Section VI Appendix
Electronic Preset Delivery System
AccuLoad III ALS1 and ALD1
Operator Reference Manual
Issue/Rev. 0.5 (4/02)
Bulletin MN06118L
Caution
The default or operating values used in this manual and in the program of the AccuLoad III
are for factory testing only and should not be construed as default or operating values for
your metering system. Each metering system is unique and each program parameter must
be reviewed and programmed for that specific metering system application.
Disclaimer
FMC Technologies Measurement Solutions, Inc. hereby disclaims any and all responsibility
for damages, including but not limited to consequential damages, arising out of or related
to the inputting of incorrect or improper program or default values entered in connection
with the AccuLoad III.
1602 Wagner Avenue P.O. Box 10428 Erie, Pa 16514-0428 Telephone: 814/898-5000 Telex: 19-9902 Fax: 814/899-8927
Table of Contents
Section I - Introduction.............................................................................................................................................. 1
Product Description............................................................................................................................................... 1
How To Use This Manual.................................................................................................................................. 1
Product Blending with AccuLoad III...................................................................................................................... 2
Sequential Blending.......................................................................................................................................... 2
Ratio Blending................................................................................................................................................... 2
CIVACON Grounding and Overfill Monitoring.......................................................................................................... 2
AccuLoad Interface Control Board.................................................................................................................... 2
Section II - Operations.............................................................................................................................................. 3
Run Mode............................................................................................................................................................. 3
Keypad Functions................................................................................................................................................. 3
Overview............................................................................................................................................................... 4
Remote Start/Stop............................................................................................................................................. 4
Additive Monitoring............................................................................................................................................ 4
Master/Slave Communications.......................................................................................................................... 4
Backup Communications Port........................................................................................................................... 5
Additive Injector Selection..................................................................................................................................... 5
Automated Proving Mode.................................................................................................................................. 6
Full Screen and Split Screen Modes..................................................................................................................... 8
Keypad Data Entry................................................................................................................................................ 8
Entry to Main Directories....................................................................................................................................... 9
Program Subdirectory Selection......................................................................................................................... 10
Changing Program Code Parameters................................................................................................................. 11
Numeric Data.................................................................................................................................................. 11
Options............................................................................................................................................................ 12
Alphanumeric Data.......................................................................................................................................... 12
Viewing the Help Messages............................................................................................................................ 13
Exiting to the Main Menu..................................................................................................................................... 14
Section III - Security............................................................................................................................................... 15
Security............................................................................................................................................................... 15
Passcode......................................................................................................................................................... 15
Set Parameter Security.................................................................................................................................... 15
Resetting Passcode......................................................................................................................................... 16
Section IV - Dynamic Displays................................................................................................................................ 17
Dynamic Displays................................................................................................................................................ 17
Keypad Functions............................................................................................................................................ 17
Entry to Dynamic Displays............................................................................................................................... 17
Dynamic Display System..................................................................................................................................... 18
System Dynamic Displays............................................................................................................................... 18
Product Dynamic Displays............................................................................................................................... 19
Recipe Dynamic Displays................................................................................................................................ 20
Batch Dynamic Displays.................................................................................................................................. 21
Transaction Dynamic Displays......................................................................................................................... 22
Blend Dynamic Displays.................................................................................................................................. 23
Section V - Diagnostics.......................................................................................................................................... 24
Table of Contents
Diagnostics Dynamic Displays............................................................................................................................ 24
Active Alarms................................................................................................................................................... 24
Alarm History................................................................................................................................................... 24
Non-Reset Volumes......................................................................................................................................... 25
Event Log........................................................................................................................................................ 25
Transaction Log............................................................................................................................................... 26
Audit Trail......................................................................................................................................................... 28
Digital Inputs.................................................................................................................................................... 28
Digital Outputs................................................................................................................................................. 28
Analog Inputs.................................................................................................................................................. 29
Analog Outputs................................................................................................................................................ 29
Pulse Inputs..................................................................................................................................................... 29
View Turbine Meter Data................................................................................................................................. 30
Communications Monitor................................................................................................................................. 30
CIVACON Overfill Monitor.................................................................................................................................. 30
Boolean Algebraic........................................................................................................................................... 31
User Boolean Registers................................................................................................................................... 31
User Algebraic Registers................................................................................................................................. 31
Equation Line Status....................................................................................................................................... 31
General Purpose Timers................................................................................................................................. 31
Software Version............................................................................................................................................. 32
Factory Diagnostics......................................................................................................................................... 32
Program Mode Diagnostics................................................................................................................................. 32
Analog Input Test............................................................................................................................................. 32
Analog Output Test.......................................................................................................................................... 33
Digital Input Test.............................................................................................................................................. 33
Digital Output Test........................................................................................................................................... 33
Pulse Input Test............................................................................................................................................... 33
Pulse Output Test............................................................................................................................................ 34
Turbine Meter Diagnostics............................................................................................................................... 34
Add-Pak Diagnostics....................................................................................................................................... 35
Software Version............................................................................................................................................. 35
I/O Diagnostics................................................................................................................................................ 35
Test Inject........................................................................................................................................................ 37
Initialize........................................................................................................................................................... 37
Communications Test...................................................................................................................................... 37
Keypad Test..................................................................................................................................................... 38
Display Pixel Test............................................................................................................................................ 38
Boolean/Algebraic Processing......................................................................................................................... 38
User Boolean Registers................................................................................................................................... 38
User Algebraic Registers................................................................................................................................. 38
Equation Line Status....................................................................................................................................... 38
General Purpose Timers................................................................................................................................. 39
Reset Totals..................................................................................................................................................... 39
Erase Event Log.............................................................................................................................................. 39
Erase Transaction Log..................................................................................................................................... 39
Table of Contents
Factory Initialize.............................................................................................................................................. 40
Factory Diagnostics......................................................................................................................................... 40
Section VI - Reference............................................................................................................................................ 41
Configuration 000 Arm Configuration Directory................................................................................................41
Configuration 001 Number of Load Arms..................................................................................................... 41
Configuration 002 Arm 1 Configuration........................................................................................................ 41
Configuration 003 Arm 1 Number of Products..............................................................................................41
Configuration 004 Arm 2 Configuration........................................................................................................ 41
Configuration 005 Arm 2 Number of Products..............................................................................................42
Configuration 020 Number of Injectors......................................................................................................... 42
Configuration 100 Pulse Input Directory....................................................................................................... 42
Configuration 101 Transmitter Channel Selection........................................................................................42
Configuration 102 Meter Pulse Transmitter Integrity.....................................................................................42
Configuration 103 Pulse Input 3 Function..................................................................................................... 42
Configuration 104 Pulse Input 3 Arm............................................................................................................ 42
Configuration 105 Pulse Input 3 Meter......................................................................................................... 43
Configuration 107 Pulse Input 4 Function..................................................................................................... 43
Configuration 108 Pulse Input #4 Arm.......................................................................................................... 43
Configuration 109 Pulse Input 4 Meter......................................................................................................... 43
Configuration 111 Pulse Input 5 Function..................................................................................................... 43
Configuration 112 Pulse Input #5 Arm.......................................................................................................... 43
Configuration 113 Pulse Input 5 Meter......................................................................................................... 43
Configuration 115 - Pulse Input 6 Function..................................................................................................... 44
Configuration 116 Pulse Input #6 Arm.......................................................................................................... 44
Configuration 117 Pulse Input 6 Meter......................................................................................................... 44
Configuration 200 Pulse Output Directory.................................................................................................... 44
Configuration 201 - Pulse Output 1 Function................................................................................................... 44
Configuration 202 - Pulse Output 1 Pulse/Volume..........................................................................................44
Configuration 203 - Pulse Output 1 Units........................................................................................................ 45
Configuration 204 Pulse Output 1 Max Frequency.......................................................................................45
Configuration 205 - Pulse Output 2 Function................................................................................................... 45
Configuration 206 - Pulse Output 2 Pulse/Volume..........................................................................................45
Configuration 207 Pulse Output 2 Units....................................................................................................... 45
Configuration 208 Pulse Output 2 Max Frequency.......................................................................................45
Configuration 300 Digital Input Directory...................................................................................................... 45
Configuration 301, 305, 309, 313, 317, 321, 325, 329, 333, 337, 341 - Digital Input Function........................46
Configuration 302, 306, 310, 314, 318, 322, 326, 330, 334, 338, 342 Digital Input Arm Assignment...........46
Configuration 304, 308, 312, 316, 320,324, 328, 332, 336, 340, 344 Digital Input Product.........................47
Configuration 400 Digital Output Directory................................................................................................... 47
Configuration 401, 405, 409, 413, 417, 421, 425, 429, 433, 437, 441, 445, 449, 453
Digital Output Function............................................................................................................................ 47
Configuration 402, 406, 410, 414, 418, 422, 426, 430, 434, 438, 442, 446, 450, 454
Digital Output Arm Assignment............................................................................................................... 48
Configuration 403, 407, 411, 415, 419, 423, 427, 431, 435, 439, 443, 447, 451, 455
Digital Output Meter Assignment............................................................................................................. 48
Table of Contents
Configuration 404, 408, 412, 416, 420, 424, 428, 432, 436, 440, 444, 448, 452, 456
Digital Output Product Assignment.......................................................................................................... 49
Configuration 600 Analog I/O Directory........................................................................................................ 49
Configuration 601, 611, 621, 631, 641, 651 - Analog I/O Function..................................................................49
Configuration 602, 612, 622, 632, 642, 652 Analog I/O Arm Assignment....................................................49
Configuration 603, 613, 623, 633, 643, 653 Analog I/O Meter Assignment..................................................49
Configuration 605, 615, 625, 635, 645, 655 - Analog I/O Type........................................................................50
Configuration 606, 616, 626, 636, 646, 656 - Analog I/O Calibration 1 Counts...............................................50
Configuration 607, 617, 627, 637, 647, 657 - Analog I/O Calibration 2 Counts...............................................50
Configuration 608, 618, 628, 638, 648, 658 - Analog I/O Low Value...............................................................50
Configuration 609, 619, 629, 639, 649, 659 - Analog I/O High Value..............................................................50
Configuration 610, 620 - RTD Offset............................................................................................................... 50
System 100 General Purpose Directory........................................................................................................... 51
Date and Time................................................................................................................................................. 51
System 101 - Date........................................................................................................................................... 51
System 102 Time.......................................................................................................................................... 51
System 111 - Flow Rate Time......................................................................................................................... 51
System 112 - Flow Rate Descriptor................................................................................................................. 52
System 121 - Dynamic Display Timeout.......................................................................................................... 52
System 122 - Auto Reset Timer....................................................................................................................... 52
System 131 - Decimal/Comma Select............................................................................................................. 52
System 132 - Start Key Disable....................................................................................................................... 52
System 133 - Default/Translated Literals......................................................................................................... 52
System 134 - Transaction ID........................................................................................................................... 52
System 135 - Transaction ID Message............................................................................................................ 52
System 136 - Number of Batches/Transaction................................................................................................53
System 137 Powerfail Alarm......................................................................................................................... 53
System 151, 152, 153, 154, 155 - Access Code..............................................................................................53
System 156, 157 - Security Input Access Level...............................................................................................53
System 300 Volume Accuracy Directory....................................................................................................... 53
System 301 - Volume Units............................................................................................................................. 53
System 302 - Mass Units................................................................................................................................. 54
System 303 Volume Descriptor.................................................................................................................... 54
System 304 Mass Descriptor........................................................................................................................ 54
System 311 Maximum Preset....................................................................................................................... 54
System 312 Minimum Preset........................................................................................................................ 54
System 313 Auto Preset............................................................................................................................... 55
System 314 - Auto Preset Increment............................................................................................................... 55
System 315 - Transaction Termination............................................................................................................ 55
System 316 Recipes per Transaction........................................................................................................... 55
System 321 - Auto Prove Select...................................................................................................................... 55
System 322 - Proving Counters....................................................................................................................... 56
System 331 Run Display.............................................................................................................................. 56
System 332 Preset Volume Type.................................................................................................................. 56
System 333 Delivery Volume Type............................................................................................................... 56
System 334 Display Resolution.................................................................................................................... 56
Table of Contents
System 400 Temperature/Density Directory.................................................................................................56
System 401 - Temperature Units..................................................................................................................... 57
System 402 - Reference Temperature............................................................................................................. 57
System 411 - Density Units............................................................................................................................. 57
System 500 Pressure Directory.................................................................................................................... 57
System 501 - Pressure Units........................................................................................................................... 57
System 600 Alarm Configuration Directory................................................................................................... 57
System 601 - Run/Ready Alarm Clearing........................................................................................................ 58
System 602 to 640 and 671 to 680 - Alarm Configuration..............................................................................58
System 686 to 695 - User Alarm Messages.................................................................................................... 60
System 700 Communications Directory........................................................................................................ 60
System 701 Load Arm 1 Address................................................................................................................. 60
System 702 Load Arm 2 Address................................................................................................................. 60
System 703, 708, 713, 718 - Comm Port Function.......................................................................................... 60
System 704, 709, 714, 719 - Baud Rate.......................................................................................................... 61
System 705, 710, 715, 720 - Data/Parity......................................................................................................... 61
System 706, 711, 716, 721 - Control............................................................................................................... 61
System 707, 712, 717, 722 - Timeout.............................................................................................................. 62
System 731 - Comm Link Programming.......................................................................................................... 62
System 732 - Modbus Endian Protocol........................................................................................................... 62
System 741 - Prompts Used............................................................................................................................ 62
