ABB Controller IM - C501 - 10.manual (SLPC) PDF
ABB Controller IM - C501 - 10.manual (SLPC) PDF
IM/C501_10
C501
ABB
The Company
RE
GI
ED
EN ISO 9001:2000
STER
The UKAS Calibration Laboratory No. 0255 is just one of the ten flow
calibration plants operated by the Company, and is indicative of our
dedication to quality and accuracy.
Electrical Safety
This equipment complies with the requirements of CEI/IEC 61010-1:2001-2 'Safety Requirements for Electrical
Equipment for Measurement, Control and Laboratory Use'. If the equipment is used in a manner NOT specified by
the Company, the protection provided by the equipment may be impaired.
Symbols
One or more of the following symbols may appear on the equipment labelling:
Warning Refer to the manual for instructions
Information in this manual is intended only to assist our customers in the efficient operation of our equipment. Use
of this manual for any other purpose is specifically prohibited and its contents are not to be reproduced in full or part
without prior approval of the Technical Communications Department.
GETTING STARTED
The COMMANDER 500 can be configured and made ready for operation in three easy
steps. This 'Getting Started' guide provides an overview of these steps and, where
necessary, refers to the relevant section of the manual.
Step 1 Decide on the Application Template and the
Output Configuration required
Step 2 Connect the process inputs and outputs
Step 3 Power up the instrument, set the template number and the
output configuration details
Choose the Control Output Type required from the list of options in Table B on the
rear foldout.
Continued
GETTING STARTED
Step 3 Setting the Parameters (Fig. GS.1)
A
Set the appropriate application template, output type and control action. Use the
key to advance between frames and upper
and
keys to adjust the
default values see Section 4.2 for further information.
Note. When the output type has been selected, the available inputs and outputs
default to the settings shown in Table B on the rear fold-out.
C
If you are not using 4 to 20mA inputs, then select Level 7 using the upper
and
keys and set up Analog Inputs I/P1 to I/P3 to suit your process see Section 4.3.
Press
A
50.1
50.5
LEV.6
APPL
LEV.7
INPt
LEV2
tUNE
F
50.1
50.5
B
50
t.APP
01.SL
O.tYP
ANLG
50.1
50.5
C.ACt
rEV
50
50
FrEJ
50
Fig. GS.1 Setting the Parameters
OVERVIEW
This manual is divided into 5 sections which contain all the information needed to install, configure,
commission and operate the COMMANDER 501 Process Controller. Each section is identified
clearly by a symbol as shown in Fig. 1.
Displays and Controls
Displays and Function Keys
LED Indication
Error Messages
Installation
Siting
Mounting
Electrical Connections
Getting
Started
Fig. 2 Foldouts
Shunt Resistors
2 x 100
(+1 optional)
Process Labels
x3
Panel Clamps
x2
CJ Sensor
x1
(+1 optional)
Fig. 3 Accessories
CONTENTS
Section
Page
OVERVIEW .................................................... 1
1
SET
3.1
3.2
3.3
3.4
3.5
UP MODE ...................................... 27
Introduction .................................... 27
Level 2 Tune ............................... 28
Level 3 Set Points ...................... 32
Level 4 Alarm Trip Points ........... 34
Level 5 Valve Setup .................... 35
Section
5
Page
INSTALLATION ..................................... 71
5.1 Mechanical Installation .................. 71
5.2 Electrical Installation ..................... 76
5.3 Relays ........................................... 79
5.4 Digital Output ................................ 79
5.5 Control or Retransmission
Analog Output ................................ 79
5.6 Motorized Valve Connections ....... 80
5.7 Input Connections ......................... 80
5.8 Output Connections ...................... 81
5.9 Power Supply Connections ........... 81
SPECIFICATION ......................................... 82
APPENDIX A CONTROL TEMPLATES .. 84
A1 Single Loop Controller
(Templates 1 and 2) ....................... 85
A2 Auto/Manual Station and Analog
Backup Station .............................. 86
A3 Indicator/Manual Loader Station
(Templates 7 and 8) ....................... 89
B4 Six Logic Equations ....................... 90
APPENDIX B COMMANDER
CONFIGURATION EDITOR ........................ 90
B1 Introduction .................................... 90
B2 Analog Input Customization .......... 90
B3 Four Programmable Maths Blocks 90
B5 Process Alarm Customization ....... 90
B6 Two Real Time Alarms ................... 90
B7 Two Delay Timers .......................... 90
B8 Two Custom Linearizers ................ 91
B9 Template Customization ................ 91
B10 Connecting the
COMMANDER PC Configurator ... 91
FRAMES INDEX ......................................... 92
INDEX ........................................................ 95
1.1 Introduction
The COMMANDER 500 front panel displays, function keys and LED indicators are shown in Fig. 1.1.
COMMANDER 500
100
58.8
62.4
80
60
40
LR
15.0
20
OP1
OP2
Function Keys
Raise
Lower
Alarm
Acknowledge
Local/Remote
Up
Parameter Advance
LR
Auto/manual
Down
bIAS
50.0
51.0 +
LEV1
OPEr
49.0
Use to change/set a parameter value
LEV2
tUnE
and
700
710 +
2.00
LEV2
tUnE
2.01
CYCl
5.0
690
Use to adjust the output value
Frame 1
(top of level)
Frame 2
and
LEV2
tUnE
Frame 1
(top of level)
CYCl
5.0
Frame 2
LEVx
1001
1002
1003
or
Note. This key also stores any changes made in the previous frame
D Auto/Manual Key
Auto
Manual
450.2
500.0
450.2
500.0
70
70
M
Use to select Auto or Manual control mode
Process Variable
Control Set Point
Control Output (%)
(On continuously)
(Off)
Any active,
unacknowledged alarms
No active
alarms present
1.HP1
200.3
1HP1
2003
450.2
500.0
70
450.2
500.0
70
ACt
or
ACK
CLr
LAt
2.xxx
200.3
ACK
or
ACt
LAt
Unacknowledged
alarms only
Note. If no alarms have been enabled in the Set Up level, pressing the
key has no effect.
Pressing
again acknowledges the displayed alarm.
Lower display changes to reflect new status.
450.2
500.0
L
450.2
400.0
LR
70
LR
450.2
400.0
R
Process variable and local set point displayed on red and green displays.
symbol flash to
450.2
350.0
L
70
LR
450.2
400.0
LR
450.2
475.0
LR
450.2
475.0
LR
LEVA
CntL
LEV6
APPL
450.2
350.0
LEV1
OPEr
70
450.2
350.0
70
COdE
0
Press and hold to move from the Operator Level to
the Security Code Frame and then to other levels:
Tune Level See Section 2.13.3
Set Up Level See Fig. 3.1
Configuration Level See Fig. 4.1
Flashing
450.2
350.0
OFF
ON
One or more
All active alarms
alarms active and acknowledged
unacknowledged
R
No alarms active
Remote or
Cascade set
point in use
A Upper Display
450.2
350.0
Flashing
M
150
Autotune in
progress
OP1
OFF
Manual control
selected
OP1
Output 1 (heat)
value displayed
OP2
Output 2 (cool)
value displayed
Valve opening
150
M
ON
Valve stopped
Valve closing
OP2
B Lower Display
A
b
C
d
E
F
G
H
I
J
K
L
M
N
O
P
I
J
K
L
M
N or n
O
P
R
S
T
U
V
Y
r
S
t
U
V
Y
Auto control
selected
CAL
Err
Calibration Error
Turn mains power off and on again
(if the error persists contact the
Customer Support Organization).
Press the
key
Err
NVx
Press the
key
A-d
Err
A to D Converter Fault
The analog to digital converter is not
communicating correctly.
9999
t.Err
1
Auto-tune Error
The number displayed indicates the
type of error present see Table 2.1
on page 30.
Press the
CJ.F
1
rSP.F
9999
Valve Sticking
Motorized valve not moving at the
speed expected. Valve may be
sticking.
Display
70
70
70
70
70
70
70
or
rAt.F
9999
StK
999
key
Description
Abbreviation
Description
Process Variable
di1
Digital Input 1
LSPt
di2
Digital Input 2
LSP1
di3
Digital Input 3
LSP2
di4
Digital Input 4
LSP3
ao1
Analog Output 1
LSP4
ao2
Analog Output 2
CSPt
do1
Digital Output 1
RSPt
do2
Digital Output 2
PID O/P
OP1
OP2
I/P1
Analog Input 1
I/P2
Analog Input 2
I/P3
Analog Input 3
10
2
2.1
OPERATOR LEVEL
Introduction
The Operator level (Level 1) is the normal day-to-day mode of the COMMANDER 500. This section
describes the operator facilities available on each frame depending on the control template and
output type selected.
The template types detailed in this section are:
Single loop controller
Auto/Manual station
Analog backup station
Indicator/manual loader station
Note. Only the frames relevant to the selected template are displayed see Section 4.
In addition, frames used to view the Control Efficiency Monitor and operate motorized valve and heat/
cool output types are also described.
C501
01.SL
Model C501
2001
01
Software series
Software version
11
2.2
OPERATOR LEVEL
The single loop controller is a basic feedback control system using three-term PID or on/off control
with either a local set point (template 1) or remote set point (template 2).
L
R
RSPt
Manual Output
I/P2
Control
Output
CSPt
Process Variable Input
I/P1
PV
PID
Control Loop
1 Template 2 Only
12
PID O/P
OP1
2.2
OPERATOR LEVEL
Set Point
Process
Variable
450.2
500.0
Process Variable
1
Control Output
[0 to 100% (digital/relay outputs),
10 to 110% (analog outputs)]
Adjustable in manual mode only. With on/off control
selected, 0% = control output off, 100% = control
output on. In manual mode, intermediate values can
be selected. These use time proportioning with a
60s cycle time, e.g. 25% = 15s on, 45s off.
70
OP1
Set Point
Process
Variable
rAtO
1.000
[0.001 to 9.999]
Remote set point value =
(ratio x remote set point input) + bias
70
OP1
Set Point
Process
Variable
bIAS
1.000
70
OP1
1 With the Ramping Set Point function enabled (see Section 3.3, Set Points/ Ramp Rate), the
bargraph shows the actual (ramping) set point value and the digital display shows the target set point
value.
2 Only displayed if template 2 selected and Ratio Display is enabled see Section 4.2, Basic
Configuration and Section 4.7, Operator Configuration.
3 Only displayed if template 2 selected and Bias Display is enabled see Section 4.2, Basic
Configuration and Section 4.7, Operator Configuration.
