Rack Interface Module 3500 20S
Rack Interface Module 3500 20S
Copyright 2000 Bently Nevada Corporation All Rights Reserved. The information contained in this document is subject to change without notice. The following are trademarks of Bently Nevada Corporation in the United States and other countries: Actionable Information, Actionable Information to the Right People at The Right Time, ADRE, Bently Nevada, CableLoc, Data Manager, Decision Support, DemoNet, Dynamic Data Manager, Dynamic Transmitor, Engineer Assist, FieldMonitor, FluidLoc, FlexiTIM, FlexiTAM, Helping you Protect and Manage All Your Machinery, HydroVU, Key , Keyphasor, Machine Condition Manager 2000, MachineLibrary, MicroPROX, Move Data, Not People, Move Information, Not Data, Performance Manager, PROXPAC, Proximitor, REBAM, Seismoprobe, System 1, TDIXconnX, Tecknowledgy, TipLoc, TorXimitor, Transient Data Manager, Trendmaster, TrimLoc, VAM, Velomitor, Xlerometer The Bently Nevada Corporation Orbit Design is a trademark of Bently Nevada Corporation in the United States and other countries. The following ways of contacting Bently Nevada Corporation are provided for those times when you cannot contact your local Bently Nevada representative: Mailing Address Telephone Fax Internet
.
1631 Bently Parkway South Minden, NV 89423 USA 1 775 782 3611 1 800 227 5514 1 775 782 9259 www.bently.com
Additional Information
NOTICE:
This manual does not contain all the information required to operate and maintain the Rack Interface Module. Refer to the following manuals for other required information.
3500 Monitoring System Rack Installation and Maintenance Manual (129766-01) general description of a standard system general description of a Triple Modular redundant (TMR) system instructions for installing and removing the module from a 3500 rack drawings for all cables used in the 3500 Monitoring System
3500 Monitoring System Rack Configuration and Utilities Guide (129777-01) guidelines for using the 3500 Rack Configuration software for setting the operating parameters of the module guidelines for using the 3500 test utilities to verify that the input and output terminals on the module are operating properly
3500 Monitoring System Computer Hardware and Software Manual (128158-01) instructions for connecting the rack to 3500 host computer procedures for verifying communication procedures for installing software guidelines for using Data Acquisition / DDE Server and Operator Display Software procedures and diagrams for setting up network and remote communications
3500 Field Wiring Diagram Package (130432-01) diagrams that show how to hook up a particular transducer lists of recommended wiring
iii
Contents
1
1.1 1.2 1.3
2
2.1 2.2 2.3
General Information.....................................................................2
Triple Modular Redundant (TMR) Description ............................................................3 Statuses .....................................................................................................................3 LED Descriptions........................................................................................................5
Configuration Information...........................................................6
3.1 Software Configuration Options..................................................................................6 3.1.1 Rack Interface Module Configuration Considerations..........................................6 3.1.2 Rack Interface Module Configuration ..................................................................6 3.1.3 Security Options Configuration .........................................................................10 3.2 Switches...................................................................................................................11 3.2.1 Software Switches.............................................................................................12 3.2.2 Hardware Switches............................................................................................13
4.1 Rack Interface Input/Output (I/O) Modules) ..............................................................16 4.1.1 Connecting a Rack Interface I/O Module to a Host Computer ...........................18 4.1.2 Daisy Chaining Rack Interface I/O Modules ......................................................24 4.1.3 Wiring Euro Style Connectors ...........................................................................25 4.1.4 Cable Pin Outs ..................................................................................................26 4.2 Data Manager I/O Modules.......................................................................................32 4.2.1 Cable Pin Outs ..................................................................................................33
Maintenance ...............................................................................37
5.1 RIM Host Port Test Utility .........................................................................................37 5.2 Performing Firmware Upgrades................................................................................37 5.2.1 Installation Procedure........................................................................................37 5.3 Real-Time Clock Replacement .................................................................................40
6
6.1 6.2 6.3 6.4
Troubleshooting.........................................................................42
Verification ...............................................................................................................42 LED Fault Conditions................................................................................................42 System Event List Messages....................................................................................44 Alarm Event List Messages ......................................................................................56
7 8
iv
1
1.1
1.2
Application Alert
Host communication and rack configuration capabilities will be lost when this module is removed from the rack.
Do not discharge static electricity onto the circuit board. Avoid tools or procedures that would subject the circuit board to static damage. Some possible causes include ungrounded soldering irons, nonconductive plastics, and similar materials. Personnel must be grounded with a suitable grounding strap (such as 3M Velostat No. 2060) before handling or maintaining a printed circuit board. Transport and store circuit boards in electrically conductive bags or foil. Use extra caution during dry weather. Relative humidity less than 30% tends to multiply the accumulation of static charges on any surface. When performed properly, this module may be installed into or removed from the rack while power is applied to the rack. Refer to the Rack Installation and Maintenance Manual (part number 129766-01) for the proper procedure.
1.3
Disposal Statement
Customers and third parties that are in control of product at the end of its life or at the end of its use are solely responsible for proper disposal of product. No person, firm, corporation, association or agency that is in control of product shall dispose of it in a manner that is in violation of United States state laws, United States federal laws, or any applicable international law. Bently Nevada Corporation is not responsible for disposal of product at the end of its life or at the end of its use. 1
2 General Information
General Information
The Rack Interface Module (RIM) is the primary interface into the 3500 rack. It supports a Bently Nevada proprietary protocol used to configure the rack and retrieve machinery information. The RIM must be located in slot 1 of the rack (next to the power supplies). The RIM provides the connections needed to support current Bently Nevada Communications Processors (Transient Data Interface External (TDIX) and Dynamic Data Interface External (DDIX)). Although the RIM does provide certain functions common to the entire rack, the RIM is not part of the critical monitoring path. The RIM's operation (or nonoperation) has no effect on the proper, normal operation of the overall monitoring system. Front View Rear View
1) LEDs: Indicate the operating status of the module (See section 2.3 ) 2) Hardware Switches: (See section 3.2.2 ) 2
2 General Information
3) Configuration Port: Configure or retrieve machinery data from only this rack using RS-232 protocol. 4) Rack Interface I/O Module: Daisy chain or configure racks using RS-232 and RS-422 protocol (See section 4.1 ) 5) Data Manager I/O Module: Connect two Bently Nevada Communication Processors to the 3500 rack. (See section 4.2 ) RIM Features Contacts Rack Reset Trip Multiply Alarm Inhibit OK Relay Security Password Key Switch Communications Ports Front Panel Configuration Port Rear Panel Host Port Rear Panel Rack RS-422 Port Data Manager Ports Event Lists Alarm Event List System Event List
2.1
2.2
Statuses
The Rack Interface Module returns both module and channel statuses. This section describes the available statuses and where they can be found. Module Status OK This indicates if the Rack Interface Module is functioning correctly. A not OK status is returned under any of the following conditions: Hardware Failure in the module Communication Failure with any module If any of the following security options have been configured and their conditions met: Rack Address is changed while the RIM is in Run Mode. 3
2 General Information
A module was inserted into or removed from the rack. The Key Switch was changed from Run to Program Mode. Node Voltage Failure OK Relay coil check Failed
If the Module OK status goes not OK then the system OK Relay on the Rack Interface I/O Module will be driven not OK. Configuration Fault This indicates if the Rack Interface Module configuration is invalid. Channel Status OK This indicates whether or not a fault has been detected on the channel or within the module. If the Channel OK status goes not OK then the system OK Relay on the Rack Interface I/O Module will be driven not OK. The following table shows where the statuses can be found. Statuses Communication Gateway Module X Rack Configuration Software X X X X Operator Display Software
2 General Information
2.3
LED Descriptions
The LEDs on the front panel of the Rack Interface Module indicate the operating status of the module as shown in the following figure. Refer to Section 6.2 for all of the available LED conditions.
