CFB Boiler Design, Operation and
Maintenance
By Pichai Chaibamrung
Content Day1
1. Introduction to CFB
2. Hydrodynamic of CFB
3. Combustion in CFB
4. Heat Transfer in CFB
5. Basic design of CFB
6. Operation
7. Maintenance
8. Basic Boiler Safety
9. Basic CFB control
Objective
To understand the typical arrangement in CFB
To understand the basic hydrodynamic of CFB
To understand the basic combustion in CFB
To understand the basic heat transfer in CFB
To understand basic design of CFB
To understand theory of cyclone separator
Know Principle Solve Everything
1. Introduction to CFB
1.1 Development of CFB
1.2 Typical equipment of CFB
1.3 Advantage of CFB
1.1 Development of CFB
1921, Fritz Winkler, Germany, Coal Gasification
1938, Waren Lewis and Edwin Gilliland, USA, Fluid Catalytic Cracking,
Fast Fluidized Bed
1960, Douglas Elliott, England, Coal Combustion, BFB
1960s, Ahlstrom Group, Finland, First commercial CFB boiler, 15
MWth, Peat
1.2 Typical Component of CFB Boiler
1.2 Typical Component of CFB Boiler
Wind box and grid nozzle
primary air is fed into wind box.
Air is equally distributed on
furnace cross section by passing
through the grid nozzle. This will
help mixing of air and fuel for
completed combustion
1.2 Typical Component of CFB Boiler
Bottom ash drain
coarse size of ash that is not
take away from furnace by
fluidizing air will be drain
at bottom ash drain port
locating on grid nozzle
floor by gravity.
bottom ash will be cooled
and conveyed to silo by
cooling conveyor.
1.2 Typical Component of CFB Boiler
HP Blower
supply high pressure air to
fluidize bed material in loop
seal so that it can overflow to
furnace
Rotameter
Supplying of HP
blower to loop seal
1.2 Typical Component of CFB Boiler
Cyclone separator
located after furnace exit and
before convective part.
use to provide circulation by
trapping coarse particle back to
the furnace
Fluidized boiler without this
would be BFB not CFB
10
1.2 Typical Component of CFB Boiler
Evaporative or Superheat Wing Wall
located on upper zone of furnace
it can be both of evaporative or SH
panel
lower portion covered by erosion
resistant materials
11
1.2 Typical Component of CFB Boiler
Fuel Feeding system
solid fuel is fed into the lower
zone of furnace through the
screw conveyor cooling with
combustion air. Number of
feeding port depend on the
size of boiler
12
1.2 Typical Component of CFB Boiler
Refractory
refractory is used to protect
the pressure part from
serious erosion zone such as
lower bed, cyclone separator
13
1.2 Typical Component of CFB Boiler
Solid recycle system (Loop seal)
loop seal is located between
dip leg of separator and
furnace. Its design physical is
similar to furnace which have
air box and nozzle to
distribute air. Distributed air
from HP blower initiate
fluidization. Solid behave like
a fluid then over flow back to
the furnace.
14
1.2 Typical Component of CFB Boiler
Kick out
kick out is referred to
interface zone between
the end of lower zone
refractory and water tube.
It is design to protect the
erosion by by-passing the
interface from falling
down bed materials
15
1.2 Typical Component of CFB Boiler
Lime stone and sand system
lime stone is pneumatically feed or gravitational feed into
the furnace slightly above fuel feed port. the objective is to
reduce SOx emission.
Sand is normally fed by gravitation from silo in order to
maintain bed pressure. Its flow control by speed of rotary
screw.
16
1.2 Typical Arrangement of CFB Boiler
17
1.3 Advantage of CFB Boiler
Fuel Flexibility
18
1.3 Advantage of CFB Boiler
High Combustion Efficiency
- Good solid mixing
- Low unburned loss by cyclone, fly ash recirculation
- Long combustion zone
In situ sulfur removal
Low nitrogen oxide emission
19
2. Hydrodynamic in CFB
2.1 Regimes of Fluidization
2.2 Fast Fluidized Bed
2.3 Hydrodynamic Regimes in CFB
2.4 Hydrodynamic Structure of Fast Beds
20
2.1 Regimes of Fluidization
Fluidization is defined as the operation through which fine
solid are transformed into a fluid like state through
contact with a gas or liquid.
21
2.1 Regimes of Fluidization
Particle Classification
Distribution
Size (micron)
CFB1
CFB2
BFB
100%
<600
<1000
<1680
75%
<250
<550
<1190
50%
<180
<450
<840
25%
<130
<250
<590
>100
>420
100%
22
2.1 Regimes of Fluidization
Particle Classification
23
2.1 Regimes of Fluidization
Comparison of Principal Gas-Solid Contacting Processes
24
2.1 Regimes of Fluidization
Packed Bed
The pressure drop per unit height of a packed beds of a uniformly size
particles is correlated as (Ergun,1952)
Where U is gas flow rate per unit cross section of the bed called
Superficial Gas Velocity
25
2.1 Regimes of Fluidization
Bubbling Fluidization Beds
Minimum fluidization velocity is velocity where the fluid
drag is equal to a particles weight less its buoyancy.