System 742 - Prompt Timeout......................................................................................................................... 62
System 743, 746, 749, 752, 755 - Prompt Message........................................................................................62
System 744, 747, 750, 753, 756 - Prompt Input Type.....................................................................................63
System 745, 748, 751, 754, 757 - Prompt Length...........................................................................................63
System 800 Additive Directory...................................................................................................................... 63
System 801 - Additive Selection Method......................................................................................................... 63
System 802 - Additive Pacing Units................................................................................................................. 64
System 803 - Additive Stop Option.................................................................................................................. 64
System 804 - Additive Stop Volume................................................................................................................. 64
System 805, 808, 811, 814, 817, 820, 823, 826, 829, 832, 835, 838 - Additive Types....................................64
System 806, 809, 812, 815, 818, 821, 824, 827, 830, 833, 836, 839 - Additive Arm.......................................65
System 807, 810, 813, 816, 819, 822, 825, 828, 831, 834, 837, 840 Additive Plumbing..............................65
System 841 to 852 - Smart Injector Address................................................................................................... 65
System 861, 866 - Metered Injector K Factor.................................................................................................. 65
System 862, 867 - Metered Injector Meter Factor............................................................................................65
System 863, 864, 865, 868, 869, 870 Injector Tolerances............................................................................65
System 881 Additive Injection Units Descriptor............................................................................................ 66
System 882 - Additive Totals Units Descriptor.................................................................................................66
System 883 - Injection/Totalization Conversion Factor....................................................................................66
System 884 Clean Line Additive................................................................................................................... 66
System 885 - Piston Injector Feedback Errors................................................................................................ 66
System 891, 896, 901, 906, 911, 916, 921, 926, 931, 936 Add-Pak Injector K Factor.................................66
System 892, 897, 902, 907, 912, 917, 922, 927, 932, 937 Add-Pak Injector Meter Factor...........................66
System 893, 898, 903, 908, 913, 918, 923, 933, 938 Injector High Tolerances............................................66
System 894, 899, 904, 909, 914, 919, 924, 929, 934, 939 Injector Low Tolerances.....................................67
Table of Contents
895, 900, 905, 910, 915, 920, 925, 930, 935, 940 Maximum Tolerance Errors............................................67
Load Arm General Purpose Directory................................................................................................................. 67
Load Arm 101, 104 Permissive Sense......................................................................................................... 67
Load Arm 102, 105 Permissive Messages................................................................................................... 67
Load Arm 103, 106 Permissive Restart........................................................................................................ 67
Load Arm 107 Load Arm ID.......................................................................................................................... 67
Load Arm 108 Flashing Totals...................................................................................................................... 67
Load Arm Flow Control Directory.................................................................................................................... 68
Load Arm 201 - Low Flow Start Rate............................................................................................................... 68
Load Arm 202 - Low Flow Start Volume.......................................................................................................... 68
Load Arm 203 - Low Flow Start Percentage.................................................................................................... 68
Load Arm 204 - Low Flow Start Condition....................................................................................................... 68
Load Arm 205 High Flow Rate...................................................................................................................... 68
Load Arm 206 Second High Flow Rate........................................................................................................ 68
Load Arm 207 - Start After Stop Delay............................................................................................................ 69
Load Arm 208 - Overrun Alarm Limit............................................................................................................... 69
Load Arm 209 - Zero Flow Timer..................................................................................................................... 69
Load Arm 210 - Valve Delay to Open.............................................................................................................. 69
Load Arm 211 - Pump Delay to Off.................................................................................................................. 69
Load Arm 212 Valve Fault Timeout.............................................................................................................. 69
Load Arm 221 Clean Line Volume................................................................................................................ 69
Load Arm 222 Clean Line Product............................................................................................................... 69
Load Arm 223 Clean Line Alarm Limit.......................................................................................................... 69
Load Arm 224 Ratio Factor Adjust................................................................................................................ 70
Load Arm 225 Ratio Factor Time.................................................................................................................. 70
Load Arm 226 Block Valve Position.............................................................................................................. 70
Load Arm Volume Accuracy Directory............................................................................................................. 70
Load Arm 301 Blend Tolerance (Percentage)................................................................................................70
Load Arm 302 Blend Tolerance (Volume)..................................................................................................... 70
Load Arm 303 Blend Correction................................................................................................................... 71
Load Arm Communications Directory.............................................................................................................. 71
Load Arm 701 Report Selection................................................................................................................... 71
Load Arm 702 Summary Report Print Time................................................................................................. 71
Load Arm 703 Summary Report Interval...................................................................................................... 71
Load Arm 704 Report Volume Resolution.................................................................................................... 71
Load Arm 705 Report Pages........................................................................................................................ 71
Load Arm 706 Report HM Classification...................................................................................................... 72
Meter Flow Control Directory........................................................................................................................... 72
Meter 201 Valve Type................................................................................................................................... 72
Meter 202 PID Proportional Gain Factor...................................................................................................... 72
Meter 203 PID Integral Gain Factor.............................................................................................................. 72
Meter 204 PID Derivative Gain Favor........................................................................................................... 72
Meter 205 PID Interval.................................................................................................................................. 72
Meter 206 Zero Flow Alarm Timer................................................................................................................ 72
Meter 207 Overrun Alarm Limit..................................................................................................................... 72
Meter 208 Flow Adjust Tolerance................................................................................................................. 73
Table of Contents
Meter 209 Flow Adjust Timer........................................................................................................................ 73
Meter Volume Accuracy Directory................................................................................................................... 73
Meter 301 K Factor....................................................................................................................................... 73
Meter 302 - Dual Pulse Error Count................................................................................................................ 73
Meter 303 - Dual Pulse Error Reset................................................................................................................. 73
Meter 304 - Dual Pulse Flow Rate Cutoff........................................................................................................ 73
Meter 310 Number of Turbine Blades........................................................................................................... 73
Meter 311 Turbine Meter Diagnostic Tolerance............................................................................................ 73
Meter Temperature/Density Directory.............................................................................................................. 73
Meter 401 Densitometer Type....................................................................................................................... 74
Meter 407 - S-Mass A Coefficient.................................................................................................................... 74
Meter 408 - S-Mass B Coefficient.................................................................................................................... 74
Meter 411 - Solartron Calibration Units........................................................................................................... 74
Meter 412 - Solartron DCF.............................................................................................................................. 74
Meter 413 - Solartron K0................................................................................................................................. 74
Meter 414 - Solartron K1................................................................................................................................. 75
Meter 415 - Solartron K2................................................................................................................................. 75
Meter 416 - Solartron K18............................................................................................................................... 75
Meter 417 - Solartron K19............................................................................................................................... 75
Meter 418 - Solartron K20a............................................................................................................................. 75
Meter 419 - Solartron K20b............................................................................................................................. 75
Meter 420 - Solartron K21a............................................................................................................................. 75
Meter 421 - Solartron K21b............................................................................................................................. 75
Meter 422 - Solartron Tcal............................................................................................................................... 75
Meter 423 - Solartron Pcal............................................................................................................................... 75
Meter 441 - Sarasota Calibration Units............................................................................................................ 75
Meter 442 - Sarasota DCF.............................................................................................................................. 76
Meter 443 - Sarasota K................................................................................................................................... 76
Meter 444 - Sarasota D0................................................................................................................................. 76
Meter 445 - Sarasota T0.................................................................................................................................. 76
Meter 446 - Sarasota Tcoef............................................................................................................................. 76
Meter 447 - Sarasota Tcal............................................................................................................................... 76
Meter 448 - Sarasota Pcoef............................................................................................................................. 76
Meter 449 - Sarasota Pcal............................................................................................................................... 76
UGC Densitometer.......................................................................................................................................... 77
Meter 461 - UGC Calibration Units.................................................................................................................. 77
Meter 462 - UGC DCF..................................................................................................................................... 77
Meter 463 - UGC K0........................................................................................................................................ 77
Meter 464 - UGC K1........................................................................................................................................ 77
Meter 465 - UGC K2........................................................................................................................................ 77
Meter 466 - UGC Tc........................................................................................................................................ 77
Meter 467 - UGC Kt1....................................................................................................................................... 77
Meter 468 - UGC Kt2....................................................................................................................................... 77
Meter 469 - UGC Kt3....................................................................................................................................... 77
Meter 470 - UGC Pc........................................................................................................................................ 78
Meter 471 - UGC Kp1...................................................................................................................................... 78
Table of Contents
Meter 472 - UGC Kp2...................................................................................................................................... 78
Meter 473 - UGC Kp3...................................................................................................................................... 79
Other Densitometers....................................................................................................................................... 79
Meter 491 - Other Densitometer Calibration Units...........................................................................................79
Meter 492 - Other DCF.................................................................................................................................... 79
Meter 493 - Other A Coefficient....................................................................................................................... 79
Meter 494 - Other B Coefficient....................................................................................................................... 79
Meter 495 - Other C Coefficient....................................................................................................................... 79
Product 100 General Purpose Directory.......................................................................................................... 80
Product 101 - Product ID................................................................................................................................. 80
Product 102, 103 HM Classification............................................................................................................. 80
Product 200 Flow Control Directory.............................................................................................................. 80
Product 201 Minimum Flow Rate.................................................................................................................. 80
Product 202 High Flow Rate......................................................................................................................... 80
Product 203 Second High Flow Rate............................................................................................................ 80
Product 204 Flow Tolerance Percentage...................................................................................................... 80
Product 205 Flow Tolerance Rate................................................................................................................. 81
Product 206 First Trip Volume...................................................................................................................... 81
Product 207 Second Trip Volume................................................................................................................. 81
Product 208 Second Trip Auto Adjust........................................................................................................... 81
Product 209 Excess High Flow Rate............................................................................................................ 81
Product 210 Low Flow Rate Alarm Limit....................................................................................................... 81
Product 211 Block Valve Delay to Open....................................................................................................... 81
Product 212 Block Valve Delay to Close....................................................................................................... 82
Product 300 Volume Accuracy Directory...................................................................................................... 82
Product 301 Minimum Batch Volume............................................................................................................ 82
Product 302 - Meter Factor 1........................................................................................................................... 82
Product 304 - Meter Factor 2........................................................................................................................... 82
Product 306 - Meter Factor 3........................................................................................................................... 82
Product 308 - Meter Factor 4........................................................................................................................... 82
Product 303 - Flow Rate 1............................................................................................................................... 82
Product 305 - Flow Rate 2............................................................................................................................... 82
Product 307 - Flow Rate 3............................................................................................................................... 82
Product 309 - Flow Rate 4............................................................................................................................... 82
Product 310 - Master Meter Factor.................................................................................................................. 83
Product 311 - Linearized Factor Deviation....................................................................................................... 83
Product 312 - Meter Factor Variation Select.................................................................................................... 83
Product 313 - Meter Factor Percent Change Per Degree Temperature...........................................................83
Product 314 - Meter Factor Variation Reference Temperature.........................................................................83
Product 400 Temperature/Density Directory.................................................................................................83
Product 401 Maintenance Temperature........................................................................................................ 84
Product 402 High Temperature Alarm Limit.................................................................................................. 84
Product 403 Low Temperature Alarm Limit................................................................................................... 84
Product 411 API Table.................................................................................................................................. 84
Product 412 Reference Density.................................................................................................................... 84
Product 413 - High Density Alarm Limit........................................................................................................... 85
Table of Contents
Product 414 Low Density Alarm Limit........................................................................................................... 85
Product 500 Pressure Directory................................................................................................................... 85
Product 501 Maintenance Pressure............................................................................................................. 85
Product 502 Pressure Coefficient................................................................................................................. 85
Product 503 High Pressure Alarm Limit........................................................................................................ 85
Product 504 Low Pressure Alarm Limit........................................................................................................ 86
Product 511 Differential Pressure................................................................................................................. 86
Product 512 - Minimum Back-pressure Flow Rate........................................................................................... 86
Product 513 - Minimum Back-pressure Flow Rate Timer................................................................................86
Product 514 - Back-pressure % Reduction...................................................................................................... 86
Product 515 - Back-pressure Flow Recovery Pressure...................................................................................86
Product 516 - Back-pressure Flow Recovery Timer........................................................................................87
Product 521 - Vapor Pressure Calculation Method..........................................................................................87
Product 522, 524, 526 - Vapor Pressure......................................................................................................... 87
Product 523, 525, 527 - Vapor Pressure Temperature....................................................................................87
Recipe Directory.............................................................................................................................................. 87
Recipe x01 - Recipe Used............................................................................................................................... 88
Recipe x02 - Recipe Name.............................................................................................................................. 88
Recipe x03 HM Classification....................................................................................................................... 88
Recipe x04, x06, x08, x10, x12 Product Delivered.......................................................................................88
Recipe x05, x07, x09, x11, x13 Product Percentage....................................................................................88
Recipe x14, x17, x20, x23, x26, x29, x32, x35, x38, x41, x44, x47 Injector Volume.....................................89
Recipe x15, x18, x21, x24, x27, x30, x33, x36, x39, x42, x45, x48 Injector Rate.........................................89
Recipe x16, x19, x22, x25, x28, x31, x34, x37, x40, x43, x46, x49 Product Using Injector..........................89
Recipe 50 Clean Line Deduct....................................................................................................................... 89
Minimum Recipe Preset (Read Only).............................................................................................................. 90
Product Flow Rates (Read Only)..................................................................................................................... 90
Section VI - Appendix............................................................................................................................................. 91
Appendix I Audit Trail....................................................................................................................................... 91
Audit Trail......................................................................................................................................................... 91
Appendix II - Alarms............................................................................................................................................ 92
Metered Injector Alarms...................................................................................................................................... 93
OR: Overspeed Metered Injector..................................................................................................................... 93
NA: No Additive Pulses Alarm......................................................................................................................... 93
RA: Additive Frequency Alarm......................................................................................................................... 93
KA: Low Additive Volume................................................................................................................................ 94
Appendix III Metered Injector Map on the AccuLoad III with ALS1 and ALD1 Firmware..................................95
Section I Introduction
pulse output to be stopped at the first trip point
of the product. It will count the same number of
pulses as if the additive output was stopped at
the end of the batch.
Product Description
The Smith MeterAccuLoad III is a multiple
microprocessor-based electronic preset instrument
designed to control ratio or sequential blending of
petroleum or chemical products. Up to four products
per arm are possible for sequential blending. When
using ALS1 software for sequential blending, the
AccuLoad III allows up to four products on one arm.
When using ALD1 software, the AccuLoad III allows
up to four products on each of two arms. Both the
ALS1 and ALD1 software allow one two-product
ratio blender.
Optimum measurement accuracy is attained through
the continuous linearization of the meter factor with
changes in flow rates. The AccuLoad III is also
capable of maintaining back-pressure on the
measurement system using either automatic flow
optimization or a pressure transmitter. Volumetric
correction is calculated directly from published API
equations providing precise volumetric measurement
results.
Precise
temperature,
pressure
compensation, and density correction are options
that are available in the instrument.
The dynamic real-time display of the current actual
operating conditions of the system provide the
operator with valuable system information while the
system is operating.
The AccuLoad III provides several loading system
control functions: Additive injection, pump control,
alarm control, set stop, valve control, back-pressure
control, and automatic adjustment of final trip point.
Up to twelve different additive injectors can be
simultaneously paced or controlled through communications.
The AccuLoad III will monitor and totalize the
volume of additive injected by piston-type
additive injectors or smart injectors.
The AccuLoad III, if so programmed, will
automatically calculate and adjust the additive
10
A contact is available to start and stop a pump or
other electrically operated equipment as well as
a program code that will set the time delay of
that start or stop.
