Data Sheet
Heat Shrinkable Tubing for Bus Bar
BBIA Series
5 35 kV
1. Product Description
3M BBIA Series Heat Shrinkable Tubing for Bus Bar is
designed for insulating rectangular, square and round bus bar
rated from 5 kV through 35 kV. It will also cover and insulate
inline bolted connections of rectangular bus bars. The tubing
meets the requirements of ANSI/IEEE Standard C37.20. The
standard tubing lengths are 20 feet (6,1 m) and 50 feet (15,2
m).
BBIA Tubing is made of a specially formulated cross-linked
polyolefin. The tubing is colored orange-red. The material
has high resistance to splitting, good solvent resistance and
excellent tracking resistance properties. The tubing shrinks
easily with industry standard methods, forming an
aesthetically appealing insulation cover.
Specially formulated cross-linked polyolefin
Excellent physical properties
Excellent dielectric strength
Excellent tracking resistance
Excellent chemical resistance
Good thermal endurance
Flame retardant; self extinguishing
Flexible; conforms to bends
Heat shrinkable design
Each tube fits a range of bus bar sizes and voltage
ratings
Tight fit provides good heat dissipation
2. Applications
For insulating electrical bus bars per ANSI/IEEE
Standard C37.20:
For 5, 8, 15, 25 and 35 kV voltage ratings
For rectangular, square and round bus bars
For inline bolted connections of rectangular bus
bars
For copper or aluminum bus bars
For use in metal-clad switchgear
For use on metal-enclosed bus bar
For use with substation switchgear
3. Data: Physical and Electrical
Properties
BBIA Tubing can be used on bus bar rated up to 110C
(230F), for 5, 8, 15, 25 and 35 kV voltage classes.
A. Selection Charts for Straight Bus Bar
Standard lengths = 20ft. (6,1m) and 50ft. (15,2m)
5, 8 and 15 kV Bus Bar Size Ranges
Product
Number
Bar
Circumference
(A)
Rectangular *
Square *
Round
BBI3A
3.28 5.57 in.
(83 141 mm)
1 1/2 x 1/4 2 1/2 x 1/2 in.
(38 6 64 13 mm)
1 1 1 1/2 1 1/2 in.
(25 25 38 38 mm)
1 1/8 1 3/4 in.
(29 44 mm)
BBI4A
5.43 8.86 in.
(138 225 mm)
2 1/2 3/8 4 3/4 in.
(64 10 102 19 mm)
2 2 in.
(51 51 mm)
1 3/4 2 3/4 in.
(44 70 mm)
BBI5A
6.67 10.86 in.
(169 276 mm)
3 x 5/8 5 x 3/4 in.
(76 16 127 19 mm)
2 2 2 1/2 2 1/2 in.
(51 51 64 64 mm)
2 1/8 3 3/8 in.
(54 86 mm)
BBI6A
7.57 12.86 in.
(192 327 mm)
3 1/2 1/2 6 3/4 in.
(89 13 152 19 mm)
2 1/2 2 1/2 3 3 in.
(64 64 76 76 mm)
2 1/2 4 in.
(64 102 mm)
BBI7A
8.28 13.00 in.
(210 330 mm)
4 x 1/4 6 x 3/4 in.
(102 6 152 19 mm)
2 1/2 2 1/2 3 3 in.
(64 64 76 76 mm)
2 3/4 4 1/8 in.
(70 105 mm)
BBI8A
10.29 16.43 in.
(261 417 mm)
5 1/4 8 3/8 in.
(127 6 203 10 mm)
3 3 4 4 in.
(76 76 102 102 mm)
3 3/8 5 1/8 in.
(86 130 mm)
BBI9A
12.29 19.23 in.
(312 488 mm)
6 x 1/4 9 x 3/4 in.
(152 6 229 19 mm)
3 1/2 3 1/2 5 5 in.
(89 89 127 127 mm)
4 6 1/8 in.
(102 156 mm)
BBI10A
15.43 24.14 in.
(392 613 mm)
8 1/4 10 3/4 in.
(203 6 254 19 mm)
5 5 6 6 in.
(127 127 152 152 mm)
5 7 5/8 in.
(127 194 mm)
25 kV Bus Bar Size Ranges
BBI3A
3.28 3.56 in.
(83 90 mm)
1 1/2 x 1/4 1 1/2 x 3/8 in.
(38 6 38 10 mm)
MEASURE
CIRCUMFERENCE
1 1/8 in.
(29 mm)
BBI4A
5.43 5.80 in.
(138 147 mm)
2 1/2 3/8 2 1/2 5/8 in.