26
2.1 Regimes of Fluidization
Bubbling Fluidization Beds
For B and D particle, the bubble is started when superficial
gas is higher than minimum fluidization velocity
But for group A particle the bubble is started when
superficial velocity is higher than minimum bubbling
velocity
27
2.1 Regimes of Fluidization
Turbulent Beds
when the superficial is continually increased through a
bubbling fluidization bed, the bed start expanding, then
the new regime called turbulent bed is started.
28
2.1 Regimes of Fluidization
29
2.1 Regimes of Fluidization
Terminal Velocity
Terminal velocity is the particle velocity when the
forces acting on particle is equilibrium
30
2.1 Regimes of Fluidization
Freeboard and Furnace Height
- considered for design heating-surface area
- considered for design furnace height
- to minimize unburned carbon in bubbling
bed
- the freeboard heights should be exceed or
closed to the transport disengaging heights
31
2.2 Fast Fluidization
Definition
32
2.2 Fast Fluidization
Characteristics of Fast Beds
- non-uniform suspension of slender particle agglomerates or clusters moving
up and down in a dilute
- excellent mixing are major characteristic
- low feed rate, particles are uniformly dispersed in gas stream
- high feed rate, particles enter the wake of the other, fluid drag on the leading
particle decrease, fall under the gravity until it drops on to trailing particle
33
2.3 Hydrodynamic regimes in a CFB
Cyclone Separator :
Swirl Flow
Back Pass:
Pneumatic Transport
Furnace Upper SA:
Fast Fluidized Bed
Lower Furnace below SA:
Turbulent or bubbling
fluidized bed
Return leg and lift leg :
Pack bed and Bubbling Bed
34
2.4 Hydrodynamic Structure of Fast Beds
Axial Voidage Profile
Secondary air is fed
Bed Density Profile of 135 MWe CFB Boiler (Zhang et al., 2005)
35
2.4 Hydrodynamic Structure of Fast Beds
Velocity Profile in Fast Fluidized Bed
36
2.4 Hydrodynamic Structure of Fast Beds
Velocity Profile in Fast Fluidized Bed
37
2.4 Hydrodynamic Structure of Fast Beds
Particle Distribution Profile in Fast Fluidized Bed
38
2.4 Hydrodynamic Structure of Fast Beds
Particle Distribution Profile in Fast Fluidized Bed
39
2.4 Hydrodynamic Structure of Fast Beds
Particle Distribution Profile in Fast Fluidized Bed
Effect of SA injection on particle
distribution by M.Koksal and
F.Hamdullahpur (2004). The
experimental CFB is pilot scale CFB.
There are three orientations of SA
injection; radial, tangential, and mixed
40
2.4 Hydrodynamic Structure of Fast Beds
Particle Distribution Profile in Fast Fluidized Bed
Increasing SA to 40%
does not significant on
suspension density above
SA injection point
but the low zone is
denser than low SA ratio
Increasing solid circulation
rate effect to both
lower and upper zone
of SA injection point
which both zone is
denser than low
solid circulation rate
No SA, the suspension
density is proportional
l to solid circulation rate
With SA 20% of PA,
the solid particle is hold up
when compare to no SA
41
2.4 Hydrodynamic Structure of Fast Beds
Effects of Circulation Rate on Voidage Profile
higher solid recirculation rate
42
2.4 Hydrodynamic Structure of Fast Beds
Effects of Circulation Rate on Voidage Profile
Pressure drop across the L-valve is
proportional to solid recirculation rate
higher solid recirculation rate
43
2.4 Hydrodynamic Structure of Fast Beds
Effect of Particle Size on Suspension Density Profile
- Fine particle - - > higher suspension density
- Higher suspension density - - > higher heat transfer
- Higher suspension density - - > lower bed temperature
44
2.4 Hydrodynamic Structure of Fast Beds
Core-Annulus Model
- the furnace may be spilt into two zones : core and
annulus
core
Core
- Velocity is above superficial velocity
annulus
- Solid move upward
Annulus
- Velocity is low to negative
- Solids move downward
45
2.4 Hydrodynamic Structure of Fast Beds
Core-Annulus Model
core
annulus
46
2.4 Hydrodynamic Structure of Fast Beds
Core Annulus Model
- the up-and-down movement solids in the core and
annulus sets up an internal circulation
- the uniform bed temperature is a direct result of internal
circulation
47
3. Combustion in CFB
3.1 Coal properties for CFB boiler
3.2 Stage of Combustion
3.3 Factor Affecting Combustion Efficiency
3.4 Combustion in CFB
3.5 Biomass Combustion
48
3.1 Coal properties for CFB Boiler
Properties
- coarse size coal shall be crushed by coal crusher
- sizing is an importance parameter for CFB boiler improper size might
result in combustion loss
- normal size shall be < 8 mm
49
3.2 Stage of Combustion
A particle of solid fuel is injected into an FB undergoes the
following sequence of events:
- Heating and drying
- Devolatilization and volatile combustion
- Swelling and primary fragmentation (for some types of coal)
- Combustion of char with secondary fragmentation and attrition
50
3.2 Stages of Combustion
Heating and Drying
- Combustible materials constitutes around 0.5-5.0% by
weight
of total solids in combustor
- Rate of heating 100 C/sec 1000 C/sec
- Heat transfer to a fuel particle (Halder 1989)
51
3.2 Stages of Combustion
Devolatilization and volatile combustion
- first steady release 500-600 C
- second release 800-1000C
- slowest species is CO (Keairns et al., 1984)
- 3 mm coal take 14 sec to devolatilze
at 850 C (Basu and Fraser, 1991)
52
3.2 Stages of Combustion
Char Combustion
2 step of char combustion
1. transportation of oxygen to carbon surface
2. Reaction of carbon with oxygen on the carbon surface
3 regimes of char combustion
- Regime I: mass transfer is higher than kinetic rate
- Regime II: mass transfer is comparable to kinetic rate
- Regime III: mass transfer is very slow compared to kinetic rate
53
3.2 Stage of Combustion
Communition Phenomena During Combustion
Volatile release in non-porous
particle cause the high
internal pressure result in
break a coal particle into
fragmentation
Attrition, Fine particles from
coarse particles through
mechanical contract like
abrasion with other particles
Char burn under regime I
which is mass transfer is
higher than kinetic trasfer.
