1.0
SCOPE
This Engineering Standard sets the minimum technical requirements for design, engineering
and installation of the Supervisory Control and Data Acquisition (SCADA) system to
remotely control and monitor Saudi Electricity Company (SEC) substations including grid
stations and BSPs.
2.0
FUNCTION
2.1
The SCADA system shall be able to monitor and transmit the following information
to the SEC Power Control Center (PCC) master station and/or any other designated
control center :
2.1.1
2.1.2
2.1.3
2.2
2.3
The SCADA system shall be able to respond to control commands from the Master
Station and/or any other designated Control Center and relay these commands to the
substation equipment such as :
2.2.1
2.2.2
2.2.3
Select transformer tap changer control scheme and raise or lower the tap
position of a transformer.
TESP11927R0/YBQ
PAGE NO. 4 OF 57
3.0
SCADA EQUIPMENT/MATERIALS
3.1
3.2
The Remote Terminal Unit (RTU) shall comply with SEC Transmision
Material Standard Specification no. 38-TMSS-03.
3.1.2
The RTU Local Area Network (LAN) shall have adequate protection from
noise that is inherent at the substations.
Transducers
3.2.1
General Requirements
a. Transducers shall be provided to convert primary power system
measured quantities into a form, which can be accepted by the RTU.
b. Transducers shall comply with IEC 60688. They shall be of the
numeric or solid-state design with no moving parts.
c. Transducer outputs shall be dedicated to SCADA for all voltage levels
above 34.5kV. For 34.5kV system and below same shall be provided if
specified in Project Technical Specification (PTS).
d. Transducer inputs and outputs shall be galvanically isolated from each
other and from the auxiliary power supply.
e.
3.2.2
TESP11927R0/YBQ
:
:
:
:
:
:
3 (Minimum)
Per PT secondary requirement
1 or 5 A
10 Milliamps DC (bipolar)
Sinusoidal
0.25 % or better per IEC (60688)
PAGE NO. 5 OF 57
3.2.3
Voltage Transducer
The voltage transducer is designed to convert an AC voltage into a load
independent DC signal. The input range of all voltage transducers and the
corresponding PT ratios shall be such that the full scale output of the
transducer represents a line or bus voltage of at least 120 % of the nominal
line or bus voltage.
Nominal Potential Input
Rated Output
Accuracy
3.2.4
:
:
:
Current Transducer
The input range of all current transducers and the corresponding CT ratios
shall be such that the full scale output of the transducer represents a line
current of at least 110% of the nominal line current.
Nominal Current Input
Rated Output
Accuracy
3.2.5
:
:
:
Lowest - Highest
4 20 Milliamps DC (unipolar )
0.25% or Better
:
:
:
55 - 65 Hz
4 20 Milliamps DC (unipolar )
0.01% or Better in range of 58-62 Hz
Frequency Transducer
Input Range
Output Range
Accuracy
3.3
1 or 5 Amperes, 60 Hz
10 Milliamps DC (unipolar)
0.25% or Better
3.2.6
:
:
:
Equipment Interface
3.3.1
The voltage and current ratings of the RTU I/O modules specified in 38TMSS-03 shall never be exceeded in any substation equipment interface.
Status and alarm inputs shall be dry contacts (no external voltage) dedicated
to SCADA.
3.3.2
Intelligent Electronic Device (IED) interface shall conform to ANSI/TIA232-F "Interface Between Data Terminal Equipment and Data CircuitTerminating Equipment Employing Serial Binary Data Interchange".
3.3.3
Closed Loop Control (CLC) interface shall also conform with ANSI/TIA232-F.
TESP11927R0/YBQ
PAGE NO. 6 OF 57
3.4
Control Interface
Remote control interface shall adhere to the following convention :
Table : 27-1
3.5
Close
Open (Trip)
Close
On
Auto
Start
Raise
In
Open
Off
Manual
Stop
Lower
Out
The condition that exists on the closure of a contact for status shall be noted
in the Function Tabulation Sheets. The following convention shall be
followed :
Table : 27-2
Input Type
State
Circuit Breaker
Status
Normal
Abnormal
Closed
Open
Closed
Open
Closed
Open
Breaker Control
Mode
Local
Remote
Open
Closed
ABTS
In
Out
Closed
Open
Bus Differential
Protection
Breaker Failure
Protection
In
Out
In
Out
Closed
Open
Closed
Open
Alarms
TESP11927R0/YBQ
PAGE NO. 7 OF 57
Transformer RTCC
Status
3.6
State
Closed
Open
Closed
Open
Closed
Master
Parallel
Independent
Closed
Open
Tap Position
Analog Indication
3.5.2
3.5.3
Cable runs between monitoring devices and the RTU shall be radially paired.
Pairs used for runs to the RTU shall be in the same cable.
3.5.4
SCADA Cables
SCADA analog input cables shall be shielded/sheathed, twisted pair cables and shall
comply with the requirements of SEC Materials Standard Specification 11-SMSS11. SCADA status and control cables shall be overall group shielded per 11-TMSS10.
3.7
4.0
The design shall take into consideration the type of RTU enclosure specified
in 38-TMSS-03 data schedule.
4.1.2 Type I enclosure (with Field Interface Cabinet) shall be in accordance with
38-TMSS-03.
TESP11927R0/YBQ
PAGE NO. 8 OF 57
4.1.3
4.1.4
4.2
4.3
b.
c.
d.
e.
Transducers
4.2.1
4.2.2
4.2.3
Test switches (similar in design and function to Type FT1 test switches) shall
be provided in metering circuits to allow transducer installation, testing and
maintenance without interruption to other circuits.
SCADA Cables shall be kept as far as possible from high voltage cables.
4.3.2
SCADA analog, status and control cables shall be grounded per TES-P119.10.
4.3.3
SCADA wiring cable tails shall be bonded in such a way that each wire could
be traced back to its associated cable.
4.3.4
Cable ties shall be used at all equipment to support the weight of the cables.