1) OK: Indicates that the Rack Interface Module and the I/O modules are operating correctly. 2) TX/RX: Flashes at the rate that messages are sent. 3) TM: Indicates whether the rack is in the Trip Multiply mode. 4) Config OK: Indicates that Any module in the rack is unconfigured or has a configuration error or the stored configuration of the Rack Interface Module does not match the physical configuration of the rack or a security option condition was not met.
3 Configuration Information
Configuration Information
This section describes how the Rack Interface Module is configured using the Rack Configuration Software. It also describes any configuration considerations associated with this module. Refer to the 3500 Monitoring System Rack Configuration and Utilities Guide and the Rack Configuration Software for the details on how to operate the software.
3.1
3.1.1
3.1.2
3 Configuration Information
Config ID Contains a unique six-character identifier which is entered when a configuration is downloaded to the 3500 rack. Rear Port The port on the Rack Interface I/O Module labelled HOST that is used to connect this 3500 rack to the 3500 host computer or the 3500 rack daisy chained closer to the 3500 host computer. I/O Option The two types of Rack Interface I/O Modules that are available for the 3500 Monitoring System are the RS-232/RS-422 I/O Module and Modem I/O Module. The RS-232/RS-422 I/O Module contains a 9-pin host connector which contains either RS-232 or RS-422 level signals, dependent upon the position of the I/O Module switch. The Modem I/O Module has an RJ11 connector and contains an internal modem. External Modem The following external modems are directly supported by the Rack Interface Module when configured with an RS-232/RS-422 I/O Module: None Hayes Ultra 9600 Hayes Optima 9600 Motorola FasTalkII 9600 Custom Initialization String The command that sets up and starts the modem. If you select a modem from the list, the default initialization string will be displayed in this field. If you select Custom, enter an initialization string from information found in the modem's documentation. Byte Timeout The number of byte times which the communication line must be idle before a communication is considered complete. One byte time is a function of the baud rate selected. The range of values is 3 to 255. Connect Password Provides read only access to the 3500 rack. If the password entered in this field does not match the password entered in the Rack Configuration Software "Connect" screen or in the Data Acquisition/DDE Server Software "Setup" screen, no communication with the 3500 rack will be allowed. This password is stored in non-volatile memory in the Rack Interface Module.
3 Configuration Information
Configuration Password Provides configuration write access to the 3500 rack. If the password entered in this field does not match the password entered in the Rack Configuration Software "Download" screen, the 3500 rack will not accept new configurations. This password is also required to change setpoints in the 3500 rack from the Operator Display Software. This password is stored in non-volatile memory in the Rack Interface Module. Front Port The port on the front of the Rack Interface Module labelled CONFIGURATION PORT that is primarily used to configure the 3500 rack with a personal computer. This port may also be used to retrieve machinery data for display using the Data Acquisition/DDE Server Software and the Operator Display Software. This port supports RS-232 only and provides access to only one rack. External Modem The following external modems are directly supported by the Rack Interface Module: None Hayes Ultra 9600 Hayes Optima 9600 Motorola FasTalkII 9600 Custom Initialization String The command that sets up and starts the modem. If you select a modem from the list, the default initialization string will be displayed in this field. If you select Custom, enter an initialization string from information found in the modem's documentation. Byte Timeout The number of byte times which the communication line must be idle before a communication is considered complete. One byte time is a function of the baud rate selected. The range of values is 3 to 255. Static Data Considerations Each static data port can access six monitor slots in the 3500 rack. And each monitor slot in the 3500 rack is limited to 32 PPLs. Dynamic Signal Option Identifies which monitors provide dynamic data to the DYNAMIC connectors on the Data Manager I/O Module. This field defines how the 3500 rack will provide machinery data to the Communication Processors (TDIX or DDIX). The following table shows the different options that are available. Keep the following in mind: Dynamic Port 2 is always assigned to slots 8 through 13. If a slot contains something other than a monitor, then no data for that slot is returned. No data can be returned from the modules installed in slots 14 and 15.
3 Configuration Information
Rack Type: Standard Number of Communication Processors: 2 Slots 14 and 15 can not return any data since each TDIX and DDIX can only be connected to a maximum of 24 channels. Slots 2, 4, 6, 8, 10, 12 assigned to Data Manager Port 1 Rack Type: Standard Number of Communication Processors: 1 Use this option when the rack is setup with multiple monitor/relay pairs. Slots 2, 5, 8, 11 assigned to Data Manager Port 1 Rack Type: TMR with Bussed Relay Number of Communication Processors: 1 If a monitor is removed from slots 2, 5, 8 or 11 then no data is returned to the Communication Processor from that monitor group. Slots 2, 6, 10 assigned to Data Manager Port 1
Monitor Groups
Rack Type: TMR with Individual Relays Number of Communication Processors: 1 If a monitor is removed from slots 2, 6 or 10 then no data is returned to the Communication Processor from that monitor group. Legend
Monitor Groups
3 Configuration Information
Agency Approvals The following Agency Approvals are available for the 3500 rack: None CSA-NRTL/C CE Approval Select this box if the CE mark is applicable to the racks installation. Rack Mounting Option Select the type of 3500 rack that is installed or is going to be installed. Refer to the 3500 Monitoring System Rack Installation and Maintenance Manual for a description of the various mounting options. Power Supply The following power supplies can be installed in the 3500 rack: Upper Position in Slot No Power Supply AC High Voltage AC Low Voltage DC High Voltage Lower Position in Slot No Power Supply AC High Voltage AC Low Voltage DC High Voltage
3.1.3
Change Setpoints in Program Mode Only This will only allow changes to setpoints in any of the monitors if the keylock is in the program mode position. If the key is in the run position, setpoint changes will not be allowed.
10
3 Configuration Information
Disable Front Communication Port of RIM This option disables all write functions through the front communication port on the Rack Interface Module when selected. When in this mode the Rear Communication Port is still active. Drive Rack NOT OK Relay if Rack Address is Changed in Run Mode With this option selected the NOT OK Relay will go into a NOT OK state if the Rack Address is changed at any time while the key switch is in the run position. Drive Rack NOT OK Relay if a Module is Removed From the Rack When selected this option will force the NOT OK Relay into a NOT OK state if any module is removed from its slot in the Rack. Drive Rack NOT OK Relay if Key Switch is Changed From Run to Program Mode The Rack NOT OK Relay will go into a NOT OK state any time that the key switch is changed from Run to Program mode when this option is selected.