The sudden collapse or other
type of second fragmentation
call percolative fragmentation
occurs
Volatile release cause the
particle swell
Char burn under regime I, II,
the pores increases in size
weak bridge connection of
carbon until it cant withstand
the hydrodynamic force. It will
fragment again call
secondary fragmentation
54
3.3 Factor Affecting Combustion Efficiency
Fuel Characteristics
the lower ratio of FC/VM result in higher combustion
efficiency (Makansi, 1990), (Yoshioka and Ikeda,1990),
(Oka, 2004) but the improper mixing could result in lower
combustion efficiency due to prompting escape of volatile
gas from furnace.
55
3.3 Factor Affecting Combustion Efficiency
Operating condition (Bed Temperature)
- higher combustion temperature --- > high combustion
Limit of Bed temp
efficiency
-Sulfur capture
-Bed melting
-Water tube failure
High combustion temperature result in high
oxidation reaction, then burn out time
decrease. So the combustion efficiency
increase.
56
3.3 Factor Affecting Combustion Efficiency
Fuel Characteristic (Particle size)
-The effect of this particle size is not clear
-Fine particle, low burn out time but the
probability to be dispersed from cyclone
the high
-Coarse size, need long time to burn out.
-Both increases and decreases are
possible when particle size decrease
57
3.3 Factor Affecting Combustion Efficiency
Operating condition (superficial velocity)
- high fluidizing velocity decrease combustion efficiency because
Increasing probability of small char particle be elutriated from
circulation loop
- low fluidizing velocity cause defluidization, hot spot and sintering
58
3.3 Factor Affecting Combustion Efficiency
Operating condition (excess air)
- combustion efficiency improve which excess air < 20%
Combustion loss
decrease
significantly when
excess air < 20%.
Excess air >20% less
significant improve
combustion efficiency.
59
3.3 Factor Affecting Combustion Efficiency
Operating Condition
The highest loss of combustion result from elutriation of char particle
from circulation loop. Especially, low reactive coal size smaller than 1
mm it can not achieve complete combustion efficiency with out fly
ash recirculation system.
However, the significant efficiency improve is in range 0.0-2.0 fly ash
recirculation ratio.
60
3.4 Combustion in CFB Boiler
Lower Zone Properties
- This zone is fluidized by primary air constituting about
40-80% of total air.
- This zone receives fresh coal from coal feeder and
unburned coal from cyclone though return valve
- Oxygen deficient zone, lined with refractory to protect
corrosion
- Denser than upper zone
61
3.4 Combustion in CFB Boiler
Upper Zone Properties
- Secondary is added at interface between lower and upper
zone
- Oxygen-rich zone
- Most of char combustion occurs
- Char particle could make many trips around the furnace
before they are finally entrained out through the top of
furnace
62
3.4 Combustion in CFB Boiler
Cyclone Zone Properties
- Normally, the combustion is small when compare to in
furnace
- Some boiler may experience the strong combustion in
this zone which can be observe by rising temperature in
the cyclone exit and loop seal
63
3.5 Biomass Combustion
Fuel Characteristics
- high volatile content (60-80%)
- high alkali content sintering, slagging, and fouling
- high chlorine content corrosion
64
3.5 Biomass Combustion
Agglomeration
SiO2 melts at 1450 C
Eutectic Mixture melts at 874 C
Sintering tendency of fuel is indicated by the following
(Hulkkonen et al., 2003)
65
3.5 Biomass Combustion
Options for Avoiding the Agglomeration Problem
- Use of additives
- china clay, dolomite, kaolin soil
- Preprocessing of fuels
- water leaching
- Use of alternative bed materials
- dolomite, magnesite, and alumina
- Reduction in bed temperature
66
3.5 Biomass Combustion
Agglomeration
67
3.5 Biomass Combustion
Fouling
- is sticky deposition of ash due to evaporation of alkali salt
- result in low heat transfer to tube
68
3.5 Biomass Combustion
Corrosion Potential in Biomass Firing
- hot corrosion
- chlorine reacts with alkali metal from low
temperature melting alkali chlorides
- reduce heat transfer and causing high temperature
corrosion
69
4. Heat Transfer in CFB
4.1 Gas to Particle Heat Transfer
4.2 Heat Transfer in CFB
70
4.1 Gas to Particle Heat Transfer
Mechanism of Heat Transfer
In a CFB boiler, fine solid particles
agglomerate and form clusters or
stand in a continuum of generally
up-flowing gas containing sparsely
dispersed solids. The continuum is
called the dispersed phase, while
the agglomerates are called the
cluster phase.