4.3.5
Each core of the control and instrumentation cables shall be identified with
numbered ferules. The ferules shall be made of insulating materials. A wire
TESP11927R0/YBQ
PAGE NO. 9 OF 57
list shall be prepared during the design stage. The list shall include the wire
size, color, function, origin, destination at the terminal blocks and the ferule
labels.
4.3.6
4.4
5.0
TESP11927R0/YBQ
PAGE NO. 10 OF 57
No.
1
Control Panel
Annunciator
CIRCUIT
BREAKER
ABNORMAL.
Initiator
1. Air pressure low stage-1
Status
****BREAKER
ABNORMAL/
NORMAL
OR
****ISOLATOR
ABNORMAL/
NORMAL
Non Trip
(As Applicable)
b. Supervision of MCB.
c. Spring not fully charged.
d. Compressor/pump motor supply.
11. Test switch not in normal position.
12. Breaker Lock out coil defective.
13. BFR In/Out Switch
14. Closing Coil DC Supply Fail.
15. BFR DC Fail.
16. BFR Signal Fail.
2
TRIP COIL-1
LOCK OUT
Trip Coil-1Lockout:
a. SF6 low stage -2 lockout.
b. Low air stage -2 lockout.
**** LOCKOUT
OPERATE/ NORMAL
Non Trip
TESP11927R0/YBQ
PAGE NO. 11 OF 57
Control Panel
Annunciator
TRIP COIL-2
LOCK OUT
Initiator
Trip Coil-2 Lockout:
a. SF6 low stage-2 lockout.
(Continued)
Status
Non Trip
OPERATE/ NORMAL
Non Trip
CB GAS DENSITY
HIGH
Non Trip
10
REMOTE OFF.
4
5
6
7
11
12
13
GIS GAS
PRESSURE
ALARM
GIS GAS
PRESSURE LOW
STAGE 2
CONTROL
SUPPLY FAIL
Non Trip
FAULTY / NORMAL
Non Trip
Trip
Non Trip
Non Trip
Non Trip
Non Trip
14
DC SUPPLY FAIL
15
AC SUPPLY FAIL
TESP11927R0/YBQ
PAGE NO. 12 OF 57
No.
Control Panel
Annunciator
16
CB PHASE
DISCREPANCY
Initiator
(Continued)
Status
**** PHNOTTOG
OPERATE/ NORMAL
Non -Trip
Non Trip
1. Synchrocheck Relay
a. DC Failure
17
SYNCHROCHECK RELAY
FAULTY
b. Self Supervision
2. Synchronizing Switch in Off Position
3. Synchrocheck fuse failure relay operated.
18
UNDER
FREQUENCY
****U/F PROT.
OPERATE/NORMAL
Trip
19
ALARM SUPPLY
FAILURE
****ALARM SUPPLY
FAILURE/NORMAL
Non Trip
****ABTS
FAILED/NORMAL
Non Trip
a.
AC Fail
b.
DC Fail
c.
ABTS FAILED
21
CLOSE CIRCUIT
FAULTY.
Non Trip
22
CLOSE FAILURE
PROTECTION
OPERATED
Non Trip
23
LINE CURRENT
SUPERVISION
OPERATED
Non Trip
TESP11927R0/YBQ
PAGE NO. 13 OF 57
Table 27-4: Feeder 380kV OHL & U/G Cable (As Applicable)
No.
Control Panel
Annunciator
Initiator
Status
FEEDER
PROTECTION
FIRST MAIN
FAULTY
**** PROT.
FAULTY/ NORMAL
Non Trip
FEEDER
PROTECTION
SECOND MAIN
FAULTY
BACKUP
PROTECTION
FAULTY
PLC FAILED
PLC Equipment
**** PLC
FAILED/ NORMAL
Non Trip
SIGNALING
EQUIPMENT
FAILED
Signaling equipment
**** NSD
FAILED/ NORMAL
Non Trip
RELAY SET # 1
COMM. FAIL
RELAY SET # 2
COMM. FAIL
TESP11927R0/YBQ
PSE DC Fail
c.
R1/R2 COMM
FAILED/NORMAL
Non Trip
PSE DC Fail
c.
PAGE NO. 14 OF 57
Table 27-4: Feeder 380kV OHL & U/G Cable (As Applicable)
No.
Control Panel
Annunciator
Initiator
(Continued)
Status
Non Trip
BKR FAIL
COMM.-1 FAIL
b.
PSE DC Fail
c.
10
11
BKR COMM.-2
FAIL
b.
PSE DC Fail
c.
AUTO
RECLOSER
FAULTY
AUTO
RECLOSER
BLOCKED
Non Trip
Non Trip
AUTO
RECLOSER
SUCCESSFUL
Auto recloser
Non Trip
12
OIL PRESSURE
LOW STAGE-1
**** OIL PR 1.
LOW/ NORMAL
Non Trip
13
OIL PRESSURE
LOW STAGE-2
Non Trip
14
INTER TRIP 1
FAULTY
15
Non Trip
INTER TRIP 2
FAULTY
16
FEEDER END
PROTECTION
FAULTY
Non Trip
17
FEEDER END
PROTECTION
OPERATE
Trip
18
FERRO
RESONANCE
ALARM
**** FERRORES
ALARM/ NORMAL
11A
TESP11927R0/YBQ
Non Trip
PAGE NO. 15 OF 57
Table 27-4: Feeder 380kV OHL & U/G Cable (As Applicable)
No.
Control Panel
Annunciator
Initiator
(Continued)
Status
VT FAIL
****VT
FAILED / NORMAL
Non Trip
OVER VOLTAGE
PROTECTION
OPERATED
****OVER VOLT.
ALARM / NORMAL
Non Trip
21
OVER VOLTAGE
PROTECTION
FAULTY
****OVER VOLT.
FAULTY / NORMAL
Non Trip
22
PHASE
UNBALANCED
Phase unbalanced
****PH UNBAL.
ALARM / NORMAL
Non Trip
23
SCADA ALARM
SUPPLY OFF.