(64 10 64 16 mm)
MEASURE
CIRCUMFERENCE
1 3/4 in.
(44 mm)
BBI5A
6.67 7.18 in.
(169 182 mm)
3 x 5/8 3 x 3/4 in.
(76 16 76 19 mm)
MEASURE
CIRCUMFERENCE
2 1/8 2 1/4 in.
(54 57 mm)
BBI6A
7.57 8.43 in.
(192 214 mm)
3 1/2 1/2 4 1/4 in.
(89 13 102 6 mm)
MEASURE
CIRCUMFERENCE
2 1/2 2 5/8 in.
(64 67 mm)
BBI7A
8.28 10.44 in.
(210 265 mm)
4 x 1/4 5 x 3/8 in.
(102 6 127 10 mm)
2 1/2 2 1/2 in.
(64 64 mm)
2 3/4 3 1/4 in.
(70 83 mm)
BBI8A
10.29 12.88 in.
(261 327 mm)
5 1/4 6 3/4 in.
(127 6 152 19 mm)
3 3 in.
(76 76 mm)
3 3/8 4 in.
(86 102 mm)
BBI9A
12.29 15.31 in.
(312 389 mm)
6 x 1/4 7 x 3/4 in.
(152 6 178 19 mm)
3 1/2 3 1/2 4 4 in.
(89 89 102 102 mm)
4 4 7/8 in.
(102 124 mm)
BBI10A
15.43 19.79 in.
(392 503 mm)
8 1/4 9 3/4 in.
(203 6 229 19 mm)
5 5 in.
(127 127 mm)
5 6 1/4 in.
(127 159 mm)
NOTE: * Rectangular and square bar sizes are based on bars having radiused edges and corners.
NOTE: BBIA sizing is based on straight sections of bar. For bolted connections consult bolted connection chart on page 3.
NOTE: Contact your 3M Sales Rep for recommendation on the use of BBIA on 1/8 thick bus bar.
A. Selection Charts for Straight Bus Bar (Cont.)
Standard lengths = 20ft. (6,1m) and 50ft. (15,2m)
35 kV Bus Bar Size Ranges
Product
Number
Bar
Circumference
(A)
Rectangular *
Square *
Round
BBI7A
8.28 8.86 in.
(210 225 mm)
4 x 1/4 4 x 3/4 in.
(102 6 102 19 mm)
MEASURE
CIRCUMFERENCE
2 3/4 in.
(70 mm)
BBI8A
10.29 10.94 in.
(261 278 mm)
5 1/4 5 3/4 in.
(127 6 127 19 mm)
MEASURE
CIRCUMFERENCE
3 3/8 in.
(86 mm)
BBI9A
12.29 13.00 in.
(312 330 mm)
6 x 1/4 6 x 3/4 in.
(152 6 152 19 mm)
MEASURE
CIRCUMFERENCE
4 4 1/8 in.
(102 105 mm)
BBI10A
15.43 16.86 in.
(392 428 mm)
8 1/4 8 3/4 in.
(203 6 203 19 mm)
MEASURE
CIRCUMFERENCE
5 5 1/4 in.
(127 133 mm)
NOTE: * Rectangular and square bar sizes are based on bars having radiused edges and corners.
NOTE: BBIA sizing is based on straight sections of bar. For bolted connections consult bolted connection chart on below.
NOTE: Contact your 3M Sales Rep for recommendation on the use of BBIA on 1/8 thick bus bar.
B. BBIA Coverage for Inline Bolted Connections (Rectangular Bus Bar)
NOTE: First select BBIA size from preceding selection charts for Straight Bus Bar.
5, 8 & 15 kV: Inline Bolted Connections
Rectangular Bar
Width
BBI3A
1.5 in.(38 mm)
1 LAYER
2.0 in.(51 mm)
2 LAYERS
BBI4A
BBI5A
2.5 in.(64 mm)
1 LAYER
3.0 in.(76 mm)
2 LAYERS
3.5 in.(89 mm)
2 LAYERS
4.0 in.(102 mm)
2 LAYERS 2 LAYERS
5.0 in.(127 mm)
BBI6A
BBI7A
1 LAYER
1 LAYER
BBI8A
BBI9A
BBI10A
1 LAYER
2 LAYERS 2 LAYERS
6.0 in(152 mm)
1 LAYER
2 LAYERS 2 LAYERS
1 LAYER
1 LAYER
1 LAYER
7.0 in.(178 mm)
2 LAYERS
1 LAYER
8.0 in.(203 mm)
2 LAYERS 2 LAYERS
1 LAYER
9.0 in.(229 mm)
2 LAYERS
1 LAYER
10.0 in.(254 mm)
2 LAYERS
25 & 35 kV: Inline Bolted Connections
USE 2 LAYERS OF BBIA INSULATION FOR ALL 25 & 35 kV INLINE BOLTED CONNECTIONS
3
C. Typical Dimensions
Product
Number
Length
Minimum Expanded
Tubing I. D.
