0% found this document useful (0 votes)
307 views21 pages

Section 15430 - Plumbing Specialties PDF

This document discusses plumbing specialties for a project in Saudi Arabia. It specifies performance requirements for water, soil/waste/vent, and storm drainage systems. It also lists 19 manufacturers for various plumbing specialties like backflow preventers, water filters, and roof flashing assemblies. Product data submittals are required covering rated capacities and dimensions.

Uploaded by

Mahmoud Gwaily
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
307 views21 pages

Section 15430 - Plumbing Specialties PDF

This document discusses plumbing specialties for a project in Saudi Arabia. It specifies performance requirements for water, soil/waste/vent, and storm drainage systems. It also lists 19 manufacturers for various plumbing specialties like backflow preventers, water filters, and roof flashing assemblies. Product data submittals are required covering rated capacities and dimensions.

Uploaded by

Mahmoud Gwaily
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 21

KING ABDULLAH BIN ABDULAZIZ PROJECT

THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS


SECURITY BUILDINGS IN SHAMIYA AREA

SECTION 15430 - PLUMBING SPECIALTIES


PART 1 - GENERAL
1.1

RELATED DOCUMENTS
A.

1.2

Drawings and general provisions of the Contract, including Conditions of Contract and
Division 1 Specification Sections, apply to this Section.
SUMMARY

A.

This Section includes plumbing specialties for the following:


1.
2.
3.

1.3

Water distribution systems.


Soil, waste, and vent systems.
Storm drainage systems.

SYSTEM PERFORMANCE REQUIREMENTS


A.

Provide components and installation capable of producing piping systems with following
minimum working-pressure ratings, unless otherwise indicated:
1.
2.
3.
4.

1.4

Water Distribution Piping: 860 kPa (125 psig).


Soil, Waste, and Vent Piping: 30 kPa (10-foot head of water).
Storm Drainage Piping: 30 kPa (10-foot head of water).
Force-Main Piping: 690 kPa (100 psig).

SUBMITTALS
A.

Product Data: For each plumbing specialty indicated. Include rated capacities of selected
equipment and shipping, installed, and operating weights. Indicate materials, finishes,
dimensions, required clearances, and methods of assembly of components; and piping and
wiring connections for the following plumbing specialty products:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.

Backflow preventers.
Water regulators.
Balancing valves.
Water filters.
Thermostatic water mixing valves and water tempering valves.
Strainers.
Trap seal primer valves and systems.
Drain valves.
Water hammer arresters.
Hose bibbs.
Air-admittance valves.
Vent caps, vent terminals, and roof flashing assemblies.
Cleanouts.

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 1 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

14.
15.
16.
17.
18.

Floor drains, including garage drains and terrace drains; open receptors, and trench
drains.
Roof drains, including flower bed drains and balcony drains.
Grease interceptors, grease recovery units, oil interceptors, oil storage tanks, and
solids interceptors.
Lint interceptors.
Sleeve penetration systems.

B.

Reports: Specified in "Field Quality Control" Article.

C.

Maintenance Data: For specialties to include in the maintenance manuals specified in


Division 1.

1.5

QUALITY ASSURANCE
A.

Product Options: Drawings indicate size, profiles, dimensional requirements, and


characteristics of plumbing specialties and are based on the specific types and models
selected. Other manufacturers' products with equal performance characteristics may be
considered. Refer to Division 1 Section "Product Requirements."

B.

Provide listing/approval stamp, label, or other marking on plumbing specialties made to


specified standards.

C.

Listing and Labeling: Provide electrically operated plumbing specialties specified in this
Section that are listed and labeled.
1.

Terms "Listed" and "Labeled": As defined in NFPA 70, Article 100.

D.

Comply with ASME B31.9, "Building Services Piping," for materials, products, and
installation.

E.

Comply with NFPA 70, for electrical components.

F.

Comply with NSF 14, "Plastics Piping Components and Related Materials," for plastic
potable-water piping components. Include marking "NSF-pw" on plastic potable-water
piping and "NSF-dwv" on plastic drain, waste, and vent piping.

1.6

EXTRA MATERIALS
A.

Furnish extra materials described below that match products installed, are packaged with
protective covering for storage, and are identified with labels describing contents. Deliver
extra materials to Employer.
1.
2.

Water Filter Cartridges: Furnish quantity not less than 200 percent of amount of each
type and size installed.
Operating Key Handles: Furnish one extra key for each key-operated hose bibb and
hydrant installed.

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 2 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

PART 2 - PRODUCTS
2.1

MANUFACTURERS
A.

Available Manufacturers: Subject to compliance with requirements, manufacturers offering


products that may be incorporated into the Work include, but are not limited to, the
following:
1.

Backflow Preventers:
a.
b.
c.
d.
e.
f.

2.

Dishwasher Air-Gap Fittings:


a.
b.
c.
d.
e.

3.

Amtrol, Inc.
Armstrong Pumps, Inc.
ITT Fluid Technology Corp.; ITT Bell & Gossett Div.
Taco, Inc.
Tour & Andersson, Inc.; Valve Div.
Watts Industries, Inc.; Water Products Div.

Memory-Stop Balancing Valves:


a.
b.
c.
d.
e.

6.

FLOMATIC Corp.
Honeywell Braukmann.
Spence Engineering Co., Inc.
Watts Industries, Inc.; Water Products Div.
Zurn Industries, Inc.; Wilkins Div.

Calibrated Balancing Valves:


a.
b.
c.
d.
e.
f.

5.

B & K Industries, Inc.


Brasstech, Inc.
Bristol Corp.; J & B Products Div.
Moen, Inc.; Dearborn Brass Co. Div.
Sioux Chief Manufacturing Co., Inc.

Water Regulators:
a.
b.
c.
d.
e.

4.

B & K Industries, Inc.


CMB Industries; Febco Div.
FLOMATIC Corp.
Grinnell Corp.; Mueller Co. Marketing Group for Hersey Products Div.
Watts Industries, Inc.; Water Products Div.
Zurn Industries, Inc.; Wilkins Div.

Crane Co.; Valve Div.


Grinnell Corp.
Hammond Valve Corp.
Milwaukee Valve Co., Inc.
Nibco, Inc.

