SINOTEC
C O. ,
LT D
Request for Quotation (RFQ) No: ----------Date of issue:
Closing Date and Time
Contact details for Clarifications
Tuesday, June 16, 2015
Friday, June 19, 2015
10:00 AM
Mr. Liu (
[email protected])
33-A ; Block-G ; Gulberg-III ; Lahore
Tel: +92-42-35881238-9
Fax: +92-42-35881241
1. INVITATION FOR QUOTATION
Quotations are hereby invited for the supply of a Transformers as per below requirement:
No.
Description
Qty
1
2
3
4
300 KVA Transformer (Oil Type)
5
1
1
1
400 KVA Transformer (Oil Type)
300 KVA Transformer (Dry Type)
400 KVA Transformer (Dry Type)
Rate (PKR)
Amount
(PKR)
2. QUOTATION REQUIREMENTS
The subject equipment is required at our on-going projects in Punjab and the technical data sheets are
attached also.
The price should include the detailed design and approval
The price should include supervision during Installation and commissioning
3. PRICING QUOTATION
Price needs to be provided EX-Works , with details on price elements that are subject to change in
future should be clearly indicated.
Price should include additional cost elements such as freight, insurance until acceptance, duty , taxes
(GST ect.) where applicable, etc.
Pakistan Office: 33-A, Block-G, Gulberg-III, Lahore Tel: +92 42 35881238-9 Fax: +92 42 35881241
SINOTEC
Payment Terms and Conditions.
Delivery Schedule
C O. ,
LT D
NOTE: No goods and/or services should be delivered without an official Purchase order.
SPECIFICATION - 300 KVA (Oil Type)
Rated kVA Voltage Ratio
300
Basic Insulation Level (BIL)
Frequency / Phases Vector
11000 /
50 Hz
Group
Type of Cooling
400 Y
/
Dyn 11 ONAN A
Insulation Class Ambient
40
0C
Temperature
Top Oil
Temperature Rise at Rated kVA
Average
60
65
Tapping Voltages (%)
0C
LV
LI - AC 3 HV
LI 75 AC 28
1.25,2.5,3.75,5.0
HV Terminals LV Terminals
1.25,2.5,3.75,5.0
Service Altitude Above Sea Level
Type of Tank
Type
1000 meter Sealed
Winding
0C
Indoor /Outdoor
PERFORMANCE
No Load Losses at Principle Tap Position
0.75 kW
Load Losses at Principle Tap Position & Rated Current
5.6 kW
Impedance
4.00 %
Regulation at Unity Power Factor & Rated Current
1.93 %
Regulation at 0.8 Power Factor & Rated Current
3.63 %
Efficiency at Unity Power Factor & 100% Rated Current
97.93 %
Efficiency at Unity Power Factor & 50% Rated Current
98.59 %
COMPONENTS & ACCESSORIES
Off Circuit Tap Changer
Pressure Relief Device (without contacts) (Elmek, Turkey)
Oil Filling Hole and Plug
Thermometer for Oil Temperature with maximum Temperature
Oil Level Indicator
indicator (without contacts) (Elmek, Turkey)
Oil Drain Valve
HT/ LT Cable Box
Lifting Lugs
Transport Eyes
Earthing Terminals
Rating & Diagram Plate (Stainless Steel)
Pakistan Office: 33-A, Block-G, Gulberg-III, Lahore Tel: +92 42 35881238-9 Fax: +92 42 35881241
SINOTEC
C O. ,
LT D
SPECIFICATION FOR
400 KVA (Oil Type)
Rated kVA
400
Basic Insulation Level
LV
LI
AC
Voltage Ratio
11000
Frequency / Phases
50
400
Hz
(BIL)
HV
LI
75
AC
1.25,2.5,3.75,5.0
Tapping Voltages (%)
Vector Group
Dyn 11
Type of Cooling
ONAN
HV Terminals
Insulation Class
LV Terminals
Ambient Temperature
40
Top Oil
60
Winding
65
1.25,2.5,3.75,5.0
Service Altitude Above Sea Level
1000 meter
Type of Tank
Sealed
Type
Indoor /Outdoor
Temperature Rise at Rated kVA
C
Average
PERFORMANCE
No Load Losses at Principle Tap Position
0.95 kW
Load Losses at Principle Tap Position & Rated Current
6.6 kW
Impedance
4.00%
Regulation at Unity Power Factor & Rated Current
1.72%
Regulation at 0.8 Power Factor & Rated Current
3.52%
Efficiency at Unity Power Factor & 100% Rated Current
98.15%
Efficiency at Unity Power Factor & 50% Rated Current
98.72%
COMPONENTS
ACCESSORIES
&
Off Circuit Tap Changer
Pressure Relief Device (without contacts) (Elmek, Turkey)
Oil Filling Hole and Plug
Thermometer for Oil Temperature with maximum
Oil
Temperature indicator (without contacts) (Elmek, Turkey)
Level
Indicator
Oil Drain Valve
Double Float Buchholz Relay (Elmek,
Turkey)
HT/ LT Cable Box
Lifting Lugs
Transport Eyes
Earthing Terminals
Rating
&
Diagram
Plate
(Stainless Steel)
Remarks :
1)
Transformer shall be offered with first filling of oil. Transformer Oil shall be in accordance with IEC-60296
2)
Transformer shall be manufactured and tested as per IEC 600-76 Standard.