Selector switch
Non Trip
24
DC 1 FAIL
Feeder DC -1 Failed
DC FAILED
Non Trip
25
DC 2 FAIL
Feeder DC -2Failed
26
TRIP CKT -1
FAULTY
Non Trip
27
TRIP CKT -2
FAULTY
28
PROTECTION
UNDER TEST
29
30
CABLE DIFF
PROT
OPERATED
THERMAL O/L
PROT.
OPERATED
Non Trip
Trip
Trip
TESP11927R0/YBQ
PAGE NO. 16 OF 57
No.
Control Panel
Annunciator
FEEDER
PROTECTION FIRST
MAIN (RELAY SET 1)
OPERATED
FEEDER
PROTECTION
SECOND MAIN
(RELAY SET 2)
OPERATED
Initiator
Status
1.Zone 1.
2.Zone 2 plus Acc.Signal.
3.DEF plus permissive signal.
1.Zone 1.
Trip
****BKUP PRO.
OPERATE /NORMAL
Trip
****INTRTRIP.
RECEIVE /NORMAL
Trip
BACKUP
PROTECTION
OPERATED
4
5
TESP11927R0/YBQ
PAGE NO. 17 OF 57
No.
Control Panel
Annunciator
FIRST MAIN
PROTECTION
OPERATED
SECOND MAIN
PROTECTION
OPERATED
Initiator
Status
1.Zone 1.
2.Zone without blocking signal.
Directional earth fault without blocking
signal
****LINE PRO.
OPERATE /NORMAL
Trip
****BKUP PRO.
OPERATE /NORMAL
Trip
**** PROT.
FAULTY/ NORMAL
Non Trip
****INTR TRIP
RECEIVE /NORMAL
Trip
1.Close on to fault.
2.Zone 2 plus backup timer.
3
BACKUP
PROTECTION
OPERATED
FEEDER
PROTECTION
FIRST MAIN
FAULTY
4. VT Supervision
5. Pilot Supervision Supply
6. Protection Supply Supervision
7.Line protection un-stabilised
8. Trip Relay Coil Failure
9. Protection Trip (Switch) Isolated
FEEDER
PROTECTION
SECOND MAIN
FAULTY
BACKUP
PROTECTION
FAULTY
INTER TRIP
RECEIVE
TESP11927R0/YBQ
PAGE NO. 18 OF 57
Control Panel
Annunciator
DC 1 FAIL
Initiator
(Continued)
Status
Feeder DC -1 Failed
DC 2 FAIL
Feeder DC -2Failed
10
TRIP CKT -1
FAULTY
11
TRIP CKT -2
FAULTY
12
PROTECTION
UNDER TEST
DC FAILED
Non Trip
Non Trip
TESP11927R0/YBQ
PAGE NO. 19 OF 57
No.
1
Control Panel
Annunciator
MAIN
PROTECTION
OPERATED
BACKUP
PROTECTION
OPERATED
Initiator
Status
****LINE PRO
OPERATE/NORMAL
Trip
****INTR TRIP
RECEIVE/NORMAL
Trip
****LINE PRO
FAULTY/NORMAL
Non-Trip
INTER TRIP
RECEIVE
MAIN
PROTECTION
FAULTY
BACKUP
PROTECTION
FAULTY
Trip
THERMAL O/L
PROT. OPERATED
Trip
TESP11927R0/YBQ
PAGE NO. 20 OF 57
No.
Control Panel
Annunciator
Initiator
Status
FLAG ON AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
Non-Trip
***AUTO REC
BLOCK /DEBLOCK
Non-Trip
FLAGS ON RELAYS
***TRIP CKT
FAULTY /NORMAL
Non-Trip
FLAGS ON RELAYS
FLAG ON AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
Trip
FLAG ON AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
10
FLAG ON AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
11
FLAGS ON RELAYS
***AUTO REC
FAULTY /NORMAL
Non-Trip
FLAG ON AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
INCOMER VT FAIL
BUS VT FAIL
FLAGS ON RELAYS
TESP11927R0/YBQ
PAGE NO. 21 OF 57
No.
Control Panel
Annunciator
FLAGS ON RELAYS
Initiator
FLAGS ON RELAYS
FLAGS ON RELAYS
FLAGS ON RELAYS
Status
Non-Trip
Trip
TESP11927R0/YBQ
PAGE NO. 22 OF 57
No.
Control Panel
Annunciator
FLAG ON AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
FLAGS ON RELAYS
FLAG ON AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
FLAG ON AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
FLAG ON AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
CONTROL SUPPLY
FAIL
Initiator
Status
Non-Trip
13.8 kV PROT
FAULTY /NORMAL
Non-Trip
13.8 kV PROT
OPERATE /NORMAL
Trip
Non-Trip
DC SUPPLY FAILURE
AC SUPPLY FAILURE
CLOSING CIRCUIT DC
SUPPLY FAIL
Non Trip
10
FLAG ON AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
Non-Trip
13.8kV LOCKOUT
OPERATE/NORMAL
Non-Trip
TESP11927R0/YBQ
PAGE NO. 23 OF 57
Control Panel
Annunciator
12
FLAG ON AUX.RELAY
/ DISPLAY ON
NUMERICAL RELAY
13
FLAG ON AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
14
15
FLAG ON AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
FLAG ON AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
Initiator
Pilot Wire Protection
Status
Trip
Trip
Non-Trip
13.8 kV ABTS
FAILED/NORMAL
Non-Trip
DC Fail
c.
