Multi-Application Peripherals
UL, ULC Listed; FM
and CSFM Approved*
Ionization Smoke Detectors
Model 4098-9603 for Two-Wire and Four-Wire Bases
Features
UL Listed to Standard 268
Functional chamber enclosure:
Louvered design enhances smoke capture by
directing flow to chamber
Entrance areas are minimally visible when ceiling
mounted
4098-9603 Ionization Detector Mounted in Base
Alarm indicator LED:
Pulses to indicate power-on
On steady to indicate alarm
Functional diagnostic tests:
Magnetic test initiates alarm and verifies system
operation
Service connections are available for sensitivity
verification testing
Available base options:
Bases for 2-wire or 4-wire operation
Auxiliary alarm relay output
Remote alarm indicating LED output
Application Reference
Detector Locations. Locations should be determined
only after careful consideration of the physical layout and
contents of the area to be protected. Refer to NFPA 72,
the National Fire Alarm Code. On smooth ceilings,
smoke detector spacing of 30 ft (9.1 m) may be used as a
guide.
For further detailed installation information, refer to
Simplex publication 574-709, 4098 Detectors, Sensors,
and Bases Application Manual.
Specifications
Optional remote alarm LED indicator
Voltage
8.5 to 33 VDC, from fire alarm
control panel Initiating Device
Circuit (IDC )
Standby Current
80 A @ 24 VDC
Alarm Current, 2-Wire Operation
Up to 86 mA maximum, exact
current is determined by alarm
current limiting of connected IDC
Alarm Current, 4-Wire Operation
24 mA typical @ 24 VDC
Sensitivity Level
0.61 to 1.46%/ft
Radioactive Source
0.9 Microcurie AM-241
Air Velocity Range
0-300 ft/min (0-90 m/min)
Altitude
Up to 8000 ft (2438 m)
UL Listed Temperature Range
32 F to 100 F (0 C to 38 C)
Operating Temperature Range
32 F to 122 F (0 C to 50 C)
Humidity Range
10% to 95% RH from 32 F to
122 F (0 C to 50 C)
Color
Frost White
Dimensions
Refer to diagram on page 2
Description
For applications requiring ionization detection, the
4098-9603 detector provides conventional dual-chamber
detection in an attractive housing. Bases are available for
2-wire or 4-wire operation.
A built-in magnetic test feature allows service personnel
to conveniently initiate a test alarm condition.
Options include relay outputs and remote LED alarm
status indicators.
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7271-0026:229 for allowable values and/or conditions concerning material presented in
this document. It is subject to re-examination, revision, and possible cancellation. ULC
listed models are designated with a C suffix such as 4098-9603C, refer to page 2 for
model availability. This product was not approved by MEA (NYC) as of document revision
date. Additional listings may be applicable; contact your local Simplex product supplier for
the latest status. Listings and approvals under Simplex Time Recorder Co. are the
property of Tyco Safety Products Westminster.
S4098-0018-3 6/2003
Product Selection
Model
4098-9603
Description
Compatibility
Ionization Smoke Detector
Compatible with detector bases:
4098-9788, 4098-9682, and 4098-9683
Detector Bases
Model
Description
4098-9788
2-Wire Base with connections for Remote
Alarm LED Indicator
IDC and LED connections are screw terminals for in/out
wiring, 18 to 14 AWG
4-Wire Base with Auxiliary Alarm Relay
Contacts and connections for Remote
LED Alarm Indicator
Relay Ratings, Single Form C, For Suppressed Loads:
Power limited, 3 A @ 28 VDC
Non-power limited, 3 A @ 120 VAC
Wiring Connections (In/Out where required):
Relay contacts and IDC wiring, color coded 18 AWG leads
LED wiring, screw terminals for 18 to 14 AWG
4098-9682
4098-9683
2-Wire Base with Auxiliary Alarm Relay
and connections for Remote LED
Indicator
NOTE: Must be connected as the only device
on the IDC to ensure relay operation.
Details
Relay Ratings, Dual Form C, For Suppressed Loads:
Power limited, 1 A @ 28 VDC
Non-power limited, 1/2 A @ 120 VAC
Wiring Connections (In/Out where required):
Relay contacts and IDC (-), color coded 18 AWG leads
IDC (+) and LED wiring, screw terminals for 18 to 14 AWG
Detector Accessories
Model
Description
Details
4098-9832
Adapter Plate
Required for mounting to surface mounted boxes and 4
square, flush mounted box
May be used when retrofitting existing bases
Compatible with 4098-9788, -9682, & -9683 detector bases
4098-9830
Remote LED Indicator
Mounted on single gang stainless steel plate
2098-9739
Encapsulated 24 VDC End-of-Line Relay
2098-9735
Plate Mounted 24 VDC End-of-Line Relay
Required for 4-wire circuits using 4098-9682 base, one per
circuit, select mounting type as required
Metric wire equivalents: 18 AWG = 0.82 mm2; 14 AWG = 2.08 mm2
Detector and Base Dimension Reference
4-7/8" (124 mm)
Base height
11/16"
(17 mm)
1-7/8"
(48 mm)
LED Status Indicator
(with clear lens)
S4098-0018-3 6/2003
Mounting Reference
Electrical Box Requirements:
Without relay (base 4098-9788):
4" octagonal or 4" square, 1-1/2" deep
Single gang, 2" deep
With relay (bases 4098-9682 and 4098-9683):
4" octagonal, 1-1/2" deep, with 1-1/2" extension ring
4" square, 1-1/2" deep, with 1-1/2" extension ring
Surface mount reference
4" (102 mm)
square box
4" (102 mm)
octagonal box
1-1/2" (38 mm)
minimum box depth
Flush mount reference, mount even with final
surface, or with up to 1/4" (6.4 mm) maximum recess
4098-9832 Adapter Plate, required for mounting
to surface mounted boxes and to 4" square flush mount boxes
4098-9682 and 4098-9683
include a relay module that
mounts in base electrical box
Smoke Detector Bases
4098-9788, 9682, & -9683
4098-9603 Smoke Detector
S4098-0018-3 6/2003
Tyco, Simplex and the Simplex logo are trademarks of Tyco International Services AG or its affiliates in the U.S. and/or other countries. NFPA 72 and National Fire Alarm Code
are registered trademarks of the National Fire Protection Association (NFPA).
Tyco Safety Products Westminster Westminster, MA 01441-0001 USA
www.tycosafetyproducts-usa-wm.com
S4098-0018-3 6/2003
2003 Tyco Safety Products Westminster. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.