Bedienungsanleitung Operating Instructions Notice Utilisateurs

This document provides instructions for operating a Strömungswächter flow monitor. It describes: 1. How to install the device and make electrical connections. 2. How to program the device by teaching it the minimum and maximum flow rates using the buttons. This sets the detection range. 3. Additional programming options like setting the switch point and changing the output relay function. 4. Controls, visual indicators and the menu structure for programming.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
96 views19 pages

Bedienungsanleitung Operating Instructions Notice Utilisateurs

This document provides instructions for operating a Strömungswächter flow monitor. It describes: 1. How to install the device and make electrical connections. 2. How to program the device by teaching it the minimum and maximum flow rates using the buttons. This sets the detection range. 3. Additional programming options like setting the switch point and changing the output relay function. 4. Controls, visual indicators and the menu structure for programming.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 19

Bedienungsanleitung Operating instructions Notice utilisateurs

Strmungswchter Flow monitor Contrleur de dbit SI-FKOW


12/03
DEUTSCH FRANAIS ENGLISH

Sachnr. 701640/05

Brief adjustment instructions


Installation Mounting page 24, electrical connection page 26. HI-Teach Apply the operating voltage. After approx. 15 s the unit is ready. Allow the medium to flow through the system at the required maximmum flow rate (HI).
Press the Learn/Set button and keep it pressed. The green LEDs on the right and on the left flash, after 5 s the LED bar (green) fills from left to right (release the button as soon as the first LEDs light). The indication goes off briefly. The unit stores the current flow as maximum flow.
M S LO HI

6-8 s
LO HI

LO

HI

The unit is ready for normal operation.

Further setting options ( page 27) The HI-Teach is sufficient for the majority of waterbased applications. Optional: adjustment to minimum flow (LO-Teach). Setting of the switch point (for changing the reaction time and excess gain). Manual adjustment to maximum flow. Manual adjustment to maximum flow / monitoring and optical indication of excess flow. Manual adjustment to minimum flow / flow standstill. Changing of the function of the output relay.
20

Controls and visual indication


setting buttons

MODE / ENTER LO
0 1 2

FLOW RATE

LEARN / SET HI
function display

Function display (Run mode) current flow within the display range (LED bar green) excess flow (LED 9 flashes)
0 1 2 3 4 5 6 7 8 9

underflow (LED 0 flashes) Indication of the switch point (SP): LED orange: flow SP; LED red: flow < SP Setting buttons Mode / Enter: selection of the menu items and acknowledgement Learn/Set: adjustment to maximum / minimum flow; setting of values (scrolling by holding pressed;incremental by pressing briefly)

SI-FKOW

701640/05

21

Menu structure
Run mode
LO HI

Manual settings Adjustment to maximum flow Adjustment to maximum flow

6-8s

2x >5s

Adjustment to minimum flow

11-15s

1x

Monitoring excess flow

Setting the switch point

2x >5s

1x >5s 1x

...
1x

Change output function: (normally open / normally closed)


4x > 5s 1x

Adjustment to minimum flow

3x >5s

1x

LED = green 22

LED = orange

LED = red 701640/05 SI-FKOW

Contents
Function and features . . . . . . . . . . . . . . . . . . . . Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical connection . . . . . . . . . . . . . . . . . . . . . Programming . . . . . . . . . . . . . . . . . . . . . . . . . . Installation and set-up / Operation / Maintenance Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . Programming diagrams / Technical information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 23 . page 24 . page 26 . page 27 . page 29 . page 29 . page 30

Function and features


The flow monitor detects the flow velocity in liquid and gaseous media switches the output relay according to the programming,
normally open normally closed relay energised when the switch point has been reached relay de-energised when the switch point has been reached

(for programming page 26) and indicates the relative flow value within the adjustable detection range by means of LEDs: - LED 0 = lower limit of the detection range (maximum value / LO) - LED 9 = upper limit of the detection range (minimum value / HI) It is also possible to indicate: - Switching status (LED red: flow below the switch point, LED orange: flow has reached the switch point). - Excess flow: LED 9 flashes if the flow is considerably higher (2 LEDs) than the display range. - Underflow / flow standstill: LED 0 flashes if the flow is lower than the display range.
ENGLISH

23

Installation
The unit is adaptable for various process fittings (adapters to be ordered separately as accessories). In the case of horizontal pipes mount the unit from the side, if possible (fig. 1). When the unit is to be mounted at the bottom of the pipe, it should be free from deposits. When the unit is to be mounted at the top of the pipe, it should be completely filled with the medium to be monitored. In the case of vertical pipes mount the unit in a place where the medium flows upwards (fig. 2).