Two programmable alarm contacts are available.
They operate independently and can be
configured to close on a valve fault, on any
alarm, or not at all.
The AccuLoad III contains the intelligence to
control a Smith Meter Model 210 or 215 Digital
Control Valve, or an analog valve, that will
provide low flow start and multi-stage shutdown.
The AccuLoad III contains the intelligence to
automatically reduce the flow of product and
ensure the flow is within the pumping capabilities
of the system. Once the flow is able to continue
at the programmed high flow rate, the AccuLoad
III will increase the flow to programmed values.
The AccuLoad III, if so programmed, will
automatically adjust the final trip point of the
batch (Preset).
Critical functions, such as minimum flow rate, excess
flow rate, temperature detection, preset volume
overrun and memory retention, are monitored by
internal circuits. Any failure will signal closure of the
valve. Should the valve fail to close within a
programmable time period after having been
signaled, a contact is closed. This can be wired
through external relays to shut off the pump and/or
kill power circuits.
Environmental fluctuations within specified limits
have virtually no effect on the operation of this
control system. AccuLoad III is available in an
explosion-proof housing for hazardous locations.
(See Bulletin SS06030 for Specifications.)
MN06118L Issue/Rev. 0.5 (4/02)
Section I Introduction
How To Use This Manual
This manual is to be used as a guide for the
AccuLoad III.
This manual is divided into the following sections:
Introduction,
Operations,
Security,
Dynamic
Displays, Diagnostics, Program Codes, and
Appendix.
The "Operations" section describes the daily
operation of the AccuLoad III and what is required of
an operator to effectively load the product.
The "Security" section describes the levels of security
available within the AccuLoad III and how they can be
configured and utilized.
MN06118L Issue/Rev. 0.5 (4/02)
11
Section I Introduction
The "Dynamic Displays" section describes the
information that can be displayed by the AccuLoad III
while in the "READY" state or in the Run Mode.
product's next delivery only is adjusted to maintain the
correct blend ratio and preset amount.
The "Diagnostics" section describes the diagnostic
information that can be displayed by the AccuLoad III.
Ratio blending is the process of mixing multiple
products simultaneously during delivery to another
storage tank (e.g., a tanker truck). Ratio blending is
used primarily when loading speed is an issue, or
when the component products do not easily mix.
The "Program Codes" section gives a description of
each program code available in the instrument.
The Appendix lists the default values for the Factory
Initialization and a worksheet to write the parameters
that are programmed in the AccuLoad III.
The examples presented in this manual are for clarity
and operator convenience. The values might vary for
specific installations and/or operations.
Product Blending with AccuLoad
III
Sequential Blending
Sequential blending is the act of loading multiple
products, one at a time, into a storage tank (e.g., a
tanker truck). This is most commonly done with
products that mix very easily.
The AccuLoad III accomplishes sequential blending of
multiple products in the following manner. The ratio of
varying products is designated in the recipe as a
percentage of the total preset. These percentages
must total 100%. When the operator enters the
preset, the AccuLoad automatically calculates the
actual volumes of each product to be delivered. Each
of these is delivered as a type of "mini-batch,"
complete with individual high flow rates, first trip
volumes, and so on. The order of product delivery
must be included in the recipe definition.
If an incorrect product volume is delivered, the
volumes of the remaining products are adjusted
accordingly. If this adjustment creates a blend
intolerance alarm, the operator will be prompted to
stop or continue the batch. An exception to this rule is
when another delivery of the same product is
specified in the recipe. In this case, the volume of that
12
Ratio Blending
The AccuLoad III accomplishes ratio blending of
multiple products in the following manner. All products
required for the recipe are delivered simultaneously
through their own meters, and their corresponding
pumps and control valves. Two-stage valves are
inappropriate for ratio blending; only digital or analog
valves are acceptable. The ratio of the component
products is designated in the recipe as a percentage
of the total preset. These percentages must total
100%.
When the operator enters the preset, the AccuLoad III
automatically calculates the actual volumes of each
product to be delivered. As stated above, products are
delivered simultaneously, each through its own meter.
Flow rates are adjusted for optimal blend accuracy
while conforming to the programmed system flow
profile using Smith Meter's exclusive control
algorithm. Should flow rate variations occur, the profile
is dynamically adjusted to attain the best possible
mix.
CIVACON Grounding and Overfill
Monitoring
The AccuLoad III supports the CIVACON grounding
and overfill monitoring system. This feature requires
the addition of a CIVACON circuit board internal to the
AccuLoad's housing. The interface between the
AccuLoad III and the CIVACON system consists of a
serial communications link that requires a dedicated
communications port on the AccuLoad. The C IVACON
communications line may be multi-dropped to up to
eight separate AccuLoads, with the actual hardware
resident in one AccuLoad. For further information,
please refer to the CIVACON software specification.
MN06118L Issue/Rev. 0.5 (4/02)
Section I Introduction
AccuLoad Interface Control Board
The AccuLoad Interface Control Board provides
additional flexibility to the AccuLoad's standard
features. The optional AICB provides ten additional
metered additive injector systems. With the optional
AICB, the AccuLoad III with ALS1 and ALD1
MN06118L Issue/Rev. 0.5 (4/02)
13
firmware has the capability of handling up to twelve
metered injectors, twelve meter inputs, twelve
solenoid valve outputs, and twelve additive pump
outputs. The AICB can be mounted in the AccuLoad
III housing or in a standalone enclosure. One of the
AccuLoad III's four communication ports is required
to communicate with the AICB.
Run Mode
This is the normal driver-controlled mode of
operation where a preset volume of product is
entered into AccuLoad III. The flow is then initiated,
controlled, and stopped by the AccuLoad at the end
of the batch.
All preset and control operations can be performed
either locally through the keypad or through
communications. The operation described in this
section is based on AccuLoad III being operated
locally through the keypad. For information on
operating through communications, refer to the
AccuLoad III Communications Manual.
Keypad Functions
The pushbuttons on the keypad perform the
following preset functions in the Run Mode:
0-9
Used for presetting the quantity to be
delivered
CLEAR
Used to clear incorrect entries and to
exit from the dynamic displays
ENTER
Used for dynamic displays and
selecting the recipe to be loaded
PRINT
Signals completion of transaction when
"Print Key" option is selected in
program code 315 of the Systems
Directory
SET
Used to initiate the preset sequence
and paging through recipes
START
Used to start the delivery (providing all
external permissive senses are
satisfied)
STOP
Used to stop delivery at any time (not
intended as emergency stop)
Used to move the selection arrow up in
selection of recipes and navigating the
dynamic displays
Used to move the selection arrow
down in selection of recipes and
navigating the dynamic displays
F1
In split screen mode, toggles between
one screen view and another; in full
screen mode, toggles between one
load arm display and another
F2
Toggles between full screen and split
screen modes
Section II Operations
Overview
The "RUN" Mode permits the operator to select the
recipe and the preset volume. The operator may also
start the preset volume or observe the dynamic
variables such as flow rate, temperature, volume
correction factors, transaction totals, and nonresettable totals. The AccuLoad III processes normal
start-up, flow control and shutdown sequences, and
operator-requested stops.
Product delivery is controlled by several program
code entries. Functions such as first high flow rate,
second high flow rate, low flow start, and first and
second trip points are automatically controlled and
monitored per their program entries. Safety and
volume accuracy functions including excess high flow,
low flow, overrun, and temperature probe failure are
also monitored per their program parameters. If at any
time an alarm occurs while in the Ready State or the
Run Mode, the AccuLoad III will attempt to shut down
the flow and a message indicating an alarm condition
will pop up over the current display.
When the delivery is completed, the display will read
as follows:
800
IV
Unleaded
GAL
Batch#1
800IV
0GPM
BatchComplete
The "batch complete" message will flash, alternating
with the time and date.
Depending on how the AccuLoad III is programmed, a
transaction can be ended by pressing the "PRINT"
button, by a communication command, or by an
external input. If the "STOP" button for the preset
position is pressed during flow, and if the Start after
Stop delay is programmed, the preset position will
display a screen similar to that shown below:
Restartin
5secs
MN06118L Issue/Rev. 0.5 (4/02)
15
11/03/99
11:16:10
Once the time-out has been reached, the display will
read "Press Start to Continue" alternating with the
time and date.
IV
Unleaded
GAL
Batch#1
100IV
100
0GPM
PressStarttoContinue
The operator can then press "START" and continue
the batch. If program code 211 is programmed to
disable the time-out, the display will read as above,
with the "Press Start to Continue" message
alternating with the time and date.
Remote Start/Stop
Two of the AC or DC digital inputs can be
programmed to be used for Remote Start/Remote
Stop operations. When the power is applied to these
contacts, the AccuLoad III will respond as though the
"START" or "STOP" keys have been pressed on the
keypad.
Additive Monitoring
Additive injector feedback provides the capability of
the AccuLoad monitoring the additive products that
are being injected. The AccuLoad III monitors the
injector feedback switches for a change of state and
counts the errors if no change is detected before the
next injection. An alarm will be set if the number of
errors exceeds the programmable maximum.
Master/Slave Communications
The firmware has been designed with a
Master/Slave type of communications, with the
AccuLoad as master and the Additive Injector
System as slave. The AccuLoad constantly monitors
the Additive System for its status, polls for additive
totals, and signals the system when to inject the
additive -- all through the communications line.
Section II Operations
The AccuLoad III communications package has also
been designed with a pass-through communications
mode. In this operational mode, the supervisory
computer can talk to the Additive Injector System
through the communication lines that have been run
to the AccuLoad and from the AccuLoad to the
Additive Injector System(s). (This is further described
in the AccuLoad III Communications Manual.)
Backup Communications Port
Note: This option applies only to Revision 10 firmware, or above.
The
communications
interface
allows
two
communications ports to be programmed for control.
(On revisions prior to Revision 10, only one of the four
communications ports could be programmed for "poll
and authorize" or "remote control.") This restriction
has been lifted to allow a backup automation system
to be set up on a second port. If can be configured
just like the primary system. It is imperative to ensure
that only one port is issuing control commands.
Because both communications ports are programmed
for control, and the AccuLoad will not refuse these
commands,
two
ports
issuing
commands
simultaneously could well result in chaos.
With two communication ports programmed for
control functions, a command from either port will
reset the communications timer. If the automation
system is designed such that the backup is to poll the
AccuLoad for alarms so that it can recognize when a
communications alarm occurs, then the time between
these alarm status requests must exceed the
communications timeout programmed. Otherwise,
this alarm status polling will be sufficient to prevent a
communications alarm. The communications timeout
for the first port programmed for host communications
will be used.
Additive Injector Selection
When the AccuLoad III is operating the additive
selection can be programmed to be either automatic
or manual, depending on how Code 801 of the
Systems Directory has been programmed.
Code
Description
801
Manual/Auto Additive Injector Option
must be programmed to either:
Auto injectors -- the additive outputs that
are programmed in the AccuLoad III will
automatically be selected for each batch
according to the programming in the
recipe definition
Manual injectors where the operator is
prompted at the beginning of each
transaction
Manual injectors where the operator is
prompted at the beginning of each batch
The operation is as follows for manual selection of
additives.
1. Select Recipe.
2. The driver or operator is required to select a
recipe. Using the up and down arrow keys, the
display will read as follows:
SelectRecipe
>
Recipe1
Recipe2
PressPrintforHelp
Help: Press up or down arrow to select recipe. Press
ENTER when done.
MN06118L Issue/Rev. 0.5 (4/02)
17
3. After the recipe has been selected, press
"ENTER." The following will be displayed:
and four meter factors and associated flow rates for
each product without having to enter the program
mode for each product and meter factor.
SelectInjectors
Entry to the Automated Proving Mode requires
several conditions to be met.
>
INJ#1OFF
INJ#2OFF
PressPRINTforHelp
Help: Press up or down arrows to select injector.
Press SET key to toggle injector on/off. Press ENTER
when done.
4. Press the "SET" key to toggle Injector #1 from
"OFF" to "ON." After Additive Injector #1 has
been selected to either "ON" or "OFF," press the
down arrow key and continue selection with the
next injector.
1.
The Automated Proving Mode must be enabled
via System Code 321.
2.
The programmed security must be met. Then
when normal conditions are met for starting a
transaction (pressing the "SET" key or receiving
authorization
via
communications),
the
Automated Proving Mode will be activated.
3.
To initiate the proving sequence, the AccuLoad
will prompt for the prover coefficient of cubical
expansion. Note that the most recent value for
this entry will be displayed. If this value is
acceptable, the operator need only press
"ENTER."
5. When the additive selection is complete, press the
ENTER key.
EnterProverCoefficient
Recipe1
EnterPresetVolume
>
>
0.000186005
0GAL
11/03/99
12:24:36
PressSTARTwhenReady
4. The AccuLoad III will prompt for the low flow start
volume. If low flow start is not desired, enter zero.
Press "ENTER."
Automated Proving Mode
The AccuLoad III firmware provides an automated
proving mode of operation. When the automated
proving mode is activated, the AccuLoad will
calculate the meter factor for a proving run based on
information that is obtained during the prove. The
operator can select the flow rate and meter factor
that is being proved through the keypad of the
AccuLoad. After the prove is complete the operator
enters the prover volume and prover temperature
and the AccuLoad will calculate the new meter
factor. The operator has the choice of downloading it
to the program or ignoring it. The AccuLoad also has
the capability of providing an average meter factor
over a maximum of ten proves. This feature allows
the operator to prove the meter on all four products,
EnterLowFlowStartVolume
>
11/03/99
5.
100Gal
12:25:37
Next, the AccuLoad III will display the "Select
Recipe" prompt. If in remote control
communications mode, only those recipes
allocated will be available for selection. Recipes
must be selected before the meter factors, since
the recipe determines the product being proved.
Note that only recipes comprising 100% of a
single product may be delivered when proving.
Section II Operations
SelectRecipe
>
6. Next, the operator must select the meter factor
and flow rate for proving.
Recipe1
Recipe2
PressPRINTforhelp
SelectMeterFactortoProve
>#1
#2
#3
#4
Using the up and down arrow keys, select the
required recipe.
0.99850
0.99999
1.00000
1.00055
600GPM
400GPM
200GPM
100GPM
Move the up or down arrow keys to the meter factor
associated flow rate that is required. Note that only
those factors currently programmed will be offered
as selections. Press ENTER after entering the
selection.
7.
Enter the batch amount desired.
Recipe1
EnterPresetVolume
>
1000GAL
PressSTARTwhenready
8.