Water Filters:
a.
b.

AMETEK, Inc.; Plymouth Products Div.


Campbell Manufacturing, Inc.

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 3 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

c.
d.
e.
f.
g.
h.
i.
j.
k.
7.

Thermostatic Water Mixing Valves:


a.
b.
c.
d.
e.

8.

Cooney Brothers, Inc.; Hose Station Div.


Leonard Valve Co.
LYNNWOOD Industries, Inc.
Penberthy, Inc.
Strahman Valves, Inc.
T & S Brass and Bronze Works, Inc.

Hydrants:
a.
b.
c.
d.
e.
f.

12.

B & K Industries, Inc.


IMI Cash Valve.
Symmons Industries, Inc.
Watts Industries, Inc.; Water Products Div.

Hose Stations:
a.
b.
c.
d.
e.
f.

11.

Acorn Engineering Co.


IPS Corp.
LSP-Specialty Products Co.
Oatey Co.
Plastic Oddities, Inc.
Symmons Industries, Inc.

Washer-Supply Outlets:
a.
b.
c.
d.

10.

Lawler Manufacturing Co., Inc.


Leonard Valve Co.
Mark Controls Corp.; Powers Process Controls.
Symmons Industries, Inc.
T & S Brass and Bronze Works, Inc.

Outlet Boxes:
a.
b.
c.
d.
e.
f.

9.

Eagle Spring Filtration, Inc.


Eden Equipment Co.
Filtrine Manufacturing Co.
Harmsco Industrial Filters.
Memtec America Corp.; Filterite Div.
Met-Pro Corp.; Keystone Filter Div.
Osmonics, Inc.; Hytrex Div.
Watts Industries, Inc.; Water Products Div.
Whatman, Inc.

Josam Co.
Smith: Jay R. Smith Mfg. Co.
Tyler Pipe; Wade Div.
Watts Industries, Inc.; Water Products Div.
Woodford Manufacturing Co.
Zurn Industries, Inc.; Hydromechanics Div.

Sanitary Post Hydrants:


a.

Murdock, Inc.

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 4 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

13.

Water Hammer Arresters:


a.
b.
c.
d.
e.
f.
g.
h.

14.

Trap Seal Primer Valves:


a.
b.
c.
d.
e.

15.

Elmdor/Stoneman Manufacturing Co.

Sleeve Penetration Systems:


a.

2.2

B & K Industries, Inc.


Bristol Corp.; J & B Products Div.
Durgo: AB Durgo; c/o Enerjee, Ltd.
IMI Cash Valve.
IPS Corp.
Sioux Chief Manufacturing Co., Inc.

Roof Flashing Assemblies:


a.

19.

Enpoco, Inc.
Josam Co.
Smith: Jay R. Smith Mfg. Co.
Watts Industries, Inc.; Ancon Drain Div.
Zurn Industries, Inc.; Hydromechanics Div.

Air-Admittance Valves:
a.
b.
c.
d.
e.
f.

18.

Precision Plumbing Products, Inc.

Backwater Valves:
a.
b.
c.
d.
e.

17.

Josam Co.
Smith: Jay R. Smith Mfg. Co.
Tyler Pipe; Wade Div.
Watts Industries, Inc.; Water Products Div.
Zurn Industries, Inc.; Hydromechanics Div.

Trap Seal Primer Systems:


a.

16.

Amtrol, Inc.
Josam Co.
Sioux Chief Manufacturing Co., Inc.
Smith: Jay R. Smith Mfg. Co.
Sparco, Inc.
Tyler Pipe; Wade Div.
Watts Industries, Inc.; Water Products Div.
Zurn Industries, Inc.; Hydromechanics Div.

ProSet Systems, Inc.

BACKFLOW PREVENTERS
A.

General: ASSE standard, backflow preventers, of size indicated for maximum flow rate and
maximum pressure loss indicated.
1.

DN50 (2-Inch NPS) and Smaller: Bronze body with threaded ends.

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 5 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

2.

DN65 (2-1/2-Inch NPS) and Larger: Bronze, cast-iron, steel, or stainless-steel body
with flanged ends.
a.

3.
4.
5.
B.

Interior Components: Corrosion-resistant materials.


Exterior Finish: Polished chrome-plate if used in chrome-plated piping system.
Strainer on inlet.

Reduced-Pressure-Principle Backflow Preventers: ASSE 1013, suitable for continuous


pressure application. Include outside screw and yoke gate valves on inlet and outlet, and
strainer on inlet; test cocks; and pressure-differential relief valve with ASME A112.1.2 airgap fitting located between 2 positive-seating check valves.
1.

C.

Interior Lining: AWWA C550 or FDA-approved, epoxy coating for backflow


preventers having cast-iron or steel body.

Pressure Loss: 83 kPa (12 psig) maximum, through middle one-third of flow range.

Antisiphon-Pressure-Type Vacuum Breakers: ASSE 1020, suitable for continuous pressure


application. Include shutoff valves, spring-loaded check valve, spring-loaded floating disc,
test cocks, and atmospheric vent.
1.

Pressure Loss: 35 kPa (5 psig) maximum, through middle one-third of flow range.

D.

Dual-Check-Valve-Type Backflow Preventers: ASSE 1024, suitable for continuous


pressure application. Include union inlet and 2 independent check valves.

E.

Dual-Check-Valve-Type Backflow Preventers: ASSE 1032, suitable for continuous


pressure application for carbonated beverage dispensers. Include stainless-steel body;
primary and secondary checks; ball check; intermediate atmospheric-vent port for relieving
carbon dioxide; and threaded ends, DN10 (3/8-inch NPS).

F.

Laboratory Faucet Vacuum Breakers: ASSE 1035, suitable for continuous pressure
application and chrome plated; consisting of primary and secondary checks; intermediate
vacuum breaker; and threaded ends, DN8 or DN10 (1/4- or 3/8-inch NPS) as required.

G.

Reduced-Pressure Detector Assembly Backflow Preventers: ASSE 1047, FM approved or


UL listed, and suitable for continuous pressure application. Include outside screw and yoke
gate valves on inlet and outlet, and strainer on inlet. Include test cocks; pressure-differential
relief valve with ASME A112.1.2 air-gap fitting located between 2 positive-seating check
valves; and bypass with displacement-type water meter, valves, and reduced-pressure
backflow preventer.
1.