16
FLAG ON
SYNCHRONISING
RELAY
Synchronizing Failure
13.8 kV SYNCH
FAILED/NORMAL
Non-Trip
17
FLAG ON AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
13.8 kV VT
FAILED/NORMAL
Non-Trip
18
FLAG ON AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
Non-Trip
Note for Item # 12 & 13 : In case of 13.8 kV consumer feeder with pilot wire protection, these two additional alarms to
SCADA shall be required
TESP11927R0/YBQ
PAGE NO. 24 OF 57
Control Panel
Annunciator
Initiator
Status
T # FIRST MAIN
PROTECTION FAULTY
T # SECOND MAIN
PROTECTION FAULTY
T# PROTECTION
FAULTY /NORMAL
Non-Trip
T# BUCHHOLZ ST1
ALARM /NORMAL
Non-Trip
Non-Trip
Non-Trip
2. DC Fail
3. Lock out Relay Fail
T # BUCHHOLZ STAGE
-I
T # AUX/EARTHING
TRAFO BUCHHOLZ
STAGE-1
T# WINDING
TEMPERATURE HIGH
STAGE -I
T # AUX TRAFO
WINDING
TEMPERATURE HIGH
STAGE -I
T # OIL TEMPERATURE
HIGH STAGE-1
T # OIL TEMPERATURE
HIGH STAGE-2
10
11
12
TESP11927R0/YBQ
Non-Trip
Non-Trip
PAGE NO. 25 OF 57
Table 27- 11: 380/230;132;115;110 kV & 230/69 kV Transformers (As Applicable) (Continued)
No.
13
14
Control Panel
Annunciator
T # PRESSURE RELIEF
OPERATED
T # CABLE OIL
PRESSURE LOW
Initiator
1.Main transformer pressure relief
trip .
2.Tap changer pressure relief trip.
1.HV Cable Oil Pressure Low
Stage-1.
2. HV Cable Oil Pressure Low
Stage-2
Status
Trip
Non-Trip
T # COOLING SYSTEM
FAULTY /NORMAL
Non-Trip
T # FIRE PROT
/NORMAL
FAULTY
Non-Trip
T# FIRE PROT
/NORMAL
OPERATE
COOLING SYSTEM
FAULTY
16
17
FIRE PROTECTION
FAULTY
FIRE PROTECTION
OPERATED
Non-Trip
T# TAP CHANGER
FAULTY
Non-Trip
T# TRANSFORMER TRIP
DISABLED
Non-Trip
T# TRAFO TRIP
DISABLED
TESP11927R0/YBQ
PAGE NO. 26 OF 57
Table 27- 11: 380/230;132;115;110 kV & 230/69 kV Transformers (As Applicable) (Continued)
No.
Control Panel
Annunciator
Initiator
Status
T# PROTECTION OPERATE /
NORMAL
Trip
T# PROTECTION OPERATE /
NORMAL
Trip
20
T # WINDING
TEMPERATURE HIGH
STAGE -2
21
T # FIRST MAIN
PROTECTION
OPERATED
22
T # SECOND MAIN
PROTECTION
OPERATED
23
T # BACKUP
PROTECTION
OPERATED
TESP11927R0/YBQ
PAGE NO. 27 OF 57
Table 27- 11: 380/230;132;115;110 kV & 230/69 kV Transformers (As Applicable) (Continued)
No.
Control Panel
Annunciator
Initiator
Status
24
WINDING
TEMPERATURE HIGH
STAGE-2
25
T # FIRST
PROTECTION SUPPLY
SUPERVISION
26
T # SECOND
PROTECTION SUPPLY
SUPERVISION
27
T # BACKUP
PROTECTION FAULTY
28
T # FIRST MAIN
PROTECTION LV TRIP1 OPERATED
LV Trip Relay
29
T # FIRST MAIN
PROTECTION LV TRIP2 OPERATED
LV Trip Relay
30
FLAG RELAY
VT supply failed
Trip
T # PROTECTION
FAULTY /NORMAL
Non-Trip
T # PROTECTION
OPERATE/NORMAL
Trip
T # *VT FAILED/NORMAL
Non-Trip
TESP11927R0/YBQ
PAGE NO. 28 OF 57
No.
Control Panel
Annunciator
TRANSFORMER OIL
LEVEL LOW
Initiator
1.Main transformer oil level low.
2.Tap changer oil level low.
MAIN
TRANSFORMER OIL
TEMP HIGH
AUX
TRANSFORMER OIL
TEMP HIGH
TRANSFORMER
FAULTY
Status
T # PRESS RELIEF
FAULTY/NORMAL
Trip
1.Fan MCB
5
COOLER FAIL
T # COOLING SYSTEM
FAULTY /NORMAL
Non-Trip
PROTECTION
FAULTY
T # PROTECTION
FAULTY/NORMAL
Non-Trip
BUCHHOLZ
STAGE-1
T # BUCHHOLZ ST1
ALARM/NORMAL
Non-Trip
Non-Trip
T # PROTECTION
OPERATE/NORMAL
Trip
WINDING
TEMPERATURE
HIGH STAGE-1
TRANSFORMER HV
REF. OPERATED
10
TRANSFORMER LV
REF. OPERATED
11
TRANSFORMER
DIFFERENTIAL
PROT. OPERATED
TESP11927R0/YBQ
PAGE NO. 29 OF 57
Control Panel
Annunciator
12
TRANSFORMER
BUCHHOLZ STAGE2 OPERATED
Initiator
Status
TRANSFORMER
STANDBY EARTH
FAULT PROT.
OPERATED
14
TRANSFORMER HV
O/C & E/F PROT.
OPERATED
15
TRANSFORMER LV
O/C & E/F PROT
OPERATED
16
WINDING
TEMPERATURE
HIGH STAGE-2
17
FLAG RELAY
13
(Continued)
T # PROTECTION
OPERATE/NORMAL
Trip
Trip
T # * VT
FAILED/NORMAL
Non-Trip
T # FIRE PROT
OPERATE/NORMAL
Non-Trip
T # FIRE PROT
FAULTY/NORMAL
Non-Trip
18
FIRE PROTECTION
OPERATED
19
FIRE PROTECTION
FAULTY
TESP11927R0/YBQ
PAGE NO. 30 OF 57
No.
