FENWAL SMOKE DETECTORS
Effective: August 1999
Tough, Reliable Detectors that Look Great and Cost Less to
Maintain
KF0020
The latest line of Fenwal Smoke Detectors offers exactly
what todays demanding customer is seeking: more reliability for less money, great aesthetics and significant cost savings in maintenance. Designed and tested under extreme
conditions of heat, cold and humidity, U.L.-listed Fenwal
Smoke Detectors available in ionization, photoelectric or
thermistor heat/photoelectric models are ideally suited to
all types of commercial, institutional and industrial applications.
ADVANTAGES/BENEFITS
INPLACE SENSITIVITY TESTING
All three Fenwal Smoke Detectors offer inplace sensitivity
measurement in % per foot obscuration that satisfies NFPA
72 and is U.L. listed
Faster and more economical way to test detectors readiness
LOW PROFILE STYLING
Fenwal Smoke Detectors reflect the latest in surface mount
design technology, combining functional performance with
sleek styling
Aesthetically pleasing and unobtrusive smoke detection
COST EFFECTIVE DETECTION
Fenwal Smoke Detectors incorporate customer-pleasing
features and economical maintenance at very affordable cost,
in the present and future.
Easy to specify today, easy to own tomorrow
REMOTE TEST CAPABILITY
An optional Remote Test Switch enables fast, easy testing
of detectors located in hard-to-reach spots (ducts, high ceilings, etc.)
Reduced maintenance costs
PROVEN FENWAL QUALITY
Theres only one brand of smoke detector that has a 20year record for continuous product improvement, on-the-job
reliability and superior customer service
Assure the most value, specify Fenwal Smoke Detectors Fenwal Smoke Detectors
BACKWARD COMPATIBILITY
The latest Fenwal Smoke Detectors are mechanically and
electrically backward compatible with previous series Fenwal
bases without rewiring and can even be mixed and matched
on the same initiating loop
Easy retrofitting or system expansion
WIDE RANGE OF OPERATING VOLTAGES
Fenwal Smoke Detectors have the ability to accept a wide
range of voltage from 10.2 to 36.8 VDC, when using the
2WB base
More versatile application
CHOICE OF DETECTION METHODS
Select the precise detection method ionization, photoelectric or photoelectric/thermistor combination thats right for
each application
Superior smoke detection matched to the application
See SPECIFICATION Table (following) for Dimensions
SPECIFICATIONS
IONIZATION MODEL 7051
PHOTOELECTRIC MODEL 7155
PHOTO W/HEAT MODEL 7156
Standby Voltage (using 2WB)
10.2 to 36.8 VDC
10.2 to 36.8 VDC
10.2 to 36.8 VDC
Standby Voltage (using 4WRB)
16.8 to 36.8 VDC
16.8 to 36.8 VDC
16.8 to 36.8 VDC
Maximum Ripple
50% of DC input
50% of DC input
50% of DC input
Standby Current
45A (typical) 100A peak at 24 VDC
55A (typical) 100A peak at 24VDC
55A (typical) 100A peak at 24 VDC
Startup Current
0.1mA max.
0.1mA max.
0.1mA max.
Alarm Current
100mA max.
100mA max.
100mA max.
Alarm Indicator
LED internal
o
LED internal
o
LED internal
Operating Temperature Range
32 F (0 C) to 120 F (49 C)
32 F (0 C) to 120 F (49 C)
32oF (0oC) to 120oF (49oC)
Relative Humidity Range
0 to 93% (noncondensing)
0 to 93% (noncondensing)
0 to 93% (noncondensing)
Reset Voltage
3V (typical) min.
3V (typical) min.
3V (typical) min.
Reset Time
1.0 second max.
1.0 second max.
1.0 second max.
Startup Time
20 seconds max.
20 seconds max.
20 seconds max.
Alarm Voltage
5.5V (typical)
5.5V (typical)
5.5V (typical)
Finish
High impact plastic, off white
High impact plastic, off white
High impact plastic, off white
Approvals
U.L. (Std. 268, 268A),
U.L. (Std. 268, 268A),
U.L. (Std. 268, 268A),
FM, ULC, CSFM, MEA
FM, ULC, CSFM, MEA
FM, ULC, CSFM, MEA
U.L. Sensitivity
0.85 - 1.75%/ft.
1.47 - 3.74%/ft.
1.47 - 3.75%/ft.
Compatibility I.D.
151F E 1
P 55F E 1
P 56F E 1
Height (A) Detector
1.38" (35mm)
1.38" (35mm)
1.89" (48mm)
Height (B) Base
0.43" (11mm)
.043" (11mm)
0.43" (11mm)
Diameter (C) Detector
3.90" (99mm)
3.90" (99mm)
3.90" (99mm)
Diameter (D) Base
5.90" (150mm)
5.90" (150mm)
5.90" (150mm)
Dimensions:
ACCESSORY ITEMS
Model ST-001 Smoke Detector Sensitivity Tester for performing inplace sensitivity testing and measurement. Model DH-60
and DH-60(2W) Duct Detector Housing for use in air handling duct applications to sample air and detect smoke particles.
DH-60 provides 2 auxiliary contacts for shutdowns, 24VDC, 24VAC, 120VAC, and 240 VAC operations. The DH-60(2W)
works only in conjunction with a 24VDC fire alarm control panel.
INSTALLED AND SERVICED BY:
ST-001 Sensitivity Tester
DH-60 Detector Housing
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes no
responsibility for the product's suitability for a particular application. The product must be properly applied to work correctly.
If you need more information on this product, or if you have a particular problem or question,
contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000
KIDDE-FENWAL, INC.
400 MAIN STREET, ASHLAND, MA 01721
TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
KF0020
8/99
10M
Kidde-Fenwal, Inc.
Printed in U.S.A.
CP