3.2
Switches
Switches let you control the operation of the 3500 rack and control access to the configuration of the rack. This section lists the software and hardware switches that are available for the Rack Interface Module.
11
3 Configuration Information
3.2.1
Software Switches
The Rack Interface Module supports one software module switch - Configuration Mode. The switch lets you temporarily inhibit monitor and channel functions. This switch can be set on the Software Switches screen under the Utilities Option on the main screen of the Rack Configuration Software.
No changes will take effect until the Set button is pressed. Module Switch Configuration Mode A switch that allows the rack to be configured. To set the rack in configuration mode, enable (!) this switch and set the key switch on the front of the Rack Interface Module in the PROGRAM position. When downloading a Rack Interface Module configuration, this switch will automatically be enabled and disabled by the Rack Configuration Software. If the connection to the rack is lost during the configuration process, use this switch to remove the module from Configuration Mode. The module switch number is used in the Communication Gateway Module. Module Switch Number 1 Switch Name Configuration Mode
12
3 Configuration Information
3.2.2
Hardware Switches
The Rack Interface Module has three hardware switches that are found on the front panel. Key Switch The Key Switch is used to prevent unauthorized changes to the configuration settings. When the switch is in the RUN position, the 3500 rack cannot be configured. When the switch is in the PROGRAM position, the 3500 rack can be configured and the rack continues to operate normally. By removing the key, you can lock the Rack Interface Module in the RUN or PROGRAM position. Rack Reset
Note
An RS-232/RS-422 I/O Module or a Modem I/O Module must be installed for the Rack Reset switch to function correctly. When the Rack Reset switch is pressed, any monitors in the rack will clear latched alarms and reset Timed OK Channel Defeat indications. If the Configuration LED is blinking at 5 Hz, it will be stopped. This switch performs the same function as the Rack Reset contact on the Rack Interface I/O Module. Rack Address The host computer uses the Rack Address to identify 3500 racks that are linked in a daisy chain. Set the rack address by using a 6-position DIP switch which provides for 63 possible addresses. All racks in a daisy chain must have a unique rack address. The following diagram and table show how to select the address 110001 (49 decimal).
LSB - Least Significant Bit MSB - Most Significant Bit Note: The white area shows the direction of the switch.
13
3 Configuration Information
Available Rack Address Switch Addresses MSB LSB 654321 _____ 000000 000001 000010 000011 000100 000101 000110 000111 001000 001001 001010 001011 001100 001101 001110 001111 010000 010001 010010 010011 010100 010101 1* 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Switch Addresses MSB LSB 654321 _____ 010110 010111 011000 011001 011010 011011 011100 011101 011110 011111 100000 100001 100010 100011 100100 100101 100110 100111 101000 101001 101010 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 Switch Addresses MSB LSB 654321 _____ 101011 101100 101101 101110 101111 110000 110001 110010 110011 110100 110101 110110 110111 111000 111001 111010 111011 111100 111101 111110 111111 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
* The address 000000 is reserved for the host. Setting the switches to 000000 will select a Rack Address of 1 just as 000001 will.
14
5 Maintenance
15
5 Maintenance
4.1
1) OK RELAY: The OK Relay is normally energized and is used to indicate whether the 3500 Monitoring System is OK. 2) RACK RS-422: Used to daisy chain to the next 3500 rack. Up to 12 racks can be daisy chained together. Only RS-422 can be used for this connection. 3) EXTERNAL CONTACTS: Trip Multiply Rack Alarm Inhibit Rack Reset
16
5 Maintenance
OK RELAY The following items will cause the OK Relay to go NOT OK: Removing the Rack Interface Module from the 3500 rack Plugging a module into the 3500 rack (during self-test) Transducer going not OK (except Keyphasor) Hardware failure within a module Configuration Failure Slot ID Failure Any module in the 3500 rack which has detected a fault Communication Failure with any module. If any of the following security options have been configured and their conditions met: Rack Address is changed while the RIM is in Run Mode. Any module is inserted or removed from the rack. The Key Switch is changed from Run Mode to Program Mode. The following diagrams show the different ways the OK Relay can be wired: Normally Energized
No Power (Shelf state) NO means Normally Open. ARM means Armature. NC means Normally Closed.
RACK RS-422 Used to daisy chain to the next 3500 rack in the chain. The cable will go between the RACK RS-422 connector on this rack and the HOST connector on the next 3500 rack. Only RS-422 can be used for this connection. Refer to Section 4.1.2 EXTERNAL CONTACTS These require dry contact inputs. To enable a specific function, short the desired contact to a system common (COM). Trip Multiply (TM) Used to signal when the rack should be in Trip Multiply. 17
5 Maintenance
Rack Alarm Inhibit (INHB) Used to prevent an alarm from being declared on any monitor or relay in the 3500 rack. This is typically used when performing maintenance functions. Rack Reset (RST) Used to signal when the modules in the 3500 rack are to be reset. This contact has the same function as the Rack Reset switch on the front panel of the Rack Interface Module.
4.1.1
RS-232/RS-422 HOST Connector Connect to the host computer using RS232, RS-422 (with a converter) or external Modem. Also used to connect to the previous rack in the daisy chain using RS422 ONLY. Use the RS-232/RS-422 switch to select whether the HOST connector uses RS-232 or RS-422 protocol.
Internal Modem Connector Connect to the host computer using a RJ11 compatible modular plug to link into the phone system.
18
5 Maintenance
Note
RS-232 signals are referenced to earth ground. This reference through the RS-232 cable has the potential of causing grounding problems. To avoid grounding problems when using RS-232 communications use serial data isolator P/N 02200633
4.1.1.1
1) Host Computer 2) Cable 130118-XXXX-XX is available in various lengths up to 30 meters (100 ft). Refer to Section 7 for the specific options of the cable listed above.
19
5 Maintenance
4.1.1.2
Additional Information for Connecting a Rack Interface I/O Module to a Host Computer via RS-232 in Intrinsically Safe Application
To avoid ground loops, the system must provide a single point ground. In Intrinsically Safe applications the 3500 Rack is floated and referenced to an intrinsically safe ground instead of earth ground. RS-232 communications are referenced to earth ground, and therefore to keep the rack isolated from earth ground, a serial data isolator must be used.
1) Host Computer 2) Cable 130118-XXXX-XX is available in various lengths up to 30 meters (100 ft). 3) Serial Data Isolator P/N 02200633 Refer to Section 7 for the specific options of the cable listed above.
20
5 Maintenance
4.1.1.3
The communication rate is limited by the baud rate selected between the 3500 host computer and the first Rack Interface Module. The switch on the Rack Interface I/O Module connected to the 3500 host computer must be in the RS-422 position.
For lengths of 150 meters (500 ft) or less, use cable 130120-XXXX-XX (PVC Insulation) or cable 131106-XXXX-XX (Teflon Insulation). For lengths greater than 150 meters (500 ft), use one cable 130120-XXXX-XX (PVC Insulation) or cable 131106-XXXX-XX (Teflon Insulation) along with as many RS-422 extension cables 130121-XX-XX (150 meters (500ft) standard length) to create a cable up to the maximum 1220 meters (4000 ft).