Control Panel
Annunciator
Initiator
(Continued)
Status
T# TAP CHANGER
FAULTY
T# TAP CHANGER
DRIVE
FAILED/NORMAL
Non-Trip
T# TRAFO TRIP
DISABLED
T# TRANSFORMER
TRIP DISABLED
Non-Trip
22
UNDER
FREQUENCY
PROTECTION
FAULTY
Non-Trip
23
UNDER
FREQUENCY PROT
OPERATED
Trip
24
AUXILIARY
TRANSFORMER
PROTECTION
OPERATED
AUX T # PROTECTION
OPERATE/NORMAL
Trip
25
AUXILIARY
TRANSFORMER
PROTECTION
FAULTY
AUX T # PROTECTION
FAULTY/NORMAL
Non-Trip
26
UNDER VOLTAGE
PROTECTION
OPERATED
Trip
27
UNDER VOLTAGE
PROTECTION
FAULTY
Non-Trip
TESP11927R0/YBQ
PAGE NO. 31 OF 57
No.
Control Panel
Annunciator
Initiator
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
Status
T # BUCHHOLZ
ALARM/NORMAL
Non-Trip
T # TRANSFORMER
ALARM/NORMAL
Non-Trip
Non-Trip
T # PROTECTION
FAULTY/NORMAL
Non-Trip
T # PROTECTION
OPERATE/NORMAL
Trip
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
HV protection supply
supervision.
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
TESP11927R0/YBQ
Buchholz protection.
PAGE NO. 32 OF 57
Control Panel
Annunciator
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
Transformer differential
protection (87T).
10
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
11
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
12
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
13
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL RELAY
Initiator
(Continued)
Alarm Received At ECC
T # PROTECTION
OPERATE/NORMAL
Status
Trip
# - Transformer Number
TESP11927R0/YBQ
PAGE NO. 33 OF 57
No.
Control Panel
Annunciator
Initiator
REACTOR FIRST
PROTECTION MAIN
FAULTY
REACTOR SECOND
PROTECTION MAIN
FAULTY
REACTOR
CONNECTION
PROTECTION 1
FAULTY
REACTOR
CONNECTION
PROTECTION 2
FAULTY
REACTOR BACKUP
PROTECTION FAULTY
REACTOR VOLTAGE
UNBALANCE
DETECTED
REACTOR WINDING
TEMPERATURE STAGE
-1 OPERATED
Status
**** PROT
FAULTY/NORMAL
Non-Trip
Non-Trip
REACTOR WINDING
TEMPERATURE STAGE
-2 OPERATED
Trip
REACTOR BUCHHOLZ
STAGE-1
****BUCHHOLZ ST1
ALARM/NORMAL
Non-Trip
**** REACTOR
ALARM/NORMAL
Non-Trip
REACTOR FAULTY
3.Pressure relief.
4. Oil temperature high Stage -1
5. Cooling Fail.
TESP11927R0/YBQ
PAGE NO. 34 OF 57
Control Panel
Annunciator
(Continued)
Initiator
Status
REACTOR FIRE
PROTECTION
Non-Trip
Non-Trip
Non-Trip
Non-Trip
12
13
REACTOR OIL
TEMPERATURE VERY
HIGH
REACTOR FIRE
PROTECTION FAULTY
14
REACTOR CONTROL
AC/DC SUPPLY FAIL.
15
AC SUPPLY TRIP
AC supervision relay
16
DC SUPPLY TRIP
DC supervision relay
17
REACTOR FIRST
PROTECTION MAIN
OPERATED
18
REACTOR SECOND
MAIN PROTECTION
OPERATED
19
REACTOR
CONNECTION
PROTECTION-1
OPERATED
20
REACTOR
CONNECTION
PROTECTION -2
OPERATED
TESP11927R0/YBQ
**** PROT
OPERATE/NORMAL
Trip
PAGE NO. 35 OF 57
Control Panel
Annunciator
(Continued)
Initiator
Status
21
REACTOR BACKUP
PROTECTION
OPERATED
**** PROT
OPERATE/NORMAL
Trip
22
REACTOR BUCHHOLZ
STAGE-2
**** PROT
OPERATE/NORMAL
Trip
TESP11927R0/YBQ
PAGE NO. 36 OF 57
No.
Control Panel
Annunciator
Initiator
Status
BUS BAR
ZONE1A
PROTECTION
FAULTY
Non-Trip
Non-Trip
Non-Trip
5.Supply supervision.
6.Zones interconnected.
7.CT bus wire shorting operated.
1.Bus bar protection out of service.
2.Bus bar protection faulty.
3.CT bus wire supervision.
BUS BAR
ZONE1B
PROTECTION
FAULTY
TESP11927R0/YBQ
PAGE NO. 37 OF 57
Control Panel
Annunciator
Initiator
Status
Non-Trip
BB CHK.PROT.
FAULTY/NORMAL
Non-Trip
5.Supply supervision.
6.Zones interconnected.
7.CT bus wire shorting operated.
BUS BAR
PROTECTION
CHECK ZONE
FAULTY
10
10
BUS BAR
ZONE1A
PROTECTION
OPERATED
BUS CHECK
ZONE
PROTECTION
OPERATED
BUS COUPLER /
TIE OVER
CURRENT
PROTECTION
OPERATED
TESP11927R0/YBQ
Trip
Trip
Trip
Trip
BUS 1A/1B/2A/2B
BUSBAR CHECK ZONE
PROT
OPERATE/NORMAL
Trip
Trip
PAGE NO. 38 OF 57
Control Panel
Annunciator
11
BUS COUPLER /
TIE OVER
CURRENT
PROTECTION
FAULTY
Initiator
1.Protection supply supervision.
12
13
BUS SECTION
OVER CURRENT
PROTECTION
FAULTY
14
BUS VT FAILED
15
BUSBAR GAS
PRESSURE
ALARM
16
BUSBAR GAS
PRESSURE LOW
STAGE-2
1.Relay flag.
17
BUSBAR
PROTECTION
TRIP SUPPLY -1
SUPERVISION
BUSBAR
PROTECTION
TRIP SUPPLY -2
SUPERVISION
1.Relay flag.
19
BUSBAR
LOCKOUT RESET
SUPPLY FAIL
TESP11927R0/YBQ
Status
Non-Trip
Trip
Non-Trip
BB VT .