Pressure Loss: 83 kPa (12 psig) maximum, through middle one-third of flow range.

H.

Hose-Connection Backflow Preventers: ASSE 1052, suitable for at least 0.19-L/s (3-gpm)
flow and applications with up to 30-kPa (10-foot head) back pressure. Include 2 check
valves; intermediate atmospheric vent; and nonremovable, ASME B1.20.7 garden-hose
thread on outlet.

I.

Back-Siphonage Backflow Vacuum Breakers: ASSE 1056, suitable for continuous pressure
and backflow applications. Include shutoff valves, check valve, test cocks, and vacuum
vent.

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 6 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

2.3

WATER REGULATORS
A.

General: ASSE 1003, water regulators, rated for initial working pressure of 1035 kPa (150
psig) minimum, of size, flow rate, and inlet and outlet pressures indicated. Include integral
factory-installed or separate field-installed Y-pattern strainer.
1.
2.

3.
4.
2.4

DN50 (2-Inch NPS) and Smaller: Bronze body with threaded ends.
DN65 (2-1/2-Inch NPS) and Larger: Bronze or cast-iron body with flanged ends.
Include AWWA C550 or FDA-approved interior epoxy coating for regulators with
cast-iron body.
Interior Components: Corrosion-resistant materials.
Exterior Finish: Polished chrome-plate if used in chrome-plated piping system.

BALANCING VALVES
A.

Calibrated Balancing Valves: Adjustable, with 2 readout ports and memory setting
indicator. Include manufacturer's standard hoses, fittings, valves, differential pressure
meter, and carrying case.
1.
2.
3.

B.

2.5

DN50 (2-Inch NPS) and Smaller: Bronze body with brass ball, adjustment knob,
calibrated nameplate, and threaded or solder-joint ends.
DN50 (2-Inch NPS) and Smaller: Bronze, Y-pattern body with adjustment knob and
threaded ends.
DN65 (2-1/2-Inch NPS) and Larger: Cast-iron, Y-pattern body with bronze disc and
flanged or grooved ends.

Memory-Stop Balancing Valves, DN50 (2-Inch NPS) and Smaller: MSS SP-110, ball
valve, rated for 2760-kPa (400-psig) minimum CWP. Include 2-piece, ASTM B 62 bronze
body with standard port, chrome-plated brass ball, replaceable seats and seals, blowoutproof stem, solder-joint ends, and vinyl-covered steel handle with memory-stop device.
WATER FILTERS

A.

General: Cartridge-type assemblies suitable for potable water of size and at flow rate and
pressure loss indicated. Include housing, fittings, filter cartridges, and cartridge end caps.

B.

Wall-Mounting Type: Housing head section with threaded inlet and outlet, mounting
bracket, and removable lower section for 250-mm- (10-inch-) long filter cartridge.
1.
2.

C.

Housing Material: Stainless steel, 1035-kPa (150-psig) minimum operating pressure.


Cartridge: Activated-charcoal filter media, 250 mm (10 inches), 10-micronparticulate removable rating.

Floor-Mounting Type:
operating pressure.
1.

2.
3.
4.

Stainless-steel housing rated at 1035-kPa (150-psig) minimum

Base Section: Floor-mounting section with inlet and outlet connections and
removable top section for one or more 10-micron-particulate removable-rating
cartridges.
Connections, DN50 (2-Inch NPS) and Smaller: Threaded.
Connections, DN65 (2-1/2-Inch NPS) and Larger: Flanged.
Cartridge: Activated-charcoal filter media.

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 7 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

D.

Ultra-Violet (UV) Sterilizing Unit:


1.

2.
E.

Multi media filters


1.

2.6

Unit: To include 304 stainless-steel sterilizing chambers with removable head. UV


lamps to slide into high purity sleeves. Sleeves are attached to chamber head so that
they may be easily removed as a bundle for inspection or cleaning. Flow regulator on
discharge line to maintain flow to ensure an exposure dosage of 30,000 micro-wattsec/cm. Sterilizer to include high powered ballast, fuse, power safety switch, all
inside white enamel housing with stainless-steel cover and electrical cord rated for a
flow of <2> gpm.
Unit: To include UV intensity sensor and meter with safe/unsafe zones to indicate UV
below effective range, mounted on sterilizer housing.

A multi-media filter bed will be provided for superior quality effluent and long filter
runs. The filter bed shall be constructed of graded layers of media to provide deep bed
filtration, low pressure drop and the ability to remove particles down to 10 microns. The
top layer will consist of hard coal anthracite with an effective size of 0.6 to 0.8 mm.
The second layer consist of sand with an effective size of 0.45 to 0.55 mm. The third
layer consists of 30 to 40 mesh garnet with and effective size of 0.25 to 0.42 mm. The
fourth layer consists of 8 - 12 mesh garnet with and effective size of 1.4 mm. Total
bed depth shall be a minimum of 30 inches.

THERMOSTATIC WATER MIXING VALVES


A.

General: ASSE 1017, manually adjustable, thermostatic water mixing valve with bronze
body. Include check stop and union on hot- and cold-water-supply inlets, adjustable
temperature setting, and capacity at pressure loss as indicated.
1.

B.

Thermostatic Water Mixing Valves: Unit, with the following:


1.
2.
3.

C.

Piping, of sizes and in arrangement indicated. Include valves and unions.


Piping Component Finish: Polished chrome-plate.
Thermometer: Manufacturer's standard.

Manifolded, Thermostatic Water Mixing Valve Assemblies: Factory-fabricated unit


consisting of parallel arrangement of thermostatic water mixing valves.
1.

2.
3.
D.

Bimetal Thermostat, Operation and Pressure Rating: 860 kPa (125 psig) minimum.

Arrangement: One large-flow, thermostatic water mixing valve with flow-control


valve, pressure regulator, inlet and outlet pressure gages, and one small-flow,
thermostatic water mixing valve with flow-control valve.
Include outlet
thermometer, factory- or field-installed inlet and outlet valves, and other indicated
options.
Piping, of sizes and in arrangement indicated. Include valves and unions.
Piping Component Finish: Polished chrome-plate.