Pakistan Office: 33-A, Block-G, Gulberg-III, Lahore Tel: +92 42 35881238-9 Fax: +92 42 35881241
28
SINOTEC
C O. ,
LT D
SPECIFICATIONS 300 KVA (Dry Type)
1
IEC Standard
IEC 60076-11
Structure
Indoor Type (With Enclosure)
Rated Power
Cooling
Rated frequency
Hz
50
Rated primary voltage
KV
11
Rated Primary Insulation Level
KV
12
Applied Voltage to Industrial frequency
Basic Insulation Level
KV
75
10
Power Frequency (AC)
KV
28
11
Off- circuit tapping (No Load)
12
Secondary Voltage at No Load (Line-
400
230.9
kVA
300
AN / AF
11 KV at 50 Hz
1.25 , 2.5 , 3.75 , 5.0 ,
Line)
13
Line to Neutral Voltage
15
Applied
Secondary
to
Industrial
0.400KV at 50 Hz
frequency
16
Vector group
Dyn 11
17
Noise level
dB
18
No Load losses
kW
0.90
19
Load losses at Rated kVA (Winding
kW
3.8
4%
50 dB
Temp: 115 C)
20
% Impedance
22
Maximum ambient temperature
oC
50 C
23
Winding temperature rise
oC
80 C
24
Maximum Hot Spot Temperature
98 K
25
Maximum Altitude
Meter
1000 Meter above Sea Level
26
HV winding tempreature class
27
LV winding tempreature class
28
Temperature of insulation system
29
Conductor material (HV/LV)
Copper
Off Circuit Tap Changer
Caution Plate
Rating & Diagram Plate (Stainless
Steel)
30
Components and Accessories
Roller
Wheels
Lifting Lugs
Earthing
Pakistan Office: 33-A, Block-G, Gulberg-III, Lahore Tel: +92 42 35881238-9 Fax: +92 42 35881241
SINOTEC
C O. ,
LT D
Terminals
Enclosure
with
IP 20
Remarks :
1
Transformer shall be manufactured and tested as per IEC 600-76 Standard.
SPECIFICATIONS 400 KVA (Dry Type)
1
IEC Standard
IEC 60076-11
Structure
Indoor Type (With Enclosure)
Rated Power
Cooling
Rated frequency
Hz
50
Rated primary voltage
KV
11
Rated Primary Insulation Level
KV
12
Applied Voltage to Industrial frequency
Basic Insulation Level
KV
75
10
Power Frequency (AC)
KV
28
11
Off- circuit tapping (No Load)
12
Secondary Voltage at No Load (Line-
400
230.9
kVA
400
AN / AF
11 KV at 50 Hz
1.25 , 2.5 , 3.75 , 5.0 ,
Line)
13
Line to Neutral Voltage
15
Applied
Secondary
to
Industrial
0.400KV at 50 Hz
frequency
16
Vector group
Dyn 11
17
Noise level
dB
18
No Load losses
kW
1.00
19
Load losses at Rated kVA (Winding
kW
4.4
4%
50 dB
Temp: 115 C)
20
% Impedance
22
Maximum ambient temperature
oC
50 C
23
Winding temperature rise
oC
80 C
24
Maximum Hot Spot Temperature
98 K
25
Maximum Altitude
Meter
1000 Meter above Sea Level
26
HV winding tempreature class
27
LV winding tempreature class
28
Temperature of insulation system
29
Conductor material (HV/LV)
Copper
Off Circuit Tap Changer
Caution Plate
Rating & Diagram Plate (Stainless
Pakistan Office: 33-A, Block-G, Gulberg-III, Lahore Tel: +92 42 35881238-9 Fax: +92 42 35881241
SINOTEC
C O. ,
LT D
Steel)
30
Components and Accessories
Roller
Wheels
Lifting Lugs
Earthing
Terminals
Enclosure
with
IP 20
Remarks :
1
Transformer shall be manufactured and tested as per IEC 600-76 Standard.
Pakistan Office: 33-A, Block-G, Gulberg-III, Lahore Tel: +92 42 35881238-9 Fax: +92 42 35881241