Expanded Wall
Thickness
Max. Recovered
Tubing I. D.
Recovered Wall
Thickness
BBI3A
20 & 50 ft.
(6,1 & 15,2 m)
2.38 in.
(60 mm)
0.049 in.
(1,24 mm)
1.01 in.
(26 mm)
0.113 in.
(2,87 mm)
BBI4A
20 & 50 ft.
(6,1 & 15,2 m)
4.35 in.
(110 mm)
0.043 in.
(1,09 mm)
1.67 in.
(42 mm)
0.113 in.
(2,87 mm)
BBI5A
20 & 50 ft.
(6,1 & 15,2 m)
5.30 in.
(135 mm)
0.043 in.
(1,09 mm)
2.04 in.
(52 mm)
0.114 in.
(2,90 mm)
BBI6A
20 & 50 ft.
(6,1 & 15,2 m)
5.90 in.
(150 mm)
0.046 in.
(1,17 mm)
2.33 in.
(59 mm)
0.117 in.
(2,97 mm)
BBI7A
20 & 50 ft.
(6,1 & 15,2 m)
6.78 in.
(172 mm)
0.048 in.
(1,22 mm)
2.55 in.
(65 mm)
0.130 in.
(3,30 mm)
BBI8A
20 & 50 ft.
(6,1 & 15,2 m)
8.25 in.
(210 mm)
0.049 in.
(1,24 mm)
3.18 in.
(81 mm)
0.128 in.
(3,25 mm)
BBI9A
20 & 50 ft.
(6,1 & 15,2 m)
8.83 in.
(224 mm)
0.054 in.
(1,37 mm)
3.78 in.
(96 mm)
0.127 in.
(3,23 mm)
BBI10A
20 & 50 ft.
(6,1 & 15,2 m)
10.28 in.
(261 mm)
0.059 in.
(1,50 mm)
4.53 in.
(115 mm)
0.138 in.
(3,51 mm)
Typical Clearances for Rectangular and Square Bus Bars
Voltage Rating
(kV)
BIL
(kV)
15 & Below
BBIA Insulated
(Indoor Clearance)
Uninsulated
(Indoor Clearance)
Dimension
b
Dimension
c
Dimension
b
Dimension
c
110
2.7 in.
(69 mm)
3.0 in.
(76 mm)
7.5 in.
(191 mm)
5.0 in.
(127 mm)
25
125
3.0 in.
(76 mm)
3.5 in.
(89 mm)
10.5 in.
(267 mm)
7.5 in.
(191 mm)
35
150
4.5 in.
(114 mm)
5.5 in.
(140 mm)
12.5 in.
(318 mm)
9.5 in.
(241 mm)
NOTE: b = minimum phasetophase dimension
c = minimum phasetoground dimension
The table indicates typical minimum clearance dimensions for BBIA bus bar insulation, as compared to that for uninsulated bus
bar. These dimensions are based on 60 Hz withstand, DC withstand (hypot) and BIL tests (Reference: ANSI/IEEE C37.20) and
from partial discharge (corona) tests. Testing was performed on 12 ft. (3,7 m) lengths of copper and aluminum bus bar enclosed in
a 3 ft. (0,9 m) long duct, with air spacing between the bar and grounded duct.
D. Typical Physical and Electrical Properties
Electrical Properties
Test Method
E. Fluid Resistance (MILI23053/15A)
Immersion at 23_C (73_F) for 24 hours
Typical Value*
D Dielectric Constant
(ASTM D150)
Typical Physical Properties after Immersion
Fluid
3.5
Fluid
Absorption
(% by wt.)
Tensile
Strength
(PSI)
(MPa)
Elongation
Dielectric
Results
at Break
Strength
(%)
(V/mil @ 0.150 in.)