Hydrotherapy, Thermostatic Water Mixing Valve Assemblies:


Factory-fabricated,
thermostatic water mixing valve; 2 shutoff valves and 1 volume-control valve; unions;
check stops; thermometer; atmospheric vacuum breaker; piping; escutcheons; and cabinet.
1.

Sizes and Arrangement: As indicated.

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 8 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

2.
E.

Photographic-Process, Thermostatic Water Mixing Valve Assemblies: Factory-fabricated,


thermostatic water mixing valve; volume-control valve; unions; check stops; thermometer;
atmospheric vacuum breaker; piping; escutcheons; and panel enclosure.
1.

2.
3.
2.7

Piping Component Finish: Polished chrome-plate.

Sizes and Arrangement: As indicated, with controls mounted in front of panel cover
and factory- or field-installed inlet valves. Assembly can control outlet-water
temperature within 0.25 deg C (0.5 deg F) throughout temperature and flow operating
ranges.
Panel: Steel box with white enameled finish.
Panel Mounting: Recessed.

STRAINERS
A.

Strainers: Y-pattern, unless otherwise indicated, and full size of connecting piping. Include
ASTM A 666, Type 304, stainless-steel screens with 1.2-mm round perforations, unless
otherwise indicated.
1.
2.
3.
4.

Pressure Rating: 860-kPa (125-psig) minimum steam working pressure, unless


otherwise indicated.
DN50 (2-Inch NPS) and Smaller: Bronze body, with female threaded ends.
DN65 (2-1/2-Inch NPS) and Larger: Cast-iron body, with interior AWWA C550 or
FDA-approved epoxy coating and flanged ends.
Y-Pattern Strainers: Screwed screen retainer with centered blowdown.
a.

5.
6.

T-Pattern Strainers: Malleable-iron or ductile-iron body with grooved ends; access


end cap with drain plug and access coupling with rubber gasket.
Basket Strainers: Bolted flange or clamp cover, and basket with lift-out handle.
a.
b.

B.

Simplex Type: Single unit, with one basket.


Drain: Factory- or field-installed, hose-end drain valve.

Drainage Basket Strainers: Non-pressure-rated, cast-iron or coated-steel body; with bolted


flange or clamp cover and drain with plug.
1.
2.

2.8

Drain: Factory- or field-installed, hose-end drain valve.

Basket: Bronze or stainless steel with 3.2- or 4.8-mm diameter holes and lift-out
handle.
Female threaded ends for DN50 (2-inch NPS) and smaller, and flanged ends for
DN65 (2-1/2-inch NPS) and larger.

TRAP SEAL PRIMER VALVES


A.

Trap Seal Primer Valves:


characteristics:
1.
2.
3.
4.

ASSE 1018, water-supply-fed type, with the following

860-kPa (125-psig) minimum working pressure.


Bronze body with atmospheric-vented drain chamber.
Inlet and Outlet Connections: DN15 (1/2-inch NPS) threaded, union, or solder joint.
Gravity Drain Outlet Connection: DN15 (1/2-inch NPS) threaded or solder joint.

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 9 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

5.
B.

Trap Seal Primer System: Factory-fabricated, automatic-operation assembly for wall


mounting with the following:
1.

2.
3.
4.
5.
2.9

Finish: Chrome plated, or rough bronze for units used with pipe or tube that is not
chrome finished.

Piping: DN20, ASTM B 88M, Type B (3/4-inch NPS, ASTM B 88, Type L); copper,
water tubing inlet and manifold with number of DN15 (1/2-inch NPS) outlets as
indicated.
Cabinet: Steel box with stainless-steel cover.
Electric Controls: 24-hour timer, solenoid valve, and manual switch for [120-V]
[220-V], ac power.
Water Hammer Arrester: ASSE 1010.
Vacuum Breaker: ASSE 1001.

DRAIN VALVES
A.

Hose-End Drain Valves: MSS SP-110, DN20 (3/4-inch NPS) ball valve, rated for 2760-kPa
(400-psig) minimum CWP. Include 2-piece, ASTM B 62 bronze body with standard port,
chrome-plated brass ball, replaceable seats and seals, blowout-proof stem, and vinylcovered steel handle.
1.
2.

B.

2.10

Inlet: Threaded or solder joint.


Outlet: Short-threaded nipple with ASME B1.20.7 garden-hose thread and cap.

Stop-and-Waste Drain Valves: MSS SP-110, ball valve, rated for 1380-kPa (200-psig)
minimum CWP or MSS SP-80, Class 125, gate valve; ASTM B 62 bronze body, with DN6
(1/8-inch NPS) side drain outlet and cap.
MISCELLANEOUS PIPING SPECIALTIES

A.

Water Hammer Arresters: ASME A112.26.1M, ASSE 1010, or PDI-WH 201, bellows or
piston type with pressurized cushioning chamber. Sizes are based on water-supply fixture
units, ASME A112.26.1M sizes A through F and PDI-WH 201 sizes A through F.

B.

Hose Bibbs: Bronze body, with renewable composition disc, DN15 or DN20 (1/2- or 3/4inch NPS) threaded or solder-joint inlet. Provide ASME B1.20.7 garden-hose threads on
outlet and integral or field-installed, nonremovable, drainable, hose-connection vacuum
breaker.
1.
2.

C.

Finish: Chrome or nickel plated.


Operation: Wheel handle.

Air Vents: Float type for automatic air venting.


1.

Welded Construction: Stainless-steel body with corrosion-resistant metal float,


stainless-steel mechanism and seat, threaded DN 10 (NPS 3/8) minimum inlet, 1035kPa (150-psig) minimum pressure rating, and threaded vent outlet.

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 10 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

D.

Air-Admittance Valves: Plastic housing with mechanical-operation sealing diaphragm,


designed to admit air into drainage and vent piping and to prevent transmission of sewer gas
into building.
1.

2.
E.

Stack Vent Valve: ASSE 1050, designed for installation as terminal on soil, waste,
and vent stacks, instead of stack vent extending through roof, in DN50 to DN100 (2to 4-inch NPS).
Fixture Vent Valve: ASSE 1051, designed for installation on waste piping, instead of
vent connection, for single fixture, in DN32 to DN50 (1-1/4- to 2-inch NPS).