FAILED/NORMAL
Non-Trip
Non-Trip
Non-Trip
Non-Trip
Non-Trip
BB PROT RESET
SUPPLY FAIL/NORMAL
Non-Trip
BUS SECTION
OVER CURRENT
PROTECTION
OPERATED
18
(Continued)
2.Actuator position.
2.Actuator position.
1.Relay flag.
2.Actuator position.
PAGE NO. 39 OF 57
No.
Control Panel
Annunciator
Initiator
(Continued)
Status
20
MESH CORNER
PROTECTION
FAULTY
MESH COR*PROT
FAULTY/NORMAL
Non-Trip
MESH COR*PROT
OPERATE/NORMAL
Trip
5.Supply supervision.
6.CT bus wire shorting operated one for
each mesh corner.
21
MESH CORNER
PROTECTION
OPERATED
22
BUSBAR *
PROTECTION
FAULTY
BUSBAR *PROT
FAULTY/NORMAL
Non-Trip
Trip
5.Supply supervision.
6.CT bus wire shorting operated one for
each mesh zone
23
BUSBAR * PROT.
OPERATED
BUSBAR *PROT
OPERATE/NORMAL
24
BUS VT FAILED
BB VT .
FAILED/NORMAL
Non-Trip
Non-Trip
Trip
25
26
13.8 BUSBAR
STUCK BREAKER
PROTECTION
FAULTY
13.8 BUSBAR
STUCK BREAKER
PROT OPERATED
* = Busbar Section
TESP11927R0/YBQ
PAGE NO. 40 OF 57
Control Panel
Annunciator
Initiator
Status
EMERGENCY
DIESEL FAULT
125 VOLT
BATTERY #
1EARTH FAULT
125 VOLT
BATTERY # 2
EARTH FAULT
DIESEL GEN.
FAULTY/NORMAL
Non-Trip
125 V DC GROUND
ALARM/NORMAL
Non-Trip
125V BATTERIES
FAULTY/NORMAL
Non-Trip
125V BATTERIES
FAULTY/NORMAL
Non-Trip
48 V DC GROUND
ALARM/NORMAL
Non-Trip
125 VOLT
BATTERY # 1
FAULTY
125VOLT
BATTERY # 2
FAULTY
48 V BATTERY
EARTH FAULT
TESP11927R0/YBQ
PAGE NO. 41 OF 57
No.
Control Panel
Annunciator
Initiator
Status
48 VOLT
BATTERY
FAULTY
48 V BATTERY
FAULTY/NORMAL
Non-Trip
EXHAUST FAN
FAIL/NORMAL
Non-Trip
SMOKE DETECTOR
OPERATE/NORMAL
Non-Trip
ROOM TEMPERATURE
HIGH/NORMAL
Non-Trip
Non-Trip
EXHAUST FAN
FAIL
SMOKE
DETECTOR
OPERATED
10
ROOM
TEMPERATURE
HIGH
11
RTU POWER
SUPPLY FAIL
12
------------------
Entrance alarm-1
ENTRANCE
ALARM/NORMAL
Non-Trip
13
------------------
Entrance alarm-2
INTRUDER
ALARM/NORMAL
Non-Trip
14
ISOLATOR
SWITCHING
INCOMPLETE
Non-Trip
15
EARTH SWITCH
SWITCHING
INCOMPLETE
SWITCHING
INCOMPLETE
ALARM/NORMAL
PLC CHARGER
FAULTY/NORMAL
Non-Trip
PLC CHARGER
FAULTY
TESP11927R0/YBQ
PAGE NO. 42 OF 57
Control Panel
Annunciator
Initiator
(Continued)
Alarm Received At ECC
Status
FIRE SYSTEM
FAULTY
FIRE SYSTEM
FAULTY/NORMAL
Non-Trip
OLS CHARGER
FAULTY/NORMAL
Non-Trip
S/S AUXILIARY
SUPPLY
FAILED/NORMAL
Non-Trip
MAIN DC SUPPLY
FAILED /NORMAL
Non-Trip
COMPRESSOR
FAULTY/NORMAL
Non-Trip
NEUTRAL CURRENT
OPERATE/NORMAL
Non-Trip
FIRE SYSTEM
OPERATE/NORMAL
Non-Trip
OLS CHARGER
FAULTY.
19
20
21
S/S AUXILIARY
SUPPLY FAIL AC
MCB OFF.
MAIN DC
SUPPLY FAILED
DC MCB OFF.
COMPRESSOR
FAULTY
2.Compressor CB.
3.Air pressure low.
23
NEUTRAL
CURRENT
ALARM
OPERATED
FIRE SYSTEM
OPERATED
TESP11927R0/YBQ
PAGE NO. 43 OF 57
Control Panel
Annunciator
Initiator
(Continued)
Alarm Received At ECC
Status
25
OLS # FAILED
OLS # system
OLS #
FAILED/NORMAL
Non-Trip
26
OLS SYSTEM
FAULTY
OLS #
FAULTY /NORMAL
Non-Trip
27
ALARM SYSTEM
FAULTY
ALARM SYSTEM
FAULTY/NORMAL
Non-Trip
Non-Trip
Non-Trip
AUTO RESET
FAULTY/NORMAL
Non-Trip
RTU CHARGER
FAULTY/NORMAL
Non-Trip
HVAC SYSTEM
MAIN FAULTY
28
HVAC SYSTEM
BACKUP FAULTY
29
AUTO RESET
SUPPLY FAIL
30
RTU CHARGER
FAULTY
31
SYSTEM
SYNCHRONIZER
UNIT FAULTY
System synchronizer
SYS.SYNC.
FAULTY/NORMAL
Non-Trip
32
****U/F PROT.
FAULTY /NORMAL
Non -Trip
AUTOMATIC SWITCHING
33
AUTOMATIC
SWITCHING
FAILED
AUTO SWITCHING.
FAILED/NORMAL
Non-Trip
AUTO SWITCHING
EQUIP
FAULTY/NORMAL
Non-Trip
1.Logic Faulty.
2.Processor watchdogs.