13
2.3
OPERATOR LEVEL
Manual Output
Analog Output
ao1
Master Output
I/P2
Low Signal Select
(Alarm A1)
Digital Select
di1
Auto / Manual
Select
1 Template 3 Only
2 Template 4 Only
14
2.3
OPERATOR LEVEL
Master
output
Auto Mode
55.0
50. 0
Process Variable
Master Output (I/P2)
Process
Variable
70
or
or
2 Low Master
Output Value
or
3 Digital Input
Active
Master
output
Process
Variable
2 Restored
Master Output
or
3 Digital Input
Inactive
55. 5
50. 0
50
Manual Mode
2.4
OPERATOR LEVEL
Manual Output
Analog Output
LSPt
Process Variable
PID
Control Loop
ao1
PV
I/P1
Master Output
I/P2
Digital Select
1
2
di1
L
R
1 Template 5 Only
2 Template 6 Only
16
Local/
Remote
Select
2.4
OPERATOR LEVEL
Set Point
Remote Mode
55.0
50. 0
Process
Variable
Process Variable
Set Point
['SPLO' to 'SPHI' see Section 4.5]
70
OP1
or
or
1 Low Master
1 Restored
Output Value
or
2 Digital Input
Active
Master Output
or
2 Digital Input
Inactive
Set Point
Process
Variable
55. 5
50. 0
50
OP1
Local Mode
2.5
OPERATOR LEVEL
One or two process variables can be displayed on the digital and bargraph displays. If the control
output is assigned to an analog output the lower display indicates its value which can be adjusted by
the user.
Process
Variable
(PV2)
Process
Variable
(PV1)
55.0
50. 0
50
Output Value
[10 to 110%]
OP1
OPERATOR LEVEL
100%
OP2 (cool)
OP1 (heat)
0%
Y2.St
Y1.St
PID O/P
100%
450.2
500.0
50
OP1
Heat Output
[0 to 100% (0 to 110% in manual mode with analog
outputs)]
Adjustable in manual mode only.
50
OP2
Cool Output
[100 to 0% (110 to 0% in manual mode with
analog outputs)]
Adjustable in manual mode only.
19
2.6.2
OPERATOR LEVEL
It is not possible to view or adjust the heat/cool outputs directly. The PID output (0 to 100%), used to
calculate the heat (OP1) and cool (OP2) outputs, is displayed and may be adjusted in manual mode.
The OP1 and OP2 l.e.d.s indicate which output is changing.
100%
100%
OP2
(cool)
OP1
(heat)
0%
0%
Y2.St
PID O/P
Y1.St
450.2
500.0
[0 to 100% of travel]
75
Valve opening
Valve stopped
Valve closing
2.7.2
StP
Valve opening
Valve stopped
Valve closing
20
OPN
StP
CLS
Valve opening
Valve stopped
Valve closing
2.8
OPERATOR LEVEL
Auto-tune
Note. Auto-tune is not available for Auto/Manual Station, Indicator or Ratio Station templates, or
when boundless or heat/cool control types are selected.
Information.
Auto-tune optimizes process control by manipulating the COMMANDER 500 output and then
monitoring the process response.
At the end of an auto-tune, the control parameters are updated automatically.
Before starting auto-tune, the process variable must be stable.
The COMMANDER 500 monitors the noise level of the process variable for 30 seconds and if
it is greater than 2% of the engineering range the auto-tune is aborted.
The COMMANDER 500 selects either 'start-up' or 'at set point' tuning automatically, depending
upon the level of the process variable relative to the control set point.
2.8.1
Start-up Auto-tune
If the process variable is more than 10% from the set point, 'start-up' tuning is carried out.
'Start-up' tuning steps the output to drive the process towards the set point. The process
response to this step change is monitored and PID parameters are calculated.
The output step applied = % deviation from the set point x 1.5.
If no errors exist, the COMMANDER 500 enters auto mode and begins to control the process
using the new PID parameters.
If an error occurs during the auto-tune, the COMMANDER 500 reverts to manual mode with the
control output set to the default output value. An error message is displayed in the operator
level see Table 2.1.
PV
PV
1/4 wave
damping
SPT
SPT
>10% span
Auto-tune complete
+2%
2%
t
t
B Process response during auto-tune
Error
Description
Error
Description
10
11
2.8.2
OPERATOR LEVEL
If the process variable is within 10% of the set point, 'at set point' tuning is carried out.
'At set point' tuning manipulates the control output to produce a controlled oscillation of the
process.
A step change of 10% of the starting output value is applied initially. This is adjusted to give an
amplitude of oscillation 3 times the noise level.
Once the amplitude and period of oscillation are consistent (minimum 2 cycles, maximum 4
cycles) PID parameters are calculated.
If no errors exist the controller enters auto mode and begins to control the process using the new
PID parameters.
If an error occurs during the auto-tune, the controller reverts to manual mode with the control
output set to the default output value. An error message is displayed in the operator level
see Table 2.1.
PV
PV
+2%
2%
12 hours max.
SPT
SPT
Controlling to
Set Point
< 10 span
Auto-tune
complete
Note. The time taken to complete auto-tune depends upon the system response time.
Note. Time Proportioning the cycle time must be set prior to running an auto-tune. The cycle
time is not changed by the auto-tune.
22
2.8.3
OPERATOR LEVEL
Auto-tune
1..xx
1.xx
1.xx
xxxx
xxxx
COdE
1
AtNE
OFF
key
Auto-tune Enable
Select the type of auto-tune required.
Single Loop Templates
OFF Off
A
Type A
b
Type B
Auto-tune is started automatically when the
pressed.
key is
xxxx
xxxx
PV
x1
PV
x2
Set Point
x2
x1
Set Point
1
4
2.9
OPERATOR LEVEL
The Control Efficiency Monitor can be used either to compare the relative performance with different
tuning parameters, or when fine tuning the PID settings, to give optimum control.
When the set point is changed, auto mode is selected or following a power failure, input failure or a
large load disturbance, the control monitor performs a series of measurements to indicate the
effectiveness of the current control parameters.
General guidelines are shown in Table 2.2.
Parameter
Ideal
Setting
Actual
Setting
Rate of
Approach
Fast
Too slow
Overshoot
Small
Too large
Decay Ratio
Small
Too large
(Oscillatory)
Settling Time
Short
Too long
Error Integral
Small
Too large
Action
Effect on Response
24
2.9
OPERATOR LEVEL
tperiod
x2
PV
+2%
95%
y2
Set Point
2%
y1
5%
tapproach
tsettle
Start of
Calculation
2.9.1
Manual Tuning
The Control Efficiency Monitor may be used for manually tuning the PID parameters. The following
method describes how to tune the controller for 1/4 wave damping:
a) Set the integral and derivative action times to OFF.
b) Set the proportional band (PB) to a low setting.
c) Apply a small set point change.
d) Use the Control Efficiency Monitor to note the decay ratio.
e) If the decay ratio > 0.25, increase the Proportional Band until decay ratio = 0.25
If the decay ratio < 0.25, decrease the Proportional Band until decay ratio = 0.25
f)
Leave the proportional band at the setting which gives 0.25 decay ratio and, using the Control
Efficiency Monitor, note the period between peaks.
25
2.9.2
OPERATOR LEVEL
70
and
Note.
If the front panel keys are not operated for 60 seconds whilst any
Control Efficiency Monitor frame is being displayed, the instrument
reverts to the first operating frame.
rAtE
10.1
OVEr
10
Overshoot
The maximum error, expressed as a percentage of the set point.
Overshoot =
rAtO
0.25
Y1
tapproach
X1
x100
Set Point
Decay Ratio
The ratio of the amplitude of the first and second overshoots.
Ratio =
X2
X1
Prd
35
Period
The time (in seconds) between the first two peaks (tperiod).
SEtL
0.3
Settling Time
The time taken (in minutes) for the process variable to settle within
2% of the set point value (tsettle).
IAE
2.1
Error Integral
The integral of the error value until the process variable settles to
within 2% of the set point value in 'engineering-unit hours'.
tsettle
450.2
500.0
Error integral =
|PV SP|dt
0
26
SET UP MODE
3.1
Introduction
To access the Set Up mode (Levels 2 to 5) the correct password must be entered in the security code frame.
Press
and hold
450.2
500.0
COdE
50
Invalid
password
70
Valid Set Up or
Configuration
password
450.2
500.0
LEV1
OPEr
LEV3
LEV5
VLVE
LEV2
tUNE
70
LEV2
LEV1
OPEr
AtNE
OFF
Tuning
Cycle time, output 1 & 2
On/off hysteresis values
Proportional bands 1 to 4
Integral action times 1 to 4
Derivative action times 1 & 2
Manual reset value
Control deadband
Heat Cool Output 1 & 2 Start
LEV4
LEV5
Set Points
Local set point values 1 to 4
Slave set point value
Remote set point ratio/bias
Ramp rate
2.00
Frame number
2.xx Level 2
3.xx Level 3 etc.
LEV.2
tUNE
450.2
500.0
2.00
450.2
500.0
2.01
2.00
CYC.1
1.0
450.2
500.0
2.00
Parameter
Parameter
adjustment
Default
value
27
8
3.2
SET UP MODE
Level 2 Tune
2.00...2.04
2.00
2.01
LEV.2
tUNE
CYC.1
1.0
Level 2 Tune
Note. To select this frame from anywhere in this page, press and hold the
key for a few seconds.
2.02
2.03
CYC.2
1.0
1
2
HYS1
0
PV
Set Point
Hysteresis
Value
Hysteresis
Value
Set Point
ON
Reverse Acting
Control Output
OFF
2.04
HYS2
0
ON
OFF
Direct Acting
Control Output
Output 2
Output 1
Hys 2
Y2.St
Y1.St
PID Output
Only displayed if Relay or Digital output type is selected see Section 4.2, Basic Configuration/ Output Type.
Only if On/Off control is selected see parameters 2.01 and 2.02 above.
Only displayed if Heat/Cool output type is select and the 'CYC.2' parameter is set to 'OnOF'.
28
3
3.2
2.05
SET UP MODE
Level 2 Tune
Pb-1
100.0
2.05...2.13
Proportional Band 1
Enter the value for Proportional Band 1.
[0.1% to 999.9%]
'Pb-1' is the default proportional band.
2.06
Pb-2
100.0
1
2
2.08
Pb-4
100.0
2.09
IAt.1
OFF
2.10
IAt..2
OFF
2..12
IAt.4
OFF
2.13
drV1
OFF
Only displayed if a tune parameter source is selected see Section 4.2, Basic Configuration/ Template
Application and Section 4.6, Control Configuration/ Tune Parameter Source.
Only displayed if a tune parameter source is selected see section 4.6, Control Configuration/ Tune
Parameter Source.
29
8
3.2
2.15
SET UP MODE
Level 2 Tune
Ab.1
1.0
2.17
rSt.1
50.0
2..21
Cbnd
OFF
Control Deadband
When the process variable is in the deadband, changes to the control
output due to proportional and integral action are suppressed.
Set Point
Process Variable
Deadband
Control Output
If manual control is selected and no integral action time is set, the manual reset value is calculated
automatically to give bumpless transfer into auto control.
30
3
3.2
SET UP MODE
Level 2 Tune
2..22
Y1.St
50.0
2.22...2.23
Heat/Cool Output 1 Start
This parameter defines the PID output value above which Output 1 (heat)
becomes active.