Roof Flashing Assemblies: Manufactured assembly made of 20-kg/sq. m, 1.6-mm thick,


lead flashing collar and skirt extending at least 200 mm from pipe with galvanized steel boot
reinforcement, and counterflashing fitting.
1.

Vent Cap: Extended model with field-installed, vandal-proof vent cap.

F.

Open Drains: Shop or field fabricate from ASTM A 74, Service class, hub-and-spigot, castiron, soil-pipe fittings. Include P-trap, hub-and-spigot riser section of length to provide
depth indicated; and where indicated, increaser fitting of size indicated, joined with
ASTM C 564 rubber gaskets. Size P-trap as indicated.

G.

Deep-Seal Traps: Cast iron or bronze, with inlet and outlet matching connected piping,
cleanout where indicated, and trap seal primer valve connection where indicated.
1.
2.

DN50 (2-Inch NPS): 100-mm- (4-inch-) minimum water seal.


DN65 (2-1/2 Inch NPS) and Larger: 125-mm- (5-inch-) minimum water seal.

H.

Floor-Drain Inlet Fittings: Cast iron, with threaded inlet and threaded or spigot outlet, and
trap seal primer valve connection.

I.

Air-Gap Fittings: ASME A112.1.2, cast iron or cast bronze, with fixed air gap, inlet for
drain pipe or tube, and threaded or spigot outlet.

J.

Stack Flashing Fittings: Counterflashing-type, cast-iron fitting, with bottom recess for
terminating roof membrane, and with threaded or hub top for extending vent pipe.

K.

Vent Caps: Cast-iron body with threaded or hub inlet and vandal-proof design. Include
vented hood and set-screws to secure to vent pipe.

L.

Vent Terminals: Commercially manufactured, shop-fabricated or field-fabricated, frostproof assembly constructed of galvanized steel, copper, or lead-coated copper. Size to
provide 25-mm enclosed air space between outside of pipe and inside of flashing collar
extension, with counterflashing, as indicated.

M.

Expansion Joints: ASME A112.21.2M, assembly with cast-iron body with bronze sleeve,
packing gland, and packing, of size and end types corresponding to connected piping.

N.

Downspout Boots: ASTM A 74, Service class, hub-and-spigot, cast-iron soil pipe.

O.

Downspout Nozzles: Cast-bronze body with threaded inlet for pipe size indicated, and castbronze wall flange with mounting holes.
1.

Finish: Polished bronze.

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 11 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

2.11
A.

SLEEVE PENETRATION SYSTEMS


Description: UL 1479, through-penetration firestop assembly for plastic soil, waste and
vent stacks, consisting of sleeve and stack fitting with firestopping plug.
1.
2.

Sleeve: Molded PVC plastic, of length to match slab thickness and with integral
nailing flange on one end for installation in cast-in-place concrete slabs.
Stack Fitting: ASTM A 48, cast-iron, hubless-pattern, wye-branch stack fitting with
neoprene O-ring at base and cast-iron plug in thermal-release harness in branch.
Include PVC protective cap for plug.
a.

2.12
A.

FLASHING MATERIALS
Lead Sheet: ASTM B 749, Type L51121, copper bearing, with the following minimum
weights and thicknesses, unless otherwise indicated:
1.
2.
3.

B.

Special Coating: Include corrosion-resistant interior coating on fittings for


plastic chemical waste and vent stacks.

General Use: 20 kg/sq. m or 1.6-mm thickness.


Vent Pipe Flashing: 15 kg/sq. m or 1.2-mm thickness.
Burning: 30 kg/sq. m or 2.4-mm thickness.

Copper Sheet: ASTM B 152M (ASTM B 152), of the following minimum weights and
thicknesses, unless otherwise indicated:
1.
2.

General Applications: 3.7 kg/sq. m or 0.41-mm thickness.


Vent Pipe Flashing: 2.5 kg/sq. m or 0.27-mm thickness.

C.

Zinc-Coated Steel Sheet: ASTM A 653M (ASTM A 653), with 0.20 percent copper content
and 1.016-mm minimum thickness, unless otherwise indicated. Include Z275 hot-dip
galvanized, mill-phosphatized finish for painting if indicated.

D.

Elastic Membrane Sheet:


minimum thickness.

E.

Fasteners: Metal compatible with material and substrate being fastened.

F.

Metal Accessories: Sheet metal strips, clamps, anchoring devices, and similar accessory
units required for installation; matching or compatible with material being installed.

G.

Solder: ASTM B 32, lead-free alloy.

H.

Bituminous Coating: SSPC-Paint 12, solvent-type, bituminous mastic.

2.13
A.

ASTM D 4068, flexible, chlorinated polyethylene, 1-mm

FLOOR-DRAIN SCHEDULE
Drain FD-[1]: Where plumbing specialties of this designation are indicated, provide
products complying with the following:
1.

Applicable Standard:
classification.]

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

[ASME A112.21.1M, except material and top loading

15430
Page 12 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

2.

Available Products: Subject to compliance with requirements, products that may be


incorporated into the Work include, but are not limited to, the following:
a.

3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
B.

Material: [Cast Iron.]


Seepage Flange: [Required.]
Clamping Device: [Required.]
Outlet: [Bottom.]
Sediment Bucket: [Required.]
Top or Strainer Material: [Stainless Steel.]
Top of Body and Strainer Finish: [Stainless steel.]
Top Shape: [Round.]
Shape: [Round.]
Trap Material: [Cast Iron.]
Trap Pattern: [Standard P-trap.]
Typical to JAY R. SMITH model: 2005Y-A05NB or equal approved.

Floor Drain FD-[2]: Where plumbing specialties of this designation are indicated, provide
products complying with the following:
1.
2.

Applicable Standard: [ASME A112.21.1M.]


Available Products: Subject to compliance with requirements, products that may be
incorporated into the Work include, but are not limited to, the following:
a.
b.
c.
d.
e.

3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
C.

<Z356>Zurn Industries, Inc., Hydromechanics Div.

Josam Co.
Smith: Jay R. Smith Mfg. Co.
Tyler Pipe, Wade Div.
Watts Industries, Inc., Ancon Drain Div.
Zurn Industries, Inc., Hydromechanics Div.