RS-232/RS-422 Converter For 110 Vac use part number 02230411. For 220 Vac use part number 02230412.
Refer to Section 7 for the specific options of the cables listed above.
21
5 Maintenance
4.1.1.4
Connecting a Rack Interface I/O Module to a Host Computer via an External Modem
The communication rate is limited by the baud rate selected between the 3500 host computer and the first Rack Interface I/O Module. The switch on the Rack Interface I/O Module connected to the modem must be in the RS-232 position.
1) Cable 02290860 is available in 3 meter (10ft) length. Refer to Section 7 for the specific options of the cable listed above.
22
5 Maintenance
4.1.1.5
Connecting a Rack Interface I/O Module to a Host Computer via an Internal Modem
The communication rate is limited by the baud rate selected between the host computer and the first Rack Interface I/O Module.
Refer to Section 7 for the specific options of the cables listed above.
23
5 Maintenance
4.1.2
Take note of the following items when daisy chaining Rack Interface I/O Modules: Use the HOST port to connect to the host computer or to the rack in the daisy chain that is closer to the host computer. Use the RACK RS-422 port to connect to the rack that is farther from the host computer. Use the following cables for the connection between the racks in the daisy chain: For lengths of 150 meters (500 ft) or less, use cable 130122-XXXX-XX (PVC Insulation) or cable 131107-XXXX-XX (Teflon Insulation). For lengths greater than 150 meters (500 ft), use one cable 130122-XXXX (PVC Insulation) or cable 131107-XXXX-XX (Teflon Insulation) along with as many RS-422 extension cables 130121-XX-XX (150 meters (500 ft) standard length) to create a cable up to 1220 meters (4000 ft) in length.
Refer to Section 7 for the specific options of the cables listed above.
24
5 Maintenance
4.1.3
Typical I/O module Refer to the 3500 Field Wiring Diagram Package for the recommended wiring. Also, do not remove more than 6 mm (0.25 inches) of insulation from the wires.
25
5 Maintenance
4.1.4
Cable Number 130118-XXXX-XX Host Computer to 3500 Rack RS-232 Interface Cable
26
5 Maintenance
Cable Number 132632-XXXX-XX Host Computer to 3500 Rack Cable RS-422 PVC
Cable Number 132633-XXXX-XX Host Computer to 3500 Rack Cable RS-422 Teflon
27
5 Maintenance
Cable Number 130120-XXXX-XX RS-232/422 Converter to 3500 Rack Cable (RS-422) - PVC Insulation
28
5 Maintenance
Cable Number 130122-XXXX-XX RS-422 3500 Rack to 3500 Rack Cable - PVC Insulation
29
5 Maintenance
Cable Number 131106-XXXX-XX RS-232/422 Converter to 3500 Rack Cable (RS-422) - Teflon Insulation
Cable Number 131107-XXXX-XX RS-422 3500 Rack to 3500 Rack Cable - Teflon Insulation
30
5 Maintenance
Cable Number 145164-XXXX-XX Integrated PC Display to 3500 Rack Cable, RS-422, PVC Insulated
Cable Number 145165-XXXX-XX Integrated PC Display to 3500 Rack Cable, RS-422, Teflon Insulated
31
5 Maintenance
4.2
1) Used to transfer the static information from Port 1 of this 3500 rack to the static connector on the Communication Processor. 2) Used to transfer the dynamic information from Port 1 of this 3500 rack to the dynamic connector on the Communication Processor. 3) Used to transfer the information from Port 2 of this 3500 rack to the static connector on the Communication Processor. 4) Used to transfer the dynamic information from Port 2 of this 3500 rack to the dynamic connector on the Communication Processor.
Note: The 3500 Monitoring System supports the DDIX and TDIX Communication Processors. Note: The Data Manager I/O will cease to operate if the Rack Interface Module is removed.
32
5 Maintenance
4.2.1
33
5 Maintenance
Note: The signals passed through cable 02290160 depend on which dynamic port the cable is connected to on the Data Manager I/O and which 3500 Dynamic options are selected. The following table describes what signals are passed through Dynamic ports 1 and 2 depending on the options chosen.
34
5 Maintenance
1 1 7 14 18 16 11 21 25 23 2 9 4 6 20 3 19 5 24 10 13 12 15 22 17 8 NONE 2,1 2,2 2,3 2,4 3,1 3,2 3,3 3,4 4,1 4,2 4,3 4,4 5,1 5,2 5,3 5,4 6,1 6,2 6,3 6,4 7,1 7,2 7,3 7,4
2 NONE 2,1 2,2 2,3 2,4 4,1 4,2 4,3 4,4 6,1 6,2 6,3 6,4 8,1 8,2 8,3 8,4 10,1 10,2 10,3 10,4 12,1 12,2 12,3 12,4
3 NONE 2,1 2,2 2,3 2,4 5,1 5,2 5,3 5,4 8,1 8,2 8,3 8,4 11,1 11,2 11,3 11,4 NONE NONE NONE NONE NONE NONE NONE NONE
4 NONE 2,1 2,2 2,3 2,4 6,1 6,2 6,3 6,4 10,1 10,2 10,3 10,4 NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE
35
5 Maintenance
1 1 7 14 18 16 11 21 25 23 2 9 4 6 20 3 19 5 24 10 13 12 15 22 17 8 NONE 8,1 8,2 8,3 8,4 9,1 9,2 9,3 9,4 10,1 10,2 10,3 10,4 11,1 11,2 11,3 11,4 12,1 12,2 12,3 12,4 13,1 13,2 13,3 13,4
2 NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE
3 NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE
4 NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE
36
5 Maintenance
Maintenance
This section shows how to verify that the Rack Interface Module and the I/O modules are operating correctly. When performed properly, this module may be installed into or removed from the rack while power is applied to the rack. Refer to the Rack Installation and Maintenance Manual (part number 129766-01) for the proper procedure.
5.1
5.2
5.2.1
Installation Procedure
The following steps will need to be followed to complete the RIM firmware upgrade: Ensure that the Rack Interface Modules configuration is saved using the 3500 Rack Configuration software. Refer to Section 1.2 (Handling and Storing Considerations) before handling the RIM or the upgrade firmware IC. 37
5 Maintenance
Remove the RIM from the 3500 rack. Remove the Top Shield from the RIM. Remove the original firmware IC from the RIM PWA. Install the upgrade firmware IC into the socket on the RIM PWA. Replace the RIM Top Shield. Replace the RIM into the 3500 system. Reconfigure the RIM using the 3500 Rack Configuration software. Detailed instructions for some of the steps listed above are provided on the following pages. Please review completely before proceeding. Top Shield Removal
1) Top Shield. 2) Standoff. 3) Screwdriver. Step 1. Place the large flathead screwdriver under the top shield and on the ridge of the rear standoffs and lift upward on the screwdriver to pop the cover loose from the rear standoffs. Step 2. Move the top shield up and down to work it loose from the two front standoffs.
38
5 Maintenance
Original Firmware IC Removal Step 1. Insert the small flathead screwdriver under the lip of either end of the IC. The diagram shows the approximate location of the chip to be removed, but not necessarily its orientation.