[0.0 to 100.0%]
Reverse-direct
or direct-reverse
100%
Reverse-reverse
or direct-direct
100%
Output 2
Output 2
Output 1
Output 1
0%
0%
2..23
Y2.St
50.0
Y2.St
Y1.St
PID Output
100%
0%
0%
Y2.St Y1.St
PID Output
100%
LEV2
tUNE
Return to top of page
Only displayed if a Heat/Cool output type is selected see Section 4.2, Basic Configuration/ Output Type.
31
8
3.3
SET UP MODE
3.00...3.07
Note. Level 3 is not applicable if Auto/Manual Station or Indicator templates are selected.
3.00
LEV.3
SEtP
3.01
LSP1
500
3.02
LSP2
200
3.04
LSP4
400
3.06
rAtO
1.000
Note. To select this frame from anywhere in this page, press and hold the
key for a few seconds.
3.07
BIAS
0
Continued
1 Displayed only if a local set point source is selected see Section 4.5/ Set Point Configuration/ Local/Remote
Set Point Source.
2
32
3
3.3
SET UP MODE
3.10
r.rtE
OFF
8
3.10
Ramp Rate
[1 to 9999 engineering units per hour, or OFF]
The Ramping Set Point facility can be used to prevent a large disturbance
to the control output when the set point value is changed. The rate set
applies to both the local and the remote set points.
PV
Displayed Local Set Point Value
300
200
Actual (Ramping) Set Point Value
used by PID Algorithm*
100
0
1 Hour
LEV3
SEt.P
Time
33
8
3.4
SET UP MODE
4.00...4.08
Note. Level 4 is not applicable if all alarm types are set to 'None' see Section 4.4, Alarms/ Alarm Type.
4.00
4.01
LEV.4
triP
1.xxx 1
0
Alarm 1 Trip
Note. To select this frame from anywhere in this page, press and hold the
key for a few seconds.
Display Description
NONE None
HPV High Process, PV
LPV Low Process, PV
HLP High Latch, PV
LLP Low Latch, PV
High Deviation
Hd
Low Deviation
Ld
HP1 High Process I/P1
LP1 Low Process I/P1
HP2 High Process I/P2
LP2 Low Process I/P2
HP3 High Process I/P3
Display Description
LP3 Low Process I/P3
High Output
HO
Low Output
LO
Hb1 Maths Block 1 High
Lb1 Maths Block 1 Low
Hb2 Maths Block 2 High
Lb2 Maths Block 2 Low
Hb3 Maths Block 3 High
Lb3 Maths Block 3 Low
Hb4 Maths Block 4 High
Lb4 Maths Block 4 Low
2
2
Trip Value
[In engineering units]
Note. When an auto/manual station template or analog backup template
is selected, Alarm 1 is set automatically as a low process alarm on Analog
Input 2.
4.02
2.xxx
0
4.08
8.xxx 1
0
Trip Value
[In engineering units]
LEV.4
trIP
Return to top of page.
Not displayed if alarm type set to 'None' see Section 4.4, Alarms/ Alarm Type.
34
3
3.5
SET UP MODE
5.00...5.04
Note. Level 5 is applicable only for a motorized valve output type see Section 4.2, Basic Configuration/ Output
Type.
PV
SPt
PID
Control
Terms
PID
Output
Valve
Controller
Open relay
Process
Close relay
Position Feedback
3.5.1
5.00
5..01
LEV.5
U.LU.E
VrAt
0
Note. To select this frame from anywhere in this page, press and hold the
key for a few seconds.
5.02
VbIA
0
5.03
d.bnd
1.0
.
Deadband
(centered around
required position)
Example. If the valve is set to be driven to the 50% open position and the
deadband is set to 4%, the motor stops driving when the position feedback
is 48%. The deadband is between 48% and 52%.
5.04
LEV.5
VLVE
r.trU.
30
35
8
3.5.2
SET UP MODE
A boundless process controller provides an output that is effectively the time derivative of the required regulator
position, i.e. the COMMANDER 500 signals the regulator, not where to go to (position derivative), but in which
direction to travel and how far to move, by a series of integral action pulses. Thus, the COMMANDER 500 does
not need to know the absolute regulator position and is unaffected when regulator reaches the upper or lower limit,
as determined by the regulators limit switches (giving rise to the term boundless).
When a deviation from set point is introduced the regulator is driven, for a length of time equivalent to the
proportional step. The regulator is then driven by integral action pulses until the deviation is within the deadband
setting.
+
Control
Deviation
Time
Integral
Action Pulses
Raise
Lower
Proportional
Step
Time
Proportional
Step
Proportional Integral
Step
Action Pulses
(in seconds)
Minimum (approximate) time between integral action pulses (for a fixed control deviation)
(in seconds)
% Control Deviation
% Proportional Band
% Control Deviation
=
% Deadband
Deadband (eng units)
=
Eng Hi Eng Lo
36
x 100%
x 100%
3
3.5.2
5.00
5.03
SET UP MODE
5.00...5.04
LEV.5
U.LU.E
d.bnd
0
Boundless Deadband
Note. To select this frame from anywhere in this page, press and hold the
key for a few seconds.
5..04
r.trU.
0
Deadband
(centered around
Set Point)
LEV.5
VLVE
Return to top of page.
37
4
4.1
CONFIGURATION MODE
Introduction
To access the Configuration mode (Levels 6 to E) the correct password must be entered in the security code
frame.
LEVE
CAL
LEV6
APPL
Press
and hold
LEV5
VLVE
450.2
500.0
70
Press
and hold
COdE
50
Invalid
password
LEV6
APPL
Basic Configuration
Template application
Output type
Control action
Mains rejection frequency
LEV7
INPt
Analog Inputs 1 to 3
Type
Electrical range
Decimal places
Engineering range
Broken sensor drive
Input filter time constant
LEV8
ALr
Alarms 1 to 8
Type
Trip level
Hysteresis band
LEV9
SEt.P
Set Points
Tracking enable
Set point limits
Local set point sources 1 to 4
Local/remote set point selection
LEVA
CNtL
Control Configuration
Power fail recovery action
Output high/low limits
Slew rate + disable
Configured outputs 1 to 3
Manual output selection sources
Auto mode selection source
Tune parameter sources 1 to 4
Valid Auto-tune,
Set Up or
Configuration
password
AtNE
OFF
Autotune
password
Set Up
password
LEV2
tUNE
LEV1
OPEr
Valid Set Up or
Configuration
password
LEVb
OPEr
Operator Configuration
Auto/manual key enables
Local/remote key enables
Alarm acknowledge key enable
Operator set point adjust enable
Operator ratio/bias enable
Password settings
Clock settings
LEVC
ASSN
Output Assignment
Outputs 1 and 2 type
Digital output
Assignment source
Polarity
Analog output
Assignment source
Electrical range
Engineering range
Relay outputs 1 to 4
Assignment source
Polarity
LEVd
SErL
Serial Communications
2-/4-wire connection
2400/9600/19200 baud rate
Parity
MODBUS address
LEVE
CAL
Calibration
Offset/span adjustment
Motorized valve feedback
38
Valid
Configuration
password
4
4.2
CONFIGURATION MODE
6.00
6..01
6.00...6.01
LEV.6
APPL
t.APP
1.SL
Template Application
Templates are provided to make the basic configuration for a particular
application as simple as possible. The appropriate template should be
selected before any other parameters are configured. When a template is
selected, the COMMANDER 500 assumes the preset form for that
template (see Appendix A). The inputs and software blocks are
automatically soft-wired to perform the selected function.
Note. To select this frame from anywhere in this page, press the
for a few seconds.
key
Template Description
01S
. L
02S
. L
03A
. M
04A
. M
05A
. b
06A
. b
07I
. N
08I
. N
Continued
39
4
4.2
6.02
CONFIGURATION MODE
O.tYP
ANLG
6.02
NONE
ANLG
rLY
dIG
None
Analog output (Control output = ao1)
Relay output (Control output = RLY1)
Digital output (Control output = do1)
PFb
bNd
HCr
. r
HCr
. d
HCd
. r
HCd
. d
HCA
. r
HCA
. d
HCA
. A
2
3
Continued
1 Only output types 'NONE' and 'ANLG' are applicable to indicator templates. Only output type 'ANLG' is
applicable to auto/manual station and analog backup templates.
2
40
4
4.2
CONFIGURATION MODE
Output Types:
PV
ANLG
rLY
dIG
Relay Output
Control
Algorithm
Digital Output
Process
Analog Output
SPt
A Single Output
Output Type:
PV
PFb
Control
Algorithm
Open relay
Valve
Controller
Process
Close relay
Position Feedback
SPt
Output Type:
PV
bNd
Control
Algorithm
Valve
Controller
Open relay
Process
Close relay
SPt
C Motorized Valve Output without Feedback (Boundless)
Output Types:
HC.rr
HC.rd
HC.dr
HC.dd
HC.Ar
HC.Ad
HC.AA
PV
Heat Output
Control
Algorithm
See Note
SPt
Cool Output
Relay or
Digital or
Analog Output
Process
Relay or
Digital or
Analog Output
D Heat/cool Output
See Note
41
4
4.2
6.03
6.06
CONFIGURATION MODE
C.ACt
rEU
F.rEJ
50
6.03...6.06
Control Action
Single Loop
Output 1
rEV
Reverse
dir
Direct
Heat/Cool
Output 1 (Heat)
r-d
Reverse
Direct
r-r
Reverse
Reverse
d-r
Direct
Reverse
d-d
Direct
Direct
LEV.6
APPL
Return to top of page.
42
Output 2 (Cool)
4
4.3
CONFIGURATION MODE
7.00
LEV.7
InPt
7.00...7.03
Level 7 Analog Inputs
Note 1. Refer also to the rear fold-out, Table A Template Applications.
Note 2. To select this frame from anywhere in this page, press the
for a few seconds.
7.01
tYP.1
2
b
E
J
K
L
N
r
S
t
7.02
7.03
THC Type B
THC Type E
THC Type J
THC Type K
THC Type L
THC Type N
THC Type R
THC Type S
THC Type T
Display Description
PT100 RTD
P
1
2
3
4
6
7
8
9
U
0 to 20mA
4 to 20mA
0 to 5V
1 to 5V
0 to 50mV
4 to 20mA square root linearizer
4 to 20mA power 3/2
4 to 20mA power 5/2
Custom
UNt.1 1
C
dP.1
key
C
F
0
1
2
3
XXXX
XXX.X
XX.XX
X.XXX
Continued
43
4
4.3
7.04
CONFIGURATION MODE
En1.H
1000
7.04...7.07
Engineering High (I/P1)
[999 to 9999]
Note. This parameter defaults to the maximum allowed value when THC
or RTD inputs are selected see Table 4.1.
THC/RTD Type
C
Min.
Max.
18 1800
Type B
F
Min. Span
Min.
Max.
