DSC Troubleshooting Guide
DSC Troubleshooting Guide
NOTE: This Guide is intended for use by qualified SERVICE PERSONS ONLY. It shall be used in conjunction with the Installation Manual(s) for PowerSeries ALARM CONTROLLER(s)
LED Keypads, LCD Fixed Message Keypads Press [][2] to view a trouble condition. The trouble light will flash. Refer to the chart below to determine the trouble condition(s) present.
NOTE: Some trouble conditions provide additional information (indicated with an in the chart below). Press the number corresponding to the trouble condition to view the additional information. LCD5500 LCD Programmable-Message Keypad Press [][2] to view a trouble condition . The trouble light will flash and the LCD will display the first trouble condition present. Use the arrow keys to scroll through all trouble conditions present.
NOTE: When additional information is available for a specific trouble condition a [] will appear on the display. Press the [] key to view the additional information .
TROUBLE SUMMARY Light [1] Light [2] Light [3] Light [4] Light [5] Light [6] Light [7] Light [8] Service Required Press [1] for more information AC Trouble Telephone Line Trouble Failure to Communicate Zone Fault Press [5] for more information Zone Tamper Press [6] for more information Wireless Device Low Battery Press [7] for more information Loss of Time or Date
Trouble
Trouble [1] Service Required
[1] Low Battery
Cause
Main panel battery less than 11.5VDC NOTE: This trouble condition will not clear until the battery voltage is 12.5VDC min., under load.
Troubleshooting
NOTE: If battery is new allow 1 Hr. for battery to charge. Verify voltage measured across AC terminals is 16-18 VAC. Replace transformer if required. Disconnect battery wire leads Verify battery charging voltage measured across battery leads = 13.75VDC min. Connect battery, remove AC power Verify measured voltage across battery terminals is 12.5VDC min. Disconnect Bell-/Bell+ wire leads, measure resistance of wire leads. Open circuit indicates break in wiring or defective siren/bell Jumper Bell+, Bell- with 1K resistor (Brown, Black, Red) Verify trouble clears If Output#1 is unused: Ensure that terminals O1, AUX are jumpered with 1K resistor (Brown, Black, Red) If Output #1 is used: Disconnect wire leads from O1, AUX terminals, measure the resistance of the wire leads Open circuit indicates a break in the wiring Verify voltage measured across AC input terminals is 16-18VAC. Disconnect all connections to PC5204 AUX terminal. Verify AUX voltage is13.75VDC min.
Printer connected to PC5400 offline [4] General System Tamper Tamper input on module(s) open circuit Wireless Receiver - excessive noise detected [5] Module Supervision Panel does not communicate with module(s) on KEYBUS Keypad assigned to incorrect slot.
Verify printer operation (out of paper, paper jam etc.) Short tamper terminal to COM terminal on unused modules connected to KEYBUS (PC5100, PC5108, PC5200, PC5204, PC5208, PC5320, PC5400, PC5401, PC5700). Check for external 433MHZ signal sources To disable RF Jam: enable Option [7] in program section [804] subsection [90]. Modules are immediately enrolled and supervised when detected on the KEYBUS. If a module has been removed, or if the slot assignment of a keypad has been changed, module supervision must be reset. View the event buffer (via DLS or LCD5500 keypad) to identify the specific module(s) in trouble To reset module supervision: Enter Program Section [902]. Press [#] (wait 1 minute for panel to scan KEYBUS). Enter Program Section [903] to identify modules connected to KEYBUS. Check for external 433MHZ signal sources To disable RF Jam: enable Option [7] in program section [804] subsection [90]. See [1] Low Battery above
Wireless Receiver - excessive noise detected (Power864 only) PC5204 battery less than 11.5VDC NOTE: This trouble condition will not clear until the battery voltage is 12.5VDC min., under load.
No AC at PC5204 AC inputs
Trouble
Trouble [2] AC Failure
Cause
No AC at panel AC input terminals
Troubleshooting
Verify voltage measured across AC terminals is 16-18VAC. Replace transformer if required.
An open circuit is present on PGM2 being used as a 2-wire smoke detector input
Trouble
Trouble [5] Zone Fault (Cont.)
Cause
One or more wireless devices have not checked in within the programmed time
Troubleshooting
If the trouble occurs immediately, a conflict with a hard wired zone exists: The zone being used is already assigned to a PC5108 zone expander The zone being used is assigned as a keypad zone Perform a Module Placement Test Program Section [904] and verify the wireless device is in a good location. If bad test results occur, test the wireless device in another location If the wireless device now tests good, the original mounting location is bad If the wireless device continues to give bad test results replace the wireless device Remove the wire leads from Z and COM terminals and measure the resistance of the wire leads. A short circuit indicates a short in the wiring. Connect a 5.6K resistor (Green, Blue, Red) across the Z and COM terminals. Verify the trouble condition clears.
A short circuit is present on one or more zones with double end-of-line resistors enabled
Press [7] to toggle through specific devices with low battery trouble
Replace battery NOTE: The trouble will not clear until the detector is violated
One or more wireless devices has a low battery NOTE: The event will not be logged to the event buffer until the wireless device low battery delay time expires Program Section [370]
IMPORTANT! Ensure you have the following information available before contacting Customer Support - Control Panel Type and Version, (e.g., PC5020 v3.2) - List of modules connected to Control Panel, (e.g., PC5400, PC5204 etc.)
wewe