Step 2. Slightly lift the one end of the chip by gently prying with the screwdriver. Move to the other end of the chip and repeat. Continue this process until the chip comes loose from the socket.
39
5 Maintenance
Install the upgrade firmware IC into the PWA. Be sure that the notched end of the IC is matched to the notched end of the socket. Ensure that the IC is firmly seated in the socket. Top Shield Replacement Replace the top shield. Be sure that the notch on the top shield is positioned at the top left corner of the module as shown in the diagram under Top Shield Removal. Align the holes in the top shield with the standoffs and press down around each standoff until they snap in place.
5.3
CAUTION
Dispose of the Real-Time Clock component properly. Do not incinerate!
The Real-Time Clock component on the Rack Interface Module uses an internal Lithium battery that needs to be replaced every 3 to 10 years. The replacement interval depends on environmental conditions such as operating temperature. A 40
5 Maintenance
discharged Lithium battery may cause loss of operating information if the power to the rack is lost. The Real-Time Clock component is socketed for easy replacement. Refer to the System Event List Messages in Section 6 for the message that will be displayed when the Real-Time Clock must be replaced. Contact your nearest Bently Nevada Corporation office for replacement. To replace the Real-Time Clock, follow the instructions in section 5.2 (Performing Firmware Upgrades) with the following exceptions: The approximate location of the clock component on the Pwa is shown below:
41
6 Troubleshooting
Troubleshooting
This section describes how to troubleshoot a problem with the Rack Interface Module or the I/O modules by using the information provided by the verification screen, the LEDs, the System Event List, and the Alarm Event List. You can display the verification screen and the two event lists by using the Rack Configuration Software.
6.1
Verification
To perform the Rack Interface Module's verification: 1. Connect a computer running the Rack Configuration Software to the 3500 rack (if needed). 2. Select Utilities from the main screen of the Rack Configuration Software. 3. Select Verification from the Utilities menu. 4. Select the Rack Interface Module and select the channel you want to verify. 5. Press the Verify button. 6. Select the Front Port or the Rear Port to get the status. 7. The Module OK State will show the Rack Interface Module's status and the Channel OK State will show the channel's status.
6.2
5 Hz
ON
42
6 Troubleshooting
TM LED ON OFF
Condition Rack is in Trip Multiply (due to hardware or software). Rack is not in Trip Multiply. Condition Configuration information for every module in the rack is valid. One of the selected security options has had its condition met.
Config OK LED ON
5 Hz
Check the System Event List. Press the Rack Reset switch to clear.
OFF
At least one module has a configuration fault. A non-configured active Power Supply is present in the rack.
Check System Event List for which module(s) need to be reconfigured. OR Reconfigure module(s) that are flashing OK and TX/RX LEDs at 1 Hz. Remove Power Supply or change RIM configuration to include additional Power Supply.
43
6 Troubleshooting
6.3
Event Number 32
Class
Event Specific
Slot
5L
The number of the event in the System Event List (for example 123). The name of the event (for example Device Not Communicating). Identifies a specific event. Used to display the severity of the event. The following classes are available:
Classification Severe/Fatal Event Potential Problem Event Typical Logged Event Reserved
The date the event occurred. The time the event occurred. Provides additional information for the events that use this field. Identifies the module that the event is associated with. If a half-height module is installed in the upper slot or a full-height module is installed, the field will be 0 to 15. If a half-height module is installed in the lower slot, then the field will be 0L to 15L. For example, the module is installed in the lower position of slot 5 (5L).
44
6 Troubleshooting
The following System Event List Messages may be placed in the list by the Rack Interface Module and are listed in numerical order. If an event marked with a star (*) occurs... the host link on the back of the Rack Interface I/O Module supplying the message will not communicate with the host computer the other Rack Interface Modules in the daisy chain will still be able to communicate with the host computer both ports of the Data Manager I/O Module will stop communicating If you are unable to solve any problems, contact your nearest Bently Nevada Corporation office. Flash Memory Failure Event Number: 11 Event Classification: Potential Problem Action: Replace the Rack Interface Module as soon as possible. Real Time Clock Failure Event Number: 12 Event Classification: Severe/Fatal Event Action: Replace the Real Time Clock in the Rack Interface Module immediately. Internal Network Failure Event Number: 30 Event Classification: Severe/Fatal Event Action: Replace the Rack Interface Module immediately. Resync Internal Network (Resynchronize Internal Network) Event Number: 31 Event Classification: Potential Problem Action: Check to see if one of the following components is faulty: the Rack Interface Module the rack backplane Device Not Communicating Event Number: 32 Event Classification: Potential Problem Action: Check to see if one of the following components is faulty: the module installed in the slot the rack backplane Device Is Communicating Event Number: 33 Event Classification: Potential Problem Action: Check to see if one of the following components is faulty: the module installed in the slot the rack backplane
45
6 Troubleshooting
Config Token Acquired (Configuration Token Acquired) Event Number: 50 Event Classification: Typical logged event Event Specific: Front, Back, DM1 (Data Manager port 1), DM2 (Data Manager port 2), ComGate (Communication Gateway) The specified port can download configuration, change setpoints, set software switches, enable/disable Rack Alarm Inhibit, enable/disable Trip Multiply, or perform Rack Reset. Action: No action required. Config Token Released (Configuration Token Released) Event Number: 51 Event Classification: Typical logged event Event Specific: Front, Back, DM1 (Data Manager port 1), DM2 (Data Manager port 2), ComGate (Communication Gateway) The specified port can no longer download configuration, change setpoints, set software switches, enable/disable Rack Alarm Inhibit, enable/disable Trip Multiply, or perform Rack Reset. Action: No action required. Config Token Expired (Configuration Token Expired) Event Number: 52 Event Classification: Potential Problem Action: Check to see if one of the following components is faulty: the connection between the Rack Interface Module and the computer running the Rack Configuration Software the Rack Interface Module the computer running the Rack Configuration Software Config Token Override (Configuration Token Override) Event Number: 53 Event Classification: Typical Logged Event Action: No action required. Fail Relay Coil Sense Event Number: 55 Event Classification: Potential Problem Action: Check to see if the Rack Interface I/O Module is installed. If installed, check to see if one of the following components is faulty: the Rack Interface Module the Rack Interface I/O Module
46
6 Troubleshooting
Pass Relay Coil Sense Event Number: 56 Event Classification: Potential Problem Action: Check to see if the Rack Interface I/O Module is installed. If installed, check to see if one of the following components is faulty: the Rack Interface Module the Rack Interface I/O Module I/O Module Mismatch Event Number: 60 Event Classification: Potential Problem Action: Verify that the Rack Interface I/O Module installed matches the Rack Interface I/O Module selected in the Rack Configuration Software. If the correct Rack Interface I/O Module is installed, there could be a fault with the installed Rack Interface I/O Module. Rack Type Mismatch Event Number: 61 Event Classification: Potential Problem Action: Verify that the rack selection jumper, installed on the rack backplane, matches the rack type selected in the software. If the jumper is installed in the correct position, there could be a fault with the rack backplane. HW Rack Alm Inh Active (Hardware Rack Alarm Inhibit Active) Event Number: 70 Event Classification: Typical Logged Event Action: No action required. HW Rack Alm Inh Inactive (Hardware Rack Alarm Inhibit Inactive) Event Number: 71 Event Classification: Typical Logged Event Action: No action required. HW override of SW Inh (Hardware override of Software Inhibit) Event Number: 72 Event Classification: Typical Logged Event Action: No action required. HW Trip Multiply Active (Hardware Trip Multiply Active) Event Number: 73 Event Classification: Typical Logged Event Action: No action required.