(MV/m)
D Dielectric Strength (70 mils)
(ASTM D149)
550 V/mil
(22 MV/m)
Specification
Requirement
D Volume Resistivity
(ASTM D257)
(MILI23053/15A)
1.4 1013
Deicing fluid
(MilA8243)
0.0
2330
(16,1)
600
333
(13,1)
Pass
Hydraulic fluid
(MilH5606)
2.8
1920
(13,2)
550
392
(15,4)
Pass
Lube oil
(MilL7808)
0.8
2330
(16,1)
515
404
(15,9)
Pass
Lubricating oil
(MilT5624)
0.3
2365
(16,3)
515
451
(17,8)
Pass
Jet fuel, JP4
(MilT5624)
7.4
1380
(9,5)
515
349
(13,7)
Pass
5% salt water
0.1
2400
(16,5)
525
436
(17,2)
Pass
30% ammonia
solution
0.4
2175
(15,0)
600
403
(15,9)
Pass
Noalox Joint
Compound
0.4
2180
(15,0)
515
439
(17,3)
Pass
Contact cleaner
(3M #1607)
42.0
830
(5,7)
385
287
(11,3)
Pass
Black enamel
paint
23.1
810
(5,6)
350
366
(14,4)
Pass
Acetone
4.2
1550
(10,7)
510
339
(13,3)
Pass
Methylene
chloride
37.9
900
(6,2)
340
313
(12,3)
Pass
D Track Resistance (7 hrs.)
(ASTM D2303)
(ANSI/IEEE C37.20)
1 in. @ 3 kV
(25 mm @ 3 kV)
Physical Properties
Test Method
Typical Value*
D Tensile Strength
(ASTM D257)
(MILI23053/15A)
2200 psi
(15 MPa)
D Ultimate Elongation
(ASTM D638)
(MILI23053/15A)
575%
D Water Absorption
7 days @ 23_C (73_F)
(MILI23053/15A)
0.3%
D Corrosion (Copper)
16 hrs. @ 120_C (248_F)
(MILI23053/15A)
Pass
D Fluid Resistance
24 hrs. immersed
(MILI23053/15A)
Product
All straight sections of bus bar shall be insulated with 110_C
(230_F) rated heat shrink tubing which meets the
requirements of ANSI/IEEE C37.20. The tubing shall be
made of halogen free, cross-linked polyolefin, orange-red in
color. The tubing shall be rated for the same voltage rating as
the bus bar, up to 35 kV. The insulation shall be designed for
use on rectangular, square and round bus bars, and it must be
designed to cover and insulate inline bolted connections of
rectangular bus bars. The product must be packaged with
complete installation instructions.
Dielectric Str. = 287451 V/mil
(11.317.8 MV/m)
Thermal Properties
Typical Value*
D Flammability
(ANSI/IEEE C37.20)
Pass
D Thermal Endurance
(ANSI/IEEE 1)
(IEC 216)
110_C (230_F)
D Accelerated Aging
7 days A 175_C (347_F)
(MILI23053/15A)
Tensile = 1430 psi
(10 MPa)
Elongation = 400%
D Heat Shock
4 hrs. @ 225_C (437_F)
(MILI23053/15A)
Pass
D Low Temperature Flexibility
4 hrs. @ 55_C (67_F)
(MILI23053/15A)
Pass
> 200
(>7,9)
4. Specifications
Tensile = 8102400 psi
(5.616.5 MPa)
Test Method
> 750
(>5,2)
Engineering/Architectural
All straight sections of bus bar, and inline connections of
rectangular bus bars, shall be insulated in accordance with the
instructions included with the 3M BBIA Series, Heat
Shrinkable Tubing for Bus Bar. This coverage shall include
all copper and aluminum, rectangular, square and round bus
bars rated at 5, 8, 15, 25 and 35 kV.
5. Performance Tests
A. Dielectric Withstand Tests
(ANSI/IEEE C37.20)
Tests were performed on BBI Series Tubing installed on
rectangular bus bar, on both straight sections and inline
bolted connections. The 2 and 3 in. (51 and 76 mm) bars
were 10 ft. (3,05 m) long, and all other bars were 12 ft.
(3,66 m).
* All values are averages, based on several determinations,
and are not intended for specification purposes.
Power Frequency and Impulse Withstand Tests: The
samples were inserted through a grounded 3 ft. (0.9 m) long
duct and positioned to the required air gap clearance from
one duct wall.
Test for Bus Bar Insulation: The samples were wrapped
with a half-lapped layer of 3M Scotcht 24 Electrical
Shielding Tape to establish a ground plane in contact with
the BBI insulation.
(
*!)!
# (
'(
'&$,
(#"
%)&!"(
)1", ,"+/"( 3
%(/." %.$-.(!
/ . **&% .%)(
/- , (-/&.%)(
%(/." %.$-.(!
$%"&!%(# .*"
**&% .%)(
'*/&-" %.$-.(!
2 /- 10"
3. Slide BBIA Tubing into position and shrink onto bus
bar using standard industry methods.
+$
*!)!
