Output Ratings
Voltage, Frequency
480V, 60 Hz
Ratings and Performance Data
Prime
Standby
- / -
- / -
437.5 kVA / 350.0 kW
500.0 kVA / 400.0 kW
Ratings at 0.8 power factor.
Please refer to the output ratings technical data section for specific
generator set outputs per voltage.
Prime Rating
These ratings are applicable for supplying continuous electrical power
(at variable load) in lieu of commercially purchased power. There is no
limitation to the annual hours of operation and this model can supply 10%
overload power for 1 hour in 12 hours.
Standby Rating
These ratings are applicable for supplying continuous electrical power (at
variable load) in the event of a utility power failure. No overload is
permitted on these ratings. The alternator on this model is peak
continuous rated (as defined in ISO 8528-3).
Standard Reference Conditions
Note: Standard reference conditions 25C (77F) Air Inlet Temp, 100m
(328 ft) A.S.L. 30% relative humidity.
Fuel consumption data at full load with diesel fuel with specific gravity of
0.85 and conforming to BS2869: 1998, Class A2.
Engine Make & Model:
Perkins 2206A-E13TAG6
Alternator manufactured for
FG Wilson by:
Leroy Somer
Alternator Model:
LL6114B
Control Panel:
PowerWizard 1.1+
Base Frame:
Heavy Duty Fabricated Steel
Circuit Breaker Type:
3 Pole MCCB
Frequency:
50 Hz
60 Hz
1800
Engine Speed: RPM
Fuel Tank Capacity:
888 (234.6)
litres (US gal)
Fuel Consumption: l/hr (US gal/hr)
- Prime
89.1 (23.5)
- Standby
101.0 (26.7)
(100% Load)
Available Options
FG Wilson offer a range of optional features to tailor our generating
sets to meet your power needs. Options include:
Upgrade to CE Certification
A wide range of Sound Attenuated Enclosures
A variety of generating set control and synchronising panels
Additional alarms and shutdowns
A selection of exhaust silencer noise levels
For further information on all of the standard and optional features
accompanying this product please contact your local Dealer or visit:
www.FGWilson.com
Dimensions and Weights
Length (L)
Width (W)
Height (H)
Dry
Wet
mm (in)
mm (in)
mm (in)
kg (lb)
kg (lb)
3800 (149.6)
1131 (44.5)
Dry = With Lube Oil
2156 (84.9)
3183 (7017)
3241 (7145)
Wet = With Lube Oil and Coolant
Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1.22.
Generating set pictured may include optional accessories.
Engine Technical Data
50 Hz
Air Systems
No. of Cylinders / Alignment:
Air Filter Type:
6 / In Line
Cycle:
Bore / Stroke: mm (in)
130.0 (5.1)/157.0 (6.2)
Induction:
Turbocharged Air To Air
Charge Cooled
Water
Governing Type:
Electronic
Governing Class:
ISO 8528 G2
Compression Ratio:
16.3:1
12.5 (762.8)
Moment of Inertia: kg m (lb/in)
2.77 (9465)
Weight: kg (lb)
26.9 (950)
- Standby
29.0 (1024)
6.4 (25.7)
50 Hz
60 Hz
45.2 (11.9)
Max. Combustion Air Intake
Restriction: kPa (in H2O)
Cooling System Capacity: l (US gal)
Water Pump Type:
Engine Electrical System:
- Voltage / Ground
- Prime
Cooling System
Displacement: l (cu. in)
Centrifugal
Heat Rejected to Water & Lube Oil:
24/Negative
- Battery Charger Amps
Non Canister
Combustion Air Flow: m/min (cfm)
4 Stroke
Cooling Method:
- Prime
146.4 (8326)
- Standby
162.2 (9224)
kW (Btu/min)
70
- Dry
1301 (2868)
- Wet
1351 (2978)
Heat Radiation to Room: Heat radiated from engine and alternator
- Prime
70.0 (3981)
- Standby
92.7 (5272)
kW (Btu/min)
Radiator Fan Load: kW (hp)
50 Hz
60 Hz
Radiator Cooling Airflow: m/min (cfm)
1800
External Restriction to
Cooling Airflow: Pa (in H2O)
- Prime
406.5 (545.0)
- Standby
461.7 (619.0)
- Prime
2168.0 (314.4)
Lubrication System
- Standby
2461.0 (357.0)
Oil Filter Type:
Performance
Engine Speed: rpm
60 Hz
Gross Engine Power: kW (hp)
19.0 (25.5)
538.2 (19006)
-
125 (0.5)
Designed to operate in ambient conditions up to 50C (122F).