47
6 Troubleshooting
HW Trip Mult Inactive (Hardware Trip Multiply Inactive) Event Number: 74 Event Classification: Typical Logged Event Action: No action required. HW override of SW TM (Hardware override of Software Trip Multiply) Event Number: 75 Event Classification: Typical Logged Event Action: No action required. HW Rack Reset Active (Hardware Rack Reset Active) Event Number: 76 Event Classification: Typical Logged Event Action: No action required. HW Rack Reset Inactive (Hardware Rack Reset Inactive) Event Number: 77 Event Classification: Typical Logged Event Action: No action required. SW Rack Alm Inh Active (Software Rack Alarm Inhibit Active) Event Number: 78 Event Classification: Typical Logged Event Action: No action required. SW Rack Alm Inh Inactive (Software Rack Alarm Inhibit Inactive) Event Number: 79 Event Classification: Typical Logged Event Action: No action required. SW Trip Multiply Active (Software Trip Multiply Active) Event Number: 80 Event Classification: Typical Logged Event Action: No action required. SW Trip Mult Inactive (Software Trip Multiply Inactive) Event Number: 81 Event Classification: Typical Logged Event Action: No action required. SW Rack Reset (Software Rack Reset) Event Number: 82 Event Classification: Typical Logged Event Action: No action required.
48
6 Troubleshooting
Rack Address changed Event Number: 90 Event Classification: Typical Logged Event Action: No action required. Key Switch in Run Mode Event Number: 91 Event Classification: Typical Logged Event Action: No action required. Key Switch in Prgm Mode (Key Switch in Program Mode) Event Number: 92 Event Classification: Typical Logged Event Action: No action required. Fail Main Board +5V-A (Fail Main Board +5V - upper Power Supply) Event Number: 100 Event Classification: Potential Problem Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty: the Rack Interface Module the Power Supply installed in the upper slot Pass Main Board +5V-A (Pass Main Board +5V - upper Power Supply) Event Number: 101 Event Classification: Potential Problem Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty: the Rack Interface Module the Power Supply installed in the upper slot Fail Main Board +5V-B (Fail Main Board +5V - lower Power Supply) Event Number: 102 Event Classification: Potential Problem Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty: the Rack Interface Module the Power Supply installed in the lower slot
49
6 Troubleshooting
Pass Main Board +5V-B (Pass Main Board +5V - lower Power Supply) Pass Main Board +5V-B Event Number: 103 Event Classification: Potential Problem Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty: the Rack Interface Module the Power Supply installed in the lower slot * Fail Main Board +5V-AB (Fail Main Board +5V - upper and lower Power Supplies)
Event Number: 104 Event Classification: Severe / Fatal Event Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty: the Rack Interface Module the Power Supply installed in the lower slot the Power Supply installed in the upper slot Pass Main Board +5V-AB (Pass Main Board +5V - upper and lower Power Supplies)
Event Number: 105 Event Classification: Severe / Fatal Event Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty: the Rack Interface Module the Power Supply installed in the lower slot the Power Supply installed in the upper slot Fail Main Board +15V-A (Fail Main Board +15V - upper Power Supply) Event Number: 106 Event Classification: Potential Problem Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty the Rack Interface Module the Power Supply installed in the upper slot
50
6 Troubleshooting
Pass Main Board +15V-A (Pass Main Board +15V - upper Power Supply) Event Number: 107 Event Classification: Potential Problem Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty: the Rack Interface Module the Power Supply installed in the upper slot Fail Main Board +15V-B (Fail Main Board +15V - lower Power Supply) Event Number: 108 Event Classification: Potential Problem Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty: the Rack Interface Module the Power Supply installed in the lower slot Pass Main Board +15V-B (Pass Main Board +15V - lower Power Supply) Event Number: 109 Event Classification: Potential Problem Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty: the Rack Interface Module the Power Supply installed in the lower slot * Fail Main Board +15V-AB (Fail Main Board +15V - upper and lower Power Supplies)
Event Number: 110 Event Classification: Severe / Fatal Event Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty: the Rack Interface Module the Power Supply installed in the lower slot the Power Supply installed in the upper slot
51
6 Troubleshooting
Event Number: 111 Event Classification: Severe / Fatal Event Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty: the Rack Interface Module the Power Supply installed in the lower slot the Power Supply installed in the upper slot Fail Main Board -24V-A (Fail Main Board -24V - upper Power Supply) Event Number: 112 Event Classification: Potential Problem Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty: the Rack Interface Module the Power Supply installed in the upper slot Pass Main Board -24V-A (Pass Main Board -24V - upper Power Supply) Event Number: 113 Event Classification: Potential Problem Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty: the Rack Interface Module the Power Supply installed in the upper slot Fail Main Board -24V-B (Fail Main Board -24V -upper and lower Power Supply)
Event Number: 114 Event Classification: Potential Problem Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty: the Rack Interface Module the Power Supply installed in the lower slot Pass Main Board -24V-B (Pass Main Board -24V - lower Power Supply) Event Number: 115 Event Classification: Potential Problem Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty: the Rack Interface Module the Power Supply installed in the lower slot
52
6 Troubleshooting
Event Number: 116 Event Classification: Severe / Fatal Event Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty: the Rack Interface Module the Power Supply installed in the lower slot the Power Supply installed in the upper slot Pass Main Board -24V-AB (Pass Main Board -24V - upper and lower Power Supplies)
Event Number: 117 Event Classification: Severe / Fatal Event Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, check to see if one of the following components is faulty: the Rack Interface Module the Power Supply installed in the lower slot the Power Supply installed in the upper slot Device Configured Event Number: 300 Event Classification: Typical Logged Event Action: No action required. Configuration Failure Event Number: 301 Event Classification: Severe/Fatal Event Action: Replace the Rack Interface Module immediately. Configuration Failure Event Number: 301 Event Classification: Potential Problem Action: Download a new configuration to the Rack Interface Module. If the problem still exists, replace the Rack Interface Module as soon as possible. Module Entered Cfg Mode (Module Entered Configuration Mode) Event Number: 302 Event Classification: Typical Logged Event Action: No action required.
