The information on this document is the property of Infnitas Energy Solutions Pvt Ltd.
COPY RIGHT AND CONFIDENTIAL
S CAD A S YS TE M
1.0 SCOPE:
The scope of work covers design, supply, testing, installation and commissioning of
SCADA System for remote monitoring of EHV switchyards adjoining the switchyard of EHV
Consumer from Maharashtra State Electricity Transmission Company Limited (MSETCL)'s
nearby manned substation. The communication link will be either PLCC or Fibre Optic (FO) cable
depending upon site conditions/length of line. Substation layout indicates the details of the
switchyard(s) to be monitored and the details of the substation, where the work station of
SCADA is to be installed for remote monitoring. The system shall include Substation
Communication Gateway cum RTU (SCGRTU) to interface with Numerical Relays and
Multifunction Meter and on board Digital I/Os in unmanned switchyard and provide the
information to remote work - station. Supply of UPS for the SCADA at the manned substation is
also in the scope. The SC/ RTU shall have provision for additional Alarm/ status monitoring &
control, which are not available through numeric relays, e.g. CB/ isolator status. The scope shall also
include supply and laying of any cables required for the functional requirements of the SCADA
system as also supply and commissioning of Gateway and PLCC modem as applicable for data
transfer to MSETCLs remote (Manned) Station, from where the data is to be transferred to
the Load Dispatch Centre.
2.0
General Requirements:
2.1 The HMI cum workstation of SCADA will be placed in the manned remote Substation control
room of MSETCL. The SCADA system shall acquire and monitor the parameters of
unmanned substation and also enable control through the SCGRTU units. SCGRTU shall have
in-built Serial (RS232) and Ethernet interface (10/100Mbps), to be made available for communication to
Remote MSETCL station over PLCC (Serial RS232) and FO Network (over Ethernet). SCGRTU
shall also be able to communicate over Ethernet to an optional Local HMI.
2.2
The SCADA system envisaged shall also communicate data on real time basis to the
existing SCADA System at MSETCL's Load Dispatch Center(LDC), Kalwa / Ambazari (whichever
is nearby) using PLCC links. Matching of protocol of the proposed system at (manned
substation) with existing SCADA at LDC. Ne cessary gateway / pr otocol con vert er / har dwar e
requ ire m en t sha l l al so b e i nc l ude d i n the scop e.
2.3
A single SCGRTU unit for entire sub-station or baywise IED for monitoring &
controlling each bay in the substation should be provided. If single SCGRTU is used, the same
shall have redundancy in the power supply circuit. The SCGRTU/bay controller IEDs shall be mounted
in a panel (cubicle) of size 2312 x 800 x 800 mm unless otherwise specifically approved by the
purchaser. All the SCGRTU/ / bay IEDs shall be interlinked with each other through fiber
optic ring network. Minimum speed of the fiber optic network should be 2.5 MBPS. The
SCGRTU shall communicate with the numerical relays / meters provided in the local substation.
2.4
Time synchronization of SCGRTU shall be possible. A GPS receiver for time
synchronization, with an accuracy of 1milli second, shall also be included in the scope.
2.5
Parallel redundant online UPS shall be provided (including necessary distribution
panel) for the SCADA. UPS batteries shall provide backup for 2 hours (minimum).
2.6
The system should be scalable and it should he possible to expand the
capacity by at least 50% than the supplied capacity.
3.0
Requirements of SCADA Master:
3..1
The SCADA Master shall be a server grade PC, based on Windows
operating system.
3.2
The SCADA system shall be designed to comply with international
Industry Standards for software, networking and open protocols.
3.3
The SCADA Software offered must have been in use in electrical
substation application for
at
least
two
years as on the date of
tender submission. Necessary supporting documents
shall
he
I/O
submitted alongwith the offer.
3.4
The
PC
hardware
shall
be
of
server
grade,
capable
of
continuous operation at site.
3.5
The SCADA Master shall collect, process, and store real- time data
from the SCGRTU/ bay IED units.
3.6
One dot matrix and one LaserJet printer shall be provided on
SCADA LAN network
for
printing of
trends etc. The work station shall
the
alarms, events, displays,
be provided with high resolution
20" TFT color monitor.
3.7
3.7.1.
The
SCADA software shall
Graphical representation
of
support the
substation
following features:
mimic
diagrams, system
parameters and equipment status (dynamic).
3.7.2.
Login password for users.
3.7.3.
User
profiles - Different levels of
privileges for
operators and
engineers.
3.7.4.
User-friendly configuration interface that does not require
special software skills.
3.7.5.
Alarm Lists with minimum 6 priority levels.
3.7.6.