Press "START" to begin flow. The flow rate
associated with the selected meter factor will be
used as the high flow rate. The batch will be
delivered. The flow rate ramp-down from first trip
to the end of the batch will be the same as if not
proving.
If, after the batch is completed, the operator presses
"PRINT," the display reverts to the Ready Mode
display and will not go through the Auto Prove
Sequence.
9.
When the batch has completed, the AccuLoad
will prompt for the actual prover volume. Enter
the prover volume and press "ENTER."
RawMeterVolume1000.94GAL
>
MN06118L Issue/Rev. 0.5 (4/02)
19
EnterProverVolume
1000
BatchComplete
"Batch Complete" will flash with the time and date.
10. The AccuLoad III will prompt for the prover
temperature. Press ENTER to have the meter
factor calculated.
MeterTemperature60.0F
EnterProverTemperature
>
60.5F
BatchComplete
11. The AccuLoad III will then calculate the meter
factor. The new meter factor will be displayed.
#1
0.99850
NewMeterFactor
AverageFlowRate
600GPM
0.98375
500GPM
PressENTERtocontinue
12. When the ENTER key is pressed, the AccuLoad
III will display the following screen.
NewMeterFactor0.98375
>
Reject
Save
Average
Reenterprovevalues
13. If "Reject" or "Save" is selected, the AccuLoad III
will return to the Run Mode display where the
transaction can be ended. If "Average" is
selected, the AccuLoad III will then average all
meter factors in the buffer (up to ten of them).
The average meter factor will be displayed.
Select "Save" to download the average meter
factor into the Program Mode.
AverageMeterFactor0.98400
>
Continue
Save
Section II Operations
14. If "Save" is selected, the AccuLoad III will
download the average meter factor and will
return to the "RUN" mode display where the
transaction can be ended or a new batch can be
started. If "Continue" is selected, a new batch
can be started allowing the AccuLoad III to
continue proving at this rate. Note that if the
AccuLoad III is in remote control mode,
authorization is required for each batch.
15. Each time a transaction is ended and a new
transaction is begun, the AccuLoad III will start a
new prove with Step 1.
16. In the event that the meter factor is not
successfully downloaded, the AccuLoad III will
display a message indicating that the meter
factor was rejected.
Full Screen and Split Screen
Modes
While in RUN mode, the AccuLoad III operates in
one of two screen modes: full and split screen. In
split screen mode, load arms 1 and 2 appear side by
side, with a black border around the active view. Use
the F1 key to toggle between one view and the other.
Use the F2 key to switch from split to full screen
mode. If the AccuLoad is in full screen mode,
pressing F2 will shift from one full-screen load arm
display to the other full-screen load arm display. The
chart below illustrates the keystrokes that move
between states, given the starting screen state.
Split
Screen
(Arm 1)
Split
Screen
(Arm 2)
Full
Screen
(Arm 1)
Full
Screen
(Arm 2)
F1
Split Screen
(Arm 2)
Split Screen
(Arm 1)
Full Screen
(Arm 2)
Full Screen
(Arm 1)
F2
Full Screen
(Arm 1)
Full Screen
(Arm 2)
Split Screen
(Arm 1)
Split Screen
(Arm 2)
Keypad Data Entry
All programming information is entered via the
keypad or through communications. This document
will describe information being entered via the
keypad. The program codes for AccuLoad III are
divided into five main directories plus Diagnostics.
The main directories are as follows:
Configuration Directories
System Directories
Load Arm Directories
Meter Directories
Product Directories
The subdirectories for each of the five main
directories are as follows:
Configuration Directories
Code
Description
000
Load Arm Configuration Directory
100
Pulse Input Directory
200
Pulse Output Directory
300
Digital Input Directory
400
Digital Output Directory
600
Analog I/O Directory
System Directories
Code
Description
100
General Purpose Directory
300
Volume Accuracy Directory
400
Temperature/Density Directory
500
Pressure Directory
600
Alarm Configuration Directory
700
Communications Directory
800
Additive Directory
Load Arm Directories
Code
Description
100
General Purpose Directory
200
Flow Control Directory
300
Volume Accuracy Directory
700
Communications Directory
Meter Directories
Code
Description
MN06118L Issue/Rev. 0.5 (4/02)
21
200
300
400
Flow Control Directory
Volume Accuracy Directory
Temperature/Density Directory
Product Directories
Code
Description
100
General Purpose Directory
200
Flow Control Directory
300
Volume Accuracy Directory
400
Temperature/Density Directory
500
Pressure Directory
The pushbuttons on the keypad perform the following
functions while the instrument is in the Program
Mode:
09
Used to enter the access code and for
data entries
CLEAR
Used for clearing incorrect entries or
for getting to an exit point
ENTER
Used to enter the Program Mode
security access code, to enter the
subdirectory, and to enter program
data
START
Not used in Program Mode
SET
Page scrolling
PRINT
Used to access Help Messages
STOP
Used to set the security level
F1
Not used in Program Mode
F2
Not used in Program Mode
Used to move up through the menus
Used to move down through the
menus
+/-
Used for adding signs to values being
programmed
Decimal point, for values requiring
one
Section II Operations
Used for alphanumeric entries
Entry to Main Directories
1.
Close the Security input if configured. This will
provide the first step for access to program
codes. (At the factory, no Security input is
configured, so none is required.)
AccuLoadIIIReady
FMCSmithMeterInc.
PressSETKey
10/03/9916:38:00
2. Press "ENTER." This displays the main menu.
>
3.
MainMenu
DynamicDisplays
PrintMenu
ProgramModeMenu
DiagnosticsMenu
Move the arrow to the Program Mode menu and
press "ENTER." This will display the "Enter
Passcode" screen.
EnterPasscode
>
4.
Enter the access code. (The access code preset
at the factory is "0".) For security, any digit
entered will be displayed as an "X". (Access
codes can be up to four digits long.)
5.
Press "ENTER." This checks for the proper
access code. If it is correct, the following will be
displayed.
>
MN06118L Issue/Rev. 0.5 (4/02)
23
XXXX
ProgramModeMenu
ConfigDirectories
SystemDirectories
LoadArm1Directories
More
6.
Pressing the down arrow key will display the last
four items on the menu, which are as follows:
Load Arm 2 Directories
Recipe Directory
Exit Without Saving
Diagnostics
Press ENTER with the arrow in front of "System
Directories" to enter the systems directories. The
following screen will be displayed.
SystemDirectories
>
100GenPurposeDir
300VolAccuracyDir
400Temp/DensDir
7. Press ENTER with the arrow in front of "Config
Directories" to enter the configuration directories.
The following screen will be displayed.
More
Pressing the down arrow will display the remainder of
the System Directories, which is as follows:
ConfigDirectories
>
000LoadArmConfiguration
100PulseInputs
200PulseOutputs
More
Pressing the down arrow will display the remainder of
the Configuration Directory, which is as follows:
300 DC & AC Digital Inputs
400 DC & AC Digital Outputs
600 Analog Inputs/Outputs
8. If an incorrect access code was entered, the
following prompt will appear.
500 Pressure Directory
600 Alarm Directory
700 Communications Directory
800 Additive Directory
Program Subdirectory Selection
Once in the Program Mode menu, move the arrow to
the main directory required. Pressing the ENTER
key will display the subdirectories in that directory. To
select one of the subdirectories, move the arrow by
using the up and down arrow keys to the
subdirectory required. Once the arrow is in front of
the desired subdirectory, press ENTER to display the
menu for that subdirectory. The same steps are used
to get to the specific program codes.
Example:
EnterPasscode
>XXXX
AccessDenied
PressCLEARtoreenter
9. Press CLEAR to return the display to the "Enter
Passcode Screen" in Step 3.
10. Repeat Steps 3, 4, and 5 to re-enter Program
Mode.
ProgramModeMenu
>
ConfigDirectories
SystemDirectories
LoadArm1Directories
More
1. Select the required directory by moving the
cursor with the up and down arrow key on the
keypad.
Section II Operations
deliveryduringlowflowstart
ProgramModeMenu
>
LoadArm2Directories
RecipeDirectory
ExitWithoutSaving
6. Press the ENTER key on the keypad. The
display will return to the submenu, and the new
value will appear on the screen.
More
2. Press the ENTER key.
200FlowControlArm2
LoadArm2Directories
>
>
100GenPurpose
200FlowControl
300VolAccuracy
3. Choose the required subdirectory by moving
through the menu using the up and down arrow
keys.
LoadArm2Directories
4. Press the ENTER key. This will display the menu
for the subdirectory.
200FlowControlArm2
201LoFloStRate
202LoFloStVol
203LoFloSt%
0.0
0.0
0
More
5. Indicate the appropriate parameter by using the
keypad to type the required data.
203LoFloSt%
Enterpercentofpresetfor
MN06118L Issue/Rev. 0.5 (4/02)
25
7. To exit at any point in Program mode, press the
CLEAR button. Each time the CLEAR key is
pressed, the AccuLoad III will back out one
menu level. Repeat this step until the Ready
mode is reached.
Changing Program Code
Parameters
100GenPurpose
200FlowControl
300VolAccuracy
More
>
0.0
0.0
4
More
More
>
201LoFloStRate
202LoFloStVol
203LoFloSt%
>4
The program codes represent parameters that can
be changed to enhance the performance of
AccuLoad III or to accommodate application
changes. There are three types of parameters in
AccuLoad III: codes that require numerical data,
codes where an option can be selected from a list,
and codes where alphanumeric data is entered.
Once a code has been selected, change the
programmed contents by entering a new value
through the keypad.
Numeric Data
The numeric data is entered into the program codes
via the keypad just as numbers are entered into a
calculator. The number of digits for each entry is
listed in the Reference section of this manual.
Example: To change the Level 1 Access Code for
parameter 151, do the following:
1. Choose the General Purpose Directory
submenu from the System Directories menu.
>
DateandTime
Units&Identifiers
Timeouts
Display&Control
Security
2. Select "151 Level 1 Access Code" from the
Security submenu.
Security
>
151Lev1AccessCode
152Lev2AccessCode
153Lev3AccessCode
0
0
0
3. To specify a new Level 1 Access Code, enter the
desired code number.
151Lev1AccessCode
EnterAccesscodeforthis
securitylevel
>1182
4. Press ENTER to store the new value. The
display will revert to the submenu and will
indicate the new value.
>
Security
151Lev1AccessCode
152Lev2AccessCode
153Lev3AccessCode
More
1182
0
0
Note: If an incorrect value is entered on the screen and has not
been stored, the value can be cleared by pressing CLEAR twice
and a new value can then be entered.
Section II Operations
Options
Codes that have a number of options are changed
by moving the arrow to the option required by the
application, then pressing "ENTER."
Example: To configure Load Arm 1 for sequential
blending, choose the Load Arm Configuration
submenu from the Configuration Directories menu.
1. Position the cursor beside "002 Arm1 Config"
and press ENTER.
000LoadArmConfiguration
>
001NumberofLoadArms
002Arm1Config
003Arm2Config
More
2. The following screen will appear. Position the
cursor beside the desired configuration and
press ENTER.
002Arm1Config
Straight
> Sequential
Ratio
PressPRINTforhelp
3. The new value will be stored and the display will
revert to the submenu. Notice that the new value
appears beside the parameter on the submenu
display.
>
000LoadArmConfiguration
001NumberofLoadArms
002Arm1Config
Sequential
003Arm1NumProds
More
MN06118L Issue/Rev. 0.5 (4/02)
27
Note: An entry that requires a relay to also be set up for proper
operation will display a critical message if the relay has not been
programmed.
Alphanumeric Data
Key
Description
The parameters that require alphanumeric data are
the codes that display Product Messages, Prompt
Messages, or Permissive Messages on the displays
of AccuLoad III, or provide information to be printed
out on the Bill of Lading Emulation. When adding or
changing information in these alphanumeric program
codes, the keys listed below perform the following
functions.
ENTER
Moves the character from the character
set to the ID line. Also enters the data
into the instrument's memory after END
has been selected from the character set
SET
Moves the cursor six positions to the
right
Moves the cursor one position to the right
each time it is pressed
Moves the cursor one position to the left
each time it is pressed
and
Selects the next block of characters. An
example of this is changing from
uppercase letters to lowercase letters.
The blocks of characters available in
AccuLoad III are as follows:
ABCDEFGHIJKLMNOPQRSTUV
WXYZ#*
abcdefghijklmnopqrstuvwxyz&
@
0 1 2 3 4 5 6 7 8 9 < > ( ) ? ! . ,' - " / + = _ END
Example:
1. Choose the Recipe Directory submenu from the
Program Mode menu by placing the cursor
beside the desired option and pressing ENTER.
The following display will appear.
>
RecipeDirectory
EnterRecipe#
SelectRecipe
Section II Operations
2. Position the cursor beside "Select Recipe" and
press ENTER. The following display will appear.
>
RecipeDirectory
Recipe1Recipe1
Recipe2Recipe2
Recipe3Recipe3
and right arrows, move the cursor to the
character required.
>
ABCDEFGHIJKLMNOPQRSTUVWXYZ#*
abcdefghijklmnopqrstuvwxyz&@
0123456789<>()?!.,'"/+=_END
^
02RecipeName
3. Position the cursor beside "Recipe 1 Recipe 1"
and press ENTER. The following display will
appear.
Recipe1
ProgramParameters
ReadOnlyParameters
>
4. Position
the
cursor
beside
"Program
Parameters" and press ENTER. The following
display will appear.
>
Recipe1
01RecipeUsed
02RecipeName
03HMClass
LoadArm1
Recipe1
Product1
more
5. Position the cursor beside "Recipe Name" and
press ENTER. The following display will appear.
>
ABCDEFGHIJKLMNOPQRSTUVWXYZ#*
abcdefghijklmnopqrstuvwxyz&@
0123456789<>()?!.,'"/+=_END
02RecipeName
Recipe1
6. To change or add information, move the arrow to
the required set of characters using the up and
down arrows on the keypad. Then, using the left
MN06118L Issue/Rev. 0.5 (4/02)
29
C_
7. Repeat Step 6 until the desired ID is displayed,
then press ENTER.
>
ABCDEFGHIJKLMNOPQRSTUVWXYZ#*
abcdefghijklmnopqrstuvwxyz&@
0123456789<>()?!.,'"/+=_END
^
02RecipeName
002Arm1Config
Sequential
Straight
> Sequential
Ratio
CustomBlend
8. The display will revert to the Recipe 1 submenu,
and the new parameter for recipe 1 will appear.
>
1. With the cursor beside "002 Arm1 Config," press
ENTER. The following display will appear.