53
6 Troubleshooting
Software Switches Reset Event Number: 305 Event Classification: Potential Problem Action: Download the software switches to the Rack Interface Module. If the software switches are not correct, replace the Rack Interface Module as soon as possible. Init Real Time Clock (Initialize Real Time Clock) Event Number: 306 Event Classification: Potential Problem Action: Replace the Real-Time Clock component in the Rack Interface Module as soon as possible. Monitor TMR PPL Failed (Monitor TMR Proportional value Failed) Event Number: 310 Event Classification: Potential Problem Action: Replace the monitor installed in the slot as soon as possible. Monitor TMR PPL Passed (Monitor TMR Proportional value Passed) Event Number: 311 Event Classification: Potential Problem Action: Replace the monitor installed in the slot as soon as possible. Module Reboot Event Number: 320 Event Classification: Typical Logged Event Action: No action required. Module Removed from Rack Event Number: 325 Event Classification: Typical Logged Event Action: No action required. Module Inserted in Rack Event Number: 326 Event Classification: Typical Logged Event Action: No action required. Supply OK/Installed Event Number: 330 Event Classification: Potential Problem Action: Determine if a power supply has been installed. Verify that there is not a problem with the power source. If there are no problems with the power source, replace the power supply as soon as possible.
54
6 Troubleshooting
Supply Faulted/Removed Event Number: 331 Event Classification: Potential Problem Action: Determine if a power supply has been removed. Verify that there is not a problem with the power source. If there are no problems with the power source, replace the power supply as soon as possible. Rack/RIM Powered Down (Rack or Rack Interface Module Powered Down) Event Number: 340 Event Classification: Typical Logged Event Action: No action required. Rack/RIM Powered Up (Rack or Rack Interface Module Powered Up) Event Number: 341 Event Classification: Typical Logged Event Action: No action required. Modem Reinitialized Event Number: 350 Event Classification: Typical Logged Event Action: No action required. Device Events Lost Event Number: 355 Event Classification: Typical Logged Event Action: No action required. Module Alarms Lost Event Number: 356 Event Classification: Typical Logged Event Action: No action required. Rack Time Changed Event Number: 360 Event Classification: Typical Logged Event Action: No action required. Module Entered Calibr. (Module Entered Calibration Mode) Event Number: 365 Event Classification: Typical Logged Event Action: No action required. Module Exited Calibr. (Module Exited Calibration Mode) Event Number: 366 Event Classification: Typical Logged Event Action: No action required.
55
6 Troubleshooting
Config Password Changed (Configuration Password Changed) Event Number: 400 Event Classification: Typical Logged Event Action: No action required. Connect Password Changed Event Number: 401 Event Classification: Typical Logged Event Action: No action required.
6.4
When the message will occur module went not OK module returned to the OK state
56
6 Troubleshooting
When the message will occur A proportional value in the channel has entered Alert / Alarm 1 and changed the channel Alert / Alarm 1 status A proportional value in the channel has left Alert / Alarm 1 and changed the channel Alert / Alarm 1 status A proportional value in the channel has entered Danger / Alarm 2 and changed the channel Danger / Alarm 2 status A proportional value in the channel has left Danger / Alarm 2 and changed the channel Danger / Alarm 2 status module went not OK module returned to the OK state
When the message will occur module went not OK module returned to the OK state
Relay Module Entered not OK Left not OK Relay Activated Relay Deactivated
When the message will occur module went not OK module returned to the OK state condition for driving the relay channel met condition for driving the relay channel is not met anymore
57
7 Ordering Information
Ordering Information
A B C Part number 3500/20 - XX - XX - XX A 01 02 B 01 02 C 00 01 Rack Interface Type Standard RIM (Use for standard monitoring applications) TMR RIM (Use only for application that requires a Triple Modular Redundant Configuration) Type of I/O Module I/O Module with built-in Modem I/O Module with RS-232/RS-422 Interface Agency Approval Option None CSA-NRTL/C
Spares Standard Rack Interface Module TMR Rack Interface Module RIM I/O Module with Modem Interface RIM I/O Module with RS-232/RS-422 Interface Data Manager I/O Module RIM Module Manual I/O Module Connector Header, Euro Style, 6 Pin I/O Module Connector Header, Euro Style, 3 Pin Grounding Wrist Strap (single use only) Real Time Clock IC Serial Data Isolator *Firmware IC
125744-02 125744-01 135031-01 125768-01 125760-01 129768-01 00580437 00580440 04425545 00801286 02200633 128755-01
*Firmware ICs are available only for PWA 125744-01 revision P or later, or for PWA 125744-02 revision N or later. Cables RS-232 Modem cable from: 3500 Rack External Modem Host Computer to External Modem Host Computer to RS-232/422 Converter Cable RS-232 TDIX - Static Data Cable DDIX - Static Data Cable DDIX/TDIX - Dynamic Data Cable RS-232 to RS-422 Converter 110 VAC RS-232 to RS-422 Converter 220 VAC 02290860
58
7 Ordering Information
Host Computer to 3500 Rack Cable RS-232 A B Part number 130118 - XXXX - XX A 0010 0025 0050 100 B 01 02 Cable Length 10 feet (3 meters) 25 feet (7.5 meters) 50 feet (15 meters) 100 feet (30.5 meters) Assembly Instructions Not Assembled Assembled
Host Computer to 3500 Rack Cable RS-422 PVC A B Part number 132632 - XXXX - XX A 0010 0025 0050 0100 0250 500 B 01 02 Cable Length 10 feet (3 meters) 25 feet (7.5 meters) 50 feet (15 meters) 100 feet (30.5 meters) 250 feet (76 meters) 500 feet (152 meters) Assembly Instructions Not Assembled Assembled
Host Computer to 3500 Rack Cable RS-422 Teflon A B Part number 132633 - XXXX - XX A 0010 0025 0050 0100 0250 500 B 01 02 Cable Length 10 feet (3 meters) 25 feet (7.5 meters) 50 feet (15 meters) 100 feet (30.5 meters) 250 feet (76 meters) 500 feet (152 meters) Assembly Instructions Not Assembled Assembled
59
7 Ordering Information
RS-232/422 Converter to 3500 Rack Cable RS-422 PVC Insulated A B Part number 130120 - XXXX - XX Cable Length A ! 0010 10 feet (3 meters) 0025 25 feet (7.5 meters) 0050 50 feet (15 meters) 0100 100 feet (30.5 meters) 0250 250 feet (76 meters) 0500 500 feet (152 meters) B 01 02 Assembly Instructions Not Assembled Assembled
RS-232/422 Converter to 3500 Rack Cable RS-422 Teflon Insulated A B Part number 131106 - XXXX - XX Cable Length A 0010 10 feet (3 meters) 0025 25 feet (7.5 meters) 0050 50 feet (15 meters) 0100 100 feet (30.5 meters) 0250 250 feet (76 meters) 0500 500 feet (152 meters) B 01 02 Assembly Instructions Not Assembled Assembled