Event lists, duly time stamped.
3.7.7.
Writing of procedures and notes for operator. It shall be possible to
present these instructions automatically to
the operator when an
alarm or event is processed.
3.7.8.
3.7.9.
Real-time and Historical Trending of data.
Report Generation (Such as Log sheets 15 minutes, hourly, hourly,
daily
and
monthly, Minimum-Maximum report, Interruption report,
Energy audit, Occurrence report, etc.).
3.7.10.
All operator actions should be recorded automatically for analysis
later on.
3.7.11.
The system shall sound audible alarm with distinction between trip
and non-trip alarms/ events.
3.8
The
proposed new SCADA master should be able to integrate the
data from the
new SCGRTU (at client end) as well as the data
from the existing RTU (if available in the MSETCL manned end)
and send all the information on single PLCC link to remote LDC
station at Kalwa or Ambazari over IEC 870-5-101/104 protocol.
4.0
Re q uire m e nts of R T U/ St atio n - c o ntroll e r /G ate way : Each
SCGRTU shall perform the following functions -
4.1
The hardware should be provided with following features:
4.1.1
Robust power supplies capable of withstanding surges &
operate at +/- 20% of rated voltages.
4.1.2.
FLASH memory for storing software and
configuration.
It should be
possible to update/upgrade the software by simply reprogramming the
FLASH memory.
4.1.3.
Real Time Clock with very high accuracy of minimum 100
ppm or better.
4.1.4.
4.1.5.
SMD (Surface Mounted Device) technology for manufacturing.
Very high M.T.B.F. (Mean Time Between Failures).
4.1.6.
Compliance to
the
internationally accepted IEC
isolation, impulse, fast
standards for
transient, HF disturbance, electromagnetic
disturbance, electrostatic discharge and other relevant type tests as
applicable to unprotected equipment in EHV substation environments.
Type
Testing must
have
been
carried
out
by
approved
independent accredited test houses and applicable certificates should
be provided alongwith the offer.
4.2.
Facility to monitor alarms and status inputs of
the bay through
various auxiliary contacts. Both single contact (N/O or
N/C) and
double contact (N/O & N/C) inputs should be possible. It should
be possible to invert status of the input through software.
4.3
Number of inputs/outputs to be
monitored from
each
bay is
tentatively as per I/O.
4.4
Digital Outputs (including 1 trip
+ 1 close signal), for trip
and
close functions (i.e. the commands from SCADA) should be
routed through suitable (separate) auxiliary relays.
4.5
All the alarm & status inputs shall be monitored with a resolution of
1 mSec. Time stamping of each input shall be provided.
filtering'
of
digital
inputs
shall
`Chatter-
be provided to suppress unwanted
alarms.
4.6
Shall support time synchronization from SCADA through protocol or
directly from the GPS clock.
4.7
breaker
Shall have
provision for
(Trip/Close)
when
extending control command to
initiated
from
SCADA. Select-
before-Execute feature shall be provided for control function.
External control output relays shall be provided for operation of the
breakers. The relay contact shall be rated for 220V dc @10 A. IED shall
have facility
for 8 control functions per
bay,
which includes reset
command for annunciation, electrical latch relays, alarm schemes, etc
including the breaker close/trip functions.
4.8
The
SCGRTU
multifunction meters
shall
extract
provided on
the
each
data
from
the
control panel and shall
transfer the same (modbus protocol) to the SCADA system.
4.9
Low-density plug-in type I/O modules shall be provided for digital
inputs, control outputs
and CTPT
inputs.
The I/O modules shall
be
identical for each type of input. Screw type terminations shall be provided
for all I/Os. Necessary protection to
avoid
inadvertent
disconnection
of
CT input
shall
be provided. Details of such scheme shall he furnished
in the offer. CT/PT secondary
shall not be directly terminated
on the
SCGRTU terminal but the same shall be routed through the terminal
blocks (disconnecting type) in the panel.
4.10
The
IED (SCGRTU) shall support physical Interface such
RS232/485,
Ethernet
Interface
as
for Communicating with
Numerical IEDs.
4.11
The
provide two
SCGRTU shall
communication
to
SCADA
multifunction meters etc.
Both RS232 and
as
numbers of
as
well
per
as
serial ports for
numerical relays,
each sub-station requirements.
RS485 interfaces
shall be provided for every
serial port.
4.12
The serial ports (both RS232
& RS485) shall be isolated
and support asynchronous interface capable of operating between
200 Baud and 38.4K Baud. LED indications for transmit/receive of
each channel shall be provided.
4. 13
A separate diagnostic/configuration port (RS232) shall be provided in
each SCGRTU.
