Certificate / Certificat
Zertifikat /
UEC 1210073 C001
exida hereby confirms that the:
One Series Safety Transmitter
The manufacturer
may use the mark:
United Electric Controls
Watertown, MA - USA
Has been assessed per the relevant requirements of:
IEC 61508 : 2010 Parts 1-7
and meets requirements providing a level of integrity to:
Systematic Capability: SC 3 (SIL 3 Capable)
Random Capability: Type B Element
SIL 2 @ HFT=0; SIL 3 @ HFT = 1; Route 1H
Valid until May 1, 2017
Revision 1.0 April 14, 2014
PFDAVG and Architecture Constraints
must be verified for each application
Safety Function:
The One Series Safety Transmitter will measure pressure or
temperature within the stated safety accuracy.
Application Restrictions:
The unit must be properly designed into a Safety Instrumented
Function per the Safety Manual requirements.
Place embossed
seal here for
originals, lining it
up at the bottom
ANSI Accredited Program
Evaluating Assessor
Certifying Assessor
PRODUCT CERTIFICATION
#1004
Page 1 of 2
Certificate / Certificat / Zertifikat /
UEC 1210073 C001
Systematic Capability: SC 3 (SIL 3 Capable)
Random Capability: Type B Element
SIL 2 @ HFT=0; SIL 3 @ HFT = 1; Route 1H
PFDAVG and Architecture Constraints
must be verified for each application
One Series Safety
Transmitter
Systematic Capability :
The product has met manufacturer design process requirements of Safety
Integrity Level (SIL) 3. These are intended to achieve sufficient integrity
against systematic errors of design by the manufacturer.
A Safety Instrumented Function (SIF) designed with this product must not
be used at a SIL level higher than stated.
Random Capability:
The SIL limit imposed by the Architectural Constraints must be met for each
element. This Element meets exida criteria for Route 1H.
IEC 61508 Failure Rates in FIT*
Output Type
SD
SU
DD
DU
SFF
Pressure Current with IAW
76
3429
42
98.8%
Temperature Current with
IAW
Pressure Current no IAW
76
3442
42
98.8%
78
3400
48
98.6%
Temperature Current no IAW
76
3409
45
98.7%
Pressure Relay with IAW
1755
76
1700
80
97.8%
Temperature Relay with IAW
1755
76
1719
80
97.8%
Pressure Status with IAW
1694
106
1690
46
98.7%
Temperature Status with IAW
1696
106
1710
46
98.7%
* FIT = 1 failure / 109 hours
SIL Verification:
The Safety Integrity Level (SIL) of an entire Safety Instrumented Function (SIF)
must be verified via a calculation of PFDAVG considering redundant
architectures, proof test interval, proof test effectiveness, any automatic
diagnostics, average repair time and the specific failure rates of all products
included in the SIF. Each subsystem must be checked to assure compliance
with minimum hardware fault tolerance (HFT) requirements.
The following documents are a mandatory part of certification:
64 N Main St
Sellersville, PA 18960
Assessment Report: UEC 1210073 R002 V1R1
Safety Manual: OneST-SM-02, ver. 02
T-002, V3R3-3