Body Material: Cast iron.


Seepage Flange: Required.
Clamping Device: Required.
Outlet: Bottom or Side as shown on plans.
Sediment Bucket: Not required.
Top or Strainer Material: Stainless steel.
Top of Body and Strainer Finish: Stainless steel.
Top Shape: As per ID requirements
Dimensions of Top or Strainer: minimum 150x150 mm
Top Loading Classification: Heavy Duty
Funnel: Required.
Funnel Dimensions: 100 mm.
Inlet Fitting: [Cast iron.]
Trap Material: Bronze.
Trap Pattern: Standard P-trap or Deep-seal P-trap as shown on drawings.
Trap Features: Not required.
Typical to JAY R. SMITH model: 2005Y-3591NB or equal approved.

Floor Drain FD-[3]: Where plumbing specialties of this designation are indicated, provide
products complying with the following:
1.

Applicable Standard: [ASME A112.21.1M.]

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 13 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

2.

Available Products: Subject to compliance with requirements, products that may be


incorporated into the Work include, but are not limited to, the following:
a.
b.
c.
d.
e.

3.
4.
5.
6.
7.
8.
9.
D.

Body Material: [Cast iron Opoxy painted anti acidic.]


Top or Strainer Material: Stainless steel.
Top of Body and Strainer Finish: Stainless steel.
Dome bottom strainer: aluminum interior acid resistant coated.
Inlet Fitting: [Cast iron.]
Trap Material: Stainless steel.
Typical to JAY R. SMITH model: 3120Y-69 or equal approved.

Floor Drain FD-[4]: Where plumbing specialties of this designation are indicated, provide
products complying with the following:
1.
2.

Applicable Standard: [ASME A112.21.1M.]


Available Products: Subject to compliance with requirements, products that may be
incorporated into the Work include, but are not limited to, the following:
a.
b.
c.
d.
e.

3.
4.
5.
6.
7.
8.
2.14
A.

Josam Co.
Smith: Jay R. Smith Mfg. Co.
Tyler Pipe, Wade Div.
Watts Industries, Inc., Ancon Drain Div.
Zurn Industries, Inc., Hydromechanics Div.

Josam Co.
Smith: Jay R. Smith Mfg. Co.
Tyler Pipe, Wade Div.
Watts Industries, Inc., Ancon Drain Div.
Zurn Industries, Inc., Hydromechanics Div.

Body Material: [Cast iron.]


Top or Strainer Material: Stainless steel.
Screen over polydome: Stainless steel.
Inlet Fitting: [Cast iron.]
Trap Material: Stainless steel.
Typical to JAY R. SMITH model: 2675Y or equal approved.

GARAGE DRAIN
Garage Drain: where plumbing specialties of this designation are indicated, provide
products complying with the following:
1.
2.

Applicable Standard: [ASME A112.21.1M.]


Available Products: Subject to compliance with requirements, products that may be
incorporated into the Work include, but are not limited to, the following:
a.
b.
c.
d.
e.

3.
4.

Josam Co.
Smith: Jay R. Smith Mfg. Co.
Tyler Pipe, Wade Div.
Watts Industries, Inc., Ancon Drain Div.
Zurn Industries, Inc., Hydromechanics Div.

Body Material: [Cast iron.]


Top or Strainer Material: Heavy duty hinged ductile iron grate.

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 14 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

5.
6.
7.
2.15
A.

Sediment Bucket: Required.


Inlet Fitting: [Cast iron.]
Typical to JAY R. SMITH model: SQ-2-1717Y-B or equal approved.

CLEANOUT SCHEDULE
Cleanout FCO-[1]: Where plumbing specialties of this designation are indicated, provide
products complying with the following:
1.
2.

Applicable Standard: [ASME A112.36.2M.]


Available Products: Subject to compliance with requirements, products that may be
incorporated into the Work include, but are not limited to, the following:
a.

3.
4.
5.
6.
7.
8.
9.
10.
11.
B.

Application: [Floor cleanout.]


Body or Ferrule Material: [Cast Iron.]
Clamping Device: [Required.]
Outlet Connection:
Closure: [Cast Iron.]
Adjustable Housing Material: [Cast Iron] with [threads.]
Frame and Cover Material and Finish: [Stainless steel.]
Frame and Cover Shape: [Square.]
Top Loading Classification: [Heavy Duty.]

Cleanout WCO-[1]: Where plumbing specialties of this designation are indicated, provide
products complying with the following:
1.
2.

Applicable Standard: [ASME A112.36.2M.]


Available Products: Subject to compliance with requirements, products that may be
incorporated into the Work include, but are not limited to, the following:
a.

3.
4.
5.
6.
7.
8.
9.
10.
11.
2.16
A.

<Z1440>Zurn Industries, Inc., Hydromechanics Div.

<Z1441>Zurn Industries, Inc., Hydromechanics Div.

Application: [Wall cleanout.]


Body or Ferrule Material: [Cast Iron.]
Clamping Device: [Required.]
Outlet Connection:
Closure: [Cast Iron plug.]
Adjustable Housing Material: [Cast Iron] with [threads.]
Frame and Cover Material and Finish: [Stainless steel.]
Frame and Cover Shape: [Round.]
Top Loading Classification: [Medium Duty.]

TRENCH-DRAIN SCHEDULE
Trench Drain TD-[1]: Where plumbing specialties of this designation are indicated, provide
products complying with the following:
1.
2.

Applicable Standard: [ASME A112.21.1M.]


Available Products: Subject to compliance with requirements, products that may be
incorporated into the Work include, but are not limited to, the following:

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 15 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

a.
3.
4.
5.
6.
7.
8.
9.
10.
11.
2.17
A.

Body Material: [Cast iron.]


Seepage Flange: [Required.]
Clamping Device: [Required.]
Outlet: [Side.]
Grate Material: [Cast iron.]
Grate Finish: [Painted.]
Top Loading Classification: [ Heavy-Duty.]
Trap Material: [Cast iron.]
Trap Pattern: [Standard P-trap.]

ROOF-DRAIN SCHEDULE
Roof Drain RD-[1]: Where plumbing specialties of this designation are indicated, provide
products complying with the following:
1.
2.