4.14
A user-friendly software configuration tool
configuration to
the IEDs/
RTU
to create & download
shall be supplied. The tool will be
installable in a Notebook PC.
4.15
The SCGRTU shall be provided with control logic functions for
breaker control interlocking. A software tool to create & download
all
the
required interlock logics to
the
SCGRTU shall also be
supplied. The tool shall be installable in a Notebook PC.
4.16
The IED shall support communication through different media such
as Ethernet, Radio, VSAT, Dial-up (Telephone line) and PLCC.
4.17
The
SCGRTU
shall
support
Ethernet
port
for
communication over Transmission Control Protocol / Internet
Protocol (TCP/IP) network Protocol.
4.18
The Serial and Ethernet ports shall be provided in the form of plug-in
type modules for ease of maintenance.
4.19
The
SCGRTU shall
be
provided with
an
interface for integration
with 3rd party software tools such as harmonic analysis, disturbance
data analysis etc.
4.20
A Notebook PC
with min. two serial ports shall be supplied for
diagnostics and maintenance of the SCGRTU.
5.0
For
transfer of
substation, the
data from local substation to
communication medium will
remote manned
be PLCC link or fiber
optic / ADSS cable. Suitable hardware / Interface/ Gateway required for
this purpose shall be included in
Wherever the medium is
the
scope
wherever
required.
PLCC,
VFT
modem
may
be
required for
interfacing with the
PLCC
equipment, the supply, installation & commissioning of which will be
in the scope of bidder wherever applicable. For this purpose, un it
r at e
of
VFT mod e m ( N S K- 5 of A B B )
sh all
be q u ot e d b y t h e
bidd er .
6.0
Requirements of UPS:
UPS shall be provided with following specifications:
Item
Specifications / Requirements
Capacity
Suitable capacity to meet the system
requirement, but not less than 1kVA
Technology
Microcontroller Based
Switching
Type
Parallel redundant, True Online
Conversion
Input
Voltage
170 V AC to 260 V AC or better, on full load
Input
Frequency
50 Hz +/-5%
Input Power
Factor
0.65 to 1
Output
Voltage
230 Volts +/- 2%
Output
Frequency
50 Hz Sync to mains supply
Total
Harmonic
Less
than
5.0%
and
sinusoidal
waveform, on linear load Distortion
Load Power
Factor
0.6 to1
Efficiency
High
Frequency
Double
50 Hz +/- 0.15% when on battery
> 85%
Communicat
ion Port
RS 232 for UPS Monitoring Software Remote
Monitoring UP S Monitoring Software through serial
port
Back-up
Time
2 hours
Battery Type
Sealed Maintenance Free
Alarm
/
Indications
Minimum
provided.
following
alarms
shall
he
UPS on Mains
Battery on Load
Battery Low
Mains Failure, over load
Any other
Protections
7.0
Circuit breaker at I/P, Fuse for Battery, Fuse
for I/P, Electronic short circuit protection, Electronic
overload protection
Requirements of PC Hardware:
PCs shall be provided with following specifications:
Description
Specifications /
Requirements
Make
Manufactured by ISO
9001 or 9002 certified
manufacturing unit.
HP/IBM/DELL
Model
Server Grade
(Workstation PC)
CPU
Dual core 3.0 GHz
Memory
2 GB Memory expandable up
to 4 GB
Monitor
20" High resolution TFT color
Monitor with graphical
controller
Hard Disk
Minimum 250 GB SATA
CD ROM
DVD 32-bit PCI, 10/100
Mbps Intel Ethernet
(Integrated on
motherboard)
Ethernet Interface
32-bit PCI, 10/100 Mbps Intel
Ethernet
(Integrated
on
motherboard) Ports
4 USB ports or more
2 serial (9 pin), one parallel,
one keyboard and one mouse
port
Multimedia
1 X Sound card, 2
External Speakers
Key Board
107 Keys standard
keyboard
Mouse
PS2 type Microsoft or
equivalent Mouse with
scroll wheel
Operating System
Windows XP Professional
/ Vista Business/ 2003
Server, Antivirus software
2 years subscription, MS
Office
Accessories
a) Good quality Mouse
Pad and Dust Covers
b) Set of good quality
furniture for the
workstation
7.0
Requirements of Note book PC:
IBM/COMPAQ/HP make
Intel Pentium Dual Core processor
Min. 1.6 GHz
Min. 1MB cache, 2 GB RAM, 120 GB HDD
DVD-CDRW, 15" colour TFT screen. Li-ion battery
2 X serial ports (USB - RS232 Converters), Ethernet port
Pre-loaded Operating system (XP-Pro) and antivirus
Internal Modem