The heat transfer to furnace wall
occurs through conduction from
particle clusters, convection from
dispersed phase, and radiation
from both phase.
71
4.1 Heat Transfer in CFB Boiler
Effect of Suspension Density and particle size
Heat transfer coefficient is proportional to the square root of suspension density
72
4.1 Heat Transfer in CFB Boiler
Effect of Fluidization Velocity
No effect from fluidization velocity when leave the suspension density constant
73
4.1 Heat Transfer in CFB Boiler
Effect of Fluidization Velocity
74
4.1 Heat Transfer in CFB Boiler
Effect of Fluidization Velocity
75
4.1 Heat Transfer in CFB Boiler
Effect of Vertical Length of Heat Transfer Surface
76
4.1 Heat Transfer in CFB Boiler
Effect of Bed Temperature
77
4.1 Heat Transfer in CFB Boiler
Heat Flux on 300 MW CFB Boiler (Z. Man, et. al)
78
4.1 Heat Transfer in CFB Boiler
Heat transfer to the walls of commercial-size
Low suspension density low
heat transfer to the wall.
79
4.1 Heat Transfer in CFB Boiler
Circumferential Distribution of Heat Transfer Coefficient
80
5 Design of CFB Boiler
5.1 Design and Required Data
5.2 Combustion Calculation
5.3 Heat and Mass Balance
5.4 Furnace Design
5.5 Cyclone Separator
81
5.1 Design and Required Data
The design and required data normally will be specify by owner
or client. The basic design data and required data are;
Design Data :
- Fuel ultimate analysis
- Feed water quality
- Weather condition
- Feed water properties
Required Data :
- Main steam properties
- Flue gas emission
- Flue gas temperature
- Boiler efficiency
82
5.2 Combustion Calculation
Base on the design and required data the following data
can be calculated in this stage :
- Fuel flow rate
- Combustion air flow rate
- Fan capacity
- Fuel and ash handling capacity
- Sorbent flow rate
83
5.3 Heat and Mass Balance
Main steam
Heat input
Radiation
Heat output
Feed water
Blow down
Flue gas
Moisture in fuel
and sorbent
Unburned in fly ash
Fuel and
sorbent
Combustion air
Unburned in
bottom ash
Moisture in
combustion air
84
5.3 Heat and Mass Balance
Mass Balance
Mass input
Mass output
SolidSolid
Fluein
gas
Flue gas
Make up
bed material
Fuel and
sorbent
Moisture in fuel
and sorbent
fly ash
Fuel and
sorbent
Make up
bed material
bottom ash
bottom ash
fly ash
85
5.4 Furnace Design
1.
2.
3.
The furnace design include:
Furnace cross section
Furnace height
Furnace opening
1. Furnace cross section
Criteria
- moisture in fuel
- ash in fuel
- fluidization velocity
- SA penetration
- maintain fluidization in lower
zone at part load
86
5.4 Furnace Design
2. Furnace height
Criteria
- Heating surface
- Residual time for sulfur
capture
3. Furnace opening
Criteria
- Fuel feed ports
- Sorbent feed ports
- Bed drain ports
- Furnace exit section
87
5.5 Cyclone Separator
6.1 Theory
6.2 Critical size of particle
88
5.5 Cyclone Separator
The centrifugal force on the particle entering the cyclone
is
The drag force on the particle can be written as
Under steady state drag force = centrifugal force
89
5.5 Cyclone Separator
Vr can be considered as index of cyclone efficiency, from
above equation the cyclone efficiency will increase for :
- Higher entry velocity
- Large size of solid
- Higher density of particle
- Small radius of cyclone
- low value of viscosity of gas
90
5.5 Cyclone Separator
The particle with a diameter larger than theoretical cutsize of cyclone will be collected or trapped by cyclone
while the small size will be entrained or leave a cyclone
Actual operation, the cut-off size diameter will be defined
as d50 that mean 50% of the particle which have a
diameter more than d50 will be collected or captured.