Applicable Standard: [ASME A112.21.2M.]


Available Products: Subject to compliance with requirements, products that may be
incorporated into the Work include, but are not limited to, the following:
a.

3.
4.
5.
6.
7.
8.
9.
2.18
A.

<Z886>Zurn Industries, Inc., Hydromechanics Div.

<Z-100-120>Zurn Industries, Inc., Hydromechanics Div.

Body Material: [Cast iron.]


Combination Flashing Ring and Gravel Stop: [Required.]
Outlet: [Bottom.]
Dome Material: [Cast iron.]
Extension Collars: [Required.]
Underdeck Clamp: [Required.]
Sump Receiver: [Not required.]

OIL-INTERCEPTOR SCHEDULE
Oil Interceptor OI-[#]: Where plumbing specialties of this designation are indicated,
provide products complying with the following:
1.

Available Products: Subject to compliance with requirements, products that may be


incorporated into the Work include, but are not limited to, the following:
a.

2.
3.
4.
5.
6.
7.
8.
9.

<Z1186-ST>Zurn Industries, Inc., Hydromechanics Div.

Body Material: [Cast iron or steel.]


Interior Coating: [Corrosion-resistant enamel.]
Exterior Coating: [Corrosion-resistant enamel.]
End Connections: [Threaded.]
Cleanout: [Integral or field installed on outlet.]
Mounting: [Recessed in acid-resistant, coated steel frame and cradle.]
Flow-Control Fitting: [Required.]
Oil Storage Tank: [With integral storage tank]

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 16 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

2.19
A.

2.20
A.

GREASE INTERCEPTORS
Acid Resistant Coated interior and exterior fabricated steel grease interceptor, PDI, grease
capacity, with internal air relief by-pass, bronze cleanout plug, removable pressure
equalizing/flow diffusing in baffle, fixed bottom outlet baffle, and visible double wall trap
seal. Gasketed non-skid secured cover complete with center tie down assembly with flow
control fitting. Regularly furnished with a high inlet and outlet connection. Typical to Zurn
Z1170 and Z1108 flow control fitting or equal approved.
LINT INTERCEPTORS
Acid Resistant Coated interior and exterior fabricated steel lint interceptor, non-skid secured
cover with removable lift handle, stainless lint intercepting secondary screen assembly with
3/32 [2] Square openings and permanent primary straining baffle with 3/8 [10] diameter
perforated holes. Regularly furnished with high inlet and low outlet Note: size #3 and #7
covers are not furnished with a lift handle. Typical to Zurn Z1185 or equal approved.

PART 3 - EXECUTION
3.1

PLUMBING SPECIALTY INSTALLATION


A.

General: Install plumbing specialty components, connections, and devices according to


manufacturer's written instructions.

B.

Install backflow preventers of type, size, and capacity indicated, at each water-supply
connection to mechanical equipment and systems, and to other equipment and water
systems as indicated. Comply with authorities having jurisdiction. Locate backflow
preventers in same room as connected equipment. Install air-gap fitting on units with
atmospheric-vent connection and pipe relief outlet drain to nearest floor drain. Do not
install bypass around backflow preventer.

C.

Install pressure regulators with inlet and outlet shutoff valves and balance valve bypass.
Install pressure gages on inlet and outlet.

D.

Install strainers on supply side of each control valve, pressure regulator, and solenoid valve,
and where indicated.

E.

Install hose bibbs with integral or field-installed vacuum breaker.

F.

Install wall hydrants with integral or field-installed vacuum breaker.

G.

Install trap seal primer valves with valve outlet piping pitched down toward drain trap a
minimum of one percent and connect to floor-drain body, trap, or inlet fitting. Adjust valve
for proper flow.

H.

Install backwater valves in building drain piping as indicated. For interior installation,
provide cleanout deck plate flush with floor and centered over backwater valve cover, and
of adequate size to remove valve cover for servicing.

I.

Install expansion joints on vertical risers, stacks, and conductors as indicated.

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 17 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

J.

Install cleanouts in aboveground piping and building drain piping as indicated, and where
not indicated, according to the following:
1.
2.
3.
4.

Size same as drainage piping up to DN100 (4-inch NPS). Use DN100 (4-inch NPS)
for larger drainage piping unless larger cleanout is indicated.
Locate at each change in direction of piping greater than 45 degrees.
Locate at minimum intervals of 15 m for piping DN100 (4-inch NPS) and smaller and
30 m for larger piping.
Locate at base of each vertical soil and waste stack.

K.

Install cleanout deck plates, of types indicated, with top flush with finished floor, for floor
cleanouts for piping below floors.

L.

Install cleanout wall access covers, of types indicated, with frame and cover flush with
finished wall, for cleanouts located in concealed piping.

M.

Install flashing flange and clamping device with each stack and cleanout passing through
floors with waterproof membrane.

N.

Install vent flashing sleeves on stacks passing through roof. Secure over stack flashing
according to manufacturer's written instructions.

O.

Install floor drains at low points of surface areas to be drained. Set grates of drains flush
with finished floor or as indicated. Size outlets as indicated.

P.

Set floor drains below elevation of surrounding finished floor to allow floor drainage. Set
with grates depressed according to the following drainage area radii:
1.
2.
3.

Radius, 750 mm or Less: Equivalent to 1 percent slope, but not less than 6-mm total
depression.
Radius, 750 to 1500 mm: Equivalent to one percent slope.
Radius, 1500 mm or Larger: Equivalent to 1 percent slope, but not greater than 25mm total depression.

Q.

Install individual traps for floor drains connected to sanitary building drain, unless otherwise
indicated.

R.

Install floor-drain flashing collar or flange so no leakage occurs between drain and adjoining
flooring. Maintain integrity of waterproof membranes where penetrated.

S.

Position floor drains for easy access and maintenance.

T.

Install roof drains at low points of roof areas according to roof membrane manufacturer's
written installation instructions. Size outlets as indicated.

U.

Install roof-drain flashing collar or flange so no leakage occurs between drain and adjoining
roofing. Maintain integrity of waterproof membranes where penetrated.

V.

Position roof drains for easy access and maintenance.

W.