To avoid malfunction a minimum distance between the flow monitor and bends, valves, changes in cross-section or such like must be observed: Min. 5 x pipe diameter upstream (A), min. 3 x pipe diameter downstream (B).

3
B min. 3xD

min. 5xD

24

2
A

thread M18 x 1.5

1. Lubricate the nut (3) and all threads with grease to ensure the nut can be loosened and tightened several times. Note: No grease must be applied to the sensor tip (A). 2. Screw the suitable adapter (2) onto the process fitting (1). 3. Insert the flow monitor into the adapter. While keeping the unit aligned tighten the nut (3); (max. tightening torque 50 Nm). Insertion depth of the sensor: min. 12 mm in the pipe. When the adapters are used which are available as accessories, the correct depth is ensured. Note: The sensor tip must not touch the pipe wall.
mounting dimension with M12 adapter mounting dimension with G adapter mounting dimension with G adapter

13,5

13,5

25

ENGLISH

27

27

21

35

Electrical connection
The unit must only be connected by an electrician. The national and international regulations for the installation of electrical equipment must be observed. Caution: For the output circuit the same protective measures as for the supply circuit must be taken. The permissible potential difference between supply and output circuit is max. 300 V. Disconnect power before connecting the unit. Wiring:
1 2 3 VDD 4 5 relay circuit safe separation 1 2 3 5 connector view (sensor) 4 n.c. L1 N supply voltage

ifm-sockets are available as accessories: Order no. E11248, E11249, E11250, E11251. When the supply voltage is applied, all LEDs light and go off one after the other.* The unit is then ready for operation.
*During this time the output relay is energised.

26

Programming
I Setting of the detection range ( page 30) Allow the medium to flow through the system at the required maximum flow rate. Press the Learn/Set button for 6-8 s (= adjustment to maximum flow / upper limit of the detection range). This setting is sufficient for the majority of waterbased applications. Optional: adjustment to minimum flow. Allow the medium to flow through the system at the required minimum flow rate or bring flow to a standstill. Press the Learn/Set button for 11-15 s (= adjustment to minimum flow or flow standstill / lower limit of the detection range). I Setting of the switch point ( page 32) Press the Mode/Enter button briefly. Press the Learn/Set button for 5 s, keep the Learn/Set button pressed or press the button several times until the requested switch point is set. Press the Mode/Enter button briefly. I Manual adjustment to maximum flow (HI-Teach) ( page 33) Allow the medium to flow through the system at the required maximmum flow rate. Press the Mode/Enter button twice. Press the Learn/Set button for 5 s, release the button when LED bar fills from left to right. Press the Mode/Enter button briefly, when LED 9 is lit. I Manual adjustment to maximum flow (HI-Teach) / monitoring excess flow ( page 34) Allow the medium to flow through the system at the required maximmum flow rate. Press the Mode/Enter button twice. Press the Learn/Set button for 5 s, release the button when LED bar fills from left to right. When LED 9 (= LED for the maximum display value) is lit: Press the Learn/Set button several times to shift the LED. Press the Mode/Enter button briefly.
27

ENGLISH

I Manual adjustment to minimum flow (LO-Teach) ( page 35) Allow the medium to flow through the system at the required minimum flow rate or bring flow to a standstill. Press the Mode/Enter button three times. Press the Learn/Set button for 5 s, release the button when LED bar fills from right to left. Press the Mode/Enter button briefly, when LED 0 is lit. I Change output function: (normally open / normally closed) ( page 36) Press the Mode/Enter button four times. Press the Learn/Set button for 5 s, keep the Learn/Set button pressed or press the button several times until the requested function is set (OUT = normally open when 3 LEDs on the right and 3 LEDs left are lit green. OUT = normally closed, when the 4 LEDs in the middle are lit in red). Press the Mode/Enter button briefly. I The following applies to all setting procedures: If no button is pressed for 20 s during the setting procedure, the unit returns to the operating mode with the parameter values unchanged. If adjustment has not been possible, all the red LEDs flash. The unit returns to the operating mode with the parameter values unchanged. I Locking / Unlocking The unit can be electronically locked to prevent unwanted adjustment of the set parameters: Press both setting buttons for 10 s (the unit must be in Run mode). Indication goes out briefly (acknowledgement of locking / unlocking). Units are delivered from the factory in the unlocked state. If the unit is locked, it is possible to indicate the current switch point (press the Mode/Enter button once) and the programming of the output relay (press the Mode/Enter button 2 times).
28

Installation and set-up / Operation / Maintenance


After mounting, wiring and setting check whether the unit operates correctly. When the supply voltage is applied, all LEDs light and go off one after the other.* The unit is then ready for operation.
*During this time the output is switched according to the programming: relay energised with the NO function and de-energised with the NC function.