Recipe1
01RecipeUsed
02RecipeName
03HMClass
PressPRINTforhelp
2. Press PRINT to display the following help
message.
Selecttheconfigurationfor
thisloadarm:Straight
Product,Sequentialblenderor
Ratioblender.
CustomBlend
more
Viewing the Help Messages
The AccuLoad III features unique Help Messages
that allow the operator to have at his fingertips the
ability to review what is required or what the options
are for an individual program code. Simply press the
"PRINT" key while in the Program Mode if the
message "Press PRINT for help" is displayed on the
bottom of the screen. Where there is room on the
display, some parameters will display the Help
message without requiring the PRINT key to be
pressed.
Example: To view the help message associated with
Load Arm Configuration parameter 002, choose "000
Load Arm Configuration" from the Configuration
Directories menu. The following display will appear.
>
000LoadArmConfiguration
001NumberofLoadArms
002Arm1Config
Sequential
003Arm1NumProds
More
Exiting to the Main Menu
When all changes are complete, press "CLEAR" to
back out through the menu system and return to the
main screen. If programming errors exist, the
operator will be prompted to correct them prior to
exiting Program Mode.
>
ProgrammingErrorsExist
ViewErrorList
ExitwithErrors
ExitwithoutChanges
Select "View Error List" for a complete listing of all
programming errors. A screen similar to that shown
below will appear.
>
ProgrammingErrors
A1M1301KFactor
A2M1301KFactor
A1M1201ValveType
morePRINT=errormsg
Section II Operations
For additional information regarding a specific error,
use the up and down arrow keys to position the
cursor beside the error and press PRINT on the
keypad. A screen similar to that shown below will
appear.
A1M1301KFactor
Entrymustnotbezero.
MN06118L Issue/Rev. 0.5 (4/02)
31
Press CLEAR twice to return to the "Programming
Errors Exist" display. Select "Exit with Errors," then
press ENTER, to return to the Main Menu without
correcting existing errors. Select "Exit without
Changes," then press ENTER, to return to the Main
Menu without saving any changes.
Note: The menu option "Exit with Errors" is available only with
Revision 2 and above firmware.
Security
The AccuLoad III provides the ability to set up five
levels of security. Each level may have an access
code of up to four digits. Each parameter in the
database may be assigned a security level and may
not be changed unless that security restriction has
been met. This allows access to sensitive
parameters, such as those that affect volume
accuracy, to be restricted to a higher level of security
than other parameters that can be protected at a
lower level. The highest level of security is level 5;
the lowest is level 1. If one of the two security
switches is set for low level security, that switch must
also be active to access a higher level of security.
Security levels must be programmed contiguously,
beginning with level one. For example, if only two
levels of security are desired, they must be levels
one and two.
Note: The operator must have the highest security level
programmed in the unit in order to change any data on the
security menu.
The security menu can be found by selecting System
Directories from the Program Mode Menu, then
choosing General Purpose Directory, then Security.
DateandTime
Units&Identifiers
Timeouts
Display&Control
Security
>
Pressing ENTER with the arrow in front of "Security"
will display the Security menu.
Security
>
151Lev1AccessCode
152Lev2AccessCode
153Lev3AccessCode
More
0
0
0
Additional items on the menu include the following:
154 Lev 4 Access Code
155 Lev 5 Access Code
Set Parameter Security
Section III Security
From this menu, access codes can be programmed
for each level of security desired for the application.
If the operator wants all the parameters set to the
same security level, the "Set Parameter Security"
option can be used. Note that before a security level
higher than Level 1 can be assigned to a parameter,
an access code must be assigned to that security
level; otherwise, it will not appear on the menu of
level choices.
Passcode
Select the level of security desired on the Security
menu by moving the arrow to the selection and
pressing ENTER. This will display the screen from
which passcodes can be entered. The entry can be
from one to four digits with a zero entry removing the
access code requirement.
151Lev1AccessCode>1234
EnterAccesscodeforthis
securitylevel
After the passcode has been entered, press ENTER
to save the passcode in memory and return the
display to the Security menu. If more than one
security level is defined, passcode entry will
determine which of the parameters are eligible for
modification. The highest level of security
programmed is required when changing the
parameters on the Security menu.
Set Parameter Security
When "Set Parameter Security" is selected on the
Security menu, all the parameters in the unit can be
set to Security Level 1. Pressing ENTER will display
the following screen:
SelectSecurityLevel
>
Level1
Level2
Level3
MN06118L Issue/Rev. 0.5 (4/02)
33
more
Moving the arrow to the desired level and pressing
the ENTER key will display the following screen:
Allparameterswillbe
assignedthissecuritylevel.
Areyousure?
> No
Yes
When "Yes" is selected and the ENTER key is
pressed, the AccuLoad will automatically set the
security for all parameters, which will be displayed
as follows on the Security menu:
Security
>
154Lev4AccessCode
155Lev5AccessCode
SetParameterSecurity
More
4752
1954
3
In this example, all parameters in the AccuLoad are
set to Level 3 security. If a few of the parameters
need to be set to a higher security, do the following:
1. Select the parameter that requires a higher level
security.
137PowerfailAlarm
>Enable
Disable
PressPRINTforhelp
2. Press the "STOP" key.
137PowerfailAlarm
>
SelectSecurityLevel
Level3
Level4
Level5
Enable
This display indicates that the security level is
currently set to Level 3.
Section III Security
3. To change to Level 4 security, move the cursor
to Level 4.
Pressanykey
137PowerfailAlarm
To change the parameter, Program Mode must be
exited and the Level 4 passcode entered.
SelectSecurityLevel
Level3
> Level4
Level5
4. Press "ENTER." The new security level has
been changed to Level 4 and the data has been
stored in memory. The screen then returns to the
parameter as seen in Step 1.
In order to change Parameter 137, the operator now
must enter Program Mode with his Level 4
passcode. If an associated switch input has been
assigned to Level 4, it will also have to be closed. If
these steps are not taken, the following screen will
be displayed:
AccessDenied
Thisparametercannotbemodified
atthecurrentsecurityaccesslevel.
MN06118L Issue/Rev. 0.5 (4/02)
35
Resetting Passcode
To reset the passcodes that are programmed in the
AccuLoad, Jumper J22 on the KDC board must be in
place. Moving the jumper from its parked position to
both pins (see the Installation Manual) and power
cycling the AccuLoad will temporarily reset all
passcodes to 0. This allows the operator to enter
Program Mode and set the passcode(s) as desired.
If the unit is power-failed and the jumper removed
before a Program Mode edit session has occurred,
the passcodes will revert to their former values.
Caution: Do not leave the jumper in position. If left
on the pins, the passcodes will be reset every time
the unit goes through a power cycle.
When the passcodes have been re-established,
move the jumper back to its parked position.
Dynamic Displays
This section describes informational displays that
can be viewed while in the Run or Ready Mode.
These displays are "dynamic" in the sense that the
displayed values reflect current actual conditions and
continuously update while being viewed. The
Dynamic Display menu is selected by pressing
ENTER while in the Run or Ready Mode. The
Dynamic Display menu will appear, allowing the
operator to select from the following menu:
forward through the displays
Used to navigate forward through
the menu to get into the displays.
When in the dynamic displays, the
down arrow also moves forward
through the displays.
CLEAR
Used to exit the dynamic display
ENTER
Used to enter the Dynamic Display
menu and to enter the dynamic
displays from the menu
DynamicDisplays
>
Note: Keys not listed are not used in the dynamic displays.
System
Product
Recipe
Entry to Dynamic Displays
more
Additional Dynamic Displays, available but not
appearing on the initial screen, are Batch,
Transaction, Blend, and Diagnostics.
The following steps should be used to enter the
dynamic displays. While in the Run or Ready mode
of the AccuLoad III, the following steps should be
followed.
1.
The dynamic display screen will remain displayed for
the time period that was programmed in Code 121.
This code may be accessed by choosing Systems
Directories, then General Purpose Directory, then
Timeouts. If a 0 is entered in Code 121, the display
will remain until the CLEAR button is pressed. The
AccuLoad III will continue to function normally while
the display is on.
Keypad Functions
DynamicDisplays
>
Not Used
Used to navigate backwards
through the menu to get into the
displays. When in the dynamic
displays, the up arrow also moves
backward through the displays.
Once in the dynamic displays, this
works like the up arrow to move
backwards through the displays
Once in the dynamic displays, this
works like the down arrow to move
System
Product
Recipe
more
2.
The keys on the keypad perform the following
functions when accessing the dynamic displays:
09
Press "ENTER." This will display the Dynamic
Displays menu.
Move the arrow to the displays to be viewed and
press "ENTER."
Flow(Arm1)
Flow(Arm1)
Flow(Arm2)
Flow(Arm2)
0.0Gal/Min
0.0Gal/Hr
0.0Gal/Min
0.0Gal/Hr
MoreSystem
3.
To move through the displays, press either the
or key to move backwards through the
displays. Press either the or key to move
forward through the displays.
Inj1Prg0
Cal0.0Gal
Section IV Dynamic Displays
Inj2Prg0
Inj3Prg0
Inj4Prg0
Cal0.0Gal
Cal0.0Gal
Cal0.0Gal
moreSystem
4.
Continue using the arrow keys to display the
dynamic information needed.
5.
To end the review of dynamic displays, either let
the timer expire or press CLEAR to return to the
run mode screen.
MN06118L Issue/Rev. 0.5 (4/02)
37
Dynamic Display System
System Dynamic Displays
Dynamic displays are grouped into six categories:
system, product, recipe, batch, transaction, and
diagnostics. Displays may be accessed by selecting
Dynamic Displays from the Main Menu, then using
the up or down arrow keys to select the desired
category.
System dynamic displays show all data that is
common to the entire AccuLoad. A listing of system
dynamic displays, as well as the format in which the
information appears, is set forth in the table below.
Note: On Revision 4 and above firmware, all flow rates reduced
by back-pressure control are indicated by an asterisk (*) on the
AccuLoad display screen.
Note: On Revision 10 and above firmware, mass flow rate is
reported in units as selected in System Parameter 302. Time is
reported in units as selected in System Parameter 111.
Section IV Dynamic Displays
Description
Display Format
Current Flow Rate in Units/Min for Arm 1
Flow (Arm 1)
XXXXX.X Gal/Min
Current Flow Rate in Units/Hour for Arm 1
Flow (Arm 1)
XXXXXXX.X Gal/Hr
Current Flow Rate in Units/Min for Arm 2
Flow (Arm 2)
XXXXX.X Gal/Min
Current Flow Rate in Units/Hour for Arm 2
Flow (Arm 2)
XXXXXXX.X Gal/Hr
Current Recipe for Arm 1
Recipe (Arm 1)
XXXXXXXXX
Current Recipe for Arm 2
Recipe (Arm 2)
XXXXXXXXX
Time of Last Power Fail
PF 12:01:06 AM 12-01-91
Injector 1 Current Pulse Rate
Inj 1 Prg XXX
Cal XXXX.XX
Injector 2 Current Pulse Rate
Inj 2 Prg XXX
Cal XXXX.XX
Injector 3 Current Pulse Rate
Inj 3 Prg XXX
Cal XXXX.XX
Injector 4 Current Pulse Rate
Inj 4 Prg XXX
Cal XXXX.XX
Injector 5 Current Pulse Rate
Inj 5 Prg XXX
Cal XXXX.XX
Injector 6 Current Pulse Rate
Inj 6 Prg XXX
Cal XXXX.XX
Injector 7 Current Pulse Rate
Inj 7 Prg XXX
Cal XXXX.XX
Injector 8 Current Pulse Rate
Inj 8 Prg XXX
Cal XXXX.XX
Injector 9 Current Pulse Rate
Inj 9 Prg XXX
Cal XXXX.XX
Injector 10 Current Pulse Rate
Inj 10 Prg XXX
Cal XXXX.XX
Injector 11 Current Pulse Rate
Inj 11 Prg XXX
Cal XXXX.XX
Injector 12 Current Pulse Rate
Inj 12 Prg XXX
Cal XXXX.XX
Current Mass Flow Rate
Flow (Arm 1)
XXXXXX uuuu/uu
Current Mass Flow Rate
Flow (Arm 2)
XXXXXX uuuu/uu
Product Dynamic Displays
Product dynamic displays show all data associated
with a specific product. Selecting "Product" from the
Dynamic Displays menu results in a screen similar to
that shown to the right. (Up to four products are
possible for each arm. If a product position is not
configured, it will not appear on the submenu.)
Position the cursor beside the appropriate option,
then press ENTER.
MN06118L Issue/Rev. 0.5 (4/02)
39
>
DynamicDisplays
Arm1PrdName
Arm2PrdName
A listing of product dynamic displays, as well as the
format in which the information appears, is set forth
in the table below.
Note: On Revision 10 and above firmware, mass flow rate is
reported in units as selected in System Parameter 302. Time is
reported in units as selected in System Parameter 111.
Description
Display Format
Current Flow Rate in Units/Min
Flow
XXXXX.X Gal/Min
Current Flow Rate in Units/Hour
Flow
XXXXXXX.X Gal/Hr
Current and Average Temperature
Temp Cur Avg
SXXXX.XF
SXXXX.XF
Current and Average Density
Dens Cur Avg
XXXX.X
XXXX.X Lb/F3
Average API
Avg API
Average Reference Density
Avg Ref Dens
XXXX.X Lb/F3
Average Relative Density
Avg Rel Dens
X.XXXX
Batch Average Pressure
Batch Avg Press
XXXX.X PSI
Batch Average Vapor Pressure
Avg Vapor Press
XXXX.X PSI
Current and Average Meter Factor
Mfac Cur Avg
Batch Average CTL
Batch Avg CTL
X.XXXX
Batch Average CPL
Batch Avg CPL
X.XXXX
Current Valve Requested Position
Valve Requested Closed
Current Percentage of Batch
Current Percentage
XXX%
Desired Percentage of Batch
Desired Percentage
XXX%
Indicated (Raw) Volume
IV Batch
Gross Batch Volume
GV Batch
Gross at Standard Temperature Batch
GST Batch
XXXXXXX.XX Gal
Gross at Standard Temperature and Pressure Batch
GSV Batch
XXXXXXX.XX Gal
Mass Batch
Mass Batch
XXXXXXX.XX Lbs
Raw Transaction Volume
IV Trans
Gross Transaction Volume
GV Trans
Gross at Standard Temperature
GST Trans
XXXXXXX.XX Gal
Gross at Standard Temperature and Pressure
GSV Trans
XXXXXXX.XX Gal
Mass Transaction Amount
Mass Trans
Valve Status (only available on Revision 3 and above firmware)
Valve Requested Close
Current Mass Flow Rate
Flow (Arm 1)
XXXXXX uuuu/uu
Current Mass Flow Rate
Flow (Arm 2)
XXXXXX uuuu/uu
SXXX.X
X.XXXXX
X.XXXXX
XXXXXXX.XX Gal
XXXXXXX.XX Gal
XXXXXXX.XX Gal
XXXXXXX.XX Gal
XXXXXXX.XX Lbs
Recipe Dynamic Displays
Recipe dynamic displays show all data associated
with a programmed recipe. Selecting "Recipe" from
the Dynamic Displays menu results in a screen
similar to that shown to the right. If the operator fails
to enter a recipe number, a listing of all currently
configured recipes will appear. Position the cursor
beside the appropriate option, then press ENTER.