34
AUTOMATIC
SWITCHING
EQUIPMENT
FAULTY
3.Supply supervision.
4.Input discrepancy.
5.Automatic switching .Equipment out of
service.
TESP11927R0/YBQ
PAGE NO. 44 OF 57
Control Panel
Annunciator
(Continued)
Initiator
Status
35
TRIP ON
PARALLEL
-------
TRIP ON PARALLEL
Non-Trip
36
ACSE REMOTE
-------
ACSE REMOTE
ON/OFF
Non-Trip
37
AUTO SW.EQ.
REMOTE
-------
Non-Trip
38
AUTO
CHANGEOVER
FAILED
AUTO CHANGEOVER.
FAILED/NORMAL
Non-Trip
39
AUTO
CHANGEOVER
FAULTY
AUTO CHANGEOVER.
FAULTY/NORMAL
Non-Trip
FAULT RECORDER
OPERATED
FAULT RECORDER
OPERATE/NORMAL
Non-Trip
FAULT RECORDER
FAULTY/NORMAL
Non-Trip
S/S DC SUPPLY
FAILED/NORMAL
Non-Trip
1.Logic Faulty.
2.Memory full.
3.Out of paper.
41
FAULT RECORDER
FAULTY
4.Paper low.
5.Processor watchdogs
6.Printer faulty.
7.Supply supervision.
8.Out of service.
42
FLAG ON
CHARGER PANEL
TESP11927R0/YBQ
PAGE NO. 45 OF 57
43
44
Control Panel
Annunciator
FLAG ON AC
DISTRIBUTION
BOARD
------
Initiator
1.Substation AC supply supervision relay.
Status
S/S AC SUPPLY
FAILED/NORMAL
Non-Trip
ROOM TEMPERATURE
HIGH/NORMAL
Non-Trip
RTU DC
FAILED/NORMAL
Non-Trip
1.RTU DC low.
45
46
------
Entrance - 1
ENTRANCE
ALARM/NORMAL
Non-Trip
47
------
Entrance - 2
INTRUDER
ALARM/NORMAL
Non-Trip
48
NEUTRAL
CURRENT ALARM
OPERATED
NEUTRAL CURRENT
OPERATE/NORMAL
Non-Trip
49
COMMUNICATION
FAIL
MAJ COMM
FAIL/NORMAL
Non-Trip
TESP11927R0/YBQ
PAGE NO. 46 OF 57
No.
Control Panel
Annunciator
TAP CHANGER
INCOMPLETE
VOLTAGE CONTROL
FAIL
TAP CHANGER
MOTOR FAIL
AVC SUPPLY
FAULTY
FLAG RELAY
Initiator
Status
**TAP INCOMPLETE
ALARM/NORMAL
Non-Trip
**AVC/TAP CHANGER
FAULTY/NORMAL
Non-Trip
Non-Trip
** - Transformer Number
TESP11927R0/YBQ
PAGE NO. 47 OF 57
No.
Control Panel
Annunciator
Initiator
Status
DISPLAY ON
REACTOR CONTROL
PANEL
Trip
Trip
TCR CONTROL
FAILED/NORMAL
Trip
DISPLAY ON
REACTOR CONTROL
PANEL
DISPLAY ON
REACTOR CONTROL
PANEL
Buchholz Stage 2
TCR Controller Fail
TCR Controller Trip
TCR Emergency Switch Trip
DISPLAY ON
REACTOR CONTROL
PANEL
Trip
DISPLAY ON
REACTOR CONTROL
PANEL
Non-Trip
DISPLAY ON
REACTOR CONTROL
PANEL
Buchholz Stage 1
TCR #BUCHHOLZ ST 1
ALARM / NORMAL
Non-Trip
DISPLAY ON
REACTOR CONTROL
PANEL
Non-Trip
DISPLAY ON
REACTOR CONTROL
PANEL
Non-Trip
TESP11927R0/YBQ
PAGE NO. 48 OF 57
No.
Control Panel
Annunciator
Initiator
(Continued)
Status
DISPLAY ON
REACTOR
CONTROL PANEL
Non-Trip
10
DISPLAY ON
REACTOR
CONTROL PANEL
Non-Trip
11
DISPLAY ON
REACTOR
CONTROL PANEL
TCR #OIL.LEVEL
LOW/NORMAL
Non-Trip
Non-Trip
DISPLAY ON
REACTOR
CONTROL PANEL
1. Loss of DC
2. Relay Self Supervision
3. PT Failure
4. Protection Disabled.
Backup Protection Disturbed /
Fail
13
DISPLAY ON
REACTOR
CONTROL PANEL
14
DISPLAY ON
REACTOR
CONTROL PANEL
15
DISPLAY ON
REACTOR
CONTROL PANEL
16
DISPLAY ON
REACTOR
CONTROL PANEL
17
DISPLAY ON
REACTOR
CONTROL PANEL
1. Loss of DC
2. Relay Self Supervision
3. PT Failure
4. Protection Disabled.
Non-Trip
#- Reactor Number;
Please refer Table # 27-14 for alarms applicable to Delta / Star Reactors.
TESP11927R0/YBQ
PAGE NO. 49 OF 57
Control Panel
Annunciator
Initiator
Status
DISPLAY ON
CAPACITOR
CONTROL PANEL
CAPACITOR BANK #
PROTECTION SET 1
OPERATED/NORMAL
CAPACITOR BANK #
PROTECTION SET 2
OPERATED/NORMAL
DISPLAY ON
CAPACITOR
CONTROL PANEL
DISPLAY ON
CAPACITOR
CONTROL PANEL
CAPACITOR BANK #
PROTECTION SET 1
LOCKOUT / NORMAL
DISPLAY ON
CAPACITOR
CONTROL PANEL
CAPACITOR BANK #
PROTECTION SET 2
LOCKOUT / NORMAL
DISPLAY ON
CAPACITOR
CONTROL PANEL
Trip
Non-Trip
Non-Trip
3. DC Supply Failure
Protection Stage -2 Failure
DISPLAY ON
CAPACITOR
CONTROL PANEL
1. Relay Defective
2. PT Supply Failure
3. DC Supply Failure
TESP11927R0/YBQ
PAGE NO. 50 OF 57
Control Panel
Annunciator
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL
RELAY
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL
RELAY
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL
RELAY
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL
RELAY
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL
RELAY
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL
RELAY
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL
RELAY
FLAG ON
AUX.RELAY
/DISPLAY ON
NUMERICAL
RELAY
FLAG ON
AUX.RELAY
Initiator
Status
Trip
Non-Trip
Trip
Trip
Non-Trip
Trip
Non-Trip
TESP11927R0/YBQ
PAGE NO. 51 OF 57
NO
Control Panel
Annunciator
AUXILIARY SUPPLY
FAIL.