') ('
""* ), $
&'" )0%(#
I
I
I
I
B. Instructions for Inline Bolted Connections
4 I
4 I
4 I
4 I
B. Corona Tests (ANSI/IEEE 454)
Corona (partial discharge) testing was performed on BBI
insulated bus bar which was inserted through a grounded 3
ft. (0.9 m) long duct. The bar was positioned to the required
air gap clearance from one duct wall. The test results
suggest that the air gap between the bar and duct is so large
in relationship to the air gap between the bar and
insulation, that no corona condition exits in the normal
testing range up to 38 kV.
+$ #&#" )'
(
*!)!
# (
&
$
(# )(
+$ #&#"
(&(" # (
+$ #&#"
*("(#" # (
"
$
$
,"$".
/- ,
1. For 15 kV applications consult the Inline Bolted
Connections chart on page 3. Determine whether one
or two layers of BBIA will be required. All 25 and
35 kV applications will require two layers of BBIA
(see Additional Instructions for 25 and 35 kV
Connections on page 7).
2. Clean the bolted connection.
3. Cut one layer of BBIA tubing to cover at 6 inches
(152 mm) of existing insulation on each side of the
connection. Exercise care to ensure a clean cut.
4. Cut a second (outer) layer of BBIA tubing (if
required) to a length that is 2 inches (51 mm) shorter
than the first layer.
An instruction sheet is included in each package to provide
the installer with the information required to properly install
the BBIA Series Tubing on bus bar. A brief summary of the
installation for BBIA is outlined as follows:
5. Shrink the first (inner) layer of BBIA tubing onto the
bus bar and bolted connection. If required, center the
second layer of tubing over the first layer and shrink
using standard industry methods.
A. Instructions for Straight Bus Bar
1. Clean bus bar and cut BBIA Tubing to required
length. Use a sharp knife or razor to ensure a clean cut
with no nicks.
/.", /" &3",
((", /" &3",
2%-.%(# (-/&.%)(
2. Preheating of bus bar is recommended.
4. Dimples appearing in BBIA tubing during
shrinkage are normal, and are removed with
continued even heating.
C. Additional Instructions for 25 and 35 kV
Connections
1. Fill in edges of existing bus bar insulation with an
electrical grade filler before applying two layers of
BBIA tubing.
5. Heat
application
should
be
discontinued
immediately after dimples disappear, or when tubing
has shrunk smoothly onto bar.
Filler
6. Use proper torch which produces a blue and yellow
flame.
7. CAUTION: Be careful handling insulated bus bar
while it is still hot. The heated tubing is soft and
susceptible to physical damage.
Existing Insulation
Filler
8. SAFETY: Use caution and proper safety procedures
when working with open flame and high
temperatures. This would include maintaining a well
ventilated workplace.
D. Application Tips
1. Keep Torch flame moving to prevent burning.
7. Maintenance
2. For rectangular bars: Shrink the edges of the BBIA
tubing first. This will achieve a more uniform
insulation thickness around the bar.
BBIA tubing is not impaired by freezing or overheating due
to ambient temperatures found in storage or shipping. Normal
storage and stock rotation practices are recommended.
3. BBIA tubing normally shrinks at approx. 250F
(120C).
(Caution: burn damage can occur if tubing
temperature exceeds approx. 600F (315C) for
several minutes.)
8. Availability
3M BBIA Series Heat Shrinkable Tubing for Bus Bar is
available from your local authorized 3M electrical
distributor.
IMPORTANT NOTICE TO PURCHASER:
All statements, technical information and recommendations related to the Sellers products
are based on information believed to be reliable,
but the accuracy or completeness thereof is not
guaranteed. Before utilizing the product, the
user should determine the suitability of the product for its intended use. The user assumes all
risks and liability whatsoever in connection with
such use.
80610681555
3M Electrical Products Division
6801 River Place Blvd.
Austin, Texas 78726 9000
All statements or recommendations of the seller
which are not contained in the Sellers current publications shall have no force or effect unless contained in an agreement signed by an authorized
officer of the Seller. The statements contained
herein are made in lieu of all warranties expressed
or implied, including but not limited to the implied
warranties of merchantability and fitness for a particular purpose which warranties are hereby expressly disclaimed.
3M 1993
SELLER SHALL NOT BE LIABLE TO THE
USER OR ANY OTHER PERSON UNDER ANY
LEGAL THEORY, INCLUDING BUT NOT LIMITED TO NEGLIGENCE OR STRICT LIABILITY,
FOR ANY INJURY OR FOR ANY DIRECT OR
CONSEQUENTIAL DAMAGES SUSTAINED OR
INCURRED BY REASON OF THE USE OF ANY
OF THE SELLERS PRODUCTS.