Recommended maintenance Check the sensor tip for build-up from time to time. Clean it with a soft cloth. If necessary, build-up which adheres firmly (e.g. lime) can be removed with a common vinegar cleansing agent.

Technical data
Nominal voltage [V] . . . . . . . . . . . . . . . . . . . . . 90 ... 240 AC (45....65 Hz) Voltage tolerance [%] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -5 / +10 Operating voltage [V] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 ... 265 AC Power consumption [VA] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5 Switching power of relay . . . . . . . . . . . . . . . . . . . . 3A (250V AC / 30V DC) Number of switching cycles: . . . . . . . . . . . . . . . . . . 20 million mechanically Switching cycles with 3 A load: . . . . . . . . . . . . . . . . . . . 100.000 electrically Relay type: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . contact closed at work Liquids Medium temperature [C] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25 ... +80 Setting range [cm/s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ... 300 Greatest sensitivity [cm/s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ... 60 Max. temperature gradient of medium [K/min] . . . . . . . . . . . . . . . . . . . 300 Gases Medium temperature [C] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25 ... +80 Setting range [cm/s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 ... 3000 Greatest sensitivity [cm/s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 ... 800 Response time [s] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 ... 10 Power-on delay time [s] . . . . . . . . . . . . . . . . . . . . . . . 15, optically indicated Pressure rating [bar]. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300 Operating temperature [C] . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25 ... +80 Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP 67 / II Housing material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PBT-GF-20 Material sensor surface (SI1006) . . . . . . . . . . . . . . . stainless steel (316S12); O-ring: FPM 8x1.5 gr 80 Shore A Material sensor surface (SI1106) . . . . . . . . . . . . . . . . . . . . . . . . . .titanium; O-ring: FFPM (Kalrez) 8x1.5 29

ENGLISH

Programming diagrams / Technical information


I Setting of the detection range The detection range (window) is determined by: Adjustment to the required maximum flow (HI-Teach) = upper limit of the window. This setting is sufficient for the majority of waterbased applications. Adjustment to the required minimum flow / flow standstill (LO-Teach) = lower limit of the window.

flow velocity

0
LO
0 1 2 3 4 5 6 7

sensor signal
HI
8 9

LO
0 1 2 3 4 5 6 7 8

HI
9

LO
0 1 2 3 4 5 6 7 8

HI
9

Adjustment to maximum flow (HI-Teach) The unit detects the current flow and sets this value as the maximum value for the LED display (LED 9).

Apply the operating voltage. After approx. 15 s the unit is ready. Allow the medium to flow through the system at the required maximum flow rate.
M S LO HI

6-8 s
LO HI

2
M S LO HI

Press the Learn/Set button and keep it pressed. The green LEDs on the right and on the left flash, after 5 s the LED bar (green) fills from left to right, (release the button as soon as the first LEDs light). The indication goes off briefly. The unit stores the current flow as maximum flow and passes into the operating mode.

30

Adjustment to minimum flow / flow standstill (LO-Teach), optional The unit detects the current flow and sets this value as the minimum display value for the LED display. In normal operation the first green LED (LED 0) flashes when the flow falls below this value (or when it comes to a standstill). NOTE: The LO-Teach operation may only be carried out after the HITeach operation.

1
M

Allow the medium to flow through the system at the required minimum flow rate or bring to a standstill.
S LO HI

11-15 s
LO HI

Press the Learn/Set button and keep it pressed. The green LEDs on the right and on the left flash, after 5 s the LED bar (green) fills from left to right after a further 5 s the LED bar (gren) fills from right to left (release the button as soon as the first LEDs on the left light). The indication goes off briefly. The unit stores the current flow as minimum flow and passes into the operating mode. ENGLISH 31

2
LO HI

LO

HI

I Setting of the switch point The switch point is preset at the factory (LED 7). The setting influences the reaction time of the unit. High switch point = fast reaction in the case of flow decrease. Low switch point = fast reaction in the case of flow increase.
M S LO HI

1x
M S

Press the Mode/Enter button briefly. The current switch point is indicated: LED lit: coarse setting, LED flashes: fine setting. Press the Learn/Set button and keep it pressed. After 5 s the switch point is increased* (incremental by pressing briefly or scrolling by holding pressed). Indication: The flashing LED moves from left to right. After LED 9 has been reached the cycle starts again at LED 0. The LED which is constantly lit moves on by one position.** Press the Mode/Enter button briefly (acknowledgement). The indication goes off briefly. The set switch point becomes effective; the unit passes into the operating mode.