>
DynamicDisplays
EnterRecipe#
SelectRecipe
A listing of recipe dynamic displays, as well as the
format in which the information appears, is set forth
in the table below.
Description
Display Format
Recipe Name and Number
Recipe XX XXXXXXXXX
IV Volume for the Transaction
IV Recipe
XXXXXXX.XX Gal
GV Volume for the Transaction
GV Recipe
XXXXXXX.XX Gal
GST Volume for the Transaction
GST Recipe
XXXXXXX.XX Gal
GSV Volume for the Transaction
GSV Recipe
XXXXXXX.XX Gal
Mass Volume for the Transaction
Mass Recipe
XXXXXXXXX.XX Lbs
41
MN06118L Issue/Rev. 0.5 (4/02)
Batch Dynamic Displays
Batch dynamic displays show all data associated
with a specific batch. Selecting "Batch" from the
Dynamic Displays menu, then indicating a load arm,
results in a screen similar to that shown to the right.
Type a batch number to indicate a specific past
batch, or press ENTER for current or last batch data.
DynamicDisplays
SelectBatch
>
PressENTERforcurrentor
lastbatch.
A listing of batch dynamic displays, as well as the
format in which the information appears, is set forth
in the table below.
Description
Display Format
Recipe Name and Number
Recipe XX XXXXXXXXX
Raw Batch Volume
IV Batch
Gross Batch Volume
GV Batch
Gross at Standard Temperature
GST Batch
XXXXXXX.XX Gal
Gross at Standard Temperature and Pressure
GSV Batch
XXXXXXX.XX Gal
Mass Batch Amount
Mass Batch
XXXXXXX.XX Lbs
Batch Average Temp
Batch Avg Temp
Batch Average Density
Batch Avg Dens
Batch Average Pressure
Batch Avg Press XXXX.X Psi
Batch Average Meter Factor
Batch Avg Mtr Factor
Batch Average CTL
Batch Avg CTL
X.XXXX
Batch Average CPL
Batch Avg CPL
X.XXXX
Additive 1 Batch Total
Add 1 Batch
XXXXXXXX.XXX Gal
Additive 2 Batch Total
Add 2 Batch
XXXXXXXX.XXX Gal
Additive 3 Batch Total
Add 3 Batch
XXXXXXXX.XXX Gal
Additive 4 Batch Total
Add 4 Batch
XXXXXXXX.XXX Gal
Additive 5 Batch Total
Add 5 Batch
XXXXXXXX.XXX Gal
Additive 6 Batch Total
Add 6 Batch
XXXXXXXX.XXX Gal
Additive 7 Batch Total
Add 7 Batch
XXXXXXXX.XXX Gal
Additive 8 Batch Total
Add 8 Batch
XXXXXXXX.XXX Gal
Additive 9 Batch Total
Add 9 Batch
XXXXXXXX.XXX Gal
Additive 10 Batch Total
Add 10 Batch XXXXXXXX.XXX Gal
XXXXXXX.XX Gal
XXXXXXX.XX Gal
SXXX.XF
XXXX.X Lb/F3
X.XXXXX
Additive 11 Batch Total
Add 11 Batch XXXXXXXX.XXX Gal
Additive 12 Batch Total
Add 12 Batch XXXXXXXX.XXX Gal
MN06118L Issue/Rev. 0.5 (4/02)
43
Transaction Dynamic Displays
Transaction dynamic displays show all data
associated with a specific transaction. Selecting
"Transaction" from the Dynamic Displays menu
results in a screen similar to that shown to the right.
Position the cursor beside the appropriate load arm,
then press ENTER.
DynamicDisplays
>
Arm1
Arm2
A listing of transaction dynamic displays, as well as
the format in which the information appears, is set
forth in the table below.
45
MN06118L Issue/Rev. 0.5 (4/02)
Description
Display Format
Indicated (Raw) Transaction Volume
IV Trans
XXXXXXX.XX Gal
Gross Transaction Volume
GV Trans
Gross at Standard Temperature Volume
GST Trans
XXXXXXX.XX Gal
Gross at Standard Temperature and Pressure
GSV Trans
XXXXXXX.XX Gal
Mass Transaction Volume
Mass Trans
XXXXXXX.XX Lbs
Transaction Average Temperature
Trans Avg Temp
Transaction Average Density
Trans Avg Density XXX.X Lb/F3
Transaction Average Pressure
Trans Avg Press XXXX.X Psi
Transaction Average Meter Factor
Trans Avg Mtr Factor
X.XXXXX
Transaction Average CTL
Trans Avg CTL
X.XXXX
Transaction Average CPL
Trans Avg CPL
X.XXXX
Injector 1 Transaction Total
Add 1 Trans
XXXXX.XXX Gal
Injector 2 Transaction Total
Add 2 Trans
XXXXX.XXX Gal
Injector 3 Transaction Total
Add 3 Trans
XXXXX.XXX Gal
Injector 4 Transaction Total
Add 4 Trans
XXXXX.XXX Gal
Injector 5 Transaction Total
Add 5 Trans
XXXXX.XXX Gal
Injector 6 Transaction Total
Add 6 Trans
XXXXX.XXX Gal
Injector 7 Transaction Total
Add 7 Trans
XXXXX.XXX Gal
Injector 8 Transaction Total
Add 8 Trans
XXXXX.XXX Gal
Injector 9 Transaction Total
Add 9 Trans
XXXXX.XXX Gal
Injector 10 Transaction Total
Add 10 Trans
XXXXX.XXX Gal
Injector 11 Transaction Total
Add 11 Trans
XXXXX.XXX Gal
Injector 12 Transaction Total
Add 12 Trans
XXXXX.XXX Gal
XXXXXXX.XX Gal
SXXX.XF
Blend Dynamic Displays
Blend dynamic displays are specifically designed for
blending applications, and are not selectable unless
the AccuLoad is currently configured for blending.
Selecting "Blend" from the Dynamic Displays menu
results in a screen similar to that shown below.
Position the cursor beside the appropriate load arm,
then press ENTER.
DynamicDisplays
>
Arm1
Arm2
MN06118L Issue/Rev. 0.5 (4/02)
47
The blend information will be displayed in a manner
similar to that shown on the screen below.
Recipe#1
Product1
Product2
Product3
Product4
CBR%
XXX.X
XXX.X
XXX.X
XXX.X
Flow
XXXXX
XXXXX
XXXXX
XXXXX
Volume
XXXXXX
XXXXXX
XXXXXX
XXXXXX
Diagnostics Dynamic Displays
Diagnostic dynamic displays allow the operator to
review current configurations, identify causes of
system errors, and analyze data collected by the
AccuLoad III. Selecting "Diagnostics" from the
Dynamic Displays menu, then choosing a specific
diagnostic, frequently but not always results in the
screen shown directly below. Position the cursor
beside the appropriate load arm, then press ENTER
to reach the desired diagnostic screen.
SelectLoadArm
LoadArm#1
LoadArm#2
>
Note: The diagnostics available through the Dynamic Displays
menu are run-time diagnostics only. Program mode diagnostics
are accessed from the Program Mode Main Menu.
The Diagnostics menu available through
Dynamic Display consists of the following:
the
Active Alarms
Alarm History
Non-Reset Volumes
Event Log
Transaction Log
Audit Trail
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs
Pulse Inputs
View Turbine Meter Data
Communications Monitor
CIVACON Overfill Monitor
Boolean Algebraic
Software Version
Factory Diagnostics
Active Alarms
The Diagnostics menu provides the selection "Active
Alarms" where all active alarms can be viewed with
the arrow in front of "Active Alarms." Pressing
ENTER will display one of the following displays. If
no alarms are active, the following screen will be
displayed.
Section V Diagnostics
NoActiveAlarms
Pressing the CLEAR key will revert to the Diagnostic
menu.
PressAnyKey
If there are active alarms, they will be displayed as
follows:
ActiveAlarms
>
M1DA:MtrProgramError
The active alarms can be cleared from this display
by moving the arrow to the alarm and pressing
"ENTER." The AccuLoad will then ask for the
passcode. When the passcode is entered, the alarm
will clear.
Pressing the CLEAR key will display the Diagnostic
menu.
Alarm History
The Diagnostics menu provides the selection "Alarm
History" where the most recent alarms can be
viewed. With the arrow in front of "Alarm History,"
pressing ENTER will display the historical alarms as
shown on the following display. The alarms will be
listed in order of occurrence.
AlarmHistory
1.PA:PowerfailAlarm
2.DA:MtrProgramErrorMI
3.PA:PowerfailAlarm
more
This is an alarm history for the transaction. For a
more complete history of alarms, please access the
Event Log.
Pressing the up and down arrow keys will allow the
operator to page through the Alarm History displays.
If "More" is not displayed, then there is only one
screen of alarms in the alarm history.
49
MN06118L Issue/Rev. 0.5 (4/02)
Non-Reset Volumes
The Diagnostics menu provides the selection "NonReset Volumes" where the meter and additive
injector volumes can be viewed. With the arrow in
front of "Non-Reset Volumes," pressing ENTER will
display a menu to allow the operator to view either
the meter or the additive volumes. Choosing either
the meter or additive injectors by moving the arrow
and pressing ENTER will display the non-resettable
volumes.
NonResetVolumes
>
Meter
AdditiveInjectors
Recipes
Meter volumes are displayed as follows:
Arm1NonResetVolumes
IV
GV
GST
20684Gal
20304Gal
20309Gal
More
NonResetVolumes
GSV
Mass
20309Gal
18241Lbs
More
Additive injector values are displayed as follows:
Only additives one through three are displayed in
this example. Using the arrow keys on the keypad
will allow the operator to move through all twelve of
the additives.
NonResetVolumes
INJ1
INJ2
INJ3
0.000Gal
0.000Gal
0.000Gal
More
Pressing the CLEAR key will return the display to the
Non-Reset Volumes screen.
Choosing "Recipes" from the "Non-Reset Volumes"
menu results in the following screen.
Section V Diagnostics
alarms, transaction start and end, and program
mode parameter changes.
RecipeDirectory
>
EnterRecipe#
SelectRecipe
EventLog#66
Selecting "Enter Recipe #" results in a prompt for a
specific recipe number. Type the recipe number, then
press ENTER to review the desired recipe data.
Recipe6NonResetVolumes
IV
GV
GST
0Gal
0Gal
0Gal
More
03/12/99
AlarmOccurred
DA:MtrProgramError
8:52:20
From the display, the operator can go back through
the events using the up and down arrow keys.
Pressing the CLEAR key will display the Diagnostics
menu.
Transaction Log
The Diagnostics menu provides the selection
"Transaction Log," where the transaction date can be
viewed. With the arrow in front of "Transaction Log,"
pressing ENTER will display the following.
Recipe6NonResetVolumes
TranactionLog
GSV
Mass
0Gal
0Lbs
Enter#oftransactionsback
Enter0formostrecent
More
>0
Choosing "Select Recipe" from the Recipe Directory
submenu results in the following display.
RecipeDirectory
>
Recipe1Recipe1
Recipe2Recipe2
Recipe3Recipe3
Position the cursor beside the desired recipe, then
press ENTER to obtain the same information
displayed in response to "Enter Recipe #," above.
Event Log
The View Only Diagnostics menu provides the
selection "Event Log" where past events can be
viewed. With the arrow in front of "Event Log,"
pressing ENTER will display the last event that
occurred in the AccuLoad. The "Event Log" includes
51
Entering the number of batches back, the AccuLoad
will display the following screen.
>
TransactionTotals
Batch#1
Batch#2
Batch#3
From this display, the operator can select either
"Transaction Totals" or batch data. If more than one
batch is included in a transaction, each will be listed
separately. The following information is displayed for
Transaction Totals.
Transaction#16
MN06118L Issue/Rev. 0.5 (4/02)
09/03/99
IVTrans
GVTrans
9:58:59
1980.52GAL
2110.18GAL
Transaction#16
NumberofBatches
TransAvgMtrFactor
TransAvgTemp
More
3
1.06547
11.5C
More
Transaction#16
GSTTrans
GSVTrans
MassTrans
More
2115.43GAL
2115.43GAL
2048.45LBS
Transaction#16
TransAvgDens
TransAvgPress
TransAvgCTL
961.3Kg/m3
4.2Kg/cm2
1.0025
More
Transaction#16
TransAvgCPL
Add1Trans
Add3Trans
1.0000
150.000cc
110.000cc
More
Note: Additive totals will be displayed only for those injectors used
in the transaction.
Transaction#16
AlarmOccurred
AlarmOccurred
1:VF01
1:PR01
Section V Diagnostics
When "Batch" is selected from the above menu, the
following data will be displayed.
Transaction#16Batch#1
Recipe#
IVBatch
GVBatch
2
1980.52GAL
2110.18GAL
More
Transaction#16Batch#1
GSTBatch
GSVBatch
MassBatch
2115.43GAL
2115.43GAL
2048.45LBS
More
53
MN06118L Issue/Rev. 0.5 (4/02)
Transaction#16Batch#1
BatchAvgMtrFactor
BatchAvgTemp
BatchAvgDens
1.06547
11.5C
961.3Kg/m3
02/12/99
SY:720
07/None
38/None
11:36:13
In the example on the screen above, "Audit Trail
Entry #12," "SY: 720" is system parameter 720; "0
7/None" is the old value, and "3 8/None" is the new
value.
More
Transaction#16Batch#1
BatchAvgPress
BatchAvgCTL
BatchAvgCPL
4.2Kg/cm2
1.0025
1.0000
More
Transaction#16Batch#1
Add1Batch
Add2Batch
AlarmOccurred
150.000cc
110.000cc
1:VF
More
Audit Trail
The View Only Diagnostics menu provides the
selection "Audit Trail" where audit trail data is
available for viewing. With the arrow in front of "Audit
Trail," pressing ENTER will display the last audit trail
entry that occurred in the AccuLoad.
