa GmbH | Nurtinger Str 76 | 72639 Neuffen | Germany | +49-7025-9208-0 Czech Republic | Badger Meter Czech Republic s.r.o. | Makova 2082/26 | 621 00 Brno, Czech Republic | +420-5-41420411 Slovakia | Badger Meter Slovakia s.r.o. | Racianska 109/B | 831 02 Bratislava, Slovakia | +421-2-44 63 83 01 Asia Pacific | Badger Meter | 80 Marine Parade Rd | 21-04 Parkway Parade | Singapore 449269 | +65-63464836 China | Badger Meter | 7-1202 | 99 Hangzhong Road | Minhang District | Shanghai | China 201101 | +86-21-5763 5412