91
6. Operation
92
Content
6.1 Before start
6.2 Grid pressure drop test
6.3 Cold Start
6.4 Normal Operation
6.5 Normal Shutdown
6.6 Hot Shutdown
6.7 Hot Restart
6.8 Malfunction and Emergency
93
6.1 Before Start
all maintenance work have been completely done
All function test have been checked
cooling water system is operating
compressed air system is operating
Make up water system
Deaerator system
Boiler feed water pump
Condensate system
Oil and gas system
Drain and vent valves
Air duct, flue gas duct system
94
6.1 Before Start
Blow down system
Sand feeding system
Lime stone feeding system
Solid fuel system
Ash drainage system
Control and safety interlock system
95
6.2 Grid Pressure Drop Test
For check blockage of grid
nozzle
Furnace set point = 0
Test at every PA. load
Compare to clean data or design
data
Shall not exceed 10% from
design data
Perform in cold condition
Pf= 0
Pb
Pw
FI
96
6.3 Cold Start
Fill boiler
-100 mm normal level
Start Fan
ID,HP,SA,PA
Boiler Interlock
Purge
300 S
Start up Burner
Low level cut off
Boiler Warm Up
Tb 150-200 C
Feed Bed Material
30-50 mbar, Tb 550-600 C
Feed Solid Fuel
Raise to MCR
97
Fill Boiler
-Close all water side drain valve
-Open all air vent valve at drum and
superheat
-Open start up vent valve 10-15%
-Slowly feed water to drum until level 1/3 of
sigh glass
98
Start Fan
1.Start ID.Fan
2.Start HP Blower
4.Start PA.Fan
3.Start SA.Fan
99
Boiler Interlock
Emergency stop in order
Furnace P. < Max (2/3)
Trip Solid Fuel
ID. Fan running
HP Blower start
Drum level > min (2/3)
Trip Soot Blower
Trip Oil
SA. Fan running
Trip Sand
PA. Fan running
Trip Bottom Ash
HP. Blower P. > min
Trip Lime Stone
PA. Flow to grid > min
Flue gas T after Furnace < max
100
Purge
To carry out combustible gases
To assure all fuel are isolated
from furnace
Before starting first burner for
cold start
If bed temp < 600 C or OEM
recommend and no burner in
service
Total air flow > 50%
300 sec for purging time
101
Purge
NFPA85: CFB Boiler purge logic
102
Start up burner
Help to heat up bed temp to allowable temperature for
feeding solid fuel
Will be stopped if bed temp > 850 C
Before starting, all interlock have to passed
Main interlock
Oil pressure > minimum
Control air pressure > minimum
Atomizing air pressure > minimum
103
Start up burner
NFPA85 - Typical burner safety for CFB boiler
104
Drum and DA low level cut-off
Test for safety
During burner are operating
Open drain until low level
Signal feeding are not allow
Steam drum low level = chance
to overheating of water tube
DA low level = danger for BFWP
105
Boiler warm up
Gradually heating the boiler to reduce the effect of
thermal stress on pressure part, refractory and drum swell
Increase bed temp 60-80 C/hr by adjusting SUB
Control flue gas temperature <470 C until steam flow >
10% MCR
Close vent valves at drum and SH when pressure > 2 bar
Continue to increase firing rate according to
recommended start up curve
Operate desuperheater when steam temperature are with
in 30 C of design point
Slowly close start up and drain valve while maintain steam
flow > 10% MCR
106
Feed bed material
Bed material should be sand which size is according to
recommended size
Start feed sand when bed temp >150 C
Do not exceed firing rate >30% if bed pressure <20 mbar
otherwise overheating may occur for refractory and nozzle
Continue feed bed material unit it reach 30 mbar
107
Feed solid fuel
Must have enough bed material
Bed temperature > 600 C or manufacturer
recommendation or refer to NFPA85 Appendix H
Pulse feed every 90 s
Placing lime stone feeding, ash removal system
simultaneously
Slowly decrease SUB firing rate while increasing solid fuel
feed rate
Stop SUB one by one, observe bed temperature increasing
Turn to auto mode control
108
Rise to MCR
Continue rise pressure and temperature according to
recommended curve until reach design point
Drain bottom ash when bed pressure >45-55 mbar
Slowly close start up valve
Monitor concerning parameters
109
6.4 Normal Operation
Changing Boiler load (manual)
Increasing
- manual increase air flow
- manual increase fuel flow
- monitor excess oxygen
- monitor steam pressure
Decreasing
- manual decrease air flow
- manual decrease fuel flow
- monitor excess oxygen
- monitor steam pressure
110
6.4 Normal Operation
Furnace and Emission Monitoring
Furnace and emssion
- monitor fluidization in hot
loop
- monitor gas side pressure drop
- monitor bed pressure
- monitor bed temperature
-monitor wind box pressure
- monitor SOx, Nox, CO
111
6.4 Normal Operation
Bottom ash and Soot Blower
Bottom ash drain
- automatic or manual draining
of bottom ash shall be judged by
commissioning engineer for the
design fuel.
- when fuel is deviated from the
design, operator can be judge by
themselves that draining need
to perform or not.
- bed pressure is the main
parameter to start draining
Soot blower
- initiate soot blower to clean
the heat exchanger surface in
convective part
- frequent of soot blowing
depend on the degradation of
heat transfer coefficient.