Auxiliary Supply.
Non-Trip
COOLING SYSTEM
FAULTY
Non-Trip
REFERENCE
VOLTAGE UP/DOWN
Regulation Control
Non-Trip
READY TO START
Ready To Start
RDY START
Non-Trip
URGENT ALARMS
(GROUPED)
URGENT ALARMS
(GROUPED)
URGENT ALARMS
NON-URGENT
ALARM (GROUPED)
NON-URGENT ALARM
(GROUPED)
NON-URGENT ALARMS
Initiator
TYPE
Trip
Non-Trip
NO
Control Panel
Annunciator
Initiator
TYPE
CIRCUIT SWITCHER
FAULTY / NORMAL
Non-Trip
FLAG ON RELAYS
TESP11927R0/YBQ
PAGE NO. 52 OF 57
NO
Control Panel
Annunciator
LOW PF
MAX DEMAND
EXCEEDED
CUSTOMER
TROUBLE
CUST TRB
GROUND SWITCH
CLOSE
GRD SW OPEN/CLOSE
METER FAULT
Meter Fault
TESP11927R0/YBQ
Initiator
TYPE
Non-Trip
PAGE NO. 53 OF 57
NO
TEXT
TYPE
***BREAKER
ON/OFF
C-I
***ISOLATOR
ON/OFF
C-I
***E/SW
ON/OFF
IN/OUT
C-I
IN/OUT
C-I
IN/OUT
C-I
RESET/NORMAL
C-I
*** REV.POWER
IN/OUT
C-I
***REMOTE OFF
IN/OUT
C-I
10
***V.SSYNCR
IN/OUT
C-I
11
***P.W.PROT
IN/OUT
C-I
12
IN/OUT
C-I
13
***TOP
ON/OFF
C-I
14
***INTERLOCK
ON/OFF
15
***U/F PROT
IN/OUT
C-I
16
IN/OUT
C-I
17
***ABTS
ON/OFF
C-I
18
###BB PROT
IN/OUT
C-I
19
###AUTO SW EQ
IN/OUT
C-I
20
BB CHK PROT
IN/OUT
C-I
21
===ACSE
IN/OUT
C-I
22
===TOP
IN/OUT
C-I
23
+++AVC
REMOTE/MANUAL
C-I
24
+++AVC
FOLLOWER / INDEPENDENT
C-I
25
+++AVC ECC_AUTO
ON/OFF
C-I
26
+++AVC ECC_MANUAL
ON/OFF
C-I
TESP11927R0/YBQ
PAGE NO. 54 OF 57
(Continued)
NO
TEXT
TYPE
27
+++INDEPENDENT
ON/OFF
C-I
28
+++MASTER
ON/OFF
C-I
29
+++FOLLOWER
ON/OFF
C-I
30
+++AUTOMATIC
ON/OFF
C-I
31
+++MANUAL
ON/OFF
C-I
32
+++LOCAL
ON/OFF
C-I
33
+++TAP
RAISE/LOWER
C-I
34
+++LOAD SHEDDING 0%
ON/OFF
C-I
35
+++LOAD SHEDDING 1%
ON/OFF
C-I
36
+++LOAD SHEDDING 3%
ON/OFF
C-I
37
+++LOAD SHEDDING 5%
ON/OFF
C-I
38
+++LOAD SHEDDING 9%
ON/OFF
C-I
39
IN/OUT
C-I
40
IN/OUT
C-I
41
xxx SVC
START/STOP
C-I
42
RAISE/LOWER
C-I
43
EMERGENCY STOP
C-I
44
xxxSVC COOLING
START/STOP
C-I
45
yyyTCR
START/STOP
C-I
46
RAISE/LOWER
C-I
47
MVAR/KV
C-I
48
OPEN/CLOSE
C-I
TESP11927R0/YBQ
PAGE NO. 55 OF 57
Table 27-15 Analog Measurand Value Acquisition at Local Control Panel and ECC
No
DATA
SOURCE
MW
MVAR
MWH
MVARH
TAP
Volts
Amps
11 - 34.5 kV
Feeder
69 - 380 kV
Feeder
Power
Transformer
(LV Side)
(LV Side)
Static Var
Compensator
(SVC)
Capacitor Bank
Thyristor
Controlled
Reactor (TCR)
Shunt Reactor
Bus Section
Other Power
Grids and
SWCC Inter-Tie
(Energy
Metering)
Major SEC
Customers
(Energy
Metering)
(Each
Phase)
(Position)
(Percent)
( & Ref
Voltage)
(Percent)
(High
Side)
1.Gross
(Export/Import)
1. Gross
(Export/Import)
2. Import
2. Import
3. Export
3. Export
(Gross)
(Gross)
10
TESP11927R0/YBQ
(Each
Section)
PAGE NO. 56 OF 57
BIBLIOGRAPHY
1.
ANSI/TIA-232-F, "Interface Between Data Terminal Equipment and Data CircuitTerminating Equipment Employing Serial Binary Data Interchange".
2.
3.
4.
Donald G. Fink and H. Wayne Beaty, "Standard Handbook for Electrical Engineers",
Fourteenth Edition, McGraw Hill, Inc., N.Y., 2000.
5.
TESP11927R0/YBQ
PAGE NO. 57 OF 57