Install interceptors, including trapping, venting, and flow-control fitting, according to


Engineer's requirements, and with clear space for servicing.
1.

Flush with Floor Installation: Set unit and extension if required, with cover flush
with finished floor.

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 18 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

2.

Install cleanout immediately downstream from interceptors not having integral


cleanout on outlet.

X.

Fasten wall-hanging plumbing specialties securely to supports attached to building substrate


if supports are specified and to building wall construction if no support is indicated.

Y.

Fasten recessed, wall-mounting plumbing specialties to reinforcement built into walls.

Z.

Secure supplies to supports or substrate.

AA. Install individual stop valve in each water supply to plumbing specialties. Use ball, gate, or
globe valve if specific valve is not indicated.
BB.

Install water-supply stop valves in accessible locations.

CC.

Install traps on plumbing specialty drain outlets. Omit traps on indirect wastes unless trap is
indicated.

DD. Locate drainage piping as close as possible to bottom of floor slab supporting fixtures and
drains.
EE.

Install escutcheons at wall, floor, and ceiling penetrations in exposed finished locations and
within cabinets and millwork. Use deep-pattern escutcheons if required to conceal
protruding pipe fittings.

FF.

Include wood-blocking reinforcement for recessed and wall-mounting plumbing specialties.

3.2

CONNECTIONS
A.

Piping installation requirements are specified in other Division 15 Sections. Drawings


indicate general arrangement of piping, fittings, and specialties. The following are specific
connection requirements:
1.
2.
3.

Install piping connections between plumbing specialties and piping specified in other
Division 15 Sections.
Install piping connections indicated between appliances and equipment specified in
other Sections; connect directly to plumbing piping systems.
Install piping connections indicated as indirect wastes from appliances and equipment
specified in other Sections, to spill over receptors connected to plumbing piping
systems.

B.

Install hoses between plumbing specialties and appliances as required for connections.

C.

Arrange for electric-power connections to plumbing specialties and devices that require
power. Electric power is specified in Division 16 Sections.

D.

Supply Runouts to Plumbing Specialties: Install hot- and cold-water-supply piping of sizes
indicated.

E.

Drainage Runouts to Plumbing Specialties: Install drainage and vent piping, with approved
trap, of sizes indicated.

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 19 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

F.

Interceptor Connections: Connect piping, flow-control fittings, and accessories as indicated.


1.

G.

Ground electric-powered plumbing specialties.


1.

H.

3.3

Oil Interceptors: Connect inlet, outlet, vent, and gravity drawoff piping to unit; flowcontrol fitting and vent to unit inlet piping; and gravity drawoff and suction piping to
oil storage tank.

Tighten electrical connectors and terminals according to manufacturer's published


torque-tightening values. Where manufacturer's torque values are not indicated, use
those specified in UL 486A and UL 486B.

Arrange for electric-power connections to plumbing specialties and devices that require
power. Electric power, wiring, and disconnect switches are specified in Division 16
Sections.
FLASHING INSTALLATION

A.

Fabricate flashing manufactured from single piece unless large pans, sumps, or other
drainage shapes are required.

B.

Burn joints of lead sheets where required.

C.

Solder joints of copper sheets where required.

D.

Install sheet flashing on pipes, sleeves, and specialties passing through or embedded in
floors and roofs with waterproof membrane.
1.
2.
3.

Pipe Flashing: Sleeve type, matching pipe size, with minimum length of 2500 mm,
and skirt or flange extending at least 200 mm around pipe.
Sleeve Flashing: Flat sheet, with skirt or flange extending at least 200 mm around
sleeve.
Embedded Specialty Flashing: Flat sheet, with skirt or flange extending at least
200 mm around specialty.

E.

Set flashing on floors and roofs in solid coating of bituminous cement.

F.

Secure flashing into sleeve and specialty clamping ring or device.

G.

Install flashing for piping passing through roofs with counterflashing or commercially made
flashing fittings, according to Division 7 Section "Sheet Metal Flashing and Trim."

H.

Extend flashing up vent pipe passing through roofs and turn down into pipe, or secure
flashing into cast-iron sleeve having calking recess.

I.

Fabricate and install flashing and pans, sumps, and other drainage shapes as indicated.
Install drain connection if indicated.

PLUMBING SPECIALTIES
S09107-01D-PL00-FD-SPC-11B-ME-01 REV 0

15430
Page 20 of 21

KING ABDULLAH BIN ABDULAZIZ PROJECT


THIRD SAUDI EXPANSION OF HOLY HARAM MAKKAH & SURROUNDING AREAS
SECURITY BUILDINGS IN SHAMIYA AREA

3.4

FIELD QUALITY CONTROL


A.

Manufacturer's Field Service: Provide services of factory-authorized service representative


to supervise the field assembly of components and installation of grease recovery units,
including piping and electrical connections, and to report results in writing.
1.

3.5

Test and adjust plumbing specialty controls and safeties. Replace damaged and
malfunctioning controls and components.

COMMISSIONING
A.

Startup Services: Engage a factory-authorized service representative to perform startup


services.

B.

Before startup, perform the following checks:


1.
2.
3.

C.

Before operating systems, perform the following steps:


1.
2.
3.
4.

D.

3.6

Close drain valves, hydrants, and hose bibbs.


Open general-duty valves to fully open position.
Remove and clean strainers.
Verify that drainage and vent piping are clear of obstructions. Flush with water until
clear.

Startup Procedures: Follow manufacturer's written instructions.


prescribed by manufacturer, proceed as follows:
1.

E.

System tests are complete.


Damaged and defective specialties and accessories have been replaced or repaired.
Clear space is provided for servicing specialties.

If no procedures are

Energize circuits for electrically operated units. Start and run units through complete
sequence of operations.

Adjust operation and correct deficiencies discovered during commissioning.


DEMONSTRATION

A.

3.7

Engage a factory-authorized service representative to train Employer's maintenance


personnel to adjust, operate, and maintain interceptors and/or grease recovery units. Refer
to Division 1.
PROTECTION

A.

Protect drains during remainder of construction period to avoid clogging with dirt and debris
and to prevent damage from traffic and construction work.

B.

Place plugs in ends of uncompleted piping at end of each day or when work stops.

END OF SECTION 15430