- normally 10 C higher than
normal value of exhaust
temperature
112
6.4 Normal Operation
Boiler Walk Down
- boiler expansion joint
- Boiler steam drum
- Boiler penthouse
- Safety valve
- Boiler lagging
- Spring hanger
- Valve and piping
- Damper position
- Loop seal
- Bottom screw
- Combustion chamber
- Fuel conveyor
113
6.4 Normal Operation
Sizing Quality
- crushed coal, bed material, lime stone and bottom ash
sizing shall be periodically checked by the operator
- sieve sizing shall be performed regularly to make sure
that their sizing is in range of recommendation
114
6.5 Normal Shut Down
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
Reduce boiler load to 50% MCR
Place O2 control in manual mode
Monitor bed temperature
Continue reducing load according to shut down curve
Maintain SH steam >20 C of saturation temperature
Start burner when bed temperature <750 C
Empty solid fuel and lime stone with bed material >650 C
Decrease SUB firing rate according to suggestion curve
Maintain drum level in manual mode
Stop solid fuel, line stone, sand feeding system
115
6.5 Normal Shut Down
11. Maintain drum level near upper limit
12. Continue fluidizing the bed to cool down the system at 2
C/min by reducing SUB firing rate
13. Stop SUB at bed temperature 350 C
14. Continue fluidizing until bed temperature reach 300 C
15. Slowly close inlet damper of PAF and SAF so that IDF
can control furnace pressure in automatic mode
16. Stop all fan after damper completely closed
17. Stop HP blower 30 S after IDF stopped
18. Stop chemical feeding system when BFWP stop
19. Continue operate ash removal system until it empty
116
6.5 Normal Shut Down
20. Open vent valve at drum and SH when drum pressure
reach 1.5-2 bar
21. Open manhole around furnace when bed temp < 300 C
117
6.6 Emergency Shut down
Boiler can be held in hot stand by condition about 8 hrs
Hot condition is bed temp >650 C otherwise follow cold
star up procedure
Boiler load should be brought to minimum
Stop fuel feeding
Wait O2 increase 2 time of normal operation
Stop air to combustion chamber to minimize heat loss
118
6.7 Hot restart
Purge boiler if bed temperature < 600 C
Start SUBs if bed temperature > 500 C
Monitor bed temperature rise
If bed temperature does not rise after pulse feeding solid
fuel. stop feeding and start purge
119
6.8 Malfunction and Emergency
Bed pressure
Bed temperature
Circulation
Tube leak
Drum level
120
Bed Pressure
Bed pressure is an one of importance
parameter that effect on boiler efficiency
and reliability.
Measured above grid nozzle about 20 cm.
Pf= 0
Pb
Pw
FI
121
Bed Pressure
Effect of low bed pressure
- poor heat transfer
- boiler responds
- high bed temperature
- damage of air nozzle and refractory
Effect of high bed pressure
- increase heat transfer
- more efficient sulfur capture
- more power consumption of fan
122
Bed Pressure
Cause of low bed pressure
- loss of bed material
- too fine of bed materials
- high bed temperature
Cause of high bed pressure
- agglomeration
- too coarse of bed material
123
Bed Temperature
Measured above grid nozzle about
20 cm
Measured around the furnace cross
section
It is the significant parameter to
operate CFB boiler
124
Bed temperature
Effect of high bed temperature
- ineffective sulfur capture
- chance of ash melting
- chance of agglomeration
- chance to damage of air nozzle
125
Bed temperature
Cause of high bed temperature
- low bed pressure
- too coarse bed material
- too coarse solid fuel
- improper drain bed material
- low volatile fuel
- improper air flow adjustment
126
Circulation
Circulation is particular
phenomena of CFB boiler.
Bed material and fuel are
collected at cyclone separator
Return to the furnace via loop
seal
HP blower supply HP air to
fluidize collected materials to
return to furnace
127
Circulation
Effect of malfunction circulation
- No circulation result in forced shut down
- high rate of circulation
- high circulation rate need more power of blower
- low rate of circulation
128
Circulation
Cause of malfunction circulation
- insufficiency air flow to loop seal nozzle
- insufficient air pressure to loop seal
- plugging of HP blower inlet filter
- blocking or plugging of loop seal nozzle
-
129
Tube leak
Water tube leak
- furnace pressure rise
- bed temperature reduce
- stop fuel feeding
- open start up valve
- dont left low level of drum
- continue feed water until flue gas temp < 400 C
- continue combustion until complete
- small leak follow normal shut down
130
Drum level
Sudden loss of drum level
- when the cause is known and immediately correctable
before level reach minimum allowable. Reestablish steam
drum level to its normal value and continue boiler
operation
-if the cause is not known. Start immediate shut down
according to emergency shut down procedure
131
Drum level
Gradual loss of drum level
- boiler load shall be reduced to low load
- find out and correct the problem as soon as possible
- if can not maintain level and correct the problem, boiler
must be taken out of service and normal shut down
procedure shall be applied.
132
7. Maintenance
133
Before maintenance work
Make sure that all staff are understand about safety
instruction for doing CFB boiler maintenance work
Make sure that all maintenance and safety equipments
shall be a first class
134
Overview Boiler Maintenance
Refractory and tube are the main
area that need to be checked
135
6.1 Windbox Inspection
Inspect sand inside windbox
after shutdown
Drain pipe
Crack
Air gun pipe
Refractory
Crack, wear and fall down inspect
Drain pipe
by hammer(knocking) if burner is
under bed design
136
6.2 Furnace Inspection
Nozzle :
Wear
Fall-off
Refractory
Crack, wear and fall down inspect
by hammer knocking if burner is
under bed design
Refractory
Feed fuel port
Wear
Crack
Burner
Burner
Nozzle
Feed Fuel
137
6.2 Furnace Inspection
Limestone port
Crack
Deform
Refractory damage at connection
between port and refractory
Secondary & Recirculation Air
port
Crack
Deform
Refractory damage at connection
between port and refractory
Bed Temperature
Check thermo well deformation
Check wear
Secondary & Recirculation Air port
138
6.3 Kick-Out Inspection
Refractory
Wear
Crack and fall down by
hammer(knocking)
Water tube
Wear
Thickness
139
6.3 Kick-Out Inspection
Water Tube:
Thickness measuring
Erosion at corner
CO Corrosion due to incomplete
combustion at fuel feed side.