Min. Span
710
3272
1278
81
Type E
100
900
45
148
1652
Type J
100
900
50
148
1652
90
Type K
100
1300
65
148
2372
117
Type L
100
900
50
148
1652
90
Type N
200
1300
90
328
2372
162
18 1700
Type R & S
Type T
Pt100
320
3092
576
250
300
60
418
572
108
200
600
25
328
1112
45
7.05
EnI.L
0
7.06
b.Sd1
UP
7.07
FLt.1
0
Continued
44
CONFIGURATION MODE
4.3
7.08
7.09
7..10
7..11
7.08...7.14
tYP2 1
2
UNt2 2
C
dP.2
0
En2.H
1000
C
F
0
1
2
3
XXXX
XXX.X
XX.XX
X.XXX
7.12
En2.L
0
7.13
7.14
bsd.2
UP
FLt.2
0
[0 to 60 seconds]
Continued
1
Frames 7.09 to 7.14 are not displayed if Analog Input Type 2 is set to 'OFF'.
45
4
4.3
CONFIGURATION MODE
7.15...7.21
7.15
tYP.3 1
2
7..16
UNt3 2
C
Temperature Units
7..17
7..18
dP.3
0
En3.H
1000
Display Description
OFF Not Used
THC Type B
b
THC Type E
E
THC Type J
J
THC Type K
K
THC Type L
L
THC Type N
N
THC Type R
r
THC Type S
S
THC Type T
t
PT100 RTD
P
C
F
Display Description
0 to 20mA
1
4 to 20mA
2
0 to 5V
3
1 to 5V
4
0 to 50mV
6
4 to 20mA square root linearizer
7
4 to 20mA power 3/2
8
4 to 20mA power 5/2
9
Resistance feedback for
11
motorized valve
Custom
U
Decimal Places
0
1
2
3
XXXX
XXX.X
XX.XX
X.XXX
Engineering High
[999 to 9999]
Note. This parameter defaults to the maximum allowed value when THC
or RTD inputs are selected see Table 4.1.
7..19
En3.L
0
Engineering Low
[999 to 9999]
Note. This parameter defaults to the minimum allowed value when THC or
RTD inputs are selected see Table 4.1.
7.20
7.21
LEV7
INPt
bSd.3
UP
FLt.3
0
[0 to 60 seconds]
Return to top of page.
Frames 7.16 to 7.21 are not displayed if Analog Input Type 3 is set to 'OFF'.
46
4
4.4
CONFIGURATION MODE
Level 8 Alarms
Note. Any type of alarm can be used to sound an annunciator (klaxon/horn) which is disabled when the alarm
is acknowledged. This is achieved by assigning the relay to the acknowledge state of the alarm instead of the
actual alarm state.
Process
Variable
Trip point
On
RLY.x
Alarm State
(A.x)
Off
Horn
On
Acknowledge State
(ACK.x)
Off
rLY.x
ACK.x
Relay assigment
frame in Level C,
Output Assignment.
Operator
acknowledges
alarm
Fig 4.3 Using an Alarm to Sound a Horn
Hysteresis
High Deviation
+ve Trip Value
Process Variable
Control Set Point
High Deviation
ve Trip Value
Hysteresis
Alarm On
Alarm Off
Positive
Trip Value
Negative
Trip Value
Alarm On
Alarm Off
Process
Variable
Hysteresis
Low Deviation
+ve Trip Value
Control Set Point
Hysteresis
Low Deviation
ve Trip Value
Alarm On
Alarm Off
Alarm On
Alarm Off
47
4
4.4
CONFIGURATION MODE
Level 8 Alarms
Hysteresis
Trip Point
Hysteresis
Process
Variable
Alarm On
High Process
Alarm Off
Alarm On
Low Process
Alarm Off
Trip Point
Hysteresis
Process
Variable
Alarm On
Alarm Latched
Alarm Off
Alarm acknowledged
by operator
Process
Variable
Hysteresis
Trip Point
Alarm On
Alarm Latched
Alarm Off
Alarm acknowledged
by operator
48
4
4.4
8.00
8.01
CONFIGURATION MODE
Level 8 Alarms
8.00...8.03
LEV.8
ALMS
Level 8 Alarms
tYP.1
HP1
Alarm 1 Type
See Figs 4.3 to 4.6
Note. To select this frame from anywhere in this page, press the
for a few seconds.
Display Description
NONE None
HPV High Process, PV
LPV Low Process, PV
HLP High Latch, PV
LLP Low Latch, PV
High Deviation
Hd
Low Deviation
Ld
HP1 High Process I/P1
LP1 Low Process I/P1
HP2 High Process I/P2
LP2 Low Process I/P2
HP3 High Process I/P3
Display Description
LP3 Low Process I/P3
High Output
HO
Low Output
LO
Hb1 Maths Block 1 High
Lb1 Maths Block 1 Low
Hb2 Maths Block 2 High
Lb2 Maths Block 2 Low
Hb3 Maths Block 3 High
Lb3 Maths Block 3 Low
Hb4 Maths Block 4 High
Lb4 Maths Block 4 Low
key
1
1
8.02
trP.1
0
Alarm 1 Trip
Alarm Number
Trip Value
[In engineering units]
8.03
HYS.1
0
Alarm 1 Hysteresis
Set the hysteresis value (in engineering units) for Alarm 1.
The alarm is activated at the trip level but is only deactivated when the
process variable has moved into the safe region by an amount equal to the
hysteresis value see Figs. 4.4 to 4.6.
[In engineering units]
Note. Time hysteresis is set using the PC Configurator.
Continued
Applies to the PID output with single or heat/cool output types selected see Section 3.4.
49
4
4.4
CONFIGURATION MODE
Level 8 Alarms
8.04
8.07
8.10
8.13
8.16
8.19
8.22
tYPx
NONE
8.05
8.08
8.11
8.14
8.17
8.20
8.23
trP.x
0
8.06
8.09
8.12
8.15
8.18
8.21
8.24
HYS.x
0
8.25
G.ACK
NONE
8.04...8.24
Alarm Type 2 (Alarms 2 to 8)
LEV8
ALr
50
A digital input becomes active when a volt-free contact is closed or a loww TTL signal is applied.
4
4.5
CONFIGURATION MODE
9.00...9.03
Note. Level 9 is not applicable when an Indicator template (templates 7 and 8) or an Auto/Manual station
template (templates 3 and 4) is selected.
9.00
9.01
LEV9
SEt.P
trCK
OFF
Note. To select this frame from anywhere in this page, press and hold the
key for a few seconds.
Display
OFF
LOC
rEM
L-r
ON
OFF
OFF
ON
ON
ON
Local Set Point Tracking the local set point tracks the process variable
when manual mode is selected.
Remote Set Point Tracking local set point tracks the remote set point
when in remote set point mode. If the controller is put into manual mode
the set point reverts from remote to local.
9.02
SPt.H
1000
9.03
SPt.L
0
Continued
51
4
4.5
9..06
CONFIGURATION MODE
SP.FA
NONE
NONE
LOC
dFLt
9..07
dF.SP
0.0
9.06...9.11
No action
Select local set point mode
Select local set point mode and set to the default value
9..08
L.Sr1
NONE
9..09
L.Sr2
NONE
L.Sr3
NONE
L.Sr4
NONE
LSP2
LSP3
LSP4
Continued
A digital input becomes active when a volt-free contact is closed or a low TTL signal is applied.
52
9.11
9.10
LSP1
4
4.5
9.12
Lr.5r 1
NONE
LC.5r 1
NONE
r.SrC 1
NONE
Local
1
Local
LEV9
SEt.P
Remote
9.14
9.12...9.14
9.13
CONFIGURATION MODE
Digital inputs are active when a volt-free contact is closed or a low TTL signal is applied
53
4
4.6
CONFIGURATION MODE
A.00...A.02
A.00
A.01
LEVA
CntL
P.rEC
0
Note. To select this frame from anywhere in this page, press and hold the
key for a few seconds.
Display
A.02
rEC.t
0
Setting
Last mode
Auto mode,
integral term reset
Manual mode,
using last output
Auto mode,
using last integral term
Power outage
Recovery time: Auto
mode. Power outage >
Recovery time: Manual
mode, last output
Power outage
Recovery time: Auto
mode. Power outage >
Recovery time: Manual
mode, configured output
Recovery Time
If power is restored within the recovery time, the controller continues in the
last mode when power fail recovery modes 7 or 8 are selected.
Continued
54
Setting
[0 to 9999 seconds]
Display
4
4.6
A.03
A.03...A.08
PVFA
NONE
NONE
HOLd
dFLt
A.04
CONFIGURATION MODE
No action
Put into Manual mode
Put into Manual mode and select default output
Default Output
This output is used in conjunction with Power Recovery mode 8 and
Process Variable Fail action.
dF.OP
0
A.05
OP.HI
100
A.06
OP.L0
0
A.07
OP1H
100.0
A.08
OP2H
100
[0.0 to 100.0%]
OP2H
0
+100%
OP2
OP1
0
Continued
55
4
4.6
A.09
CONFIGURATION MODE
OP2L
0
A.09...A.12
+100%
+100%
OP2
OP2L
0
A.10
OP.Sr
OFF
OP1
0
A..11
Srd5
0FF
A.12
M5r1
0FF
Manual with
output = C.OP1 2
Auto
Continued
Digital inputs are active when a volt free contact is closed or a low TTL signal is applied.
56
Enabled
4
4.6
A.13
CONFIGURATION MODE
C.OP1
0.0
A.13...A.17
Configured Output 1
The control output value required when manual is selected by manual
mode source 1.
[0 to 100% or LAST (non-heat/cool)]
[100 to 100% (heat/cool only)]
A..14
M5r2
0FF
A..15
C.OP2
0.0
Configured Output 2
The control output value required when manual is selected by manual
mode source 2.
[0 to 100% or LAST (non-heat/cool)]
[100 to 100% (heat/cool only)]
A.16
AM.5r
0FF
Auto
A.17
COP.3
0.0
Configured Output 3
The control output value required when manual mode is selected by the
auto/manual selection source.
[0 to 100% or LAST (non-heat/cool)]
[100 to 100% (heat/cool only)]
Continued
Digital inputs are active when a volt free contact is closed or a low TTL signal is applied
57
4
4.6
A.18
CONFIGURATION MODE
A.5rC
0FF
A.19
t1.Sr
0FF
t2.Sr
0FF
t3.5r
0FF
t4.Sr
0FF
LEVA
CNtL
Manual
A..22
A..21
Auto
A..20
A.18...A.22
Digital inputs are active when a volt free contact is closed or a low TTL signal is applied.
2 PBx and IAt.x values are set in Level 2 see Section 3.2, Tune/Proportional Band x and Integral Action
Time x. This function is not available with Cascade control and it is not applicable to Auto/Manual Station, Indicator
or Ratio Station templates.
58
4
4.7
CONFIGURATION MODE
b.00
b.01
b.02
b.03
b.04
b.05
LEVb
OPEr
FP.AM 1
YES
FPLr 1
Lr
FPAK
YES
S.AdJ 1
YES
r.d15 1
2
NO
Note. To select this frame from anywhere in this page, press and hold the
key for a few seconds.
YES
NO
b.d15 1
2
NO
Enabled
Disabled
YES
NO
YES
NO
YES
NO
b.06
b.00...b.06
Enabled
Disabled
Enabled
Disabled
YES
NO
Continued
59
4
4.7
CONFIGURATION MODE
b.07
A.PA5 1
0
b.07...b.13
Auto-tune Password
Enables access to the auto-tune facility in the operator level.