AuditTrailEntry#13
02/12/99
11:43:32
ProgramModeExit
abortchangesthrukeypad
The audit trail provides the date, time, and
description of what event occurred. Pressing the up
and down arrows on the keypad will allow the
operator to step through the audit trail.
AuditTrailEntry#12
AuditTrailEntry#224
09/03/99
11:24:45
ProgramModeExit
abortchangesthrukeypad
Pressing the CLEAR key will display the Diagnostic
menu.
Digital Inputs
The Diagnostics menu provides for the selection of
"Digital Inputs" where the current status of the digital
inputs can be viewed. With the arrow in front of
"Digital Input," pressing ENTER will display the first
three digital inputs, the programmed function, and
their status.
DigitalInputs
#1Permissive1
#2NA
#3Permissive2
ON
OFF
OFF
More
Viewing the above displays provides information on
digital input #1. It is used as a permissive and the
current status is ON. Likewise, the functions and
status of digital inputs #2 and #3 are also available.
By using the up and down arrows, digital inputs 4
through 11 can also be viewed.
Pressing the CLEAR key will display the Diagnostics
menu.
Section V Diagnostics
Digital Outputs
The Diagnostics menu provides the selection "Digital
Outputs" where the function and status of the digital
outputs can be viewed. With the arrow key in front of
"Digital Outputs," pressing ENTER will display the
first three digital outputs and their status.
DigitalOutputs
#1AlarmRelay1
#2N/A
#3Pump
By using the up and down arrows on the keypad,
digital outputs #4 through #14 can be viewed.
Pressing the CLEAR key will display the Diagnostics
menu.
Analog Inputs
The Diagnostics menu provides the selection
"Analog Inputs," where the function and status of the
analog inputs can be viewed. With the arrow in front
of "Analog Inputs," pressing ENTER will display the
first two analog inputs, their current reading in
engineering units, current, or voltage, and raw
analog input value.
15.0C
36863
6.2Kg/cm2
42388
AnalogInputTestmore
By using the up and down arrow keys on the keypad,
analog inputs 3 through 6 can be viewed.
Pressing the CLEAR key will display the Diagnostics
menu.
55
The Diagnostics menu provides the selection
"Analog Outputs," where the function and status of
the analog outputs can be viewed. With the arrow in
front of "Analog Outputs," pressing ENTER will
display the first two analog outputs, their current
reading in engineering units, current, or voltage, and
raw analog output value.
OFF
OFF
OFF
More
#1:M1TempIn
14.062mA
#2:M1Pressure
16.170mA
Analog Outputs
#1:Output1
14.062mA
#2:Output2
16.170mA
XXXX
36863
XXXX
42388
AnalogOutputTestmore
By using the up and down arrow keys on the keypad,
analog outputs 3 through 6 can be viewed.
Pressing the CLEAR key will display the Diagnostics
menu.
Pulse Inputs
The Diagnostics menu provides the selection "Pulse
Inputs" where the leakage pulses and the batch
pulses are displayed. The leakage pulses are the
pulses received when the valve is not told to open
and no flow is authorized. Batch pulses are zero
since no batch is in progress. With the arrow in front
of "Pulse Inputs," pressing ENTER will display the
pulse inputs. If no transaction is in progress, the
following display will appear.
PulseInputs
MtrLeak
Batch0Err
In4
DensFreq
0
0
NA
0.000Hz
PulseInputsmore
MN06118L Issue/Rev. 0.5 (4/02)
Using the up and down arrow keys on the keypad,
pulse inputs #5 and #6 can be viewed.
Pressing the CLEAR key will display the Diagnostics
menu.
The following screen will appear if a batch is in
progress. The screen shows frequency of meter
pulse input and number of pulses in the batch.
PulseInputs
Mtr1059.2HzBatch
Err
In4
9536
0
NA
The following screen will appear if a transaction is
between batches. The screen shows pulses over the
whole transaction, as well as pulses from the last
batch and the dual pulse errors.
PulseInputs
MtrTran
Batch30074Err
In4
40124
0
NA
Section V Diagnostics
View Turbine Meter Data
The Diagnostics menu provides the selection "View
Turbine Meter Data" to display turbine meter
configuration data. With the arrow in front of "View
Turbine Meter Data," pressing ENTER will display
the following:
This display allows the operator to choose the
communication port to be viewed. Pressing ENTER
when the arrow is in front of the desired
communications port will display the data that is
being received by the AccuLoad and the response of
the AccuLoad.
TurbineMeterDiagnostics
>
LoadArm#1
LoadArm#2
SelectaTurbineMeter
Position the cursor in front of the desired load arm,
then press ENTER to obtain the following screen.
TurbineMeterDiagnostics
>
Signature
CurTMDValue
#Blades:3
0.000000e+000
0.000000e+00
Tol:MostLax
Mtr#1DisabledMeterOK
Press CLEAR twice to return to the Dynamic
Displays Diagnostics Menu.
Communications Monitor
The Diagnostics menu provides the selection
"Comm Monitor" to review messages being sent and
received across the communications lines. With the
arrow in front of "Comm Monitor," pressing ENTER
will display the following:
CommMonitorLiveView
>
57
comm1
comm2
comm3
comm4
MN06118L Issue/Rev. 0.5 (4/02)
Connectplugtosocket
CommMonitorLiveView
0x000x000x000x000x00
Rx01PC_00_001_0.0
Tx
.01NO01
Enter=Freeze,print=errors
Boolean Algebraic
This display indicates that AccuLoad address 01
received a PC command from the host and
responded with a "no response," indicating that it is
in Program mode. To freeze a command or response
for further viewing, press "ENTER."
The Diagnostics menu provides the selection
"Boolean Algebraic" to view Boolean/Algebraic
registers and their results. General-purpose timers
can also be viewed from this screen. With the arrow
in front of "Boolean Algebraic," pressing ENTER will
display the Boolean/Algebraic Processing menu.
CommMonitorFreezeView
RX01PC_00_001_0.0
TX
.01N001
Enter=ToggleASCII/hex<<>>
On this display, the operator can toggle the message
between the ASCII and hex characters. The decimal
point key allows toggling between page scrolling ("<<
>>") and character scrolling ("< >"). To return to the
previous display, press "CLEAR."
Pressing the "PRINT" key in the live view will display
the following screen.
Boolean/Algebraic
Processing
>
UserBooleanRegisters
UserAlgebraicRegisters
EquationLineStatus
GeneralPurposeTimers
User Boolean Registers
The User Boolean Registers display indicates the
registers and their current True or False value, where
0 is False and 1 is True.
UserBooleanRegisters
CommMonitorErrorCounts
Overruns:00000
Parity:00000
Framing:00000
From this display, the overrun errors, parity errors,
and framing errors can be viewed. Pressing CLEAR
will return to the Live View display.
When completed, press CLEAR until the Diagnostics
menu is displayed.
CIVACON Overfill Monitor
Internal Use only.
CIVACONOverfillMonitor
#1
#2
#3
1
0
0
#4
#5
#6
0
0
1
#7
#8
#9
0
0
0
More
Using the up and down arrows, the 100 User
Boolean Registers can be viewed. Pressing CLEAR
will return to the Boolean/Algebraic Processing
menu.
User Algebraic Registers
The User Algebraic Registers display the current
values of the variables in the register. This display is
read-only, but the registers can be modified via
Boolean/Algebraic equations or via communications.
These registers are used to check the values of the
Section V Diagnostics
variables that have been set up and/or downloaded
from the AccuMate.
UserAlgebraicRegisters
#1
#2
#3
Using the up and down arrow keys, the 100 User
Algebraic Registers can be viewed. Pressing CLEAR
will return to the Boolean/Algebraic Processing
menu.
Equation Line Status
0.0
0.0
0.0
More
The Equation Line Status displays the current status
of the equations, where "D" indicates that the
equation is disabled, "T" is True, and "F" is False. All
equations without an "IF" statement will have a
"True" status. Those with an "IF" will indicate the
result of the "IF" expression: either "True" or "False."
EquationLineStatus
#1
#2
#3
D
D
F
#4
#5
#6
T
D
D
#7
#8
#9
D
D
D
More
Using the up and down arrow keys, view all 200
equations. Pressing CLEAR will return to the
Boolean/Algebraic Processing menu.
General Purpose Timers
The General Purpose Timers display the current
time on the timers. The timers are broken down as
follows:
TimerNumbers
Resolution
Range
14
58
912
1316
0.1second
1.0second
1.0minute
1hour
109minutes
18.2hours
45.5days
7.5years
Clear the timer by writing a zero to the database
location of the desired timer.
GeneralPurposeTimers
#1
#2
59
0
0
#4
#5
0
0
#7
#8
0
0
MN06118L Issue/Rev. 0.5 (4/02)
#3
#6
More
#9
Section V Diagnostics
Using the up and down arrow keys will display the
remaining timers. Pressing CLEAR will return to the
Boolean/Algebraic Processing menu. Pressing
CLEAR again will return the display to the Display
menu.
Software Version
The Diagnostics menu provides the selection
"Software Version," which allows the operator to
view the version of software that is running in the
AccuLoad. With the arrow in front of "Software
Version," pressing ENTER will display the software
version and the CRC of the proms.
Pressing ENTER with the arrow in front of
Diagnostics will display three items of the
Diagnostics Menu. Pressing the up and or down
arrows will step through the Diagnostics Menu. The
available diagnostics in the order that they appear on
the menu are as follows:
SoftwareVersion
Version
CRC
3
7F83B3BF
Copyright1999
FMCSmithMeterInc.
Pressing CLEAR will return to the Diagnostics menu.
Factory Diagnostics
Analog Input Test
Analog Output Test
Digital Input Test
Digital Output Test
Pulse Input Test
Pulse Output Test
Turbine Meter Diagnostics
Add-Pak Diagnostics
Communications Test
Keypad Test
Display Pixel Test
Boolean/Algebraic
Reset Totals
Erase Event Log
Erase Transaction Log
Factory Initialize
Factory Diagnostics
For factory use only.
Analog Input Test
Program Mode Diagnostics
The Program Mode Diagnostics are used to
troubleshoot or to determine the current status of the
AccuLoad. Program Mode Diagnostics is selected by
moving the cursor to "Diagnostics" on the Program
Mode menu and pressing "ENTER." This will display
the Diagnostics menu.
ProgramModeMenu
>
61
Selecting Analog Input Test and pressing ENTER
will display the status of the analog input points in
the AccuLoad.
#1
#2
M1TempIn
109.657Ohms
M1Pressure
14.023mA
76.6F
28744
0.0Psi
36753
AnalogInputTestmore
ConfigDirectories
SystemDirectories
LoadArm1Directories
LoadArm2Directories
RecipeDirectory
ExitWithoutSaving
Diagnostics
MN06118L Issue/Rev. 0.5 (4/02)
This screen is used to view the current status of the
inputs. The operator can view the function; the
current value of the input; the reading of the input in
ohms, milliamps, or volts; and the raw analog input
value.
Digital Output Test
Selecting "Digital Output Test" and pressing ENTER
will display the status of the digital output points in
the AccuLoad.
Analog Output Test
DigitalOutputTest
Selecting "Analog Output Test" and pressing ENTER
will display the status of the six analog output points
in the AccuLoad.
#1
#2
#3
NA
NA
Pump
OFF
OFF
OFF
More
AnalogOutputs
>
I/O1
I/O2
I/O3
Moving the arrow to the output that is to be tested
and pressing ENTER will change the state of the
output. An example would be moving the arrow to
output #3 Pump and pressing ENTER.
more
This screen is used to view the current status of the
outputs. The operator can view the function; the
current value of the output; the reading of the output
in ohms, milliamps, or volts; and the raw analog
output value.
DigitalOutputTest
>
#1NA
#2NA
#3Pump
More
Digital Input Test
Selecting Digital Input Test and pressing ENTER will
display the status of the digital input points in the
AccuLoad.
DigitalInputs
#1
#2
#3
Permissive1
Permissive2
Pressure
OFF
OFF
ON
ON
ON
OFF
More
This screen shows the Input number, the function
that is programmed in the unit for the input and the
status of the input point (i.e., if it is on (closed) or off
(open)). Check the inputs by changing the status of
the input, then referring to the diagnostic screen to
see if the AccuLoad recognizes the change of state.
Pulse Input Test
Selecting the Pulse Input Test and pressing ENTER
will display a screen that will show the meter inputs
that are configured, the pulses being received, and
the errors that have been received if dual pulse is
being used. Pressing ENTER will reset the pulse
counters. Input 1 is meter pulses. Input 2 is dual
pulse errors.
PulseInputs
IN1
IN2
IN3
17406
0
0
MorePressENTERtoclear
Input 3 will not show a count. It will show the
collision status when 0 = no collision and 1 =
Section V Diagnostics
collision. Pressing CLEAR will return the display to
the Diagnostic Menu.
63
MN06118L Issue/Rev. 0.5 (4/02)
Pulse Output Test
Selecting the Pulse Output Test and pressing
ENTER will display a screen that shows the two
pulse output tests and the counts that are output
from the AccuLoad to the pulse receiving device.
Two tests are output. The first output sends out
pulses at 100 Hz and the second output sends out
pulses at 200 Hz. The first output will send out 2000
pulses and the second will output 4000 pulses.
PulseOutputTest
Output#1@100HzCounts=0
Output#2@200Hzcounts=0
PressSTARTwhenready
When the test is completed the receiving device
counts should be compared to the diagnostic screen.
To start the test when the diagnostic screen is
displayed, press the START key.
PulseOutputTest
Output#1@100HzCounts=2000
Output#2@200Hzcounts=4000
TestdonePressCLEAR
Pressing CLEAR will return the display to the
Diagnostic Menu.
Turbine Meter Diagnostics
From Turbine Meter Diagnostics, the operator can
collect or generate information about a turbine meter,
enable or disable the diagnostic, and view
information about a meter. With the arrow in front of
"Turbine Meter Diagnostics," press ENTER to display
the following screen.
TurbineMeterDiagnostics
>
LoadArm#1
LoadArm#2
SelectaTurbineMeter
Section V Diagnostics
Place the cursor in front of the desired Load Arm,
then press ENTER to obtain the following screen.
strict flow tolerance may correct the problem. If the
alarm persists, the meter should be proved.
TurbineMeterDiagnostics
Note: This diagnostic applies to turbine meters only; it is not to be
used for positive displacement meters.