LO

HI

>5 s
LO HI

LO

HI

*Decrease the switch point: Let the flashing and lit LEDs move to the maximum setting value. Then the cycle starts again at the minimum setting value. **Overflow: If the flashing LED and the lit LED exceed the maximum setting value, the cycle starts again at the minimum setting value.

32

I Manual adjustment to maximum flow (HI-Teach) The unit detects the current flow and sets this value as the maximum value for the LED display (LED 9). In normal operation all LEDs are lit in green when the max. flow is reached. They go out step by step as the flow decreases.

1 2

Apply the operating voltage. After approx. 15 s the unit is ready. Allow the medium to flow through the system at the required maximum flow rate.
M S LO HI

2x
M S LO HI

Press the Mode/Enter button twice. LED 9 flashes. Press the Learn/Set button and keep it pressed. after 5 s the LED bar (green) fills from left to right; (release the button as soon as the first LEDs light), after this LED 9 is lit. Press the Mode/Enter button briefly (acknowledgement). The indication goes off briefly. The unit stores the current flow as maximum flow and passes into the operating mode.

>5 s
M S LO HI

LO

HI

33

ENGLISH

I Manual adjustment to maximum flow (HI-Teach) / monitoring excess flow The unit detects the current flow and sets this value as the maximum value for the LED display (LED 9). In addition the position of the display window within the detection range can be defined: Shift the LED for the maximum display value to position 8, 7, 6 or 5. In the case of maximum flow all LEDs from 0 up to this LED are lit. The LEDs above the range signal excess flow. If the switch point is above this range, the unit switches in the case of excess flow.

1 2

Apply the operating voltage. After approx. 15 s the unit is ready. Allow the medium to flow through the system at the required maximum flow rate.
M S LO HI

2x
M S LO HI

Press the Mode/Enter button twice. LED 9 flashes. Press the Learn/Set button and keep it pressed, after 5 s the LED bar (green) fills from left to right; (release the button as soon as the first LEDs light), after this LED 9 is lit. Press the Learn/Set button several times until the requested LED lights (LED 8, 7, 6 or 5). Each time the button is pressed the LED moves back by one position. When it is lower than LED 5 the cycle starts again at LED 9. Press the Mode/Enter button briefly (acknowledgement). The indication goes off briefly. The unit stores the current flow as maximum flow and passes into the operating mode.

>5 s
M S LO HI

LO

HI

5
34

LO

HI

I Manual adjustment to minimum flow (LO-Teach) The unit detects the current flow and sets this value as the minimum display value for the LED display. In normal operation the first green LED (LED 0) flashes when the flow falls below this value (or when it comes to a standstill). NOTE: The LO-Teach operation may only be carried out after the HITeach operation.

1
M

Allow the medium to flow through the system at the required minimum flow rate or bring to a standstill.
S

2
3x
M S

LO

HI

Press the Mode/Enter button three times. LED 0 flashes. Press the Learn/Set button and keep it pressed. after 5 s the LED bar (green) fills from left to right; (release the button as soon as the first LEDs on the left light), after this LED 9 is lit. Press the Mode/Enter button briefly (acknowledgement). The indication goes off briefly. The unit stores the current flow as minimum flow and passes into the operating mode.

LO

HI

>5 s
M S LO HI

LO

HI

35

ENGLISH

I Change output function: (normally open / normally closed) The set function is displayed as below:
Normally open Normally closed
M S LO HI

The 3 LEDs on the right and left are lit in green. The 4 LEDs in the middle are lit in red.

LO

HI

1
4x
M S

LO

HI

Press the Mode/Enter button four times. The current setting is indicated (here normally open). Press the Learn/Set button and keep it pressed, after 5 s the function changes (here: normally closed) Each time the Learn/Set button is pressed the function changes again. Press the Mode/Enter button briefly (= acknowledgement). The unit then passes into the operating mode.

LO

HI

>5s
LO HI

LO

HI

Unit supplied: normally open.

36

Hysteresis function
flow maximum flow switch point (SP) hysteresis

minimum flow
OUT OUT 1 0 1 0

When the flow rises, the output switches when the switch point (SP) has been reached. When the flow falls again, the output switches back when the value "SP minus hysteresis" has been reached. The hysteresis is considerably influenced by the choice of the operating range on the sensitivity curve of the sensor: In the case of adjustment to HI-Flow values in the range 0 ... 60cm/s the hysteresis is 2 - 4 cm/s (values apply to water). In the case of adjustment to HI-Flow values above 100 cm/s the hysteresis increases as the flow rises. The typical response time of the unit is 3 ... 8 s. It can be influenced by setting the LO-Teach and the switch point: The lower the LO-Teach or the switch point is set, the faster the unit switches on. The higher the LO-Teach or switch point is set, the faster the unit switches off.

37

ENGLISH