[0 to 9999 (default 0)]
b.08
S.PAS
0
Set Up Password
Enables access to the set up levels (levels 2, 3, 4 and 5) and the autotune
facility.
[0 to 9999 (default 0)]
b.09
C.PA5
0
Configuration Password
Enables access to the configuration levels, set up levels and the autotune
facility.
[0 to 9999 (default 0)]
b..10
dAY
1
b..11
HOUr
23
b..12
MIN
59
b..13
t.CLK
00.00
Day Setting
Use to set the weekday of the on-board clock.
[1 to 7. 1 = Sunday, 7= Saturday]
Hour Setting
Use to set the hour of the on-board clock.
[0 to 23]
Minute Setting
Use to set the minute of the on-board clock.
[0 to 59]
Current Time
Actual on-board clock time.
[Hours : Mins]
LEVb
OPEr
Return to top of page.
60
4
4.8
CONFIGURATION MODE
Note. The Output Assignment default settings are preconfigured to each template see Table B, Output
Sources on the rear fold-out.
C.00
LEV.C
ASSn
C.01
tYP.1
ANLG
Note. To select this frame from anywhere in this page, press the
for a few seconds.
ANLG
dIG
AN1.A
NONE
key
Analog
Digital
Press
Press
or
dIG
dG1.A
NONE
4.8.1
Digital Output 1
tYP1
dIG
C.07
dGI.A
NONE
C.08
dG1.P
POS
Continued
1 If the output is assigned to a control output by the control type, the setting displayed cannot be changed see
Section 4.2, Basic Configuration/ Control Output Type.
2
61
4
4.8.2
CONFIGURATION MODE
Analog Output 1
C02...C06
tYP1
ANLG
C.02
AnI.A
NONE
C.03
AN1.H
20.0
[0.0 to 22.0mA]
C.04
AN1.L
4.0
[0.0 to 22.0mA]
C.05
r1.H
100.0
C.06
r1.L
0.0
tYP.2
ANLG
Continued
1 If the output is assigned to a control output by the control type, the setting displayed cannot be changed see
Section 4.2, Basic Configuration/ Control Output Type.
2
62
4
4.8.3
CONFIGURATION MODE
Output 2 Assignment
r1L
0.0
dG1.P
0.0
C.09
tYP.2 1
ANLG
ANLG
dIG
AN2.A
NONE
Analog
Digital
Press
Press
or
dIG
dG2.A
NONE
4.8.4
Digital Output 2
tYP2
dIG
C.15
dG2.A 1
NONE
C.16
dG2P
0
1
2
Continued
1 Only displayed if optional ouput is fitted. If the output is assigned to a control output by the control type, the
setting displayed cannot be changed see Section 4.2, Basic Configuration/ Control Output Type.
2
63
4
4.8.5
CONFIGURATION MODE
Analog Output 2
C10...C14
tYP.2
ANLG
C.10
AN2.A 1
NONE
C.11
AN2H 1
20.0
C.12
AN2.L 1
4.0
C.13
r2H 1
2
100.0
C.14
r2L 1
2
0.0
rLY1
NONE
Continued
1 Only displayed if optional ouput is fitted. If the output is assigned to a control output by the control type, the
setting displayed cannot be changed see Section 4.2, Basic Configuration/ Control Output Type.
2
64
4
4.8.6
CONFIGURATION MODE
Relay Outputs 1 to 4
C17...C22
r2L
0.0
dG2.P
0.0
C..17
rL1.A
NONE
C.18
rL1.P
POS
2
3
Relay 1 Polarity
The relay can be set to energize for either an active or inactive digital
signal.
C.19
rL2.A
NONE
C.20
rL2.P
POS
2
3
Relay 2 Polarity
The relay can be set to energize for either an active or inactive digital
signal.
C.21
rL3.A
NONE
1
4
C.22
rL3..P
POS
2
3 4
Relay 3 Polarity
The relay can be set to energize for either an active or inactive digital
signal.
1 If the output is assigned to a control output by the control type, the setting displayed cannot be changed see
Section 4.2, Basic Configuration/ Control Output Type.
2
65
4
4.8.6
C..23
CONFIGURATION MODE
Relay Outputs 1 to 4
rL4.A
NONE
1
4
C23...C24
C.24
LEVC
ASSN
rL4.P
POS
2
3 4
Relay 4 Polarity
The relay can be set to energize for either an active or inactive digital
signal.
1 If the output is assigned to a control output by the control type, the setting displayed cannot be changed see
Section 4.2, Basic Configuration/ Control Output Type.
2
66
4
4.9
CONFIGURATION MODE
d.00...d.03
d.00
LEVd
SErL
Note. To select this frame from anywhere in this page, press and hold the
key for a few seconds.
d.01
d.02
d.03
S.CFG
0
Serial Configuration
0
1
2
3
4
5
6
Off
2-wire
4-wire
2-wire
4-wire
2-wire
4-wire
connection,
connection,
connection,
connection,
connection,
connection,
PrtY
NONE
Parity
Addr
1
MODBUSTM Address
Each slave on a MODBUS link must be assigned a unique address see
IM/C500MOD.
NONE None
Odd Odd
EVEN Even
[1 to 99]
LEVd
SErL
Return to top of page.
67
4
4.10
CONFIGURATION MODE
Level E Calibration
E.00...E.04
Note. This page enables fine tuning of the inputs to eliminate system errors.
E.00
E.01
LEVE
CAL
Level E Calibration
OFF.1
0.0
Note. To select this frame from anywhere in this page, press the
for a few seconds.
100.3
0.0
key
If the
and
keys are not operated for three seconds the display
reverts to the offset value only.
E.02
SPn.1
0.0
100.3
0.0
Span Adjustment
[0.750 to 1.250]
If the
and
keys are not operated for three seconds the display
reverts to the span value only.
E.03
OFF.2
0.0
100.3
0.0
If the
and
keys are not operated for three seconds the display
reverts to the offset value only.
E.04
SPn.2
1.0
100.3
0.0
Span Adjustment
[0.750 to 1.250]
If the
and
keys are not operated for three seconds the display
reverts to the offset value only.
Continued
68
4
4.10
E.05
CONFIGURATION MODE
Level E Calibration
OFF.3
8888
E.05...E.10
Analog Input 3 Offset Calibration
Analog Input 3 Value in Engineering Units
100.3
0.0
E.06
SPN.3
8888
100.3
0.0
Span Adjustment
[0.750 to 1.250]
If the
and
keys are not operated for three seconds the display
reverts to the offset value only.
E.07
FCAL
NO
2
rEF
2700
AUtO
r.trV
30
MAN
Fb.LO
100
F.CAL
AUtO
E.08
E.09
r.trV
30
C.CAL
NO
NO No action
YES Fully closes the valve automatically and sets the electrical input
to low range value.
Note. Input value flashes when calibration is in progress.
E.10
O.CAL
NO
NO No action
YES Fully opens the valve automatically and sets the electrical input
to high range value.
Note. Input value flashes when calibration is in progress.
rEF
2700
Only displayed if Motorized Valve with feedback output type is selected see Section 4.2, Basic Configuration.
69
4
4.10
CONFIGURATION MODE
Level E Calibration
E.11...E.16
FCAL
MAN
E11
Fb.LO
100.0
E.12
Fb.HI
500.0
rEF
2700
FCAL
NO
O.CAL
NO
Fb.HI
500
E.13
rEF
2700
E.14
bEtA
3977
E.15
CJ1
25.2
E.16
CJ3
25.2
LEV.E
CAL
2
3
Only displayed if Motorized Valve with feedback output type is selected see Section 4.2, Basic Configuration.
70
INSTALLATION
EC Directive 89/336/EEC
In order to meet the requirements of the EC
Directive 89/336/EEC for EMC regulations, this
product must not be used in a non-industrial
environment.
55C
Max.
0C
Min.
0 to 90% RH
IP66/
NEMA4X
(front panel)
IP20
Minimum
(rear)
Sensor
A Close to Sensor
B At Eye-level Location
Caution. Select a location away from
strong electrical and magnetic fields. If
these cannot be avoided, particularly in
applications where walkie talkies are
used, connect using screened cables
within grounded metal conduit.
71
5
5.1.2
INSTALLATION
The instrument is designed for panel mounting (Fig. 5.4). Overall dimensions are shown in Fig. 5.3.
Note. For NEMA4X protection, a minimum panel thickness of 2.5mm is recommended.
Dimensions in mm (in.)
18
(0.71)
137.5 (5.41)
137.8
(5.43)
76 (2.99)
148
(5.83)
5.0
(0.2)
149.5 (5.87)
68+0.7
0
(2.68+0.03
0 )
Panel
Cutout
14 (0.55)
30 (1.18)
72
138+1
0
(5.43+0.04
0 )
5
5.1.2
INSTALLATION
Fit the panel clamps to the case, ensuring that the lugs
are correctly located in their slots
1
3
Earth (Ground)
Studs
73
5
5.1.2
INSTALLATION
74
5
5.1.3
INSTALLATION
PR
OC
ES
LA
BE
75
5
5.2
INSTALLATION
Electrical Installation
Warnings.
The instrument is not fitted with a switch therefore a disconnecting device such as a switch or circuit
breaker conforming to local safety standards must be fitted to the final installation. It must be fitted in
close proximity to the instrument within easy reach of the operator and must be marked clearly as the
disconnection device for the instrument.
Remove all power from supply, relay and any powered control circuits and high common mode
voltages before accessing or making any connections.
Use cable appropriate for the load currents. The terminals accept cables up to 14AWG (2.5mm2).
The instrument conforms to Mains Power Input Insulation Category II. All other inputs and outputs
conform to Category II.
Terminals for external circuits are for use only with equipment with no accessible live parts.
If the instrument is used in a manner not specified by the Company, the protection provided by the
equipment may be impaired.
All equipment connected to the instrument's terminals must comply with local safety standards (CEI/IEC
61010-1:2001-2).
Notes.
Always route signal leads and power cables separately, preferably in earthed (grounded) metal
conduit.
It is strongly recommended that screened cable is used for signal inputs and relay connections.
Connect the screen to the earth (ground stud) see Fig. 5.4.
76
5
5.2.1
INSTALLATION
Analog
19
Input 3
20
(I/P3)
RTD2
21
RTD1
Transmitter PSU
Digital / Analog Output 2
22
23
(I/P2)
(ao2 /do2)
24
Transmitter PSU
25
26
See
Fig 5.8
Relay 3 (RLY3)
Relay 4 (RLY4)
27
NO/NC
28
10
Analog Input 1
(I/P1)
See
Fig. 5.8
Analog Input 2
29
11
NO/NC
30
12
31
13
32
14
NO/NC
33
15
34
16
35
36
17
18
RS485 Tx
RS485 Tx/Rx
RS485 Common
Relay 1 (RLY1)
85V +Vs (+)
min.
to 0V ()
265V
max.
a.c.
24V
d.c.