Contact your local FG Wilson Dealer for power ratings at specific site conditions.
BMEP: kPa (psi)
Eco, Full Flow
Total Oil Capacity: l (US gal)
40.0 (10.6)
Oil Pan: l (US gal)
38.0 (10.0)
Oil Type:
Oil Cooling Method:
Fuel System
Fuel Filter Type:
Replaceable Element
Recommended Fuel:
Class A2 Diesel or BSEN590
Water
Exhaust System
Fuel Consumption: l/hr (US gal/hr)
110%
100%
75%
50%
Silencer Type:
Prime
Load
Load
Load
Load
Silencer Model & Quantity:
50 Hz
60 Hz
101.0 (26.7)
89.1 (23.5)
68.1 (18.0)
47.3 (12.5)
100%
75%
50%
Load
Load
Load
50 Hz
60 Hz
101.0 (26.7)
77.0 (20.3)
53.2 (14.1)
Standby
API CH4 SAE15W-40
(Based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869,
Class A2)
50 Hz
60 Hz
Industrial
IND-Option (1)
Pressure Drop Across Silencer
System: kPa (in Hg)
Silencer Noise Reduction Level: dB
Maximum Allowable Back Pressure:
10.0 (3.0)
- Prime
75.5 (2666)
- Standby
84.3 (2977)
- Prime
618 (1145)
- Standby
680 (1256)
kPa (in Hg)
Exhaust Gas Flow: m/min (cfm)
Exhaust Gas Temperature: C (F)
Alternator Physical Data
Alternator Operating Data
Manufactured for FG Wilson by:
Leroy Somer
Model:
Overspeed: rpm
2250
Voltage Reguation: (Steady state)
+/- 0.5%
Wave Form NEMA = TIF:
50
Wave Form IEC = THF:
2.0%
LL6114B
No. of Bearings:
Insulation Class:
Winding Pitch Code:
2/3 - 6
Wires:
12
Ingress Protection Rating:
Radio Interference:
SHUNT
- 50 Hz
R250
- 60 Hz
26.9 (1530)
AVR Model:
Alternator
Performance Data:
4.0%
Suppression is in line with European
Standard EN61000-6
Radiant Heat: kW (Btu/min)
IP23
Excitation System:
Total Harmonic content LL/LN:
50 Hz
60 Hz
Data Item
480/277V
380/220V
440/254V
240/139V
Motor Starting
220/127V
880
572
751
300
300
300
Xd
3.350
5.253
3.986
X'd
0.193
0.302
0.229
X"d
0.135
0.212
0.161
Capability* kVA
Short Circuit
Capacity** %
Reactances: Per Unit
Reactances shown are applicable to prime ratings.
*Based on 30% voltage dip at 0.6 power factor and SHUNT excitation.
**With optional permanent magnet generator or AREP excitation.
Output Ratings Technical Data 50 Hz
Voltage
Output Ratings Technical Data 60 Hz
Prime:
kVA
Standby:
kW
kVA
Voltage
kW
Prime:
kVA
Standby:
kW
kVA
kW
480/277V
437.5
350.0
500.0
400.0
220/127V
437.5
350.0
500.0
400.0
380/220V
430.0
344.0
473.0
378.4
440/254V
437.5
350.0
500.0
400.0
240/139V
437.5
350.0
500.0
400.0
General Information
Documentation
A full set of operation and maintenance manuals and circuit wiring diagrams.
Generating Set Standards
The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, NEMA MG-1.22.
FG Wilson is a fully accredited ISO 9001 company.
Warranty
All prime equipment carries a one year manufacturer's warranty. Standby equipment, limited to 500 running hours per year, has a two year manufacturer's
warranty. For details on warranty cover please contact your local Dealer, or visit our website: FGWilson.com.
Dealer contact details:
FG Wilson manufactures product in the following locations:
Northern Ireland Brazil China India USA
With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.
FG Wilson is a trading name of Caterpillar (NI) Limited.
In line with our policy of continuous product development, we reserve the right to change specification without notice.
P501-1/4PP/0514/GB