Compact Merlin Gerin - STR

The document summarizes the functions and characteristics of STR trip units used for protection of distribution systems from 60A to 630A. There are five trip unit models that provide protection for circuits operating from 60V to 630V regardless of the circuit breaker voltage rating. The trip units offer adjustable long-time overload protection and short-time/instantaneous short-circuit protection. Additional functions include protection for the neutral circuit, protection for systems with high harmonic neutral loads, and LED indicators for load level.

Uploaded by

Alexandre Moreno
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
501 views1 page

Compact Merlin Gerin - STR

The document summarizes the functions and characteristics of STR trip units used for protection of distribution systems from 60A to 630A. There are five trip unit models that provide protection for circuits operating from 60V to 630V regardless of the circuit breaker voltage rating. The trip units offer adjustable long-time overload protection and short-time/instantaneous short-circuit protection. Additional functions include protection for the neutral circuit, protection for systems with high harmonic neutral loads, and LED indicators for load level.

Uploaded by

Alexandre Moreno
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Protection of distribution systems

Functions and
characteristics

40

DB105116

Compact NS400 to 630 circuit breakers,


types N, H and L, 3-pole and 4-pole, may
be equipped with any of the STR23SE,
STR23SV, STR53UE and STR53SV
electronic trip units.
The STR53UE and STR53SV trip units
offer a wider range of settings and the
STR53UE offers a number of optional
protection, measurement and
communications functions.

STR trip units for Compact NS400 to 630

60

250

400

500

600

STR23SE / STR53UE
STR23SE 0SN
STR23SE / STR53UE
STR23SV / STR53SV?
?

Standard protection with selectivity

Protection of systems with an


overloaded neutral
Protection of systems U > 525 V

Protection of systems supplied


by generators.
Protection of long cables

Selection of the trip unit depends on the type of distribution system protected and
the operational voltage of the circuit breaker.
Protection for all types of circuits, from 60 to 630 A, is possible with only five tripunit catalogue numbers, whatever the circuit-breaker operational voltage:
b U y 525 V: STR23SE, STR23SE OSN or STR53UE
b U > 525 V: STR23SV or STR53SV.
Trip units do not have a predefined rating. The tripping threshold depends on the
circuit breaker rating and the LT (long time) current setting.
For example, for an STR23SE trip unit set to the maximum value, the tripping
threshold is:
v 250 A, when installed on a Compact NS400 250 A
v 630 A, when installed on a Compact NS630.

STR23SE (U y 525 V) and STR23SV (U > 525 V)


electronic trip units
6

DB103751

t
STR 23 SE

E24094

1
2

Io
.8 .9

.7
.63

.5
x In

5
0

1
2
3
4
5
6
7

Ir

Isd

li

90
105 %Ir

alarm

Ir
.88
.85
.8

.9 .93
.95
.98
1

Isd
5

4
3
2

x Io

7
8
10
x Ir

Ir

Isd

test

long-time threshold (overload protection) Ir


long-time tripping delay
short-time pick-up (short-circuit protection) Isd
short-time tripping delay
instantaneous pick-up (short-circuit protection) Ii
test connector
percent load indication

Protection
The protection functions may be set using the adjustment dials.
Overload protection
Long-time protection with an adjustable threshold and fixed tripping delay:
b Io base setting (6-position dial from 0.5 to 1)
b Ir fine adjustment (8-position dial from 0.8 to 1).
Short-circuit protection
Short-time and instantaneous protection:
b short-time protection with an adjustable pick-up and fixed tripping delay
b instantaneous protection with fixed pick-up.
Protection of the fourth pole
On four-pole circuit breakers, neutral protection is set using a three-position switch
to 4P 3d (neutral unprotected), 4P 3d + N/2 (neutral protection at 0.5 In) or 4P 4d
(neutral protection at In).
Protection of an overloaded neutral (OSN):
For 4-pole circuit breakers, special protection of systems with high 3rd order
harmonic contents. In position 4P 4d, the switch sets the neutral protection
threshold to 1.6 x Ir.

Indications
A LED on the front indicates the percent load:
b ON - load is > 90 % of Ir setting
b flashing - load is > 105 % of Ir setting.

Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.

A-12