Earth
(Ground) Stud
77
5
5.2.1
INSTALLATION
Analog
Input 1
I/P 1
THC
millivolts
and volts
Milliamps * Milliamps
2-lead RTD
and Resistance
3-lead
RTD
3rd lead
RTD
RTD
RTD
RTD +
RTD +
**100
Voltage
**100
CJ Sensor#
Tx 2-wire
Transmitter
****
100K
+
Analog
Input 2
I/P 2
**100
**100
Milliamps
Millivolts
THC##
Tx
Voltage
* milliAmps
2-lead RTD
and Resistance
THC
milliVolts
and Volts
3-lead
RTD
RTD
3rd lead
RTD
RTD
+ RTD
+ RTD
19
**100
**100
****
100K
milliAmps
2-wire
Transmitter
20
CJ Sensor
Tx 2-wire
Transmitter
21
+
22
*
**
***
**** For correct broken sensor operation with voltage inputs, fit a 100K pull up resistor
#
##
I/P2 can only be used with THC inputs if I/P1 is also used as a THC input
5V
Inactive
0V
Active
TTL
Volt free
Inactive
Active
78
Analog
Input 3
I/P3 ***
5
5.3
Relays
5.4
Digital Output
15V d.c. min. at 20mA
Min. load 667
5.3.1
INSTALLATION
Normally closed
Normally open
LK1 = Relay 1
LK2 = Relay 2
LK3 = Relay 3
LK4 = Relay 4
LK3
LK2
LK4
LK1
Option Board
Processor Board
Note. The default setting for the relay links is 'Normally Open' (N/O).
79
5
5.6
INSTALLATION
5.7
Input Connections
5.7.1
Motorized Valve
Drive
12
0%
13
14
100%
15
(N)
Valve
Positioner
Power
Supply
N
L
(L)
A Relay Connections
Motorized
Valve
Drive
100
(mA inputs
only)
19
20
B Feedback Connections
(V, mA or mV Input Types)
Motorized Valve
Drive
Fitting the
CJ sensor
to I/P 1
CJ sensor, I/P 3
See Note
19
100%
20
21
0%
C Feedback Slidewire
Connection
Motorized Valve
Drive
0%
20
21
100%
D Alternative Feedback
Slidewire Connection
80
19
+ 20
+2
21
I/P3
Copper
cable
Compensating
cable
I/P1
5
5.7.2 3-lead Resistance
Thermometer (RTD) Inputs
5.8
Output Connections
5.9
Type of
Thermocouple
INSTALLATION
Compensating Cable
BS1843
+
ANSI MC 96.1
Case
Ni-Cr/Ni-Al
Brown Blue
Red Yellow
(K)
Nicrisil/Nisil
Orange Blue Orange Orange
(N)
Pt/Pt-Rh
White Blue Green Black
(R and S)
Pt-Rh/Pt-Rh
(B)
DIN 43714
Case
Red
Yellow
Red
Red
Orange
Red
Green
Red
Case
Blue
Blue
Blue
Red
Blue
Red
Blue
Black
White
Red
Black
Red
Case
White
Green *
White
Pink *
Fe/Con (J)
Yellow
Grey
White
Blue
Black
White
Grey *
Brown *
Black *
DIN 43710
Blue/ Blue
Blue
red
81
SPECIFICATION
Analog Inputs
Summary
Number
1 standard
1 optional
Type
Universally configurable to provide:
Thermocouple (THC)
Operation
Volts
Display
mA
Resistance
1999 to +9999
Input Impedance
mA
1001
mV, V
10M1
Configuration
Basic configuration via front panel keys
Advanced feature configuration by PC only
Security
Internal security switch and password-protected menus
Linearizer Functions
THC types B, E, J, K, L, N, R, S, T, PT100, 3, 3/2, 5/2
Broken Sensor Protection
Programmable for upscale or downscale drive
Sample Interval
Standard Functions
Control Strategies
Single-loop, Auto/manual Station, Analog Backup,
Indicator/Manual Loader
Output Types
Current proportioning, Time proportioning, On/off, Motorized valve
(with and without feedback), Heat/cool.
Control Parameters
125ms (1 input)
Digital filter
Programmable
Cold Junction Compensation
Automatic CJC incorporated as standard
Stability 0.05$C/$C change in ambient temperature
Input Protection
Common mode rejection
>60dB at 50/60Hz
24V DC nominal
Drive
Up to 45mA as standard,
up to 23mA on option board
Autotune
On demand for 1/4 wave or minimal overshoot
1 standard, 1 optional
Voltage
82
SPECIFICATION...
Digital Inputs
EMC
Emissions and Immunity
Meets requirements of IEC 61326 for an Industrial Environment
Number
2 standard, 2 optional
Type
Volt-free
Minimum pulse
200ms
Outputs
Advanced Features
Control/Retransmission Outputs
Maths Blocks *
Number
1 standard, 1 optional
Type
Programmable as analog or
logic (digital) output
Isolation
Analog range
Number
Operators
Number
2
Programmable Delay and Duration in seconds
Relay Outputs
Number 2 standard, 2 optional
Logic Equations *
Number
Elements
15 per equation
Operators
Custom Linearizers *
Number
Breakpoints
15 per linearizer
Maximum Range $C
Maximum Range $F
Accuracy (% of reading)
18 to 1800
0 to 3270
100 to 900
140 to 1650
100 to 900
140 to 1650
100 to 1300
140 to 2350
100 to 900
140 to 1650
200 to 1300
325 to 2350
18 to 1700
0 to 3000
18 to 1700
0 to 3000
250 to 300
400 to 550
RTD
Maximum Range $C
Maximum Range $F
Accuracy (% of reading)**
Pt100
200 to 600
325 to 1100
** RTD, 3-wire platinum, 1001 per DIN 43760 standard (IEC 751), with range of 0 to 4001
Linear Inputs
Range
Accuracy (% of reading)
Millivolts
0 to 500mV
0.1% or ( 10+A
Milliamps
0 to 50mA
0.2% or (2+A
Volts
0 to 5V
0.2% or ( 2mV
Resistance
0 to 50001
0.2% or ( 0.081
83
SPECIFICATION
Options
Electrical
Analog Inputs
Voltage
Number
Isolation
Type
Analog/Digital output
85 to 265V AC 50/60Hz
24V DC
Power consumption
<10VA
Number
Isolation
Type
Safety
Number
Dielectric Strength
Type
Number
Type
Volt-free
Minimum pulse
200ms
Serial Communications
Connections
500V DC to earth
Analog/digital output 1 to rest of the circuitry
(500V DC for 1 minute)
Digital Inputs
RS485, 2- or 4-wire
Protocol
Modbus RTU
Isolation
Environmental
Operating Limits
0$C to 55$C (32$F to 130$F)
Physical
Size
76mm x 148mm x 149.5mm
(2.99 in. x 5.83 in. x 5.87 in.)
Weight
750g (1.6lb)
5 to 95%RH (non-condensing)
Temperature stability
<0.02%/$C or 2+V/$C (<0.011%/$F or 1.11+V/$F)
Long term drift <0.02% of reading or 20+V annually
Front face
NEMA4X (IP66)
SS/C501 Issue 6
84
Template 2 Only
I/P2
RSPt
LSPt
L
L
R
Set Point
Ramp
PV
CSPt
PID
Control Loop
PID O/P
Manual Output
OP1
A1
Single Loop Control provides basic feedback control using three term PID or On/off control. The controller output is calculated from the difference
between the process variable and the control set point. The control set point can be a fixed value entered by the user or from a remote source.
85
Process
PV
C500
Process Variable
I/P1
Master Output
Output
I/P2
Status
Digital Select
di.1
Master
Controller
ao1
Actuator
ao1
Series Connection
Process
PV
C500
Process Variable
I/P1
ao1
ao1
Master Output
Output
I/P2
Status
Digital Select
di.1
Relay 1
Master
Controller
Actuator
External
Relay
Master
Output
Parallel Connection
86
Manual Output
Auto/Manual
Select
OP1
ao1
2 Template 4 only
1 Template 3 only. Alarm A1 trip value can be set to give the desired low signal detection
di.1
Digital Select
I/P2
Master Output
I/P1
Process Variable
A2.2
The auto/manual station can be used in series or in parallel with the master output signal see Fig. A1. Parallel operation is achieved by using
relay 1 in the COMMANDER 500 to energize an external relay (with suitable changeover contacts for switching low level signals) which selects the output
to be routed to the actuator.
The Auto/manual Station provides a backup for a Master controller. In normal operation the COMMANDER 500s current output follows the master
controllers output value. A fault in the master system can be identified either by detecting a low signal on the master output (template 3) or via a digital
signal (template 4). When a fault is detected the COMMANDER 500 selects manual mode with its output either set to the last valid master output value
or to a configured output value see Section 4.6/ Control Configuration/ Configured Output 1. When the master signal is restored or the digital input
returns to its normal state the COMMANDER 500 switches back to auto mode (i.e. COMMANDER 500 output = master output).
87
88
1
2
PV
LSPt
PID
Controller
L
R
Local/
Remote
Select
OP1
Template 5 only. Alarm A1 trip value can be set to give the desired low signal detection
Template 6 only.
Digital Select
di.1
I/P2
Master Output
I/P1
Process Variable
Manual Output
ao1
A2.3
The analog backup station can be used in series or in parallel with the master output signal. (See Fig. A1). Parallel operation is achieved by using
relay 1 in the COMMANDER 500 to energize an external relay (with suitable changeover contacts for switching low level signals) which selects the
output to be routed to the actuator.
The Analog Backup provides a backup for a master controller. In normal operation (remote control mode selected) the COMMANDER 500s current
output follows the master controllers output value. A fault in the master system can be identified either by detecting a low signal on the master output
(template 5) or via a digital signal (template 6). When a fault is detected the COMMANDER 500 switches into local control mode and the process is
controlled by the PID output of the COMMANDER 500. The COMMANDER 500 PID algorithm continually tracks the master output value to ensure
bumpless transfer from remote to local mode operation. When the master signal is restored or the digital input returns to its normal state the
COMMANDER 500 switches back to remote control mode (i.e. COMMANDER 500 output = master output).
1 Template 8 Only
I/P2
I/P1
PV1
PV2
ao1
Manual Output
A3
The Indicator/manual Loader Station is used to display one or two process variables on the digital and bargraph displays. If the control output
is assigned to an analog output, the lower display indicates its value which can be adjusted by the user. This output can be used to manually
control a process or to provide a set point value for another controller.
89
Introduction
Using the COMMANDER Configurator the COMMANDER 500 can be programmed without using any of the front
panel keys.
In addition to the standard settings, the Configurator also gives access to more advanced features not accessible
via the front panel keys. These are summarized below.
For information on using individual features, refer to the on-line help facility.
Note. The instrument must be in Configuration Mode (Level 6 or above) and Modbus serial communications
must be disabled when uploading or downloading from the PC Configurator.
