100% found this document useful (1 vote)
231 views4 pages

4098 0018 Ioniz Conv Detec

The document provides information about an ionization smoke detector model 4098-9603 including its features, specifications, accessories, and installation instructions.

Uploaded by

asifaliabid
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
231 views4 pages

4098 0018 Ioniz Conv Detec

The document provides information about an ionization smoke detector model 4098-9603 including its features, specifications, accessories, and installation instructions.

Uploaded by

asifaliabid
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Multi-Application Peripherals

UL, ULC Listed; FM


and CSFM Approved*

Ionization Smoke Detectors


Model 4098-9603 for Two-Wire and Four-Wire Bases

Features
UL Listed to Standard 268
Functional chamber enclosure:

Louvered design enhances smoke capture by


directing flow to chamber
Entrance areas are minimally visible when ceiling
mounted

4098-9603 Ionization Detector Mounted in Base

Alarm indicator LED:

Pulses to indicate power-on


On steady to indicate alarm

Functional diagnostic tests:

Magnetic test initiates alarm and verifies system


operation
Service connections are available for sensitivity
verification testing

Available base options:

Bases for 2-wire or 4-wire operation


Auxiliary alarm relay output
Remote alarm indicating LED output

Application Reference
Detector Locations. Locations should be determined
only after careful consideration of the physical layout and
contents of the area to be protected. Refer to NFPA 72,
the National Fire Alarm Code. On smooth ceilings,
smoke detector spacing of 30 ft (9.1 m) may be used as a
guide.
For further detailed installation information, refer to
Simplex publication 574-709, 4098 Detectors, Sensors,
and Bases Application Manual.

Specifications

Optional remote alarm LED indicator


Voltage

8.5 to 33 VDC, from fire alarm


control panel Initiating Device
Circuit (IDC )

Standby Current

80 A @ 24 VDC

Alarm Current, 2-Wire Operation

Up to 86 mA maximum, exact
current is determined by alarm
current limiting of connected IDC

Alarm Current, 4-Wire Operation

24 mA typical @ 24 VDC

Sensitivity Level

0.61 to 1.46%/ft

Radioactive Source

0.9 Microcurie AM-241

Air Velocity Range

0-300 ft/min (0-90 m/min)

Altitude

Up to 8000 ft (2438 m)

UL Listed Temperature Range

32 F to 100 F (0 C to 38 C)

Operating Temperature Range

32 F to 122 F (0 C to 50 C)

Humidity Range

10% to 95% RH from 32 F to


122 F (0 C to 50 C)

Color

Frost White

Dimensions

Refer to diagram on page 2

Description
For applications requiring ionization detection, the
4098-9603 detector provides conventional dual-chamber
detection in an attractive housing. Bases are available for
2-wire or 4-wire operation.
A built-in magnetic test feature allows service personnel
to conveniently initiate a test alarm condition.
Options include relay outputs and remote LED alarm
status indicators.

* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7271-0026:229 for allowable values and/or conditions concerning material presented in
this document. It is subject to re-examination, revision, and possible cancellation. ULC
listed models are designated with a C suffix such as 4098-9603C, refer to page 2 for
model availability. This product was not approved by MEA (NYC) as of document revision
date. Additional listings may be applicable; contact your local Simplex product supplier for
the latest status. Listings and approvals under Simplex Time Recorder Co. are the
property of Tyco Safety Products Westminster.

S4098-0018-3 6/2003

Product Selection
Model

4098-9603

Description

Compatibility

Ionization Smoke Detector

Compatible with detector bases:


4098-9788, 4098-9682, and 4098-9683

Detector Bases
Model

Description

4098-9788

2-Wire Base with connections for Remote


Alarm LED Indicator

IDC and LED connections are screw terminals for in/out


wiring, 18 to 14 AWG

4-Wire Base with Auxiliary Alarm Relay


Contacts and connections for Remote
LED Alarm Indicator

Relay Ratings, Single Form C, For Suppressed Loads:


Power limited, 3 A @ 28 VDC
Non-power limited, 3 A @ 120 VAC
Wiring Connections (In/Out where required):
Relay contacts and IDC wiring, color coded 18 AWG leads
LED wiring, screw terminals for 18 to 14 AWG

4098-9682

4098-9683

2-Wire Base with Auxiliary Alarm Relay


and connections for Remote LED
Indicator
NOTE: Must be connected as the only device
on the IDC to ensure relay operation.

Details

Relay Ratings, Dual Form C, For Suppressed Loads:


Power limited, 1 A @ 28 VDC
Non-power limited, 1/2 A @ 120 VAC
Wiring Connections (In/Out where required):
Relay contacts and IDC (-), color coded 18 AWG leads
IDC (+) and LED wiring, screw terminals for 18 to 14 AWG

Detector Accessories
Model

Description

Details

4098-9832

Adapter Plate

Required for mounting to surface mounted boxes and 4


square, flush mounted box
May be used when retrofitting existing bases
Compatible with 4098-9788, -9682, & -9683 detector bases

4098-9830

Remote LED Indicator

Mounted on single gang stainless steel plate

2098-9739

Encapsulated 24 VDC End-of-Line Relay

2098-9735

Plate Mounted 24 VDC End-of-Line Relay

Required for 4-wire circuits using 4098-9682 base, one per


circuit, select mounting type as required

Metric wire equivalents: 18 AWG = 0.82 mm2; 14 AWG = 2.08 mm2

Detector and Base Dimension Reference

4-7/8" (124 mm)

Base height
11/16"
(17 mm)

1-7/8"
(48 mm)

LED Status Indicator


(with clear lens)

S4098-0018-3 6/2003

Mounting Reference

Electrical Box Requirements:


Without relay (base 4098-9788):
4" octagonal or 4" square, 1-1/2" deep
Single gang, 2" deep
With relay (bases 4098-9682 and 4098-9683):
4" octagonal, 1-1/2" deep, with 1-1/2" extension ring
4" square, 1-1/2" deep, with 1-1/2" extension ring
Surface mount reference
4" (102 mm)
square box

4" (102 mm)


octagonal box

1-1/2" (38 mm)


minimum box depth

Flush mount reference, mount even with final


surface, or with up to 1/4" (6.4 mm) maximum recess

4098-9832 Adapter Plate, required for mounting


to surface mounted boxes and to 4" square flush mount boxes

4098-9682 and 4098-9683


include a relay module that
mounts in base electrical box

Smoke Detector Bases


4098-9788, 9682, & -9683

4098-9603 Smoke Detector

S4098-0018-3 6/2003

Tyco, Simplex and the Simplex logo are trademarks of Tyco International Services AG or its affiliates in the U.S. and/or other countries. NFPA 72 and National Fire Alarm Code
are registered trademarks of the National Fire Protection Association (NFPA).

Tyco Safety Products Westminster Westminster, MA 01441-0001 USA


www.tycosafetyproducts-usa-wm.com

S4098-0018-3 6/2003

2003 Tyco Safety Products Westminster. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.