Defect from weld build up
Water tube sampling for internal
check every 3 years
Inside water tube inspect by borescope
welded build up excessive metal because use welding rod
size bigger than tube thickness
140
6.4 Superheat I (Wingwall)
Water Tube:
Thickness measuring
Erosion at tube connection
Refractory
Crack and fall down by
hammer(knocking)
Guard
Crack
fall down
141
6.4 Superheat I (Omega Tube)
Offset Water Tube:
Thickness measuring
Erosion at offset tube
Omega Guard
SH tube
Thickness measuring
Omega Guard
Crack
fall down
Offset Water
Tube
142
6.5 Roof
Water Tube:
Thickness measuring
Erosion
Refractory
Crack, wear and fall down by
hammer(knocking)
143
6.6 Inlet Separator
Water Tube:
Thickness measuring near opening
have more erosion than another
tube because of high velocity of flue
gas
Refractory
Crack, wear and fall down by
hammer(knocking)
144
6.7 Steam Drum
Surface :
Surface were black by magnetite
Deposits
Deposits at bottom drum need to
check chemical analysis
Cyclone Separator
Loose
Demister
Blowdown hole
Plugging
U-Clamp
Loose
Deposits at bottom drum
145
6.8 Separator
Central Pipe:
Deformation
Crack
Refractory
Wear at impact zone due to high
impact velocity
Crack and fall down by
hammer(knocking)
146
6.9 Outlet Separator
Water Tube
Tube Thickness
Erosion
Outlet Central Pipe:
Support or Hook
Refractory
Crack and fall down by
hammer(knocking)
147
6.10 Screen Tube
Water Tube
Thickness measuring upper part of
screen tube at corner have more
erosion than another area because
of high velocity of flue gas
Guard
Loose
Refractory
Crack and fall down by
hammer(knocking)
upper part of screen tube at corner have more erosion
Weld build up or install guard to prevent tube erosion
148
6.11 Superheat Tube
Tube
Thickness measuring
High erosion between SH tube and
wall
Steam erosion due to improper soot
blower
Guard
Fall down
Crack
149
6.12 Economizer
Water Tube
Thickness measuring
High erosion between economizer
tube and wall
Steam erosion due to improper soot
blower
Guard
Fall down
Crack
Guard
Install guard to
prevent tube erosion
150
6.13 Air Heater
Tube
Cold end corrosion due to high
concentrate SO3 in flue gas
Steam erosion due to improper soot
blower
Inlet air heater
Cold end corrosion due to SO3 in fluegas
151
8. Basic Boiler Safety
152
Warning
Operating or maintenance procedure which, if
not as described could result in injured death
or damage of equipment
153
General safety precaution
Electrical power shall be turned off before performing
installation or maintenance work. Lock out, tag out shall
be indicated
All personal safety equipment shall be suit for each work
Never direct air water stream into accumulation bed
material or fly ash. This will become breathing hazard
Always provide safe access to all equipment ( plant from,
ladders, stair way, hand rail
Post appropriate caution, warning or danger sign and
barrier for alerting non-working person
Only qualify and authorized person should service
equipment or maintenance work
154
General safety precaution
Do not by-pass any boiler interlocks
Use an filtering dust mask when entering dust zone
Do not disconnect hoist unless you have made sure that
the source is isolated
155
Equipment entry
Never entry confine space until is has been cooled, purged
and properly vented
When entering confine space such as separator, loop seal
furnace be prepared for falling material
Always lock the damper, gate or door before passing
through them
Never step on accumulation of bottom ash or fly ash. Its
underneath still hot
Never use toxic fluid in confine space
Use only appropriate lifting equipment when lift or move
equipment
156
Equipment entry
Stand by personnel shall be positioned outside a confine
space to help inside person incase of emergency
Be carefully aware the chance of falling down when enter
cyclone inlet or outlet.
Don not wear contact lens with out protective eye near
boiler, fuel handing, ash handing system. Airborne particle
can cause eye damage
Don not enter loop seal with out installing of cover over
loop seal downcomer to prevent falling material from
cyclone
157
Operating precautions
CFB boiler process
Use planks on top of bed materials after boiler is cooled
down. This will prevent the chance of nozzle plugging
Do not open any water valve when boiler is in service
Do not operate boiler with out O2 analyzer
Do not use downcomer blown donw when pressure > 7
bar otherwise loss of circulation may occure
Do not operate CFB boiler without bed material
When PA is started. PA flow to grid must be increase to
above minimum limit to fully fluidized bed maerial
Do not operate CFB boiler with bed pressure > 80mbar.