B2
Standard Linearizers can be assigned to electrical inputs (eg. allowing transmitter inputs to have
thermocouple or resistance linearizers to be applied)
B3
Standard Arithmetic
Operands:
Average
The average value of an analog signal over a selectable time period, reset by digital
signal
Maximum detection
Minimum detection
Relative humidity
Square root
Input multiplexer
B4
Elements
Up to 15 per equation
Operators
Operands
B5
B6
B7
90
B9
Template Customization
Each template can be customized by changing the sources for various functions in the COMMANDER 500. This
allows maths blocks and custom linearizers to be added into the standard template format.
The following sources can be programmed:
ratio inputs
bias inputs
B10
Note.
The COMMANDER 500 must be in the configuration
mode (Levels 6 to E) and Modbus serial communications
must be disabled when using the PC Configurator.
91
FRAMES INDEX
Set Up Frames
P
Mnemonic
Frame Title
A
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
1
2
3
4
5
6
7
8
1.xxx
2.xxx
3.xxx
4.xxx
5.xxx
6.xxx
7.xxx
8.xxx
Trip
Trip
Trip
Trip
Trip
Trip
Trip
Trip
4.03
4.04
4.05
4.06
4.07
4.08
Pb-1
Pb-2
Pb-3
Pb-4
2.05
2.06
2.07
2.08
r.rtE
r.trV
bIAS
rAtO
3.10
5.04
3.07
3.06
LEV3
3.00
LEV2
2.00
LEV5
5.00
R
Ramp Rate
Regulator Travel Time
Remote Set Point Bias
Remote Set Point Ratio
S
Approach Band 1
Ab 1
S.SPt
CYC1
CYC2
2.21 Tune
2.01
2.02 V
Valve Set Up
D
Deadband (Feedback only)
Derivative Action Time 1
d.bNd
drV1
5.03
2.13
Y1St
Y2St
2.22
2.23
IAt.1
IAt.2
IAt.3
IAt.4
2.01
2.10
2.11
2.12
LSP.1
LSP.2
LSP.3
LSP.4
3.01
3.02
3.03
3.04
rSt.1
VbIA
VrAt
2.17
5.02
5.01
HYS.1
HYS.2
2.03
2.04
Mnemonic
H
Heat/Cool Output 1 Start
Heat/Cool Output 2 Start
I
Integral
Integral
Integral
Integral
Action
Action
Action
Action
Time
Time
Time
Time
1
2
3
4
Parameter
Setting/Value
L
Local
Local
Local
Local
Set
Set
Set
Set
Point
Point
Point
Point
1
2
3
4
M
Manual Reset
Motorised Valve Bias
Motorised Valve Ratio
O
Output 1 On/off Hysteresis Value
Output 2 On/off Hysteresis Value
92
Frame Number
FRAMES INDEX
Configuration Frames
Frame Title
Mnemonic
Number
A
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
1 Hysteresis
1 Trip
1 Type
2 Hysteresis
2 Trip
2 Type
HYS.1
trP.1
tYP.1
HYS.2
trP.2
tYP.2
8.03
8.02
8.01
8.06
8.05
8.04
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
3 Hysteresis
3 Trip
3 Type
4 Hysteresis
4 Trip
4 Type
HYS.3
trP.3
tYP.3
HYS.4
trP.4
tYP.4
8.09
8.08
8.07
8.12
8.11
8.10
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
5 Hysteresis
5 Trip
5 Type
6 Hysteresis
6 Trip
6 Type
HYS.5
trP.5
tYP.5
HYS.6
trP.6
tYP.6
8.15
8.14
8.13
8.18
8.17
8.16
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
7 Hysteresis
7 Trip
7 Type
8 Hysteresis
8 Trip
8 Type
HYS.7
trP.7
tYP.7
HYS.8
trP.8
tYP.8
8.21
8.20
8.19
8.24
8.23
8.22
FPAK
Alarm Acknowledge Enable
LEV8, ALMS
Alarm Configuration
b.03
8.00
OFF.1
SPN.1
OFF.2
SPN.2
OFF.3
SPN.3
E.01
E.02
E.03
E.04
E.05
E.06
AN1H
AN1L
r1H
r1L
AN2H
AN2L
r2H
r2L
C.03
C.04
C.05
C.06
C.11
C.12
C.13
C.14
AN1A
AN2A
tYP.1
tYP.2
C.02
C.10
C.01
C.09
ASrC
FP.AM
A.PAS
A.18
b.01
b.07
Analog
Analog
Analog
Analog
Analog
Analog
I/P
I/P
I/P
I/P
I/P
I/P
1
1
2
2
3
3
Analog
Analog
Analog
Analog
Analog
Analog
Analog
Analog
O/P
O/P
O/P
O/P
O/P
O/P
O/P
O/P
Offset Cal
Span Cal
Offset Cal
Span Cal
Offset Cal
Span Cal
1
1
1
1
2
2
2
2
Electrical High
Electrical Low
Engineering High
Engineering Low
Electrical High
Electrical Low
Engineering High
Engineering Low
LEV6, APPL
b.dIS
6.00
b.06
LEVE, CAL
bEtA
CJ 1
CJ 2
rEF
E.00
E.14
E.15
E.16
E.13
Configuration Password
Configured Output 1
Configured Output 2
Configured Output 3
Control Action
C.PAS
C.OP.1
C.OP.2
C.OP.3
C.ACt
b.09
A.13
A.15
A.17
6.03
Control Configuration
LEV.A
A.00
dAY
dG1P
dG1A
dG2P
dG2A
b.10
C.08
C.07
C.16
C.15
Fb.HI
Fb.LO
E.12
E.11
Basic Configuration
Bias Display Enable
C
Calibration
CJ Beta Value
CJ Reading - I/P1 & I/P2
CJ Reading - I/P3
CJ Reference Value
D
Day Setting
Digital Output
Digital Output
Digital Output
Digital Output
1
1
2
2
Polarity
Source
Polarity
Source
F
Feedback Range High
Feedback Range Low
I
Input
Input
Input
Input
Input
Input
Input
1
1
1
1
1
1
1
Broken Sensor
Decimal Point
Engineering High
Engineering Low
Filter Time Constant
Temp Units
Type
bSd.1
dP.1
EN1H
EN1L
FLt.1
UNt.1
tYP.1
7.06
7.03
7.04
7.05
7.07
7.02
7.01
Input
Input
Input
Input
Input
Input
Input
2
2
2
2
2
2
2
Broken Sensor
Decimal Point
Engineering High
Engineering Low
Filter Time Constant
Temp Units
Type
bSd.2
dP.2
EN2H
EN2L
FLt.2
UNt.2
tYP.2
7.13
7.10
7.11
7.12
7.14
7.09
7.08
Input
Input
Input
Input
Input
Input
Input
3
3
3
3
3
3
3
Broken Sensor
Decimal Point
Engineering High
Engineering Low
Filter Time Constant
Temp Units
Type
bSd.3
dP.3
EN3H
EN3L
FLt.3
UNt.3
tYP.3
7.20
7.17
7.18
7.19
7.21
7.16
7.15
93
...FRAMES INDEX
S
LEV7
LC.Sr
FPLr
Lr.Sr
7.00
9.13
b.02
9.12
MV Calibration selection
MV Feedback closed
MV Feedback open
Mains Rejection
Man/Auto Selection Source
Manual 1 Selection Source
Manual 2 Selection Source
FCAL
C.CAL
O.CAL
F.rEJ
AM.Sr
M.Sr1
M.Sr2
E.07
E.09
E.10
6.06
A.16
A.12
A.14
MODBUS Address
MODBUS Parity
Addr
PrtY
d.03
d.02
Level Heading
Local Set Point Source
Local/Remote Enable
Local/Remote Set Point Source
Serial Communications
Serial Configuration
Set Point Configuration
Set Point 1 Source
Set Point 2 Source
Set Point 3 Source
Set Point 4 Source
Set
Set
Set
Set
Point
Point
Point
Point
Default Value
High Limit
Low Limit
Tracking
Set up Password
Set Point Adjust Disable
LEVd
S.CFG
LEV9, SEt.P
L.Sr.1
L.Sr.2
L.Sr.3
L.Sr.4
d.00
d.01
9.00
9.08
9.09
9.10
9.11
dF.SP
SPt.H
SPt.L
trCK
9.07
9.02
9.03
9.01
S.PAS
S.AdJ
b.08
b.04
t.APP
t.CLK
t1Sr
t2Sr
t3Sr
t4Sr
6.01
b.13
A.19
A.20
A.21
A.22
T
O
OP.LO
OP.HI
OP1H
OP2H
OP2L
LEVb, OPEr
A.06
A.05
A.07
A.08
A.09
b.00
LEVC, ASSn
Assignment
OP.Sr
Slew Rate
SrdS
Slew Rate Disable
O.tYP
Type
C.00
A.10
A.11
6.02
P.rEC
rEC.t
PVFA
dF.OP
A.01
A.02
A.03
A.04
r.dIS
r.trV
rL1P
rL1A
rL2P
rL2A
b.05
E.08
C.18
C.17
C.20
C.19
Relay 3 Polarity
Relay 3 Source
Relay 4 Polarity
Relay 4 Source
Remote Set Point Source
RSPT Fault Action
rL3P
rL3A
rL4P
rL4A
r.SrC
SP.FA
C.22
C.21
C.24
C.23
9.14
9.06
P
Power Fail Recovery Mode
Power Fail Recovery Time
Process Variable Fail Action
PV Fail Default Output
94
Template Applications
Time Display
Tune Select Source 1
Tune Select Source 2
Tune Select Source 3
Tune Select Source 4
INDEX
Accessories .............................................................. 1
Alarms ........................................................... 34, 47
Acknowledge ..................................................... 5
Acknowledge enable ....................................... 59
Configuration ................................................... 47
Hysteresis ................................................. 49, 50
Set Up ............................................................. 34
Trip Settings .............................................. 34, 47
Type ........................................................... 34, 49
Analog Backup Station ..................................... 16, 84
Analog Inputs Level 7 ......................................... 43
Broken Sensor .................................... 44, 45, 46
Decimal Point ...................................... 43, 45, 46
Engineering Range ............................. 44, 45, 46
Calibration ....................................................... 68
Failure Action .................................................. 55
Analog Outputs 1 and 2 ......................................... 61
See Also: Digital Outputs 1 and 2
Electrical Ranges ...................................... 62, 64
Engineering Ranges ................................. 62, 64
Sources ..................................................... 62, 64
See Also: Rear Fold-out/ Table D
Analog Sources .................... Rear Fold-out/ Table D
Approach Band ....................................................... 30
Auto-tune ................................................................ 21
Error ................................................................. 21
Password ......................................................... 60
Starting ............................................................ 23
Auto/Manual
Mode Selection Source ....................... 56, 57, 58
A/M Station Template ............................... 14, 74
A/M Switch .................................................. 4, 50
D
Date and Time Setting ........................................... 60
Deadband
Control Output ................................................. 31
MV Feedback .................................................. 35
Default Outputs .......................................... 52, 55, 57
Delay Timer ............................................................ 86
Derivative Action Time ........................................... 30
Deviation Alarms .................................................... 47
Digital Inputs 1 to 4 .......................................... 76, 77
See Also: Rear Fold-out/ Table C
Digital Outputs 1 and 2 .......................................... 61
Polarity ...................................................... 61, 63
Source ....................................................... 61, 63
Digital Sources ..................... Rear Fold-out/ Table C
Direct Control Action .............................................. 42
Displays ......................................................... 8, 9, 11
LCD Alphabet .................................................... 8
E
Electrical Connections ........................................... 76
Error Codes .............................................................. 9
B
Bargraphs ................................................................. 3
See Also: Relevant
Operator Template in Section 2
Basic Configuration Level 6 ................................ 39
Boundless Control see Motorized Valves
Broken Sensor Drive .................................. 44, 45, 46
C
Calibration see Analog Inputs
Calibration Error ....................................................... 9
Character Set ........................................................... 8
Clock Settings ........................................................ 60
Cold Junction
Compensation ..................................... 70, 77, 80
Failed ................................................................. 9
F
Failure Modes
Analog Input .................................................... 55
Power Failure .................................................. 54
Process Variable ............................................. 55
Remote Set Point ............................................ 52
Fault-finding see Error Messages
Fault Detection Level ............................................. 86
Feedback (Motorized Valves) ................................ 35
See Also: Analog Inputs (Process Variable)
Filter Time Constant ................................... 44, 45, 46
Fine Tuning ...................................................... 25, 68
G
Gain Scheduling
Selection .......................................................... 58
Sources ........................................................... 58