3500 Rack to 3500 Rack Cable RS-422 PVC Insulated A B Part number 130122 - XXXX - XX A 0010 0025 0050 0100 0250 0500 B 01 02 Cable Length 10 feet (3 meters) 25 feet (7.5 meters) 50 feet (15 meters) 100 feet (30.5 meters) 250 feet (76 meters) 500 feet (152 meters) Assembly Instructions Not Assembled Assembled
60
7 Ordering Information
3500 Rack to 3500 Rack Cable RS-422 Teflon Insulated A B Part number 131107 - XXXX - XX A 0010 0025 0050 0100 0250 0500 B 01 02 Cable Length 10 feet (3 meters) 25 feet (7.5 meters) 50 feet (15 meters) 100 feet (30.5 meters) 250 feet (76 meters) 500 feet (152 meters) Assembly Instructions Not Assembled Assembled
Extension Cable RS-422 (Used with Cables 130120, 131106, 130122 and 131107 for lengths greater than 500 feet [152 meters]) A B Part number 130121 - XX - XX Assembly Instructions A 01 Not Assembled 02 Assembled B 01 02 Insulation PVC Insulated Teflon Insulated
61
8 Specifications
8
INPUTS
Specifications
Power Consumption: Data: Front panel: I/O modules: 4.75 watts maximum 38.4 kbaud maximum RS-232 serial communications 38.4 kbaud maximum RS-232/RS-422 serial communications 14.4 kbaud internal modem communications
OUTPUTS
Front Panel LEDs: OK LED: TX/RX LED: TM LED: CONFIG OK LED: Data Manager I/O Dynamic Data Port: Indicates when the RIM is operating properly. Indicates when the RIM is communicating with other modules in the 3500 rack. Indicates when the 3500 rack is in Trip Multiply. Indicates that the 3500 rack has a valid configuration. Provides Multiplexed Buffered Transducer signals through the Data Manager I/O Module. Output Impedance: 600 Ohms Note: The combined parallel impedance of all loads connected to Dynamic Data Port and Buffered Transducer Outputs should be a minimum of 6K Ohms. A smaller load impedance than this could affect the accuracy of the readings. Makes Static Data available to Communication Processor. Output Impedance: 1K Ohms Relay to indicate when the 3500 rack is operating normally or when a fault has been detected within the rack. User can select either an "OPEN" or "CLOSED" contact to annunciate a not OK condition. This relay always operates as "Normally Energized." Max switched power: DC: 120 W AC: 600 VA Max switched current: 5 A Min switched current: 100 mA @ 5 Vdc Max switched voltage: DC: 30Vdc AC: 120 Vac Contact life: 100,000 @ 5 A, 24 Vdc or 120 Vac Environmental sealing: Epoxy sealed Arc suppressors are provided (250 Vrms).
62
8 Specifications
63
8 Specifications
CONTROLS
Clears latched alarms and Timed OK Channel Defeat in the rack. Performs same function as "Rack Reset" contact on I/O module. Address switch: Used to set the rack address. 63 possible addresses. Configuration Keylock: Used to place 3500 rack in either RUN mode or PROGRAM mode. RUN mode allows for normal operation of the rack and locks out configuration changes. PROGRAM mode allows for normal operation of the rack and also allows for local or remote rack configuration. Key can be removed from rack in either position, allowing switch to remain in either RUN or PROGRAM positions. Locking switch in the RUN position allows you to restrict unauthorized rack configuration. Locking switch in PROGRAM position allows remote configuration of a rack at any time. I/O Module System Contacts: Trip multiply: Used to place 3500 rack in Trip Multiply. Alarm inhibit: Used to inhibit all alarms in the 3500 rack. Rack reset: Used to clear latched alarms and Timed OK Channel Defeat. Maximum Current: <1 mA DC, Dry Contact to Common RS-232/RS-422 Switch (RS-232/RS-422 I/O module only): Used to select between RS-232 and RS-422 for communications with the Bently Nevada host software. Front Panel: Rack reset button:
COMMUNICATIONS
Front Panel: Communications: Protocol: Baud rate: Purpose: Cable length: RS-232/RS-422 I/O Module: Communications: Protocol: Baud rate: Purpose: Cable length: RS-232: RS-422: Modem: RS-232 only Bently Nevada developed 38.4 kbaud maximum (auto baud capable) Permits data collection and 3500 rack configuration 30 m (100 ft) maximum RS-232, RS-422, or external modem Bently Nevada developed 38.4 kbaud maximum (auto baud capable) Permits data collection and 3500 rack configuration 30 m (100 ft) maximum 1200 m (4000 ft) maximum Consult modem manufacturer, typical ft)
3.0 m (10
64
8 Specifications
Modem I/O Module: Communications: Protocol: Baud rate: Purpose: Cable length: Rack Connector: Communications: Protocol: Baud rate: Purpose: Cable length:
Hayes AT-compatible Bently Nevada developed Up to 14.4k baud Permits data collection and 3500 rack configuration 2.1 m (7 ft) maximum modem to phone jack RS-422 only Bently Nevada developed 38.4 kbaud maximum Allows multiple 3500 racks to be daisy chained together for communications with 3500 Host Software 1200 m (4000 ft) maximum
Data Manager I/O Module (2 sets of ports): Communications: Bently Nevada developed Protocol: Bently Nevada developed Baud rate: 9600 baud only Purpose: Permits static and dynamic data collection by Bently Nevada Transient Data Interface External or Dynamic Data Interface External Communication Processors Cable length: 3.0 m (10 ft) maximum
ENVIRONMENTAL LIMITS
Rack Interface Module and RS232/RS422 I/O o o o o Operating Temperature -30 C to 65 C (-22 F to 150 F) o o o o Storage Temperature -40 C to 85 C (-40 F to 185 F) Modem I/O Module Operating Temperature Storage Temperature Humidity: 0 C to 50 C (32 F to 122 F) o o o o -40 C to 85 C (-40 F to 185 F)
o o o o
95% non-condensing
CE MARK DIRECTIVES:
EMC Directives: EN50081-2: Radiated Emissions: Conducted Emissions: EN50082-2: Electrostatic Discharge: EN 55011, Class A EN 55011, Class A EN 61000-4-2, Criteria B 65
8 Specifications
Radiated Susceptibility: Conducted Susceptibility: Electrical Fast Transient: Surge Capability: Magnetic Field: Power Supply Dip: Radio Telephone: Low Voltage Directives: Safety Requirements:
ENV 50140, Criteria A ENV 50141, Criteria A EN 61000-4-4, Criteria B EN 61000-4-5, Criteria B EN 61000-4-8, Criteria A EN 61000-4-11, Criteria B ENV 50204, Criteria B
EN 61010-01
APPROVALS
CSA-NRTL/C: Class I, Division 2, Groups A through D
PHYSICAL
RIM: Dimensions (Height x Width x Depth): 241.3 mm x 24.4 mm x 241.8 mm (9.50 in x 0.96 in x 9.52 in) Weight: 0.91 kg (2.0 lbs) RS-232/RS-422 I/O: Dimensions (Height x Width x Depth): 241.3 mm x 24.4 mm x 99.1 mm (9.50 in x 0.96 in x 3.90 in) Weight: 0.45 kg (1.0 lbs) Modem I/O: Dimensions (Height x Width x Depth): 241.3 mm x 24.4 mm x 99.1 mm (9.50 in x 0.96 in x 3.90 in) Weight: 0.45 kg (1.0 lbs) Data Manager I/O: Dimensions (Height x Width x Depth): 241.3 mm x 24.4 mm x 99.1 mm (9.50 in x 0.96 in x 3.90 in) Weight: 0.45 kg (1.0 lbs)
66
8 Specifications
67