This might be grid nozzle plugging
158
Operating precautions
on cold start up the rate of chance in saturated steam shall
not exceed 2 C/min
On cold start up the change of flue gas temp at cyclone
inlet shall not exceed 70 C/min
Do not add feed water to empty steam drum with
different temperature between drum metal and feed water
greater than 50 C
All fan must be operated when add bed material
159
Operating precautions
Refractory
When entering cyclone be aware a chance of falling down
Refractory retain heat for long period. Be prepared for hot
surface when enter this area
An excessive thermal cycle will reduce the life cycle of
refractory
After refractory repair, air cure need to apply about 24 hr
or depend on manufacturer before heating cure
Heating cure shall be done carefully otherwise refractory
life will be reduced
160
Operating precautions
Solid Fuel
Chemical analysis of all solid fuel shall be determined for
first time and compared with OEM standard
Sizing is important
Burp feeding shall be performed during starting feeding
solid fuel instead of continuous feeding
161
9. Basic CFB Boiler Control
162
Basic control
Furnace control
Main pressure control
Main steam pressure control
Drum level control
Feed tank control
Solid fuel control
Primary air control
Secondary air control
Oxygen control
163
Basic control
Simple feedback control
PR IM ARY VA RIA B LE
XT
PR O CE S S
SE T P OIN T
f(x)
M A NIP U LAT E D VAR IA BLE
164
Basic control
Simple feed forward plus feedback control
P R IM A R Y VA R IA B L E
XT
SECO NDARY
VA R IA B L E
YT
K
P ROCE SS
S E T P O IN T
A
f(x)
M A N IP U L AT E D VA R IA B LE
165
Basic control
Simple cascade control
PR IM ARY VA RIABLE
XT
SEC O N DA RY
VAR IA BLE
ZT
K
PR O C ESS
K
SE T PO IN T
A
f(x)
M AN IPU LATED VAR IABLE
166
Basic control
Control Mode of PID
PID
SP
Percent
0-100 %
Eng. Unit
0-15 m3/h
Electrical signal
4-20 mA
-MAN (Manual)
-AUT (Automatic)
-CAS (Cascade)
PV
0-15 m3/h
CO
0-100%
0-100% (closed open)
4-20 mA
Signal to open
167
Feed water control
PID
PID
Make up water
PT
Heating steam
LT
Pressure
Level
-Manual mode 0-100% heating steam valve
position
-Manual mode 0-100% make up water valve
-Auto mode, specify pressure set point
-Temperature compensation
-Auto mode, specify level set point
-Temperature compensation
-Protection, high level over flow
168
Drum Level control
Main steam Pressure
Manual mode, 0-100%
control valve
Auto mode, specify drum
level. Automatically adjust
valve
Main steam flow
A, SP
Control valve
M, 0-100%
Protection
-lower limit
DP feed
water pump
-2/3 principle
- 10 s delay
-Close steam valve for low level
169
Main steam pressure control
PV
SP
FF
CO
170
Main steam
Pressure
Combustion
Calculation
Total air SP
Total Fuel SP
PA SP
SA SP
Fuel1 SP
Fuel2 SP
Fuel3 SP
PA.Fan
SA.Fan
Conveyor1
Conveyor2
Conveyor3
171
Solid Fuel Control
Cascade
PID
Auto
WT
Manual
M
Manual : speed of coal conveyor is
specified by operator
Auto : operator specify fuel flow load
Cascade: fuel flow set point calculated by
main steam pressure control
172
Primary air control
Manual: position of damper is
specified
Auto
Cascade
Auto: desired air flow is specified by
operator
PID
Cascade: set point is calculated from
master combustion
Flow (interlock) > minimum
Manual
PV
FT
PA wind box P > minimum
PA running
173
Secondary air control
FT
PID
Auto
Cascade
Upper SA
PID
Auto
Cascade
Manual
Manual
PV
FT
M
PT
FT
Manual
Lower SA
174
HP Blower Control
Pressure is controlled by control valve
Control valve is connected to primary air
It will release the air to primary air duct if pressure higher
than set point
If operating unit stop due to disturbance or pressure fall
down, stand by unit shall be automatically started
Pressure should be higher than 300 mbar, boiler interlock
Pressure < 350 mbar parallel operation start
175
Furnace Pressure control
Auto
Furnace
pressure
PID
Auto
PID
PT
2/3 furnace P < max (35 mbar)
Manual
Manual
176
Lime stone control
Lime stone can be control by
lime stone/ fuel flow ratio
SO2 feed back control
Manual feed rate
177
Fuel oil control
Pressure control
Auto
Pressure
control valve
Manual
Flow control
valve
178
Referenced
Prabir Basu , Combustion and gasification in fluidized bed, 2006
Fluidized bed combustion, Simeon N. Oka, 2004
Nan Zh., et al, 3D CFD simulation of hydrodynamics of a 150 MWe circulating fluidized bed
boiler, Chemical Engineering Journal, 162, 2010, 821-828
Zhang M., et al, Heat Flux profile of the furnace wall of 300 MWe CFB Boiler, powder
technology, 203, 2010, 548-554
Foster Wheeler, TKIC refresh training, 2008
M. Koksal and F. Humdullahper , Gas Mixing in circulating fluidized beds with secondary
air injection, Chemical engineering research and design, 82 (8A), 2004, 979-992
179