Proportional and Integral Terms ..................... 29
Glossary of Abbreviations ...................................... 10
95
...INDEX
Heat/Cool ................................................................ 19
Control Action ........................................... 40, 42
Output limits .................................................... 55
Start positions ................................................. 31
Hysteresis
Alarms .................................................... 47 to 50
On/off Control .................................................. 28
Output
Assignment Level C ..................................... 61
Connections ........................................ 76, 78, 79
Heat/Cool ........................................................ 19
Limits ............................................................... 55
Slew Rate ........................................................ 56
Output Sources
Types ............................................................... 40
Option Board .......................................................... 76
I
Inputs see Analog Inputs
Installation .............................................................. 71
Integral Action Time ............................................... 29
K
Klaxon Alarms ........................................................ 47
L
Latch Alarms .......................................................... 48
LEDs
................................................................... 8
Linearizers ........................................... 43, 45, 46, 86
Line Filter Frequency ............................................. 42
Local Set Point see Set Points
Local/Remote Key Enable ..................................... 59
Local/Remote Mode Selection .............. 6, 16, 52, 53
Locking Front Panel Keys ...................................... 59
Logic Equations ...................................................... 86
Loop Break Monitor ................................................ 10
M
Mains Rejection Frequency ................................... 42
Manual Mode Selection ............................. 56, 57, 59
Pre-set manual output .................................... 57
Manual Reset ......................................................... 30
Maths Blocks .......................................................... 86
Mechanical Installation ........................................... 71
MODBUS .......................................................... 67, 76
Mounting ................................................................. 72
Motorized Valve
Boundless ........................................................ 36
Calibration ....................................................... 69
Connections .................................................... 79
Control Type Selection ................................... 40
Feedback ......................................................... 35
Regulator Travel Time ........................ 35, 37, 69
Set Up ............................................................. 35
O
On/Off Control ........................................................ 28
See Also: Control Types
Operator Configuration Level B .......................... 59
Operating Displays ................................................... 3
Operator Ratio/Bias Display Enable ...................... 59
Operator Level ........................................................ 11
96
P
Panel Clamps ..................................................... 2, 73
PC Configurator ...................................................... 86
PID Parameters ................................................ 29, 30
See Also: Gain Scheduling
Power Fail Recovery .............................................. 54
Power Supplies ................................................ 76, 80
Power Up Displays ................................................. 11
Process
Alarms ............................................................. 48
Labels .............................................................. 75
Optimization see Control Efficiency Monitor
Variable see Analog Inputs
Proportional Band Settings .............................. 29, 30
R
Ramp Rate (Set Point) ........................................... 33
See Also: Output Slew Rate
Ratio
Ratio Display Enable ...................................... 59
Remote Set Point ............................................ 32
Real-time Alarm ...................................................... 86
Reference Tables ................................ Rear Fold-out
Relative Humidity ................................................... 86
Regulator Travel Time see Motorized Valves
Relay
Connections .................................................... 76
Links ................................................................ 78
See Also: Output Assignment, Output Types
Remote Set Point
Failure Action .................................................. 52
Scaling ............................................................. 32
Selection Source ............................................. 53
Resistance Thermometer ........................... 43, 46, 76
Retransmission See Analog Outputs,
Analog Sources
Reverse Control Action .......................................... 42
INDEX
S
Secret-til-Lit Indicators ............................................. 8
Security Options ..................................................... 60
Serial Communications Level d .......................... 67
Set Points
Configuration Level 9 ................................... 51
Default Value ................................................... 52
Limits ............................................................... 51
Operator Adjust enable ................................... 59
Ramp Rate ...................................................... 33
Scaling ............................................................. 32
Selecting .......................................................... 52
Setting see Relevant Operator Template
Sources ........................................................... 52
Tracking ........................................................... 51
Single Loop
Controllers ........................................... 12, 16, 81, 84
Siting
................................................................. 71
Short-cut keys .......................................................... 7
Slew Rate ............................................................... 56
Soft-start see Set Point Ramp Rate,
Output Slew Rate
Span Adjustment see Calibration
T
Temperature Units ..................................... 43, 45, 46
Template Applications ................................ 11, 39, 81
Rear Fold-out, Table A
Terminals and Connections ................................... 76
Thermocouple ............................... 43, 44, 45, 46, 76
Time
Setting ............................................................. 60
Real-time alarms ............................................. 86
Delay Timers ................................................... 86
Tuning
Automatic ........................................................ 21
Manual ............................................................. 25
Tune Parameter Source ................................. 58
U
Units see Temperature Units
V
Valve see Motorized Valve
Valve Sticking ........................................................... 9
W
Warning Messages .................................................. 9
Watchdog ............................................................... 10
97
NOTES
98
NOTES
99
...NOTES
100
REFERENCE TABLES
Analog Input 1
(I/P1)
Template Title
Analog Input 2
(I/P2)
Analog Input 3
(I/P3) *
1. SL
Single loop
Process Variable
2. SL
Process Variable
3. AM
Process Variable
Master Output
4. AM
Process Variable
Master Output
Feedback
Feedback
5. Ab
Process Variable
Master Output
6. Ab
Process Variable
Master Output
7. In
Process Variable
8. In
NONE
ANLG
rLY
dIG
Relays
Output Type
Analog Outputs
Digital Outputs
Rly 1
Rly 2
Rly 3
Rly 4
ao1
ao2
do1
do2
Analog Output
Alm1#
Alm 2#
Alm 3
Alm 4
OP1
PV
Relay Output
OP1
Alm 1#
Alm 2
Alm 3
PV
CSPT
None
Digital Output
Alm 1
Alm 2
Alm 3
Alm 4
OP1
PV
OP1
PFb
Motorized valve
with FB*
OPEN
CLOSE
Alm 1
Alm 2
PV
CSPT
bnd
Motorized valve
without FB
OPEN
CLOSE
Alm 1
Alm 2
PV
CSPT
HCr
. r
Heat/Cool
OP1
(Heat)
OP2
(Cool)
Alm 1
Alm 2
PV
CSPT
HCr
. d
HCd
. r
HCd
. d
HCA
. r
HCA
. d
HCA
. A
Heat/Cool
OP1
Alm 1
Alm 2
Alm 3
PV
OP2
Heat/Cool
OP2
Alm 1
Alm 2
Alm 3
PV
OP1
Heat/Cool*
Alm 1
Alm 2
Alm 3
Alm 4
OP1
OP2
Heat/Cool
OP2
Alm 1
Alm 2
Alm 3
OP1
PV
Heat/Cool*
Alm 1
Alm 2
Alm 3
Alm 4
OP1
PV
OP2
Heat/Cool*
Alm 1
Alm 2
Alm 3
Alm 4
OP1
OP2
Alm = Alarm
Rly = Relay
ao1 = Analog Output1
ao2 = Analog Output2
do1 = Digital Output 1
REFERENCE TABLES
Display
Source Type
Description
OP1
OP2
Failure
States
Control
Modes
FI
. N1
. Input 1 failed
FI
. N2
. Input 2 failed
A1
Alarm 1 active
LbK2
A2
Alarm 2 active
dOG
Watchdog active
A8
Digital
inputs
Description
FI
. N3
. Input 3 failed
LbK1 Loop break - analog output 1
PF
Alarm
Acknowledge
Display
Alarm 8 active
Logic
equations*
D.G3
D.G4
MAN
LG 2
Power fail
Logic equation 1 true
Logic equation 2 true
:
Timers
LG 1
LG 6
rt1
rt2
dt1
Delay timer 1
dt2
Delay timer 2
_b.1
MODBUS Signal 1
_b.2
MODBUS Signal 2
AUt
_b.3
MODBUS Signal 3
LOC
_b.4
MODBUS Signal 4
rEM
MODBUS
Other
ON
Always enabled
OP1
OP2
Description
Display
SSPt
Description
Slave setpoint
dEV1
PV
Process variable 1
AVP
PV2
Process variable 2
bLK1
I/P1
Analog input 1
bLK2
I/P2
Analog input 2
bLK3
I/P3
Analog input 3
bLK4
CSPt
Control setpoint
CUS.1
rSPt
Remote setpoint
CUS.2
LSP1
Local setpoint 1
PID1
LSP2
Local setpoint 2
rb.
LSP3
Local setpoint 3
LSP4
Local setpoint 4
Customer Support
We provide a comprehensive after sales service via a
Worldwide Service Organization. Contact one of the
following offices for details on your nearest Service
and Repair Centre.
United Kingdom
ABB Limited
Tel: +44 (0)1480 475 321
Fax: +44 (0)1480 217 948
Flexible Automation
Flow Measurement
Electromagnetic Flowmeters
Mass Flow Meters
Turbine Flowmeters
Flow Elements
Electrical Systems
Marine Equipment
Offshore Retrofit and Referbishment
Process Analytics
Transmitters
Pressure
Temperature
Level
Interface Modules
Control Valves
Actuators
Positioners
Client Warranty
Prior to installation, the equipment referred to in
this manual must be stored in a clean, dry
environment, in accordance with the Company's
published specification.
Periodic checks must be made on the
equipment's condition. In the event of a failure
under warranty, the following documentation
must be provided as substantiation:
1. A listing evidencing process operation and
alarm logs at time of failure.
2. Copies of all storage, installation, operating
and maintenance records relating to the
alleged faulty unit.
www.abb.com
Printed in UK (01.06)
IM/C501
Issue 10
ABB 2006
ABB Limited
Howard Road, St. Neots
Cambridegshire, PE19 8EU
UK
Tel: +44 (0)1480 475 321
Fax: +44 (0)1480 217 948
ABB Inc.
125 E. County Line Road
Warminster
PA 18974
USA
Tel: +1 215 674 6000
Fax: +1 215-674 7183