>
BeginLearnMode
Disable/EnableDiag
ViewData
Mtr#1DisabledMeterOK
"Begin Learn Mode" signals the AccuLoad to initiate
a statistical sampling from which it derives a
signature (or numerical profile) and two subsignatures for the turbine meter. The meter
signature, as well as a standard deviation for each
meter blade, is then sent to the KDC board. Before
initiating a learn, it is best to record the current
signature so the new signature can be voided, if
necessary. Choose "View Data" from the Turbine
Meter Diagnostics display. The current signature will
appear, as shown on the screen below.
Note: On Revision 4 and above firmware, the current turbine
meter diagnostics signature value is also updated during a
"learn."
TurbineMeterDiagnostics
>
Signature
CurTMDValue
#Blades:3
0.000000e+000
0.000000e+00
Tol:MostLax
Mtr#1DisabledMeterOK
If constantly changing numbers appear at the bottom
of the AccuLoad display, the turbine meter
diagnostics feature is enabled and is working. (The
diagnostic updates once every second.) The
AccuLoad counts pulses and flow tolerance. If a
statistically significant variation occurs in 4 out of 10
meter turns, an alarm will be generated. The alarm
does not necessarily indicate the reason for the
variation; possible causes are bearing problems, a
bent blade, or flow inconsistency. Selecting a less
65
MN06118L Issue/Rev. 0.5 (4/02)
Choose "Disable/Enable Diagnostic" to disable or
enable Learn Mode. The diagnostic toggles between
"disabled" and "enabled" every time the screen is
selected and exited.
TurbineDiagnosticsforthis
meterhavebeenENABLED.
Pressanykey.
Software Version
Selecting "Software Version" from the Add-Pak
Diagnostics menu displays a screen similar to that
shown below. This option indicates the software
version and CRC associated with the Add-Pak
software for all injectors configured as Add-Paks. If
no injector is configured as an Add-Pak, a pop-up
with the message "Injector Not Configured" will
appear. All configured injectors on one Add-Pak will
return the same information.
Select "View Data" to display the turbine meter's
signature and current configuration.
>
AddPakDiagnostics
Inj#3Version00
72852B46
Inj#12Version00
72852B46
TurbineMeterDiagnostics
>
Signature
CurTMDValue
#Blades:0
0.000000e+000
0.000000e+000
Tol:MostLax
Mtr#1DisabledMeterOK
Press CLEAR twice to return to the Diagnostics
Menu.
I/O Diagnostics
Selecting "I/O Diagnostics" from the Add-Pak
Diagnostics menu displays a screen similar to that
shown below.
>
Add-Pak Diagnostics
AddPakDiagnostics
Inj#3
Inj#4
Inj#5
more
Note: Add-Pak Diagnostics are available only on Revision 3 and
above firmware.
Selecting "Add-Pak Diagnostics" from the menu
allows the operator to turn the pump on and off and
view pulse and volume information at one Add-Pak
injector at a time. These functions allow the operator
to test the additive injector I/O during a period of no
activity at the load arm. It is possible to manipulate
outputs and read pulse input data without
configuring the injector for use at the AccuLoad III.
Note that only injectors 3 through 12 are valid AddPak injectors; I/O and pulse input diagnostics exist
elsewhere on the AccuLoad for injectors 1 and 2.
>
AddPakDiagnostics
SoftwareVersion
I/ODiagnostics
TestInject
Initialize
Position the cursor beside the appropriate injector
and press ENTER. A screen similar to that shown
below will appear. This diagnostic screen allows the
pump or solenoid to be turned on and off. The state
of the output will change when the ENTER key is
pressed with the arrow positioned at one of the I/O
points. "ENTER" communicates a state change to
the Add-Pak board. The displayed state only toggles
once the Add-Pak is queried about the state of the
I/O point after it has been commanded to change.
Therefore, if the Add-Pak is not communicating, the
state will not toggle with ENTER. This diagnostic
also allows the counts to be reset to zero at any
time. Counts and volume update when incoming
pulses are seen by the Add-Pak.
>
AddPakInjector#3
Pump
Solenoid
OFF
OFF
Section V Diagnostics
ResetCounts
Counts000000Vol.0000000.000
The I/O diagnostic may be performed on an injector
not programmed as an Add-Pak. Because Injectors
1 and 2 cannot be Add-Pak injectors, AccuLoad
Injector 3 corresponds to Add-Pak Injector 1,
AccuLoad Injector 4 to Add-Pak Injector 2, and so
on. In order to perform a diagnostic, a Smart Injector
comm port must be programmed. Note that there is
a slight delay when exiting the screen as the
AccuLoad resets and verifies that the I/O points on
the Add-Pak are de-energized.
67
MN06118L Issue/Rev. 0.5 (4/02)
Test Inject
Selecting "Test Inject" from the Add-Pak Diagnostics
menu displays a screen similar to that shown below.
This option allows the operator to prove an Add-Pak
injector. Note that "Test Inject" won't work if the
additive injector is not programmed as an Add-Pak.
In this case, a pop-up will appear with the message
"Injector Not Configured."
AddPakDiagnostics
>
Inj#3
Inj#4
Inj#5
more
Select an Add-Pak injector by positioning the cursor
beside the desired injector and pressing ENTER. A
screen similar to that shown below will appear.
>
AddPakInjector#3
InjectionVol
0.000
Injectoris
NotAuthorized
Inject
Injection#0
Counts000000Vol.0000000.000
After selecting an Add-Pak injector, this diagnostic
will request the injection volume. The next step is to
authorize the injector and energize the pump. This
cannot be done if the injection volume has not been
specified. Finally, the operator can request test
injections from this diagnostic screen. A counter will
display the number of injections completed thus far,
in addition to the pulse and volume information
(which will update as the test proceeds). By
comparing the reported volume to the actual volume
injected, the injector meter factor can be calculated
and programmed by the operator. The new meter
factor must be entered by the operator in Program
Mode using conventional methods. This diagnostic
provides no facility for the computation or
programming of the newly derived additive meter
factor.
Initialize
Selecting "Initialize" from the Add-Pak Diagnostics
menu displays a screen similar to that shown below.
AddPakInitializing
PleaseWait/
Section V Diagnostics
This command will initialize all ten Add-Pak injectors
and reset all parameters and totals back to zero. The
AccuLoad will not initialize the Add-Pak injectors as
part of its own initialization. When the initialization is
complete, the display will return to the Add-Pak
Diagnostics menu. Press "CLEAR" to force an early
exit out of the display; however, be aware that the
Add-Pak may cause an Additive Communications
(AC) alarm as it completes the initializing process.
occurred during the test, the overruns, the parity, and
the framing errors. Pressing CLEAR will end the test
and return the unit to the Communications Test
menu. The test is identical for the four ports. The
only difference in the display will be the comm port
number and the channel designation.
Communications Test
Selecting "Communications Test" from the menu
allows the operator to run a diagnostic on any of the
communication ports on the AccuLoad. Pressing
ENTER with the cursor in front of selection one will
activate a popup screen where the operator can
select the communications port to be tested.
Selectcommporttotest.
>
Comm1
Comm2
Comm3
Comm4
For this test to be completed, the transmit and
receive terminals on the comm port must be
connected. Once the Communication Port has been
selected for testing by moving the arrow to the
required port, pressing ENTER will start the
communications test.
CommPort1Test
Tx
Rx
Errs
S
S
00003
overruns:00000
parity:00000
framing:00000
PressCLEARtostoptest
The test will display the characters that are being
transmitted on the transmit line, as well as the
characters as they are received back into the
instrument. Also displayed are the errors that have
69
MN06118L Issue/Rev. 0.5 (4/02)
Keypad Test
KeypadTest
Pressanykeyanditwillbe
displayed.PressCLEARtwice
toexit.
With this screen displayed, any key that is pressed
will appear on the screen as the key that was
pressed.
User Boolean Registers
User Algebraic Registers
Equation Line Status
General Purpose Timers
Select "Keypad Test" from the menu to run a
diagnostic test on the keypad of the AccuLoad.
Pressing ENTER will display the keypad test screen.
User Boolean Registers
Selecting "User Boolean Registers" and pressing
ENTER will display the first nine user Boolean
registers. There are a total of 100 user Boolean
registers. The range of these registers is 0 to 255.
These registers are set aside for the user. They can
be written to by Boolean/Algebraic equations or via
communications. The values can be printed on userdefined reports.
KeypadTest
UserBooleanRegisters
STOP
Pressanykeyanditwillbe
displayed.PressCLEARtwice
toexit.
#1
#2
#3
0
0
0
#4
#5
#6
0
0
0
#7
#8
#9
0
0
0
More
To end the test, the CLEAR key must be pressed
twice. The first time CLEAR will appear on the test
screen. The second time, the unit will return to the
Diagnostic Test menu.
Display Pixel Test
Selecting " Display Pixel Test" and pressing ENTER
will initiate the pixel test on the display. All the pixels
will be lit, allowing the operator to determine if any of
the pixels on the display are not functioning.
Pressing CLEAR will terminate the test and return
the unit to the Diagnostic menu.
User Algebraic Registers
Selecting "User Algebraic Registers" and pressing
ENTER will display the first three user algebraic
registers.
UserAlgebraicRegisters
#1
#2
#3
0
0
0
More
Equation Line Status
Boolean/Algebraic Processing
Selecting "Boolean/Algebraic Processing" and
pressing ENTER will display the following list of
Boolean/Algebraic-related diagnostic displays that
can be viewed by the operator.
The Equation Line Status displays the current status
of the equations, where "D" indicates that the
equation is disabled, "T" is True, and "F" is False. All
equations without an "IF" statement will have a
"True" status. Those with an "IF" will indicate the
result of the "IF" expression: either "True" or "False."
Section V Diagnostics
1316
1hour
7.5years
EquationLineStatus
#1
#2
#3
D
D
F
#4
#5
#6
T
D
D
#7
#8
#9
D
D
D
MoreSTOPtotoggleon/off.
Entering the equation number that is to be disabled
and pressing ENTER will change the status on the
screen from either T (True) or F (False) to D
(Disabled). The equation from that point until
enabled will not be active. To enable an equation the
same process is followed, except that the screen will
indicate that the equation is D (Disabled). Entering
the equation number will enable that equation.
The operator can clear the times by writing a zero to
the database location of the desired timer. See the
AccuMate Installation/Operation Manual for details.
Like the user Boolean and user algebraic registers,
these timers are reserved strictly for the user. They
may be started via Boolean/Algebraic equations or
via communications. Timers are very useful in the
design of equations as they allow setting a user
alarm or taking some other action after an event has
persisted for a period of time.
ToggleEquationON/OFF
EnterEquation#>1
General Purpose Timers
Selecting "General Purpose Timers" and pressing
ENTER will display nine of the sixteen general
purpose timers that can be activated and used
through the Boolean and/or algebraic equations.
GeneralPurposeTimers
#1
#2
#3
0
0
0
#4
#5
#6
0
0
0
#7
#8
#9
0
0
0
More
The timers are incremented at the following intervals:
TimerNumbers
Resolution
Range
14
58
912
0.1second
1.0second
1.0minute
109minutes
18.2hours
45.5days
71
MN06118L Issue/Rev. 0.5 (4/02)
Reset Totals
This diagnostic is used for resetting the nonresettable totals. Pressing ENTER will display the
following screen.
ResetTotals
WARNING
Nonresettablevolumeswillbe
reset.PressENTERtocontinue
orCLEARtoexit.
Pressing CLEAR will return the unit to the
Diagnostics Menu screen. Pressing ENTER on the
screen will reset the non-resettable totals (both
product and additive) and return the unit to the
Diagnostics Menu screen.
Erase Event Log
This diagnostic is used for erasing the event log.
Pressing ENTER will display the following screen.
EraseEventLog
WARNING
Theeventlogwillbeerased!
PressENTERtocontinueor
CLEARtoexit.
Pressing CLEAR will return the unit to the
Diagnostics Menu screen without erasing the event
log. Pressing ENTER will erase the event log and
return the unit to the Diagnostics Menu screen.
Erase Transaction Log
This diagnostic is used to erase the transaction log.
Pressing ENTER with the arrow in front of "Erase
Transaction Log" will display the following screen.
EraseTransactionLog
WARNING
Thetransactionlogwillbe
erased!PressENTERto
continueorCLEARtoexit.
Section V Diagnostics
Pressing CLEAR will return the unit to the
Diagnostics Menu screen without erasing the
transaction log. Pressing ENTER will erase the
transaction log and return the unit to the Diagnostics
Menu. Not only will the log be erased, but historic
transactions currently archived will no longer be
available via communications.
Factory Initialize
Selecting "Factory Initialize" and pressing ENTER
will display a screen that tells the operator that if
ENTER is pressed, all the parameters in the unit will
be reset to the default values as they were shipped
from the factory. Caution: Running this diagnostic
will change all parameters that have been
programmed previously.
73
FactoryInitialize
WARNING
Allrundataandparameters
willbeerased!PressENTERto
continueorCLEARtoexit.
This diagnostic should always be run when a new
set of PROMs is installed.
Factory Diagnostics
For factory use only.
MN06118L Issue/Rev. 0.5 (4/02)
This section describes the individual program codes
within the directories. The directories and
subdirectories are listed above each set of
parameters. The main system directories are as
follows. Please note that the numbers in
parentheses
are
reference
numbers
for
communications. In the database, pick list items
have a reference number for communications (e.g.
(2)). Through communications, a 2 would be sent to
the AccuLoad to program the item for that
parameter.
The program code explanations frequently list "fatal"
or "critical" warnings, or indicate that in some
circumstances, the code is "no entry." A fatal
warning is triggered by a selection that the AccuLoad
cannot accept and will not allow to be entered.
Possible causes include an entry that falls outside
an allowable range, or an entry that seriously
conflicts with a previous entry. A critical warning
signals that a selection is incompatible with a
previously configured program code. The AccuLoad
will accept the new entry, but the selection will
undoubtedly cause a problem in operation and
should be changed. "No entry" indicates that a
program code is unavailable and will not appear on
the menu, because previous selections make it
irrelevant. For example, ratio blending program
codes will not appear when sequential blending has
been chosen.
Configuration Directories
000 Load Arm Configuration Directory
100 Pulse Input Directory
200 Pulse Output Directory
300 DC & AC Digital Input Directory
400 DC & AC Digital Output Directory
600 Analog I/O Directory
System Directories
100 General Purpose Directory
300 Volume Accuracy Directory
400 Temperature/Density Directory
500 Pressure Directory
600 Alarm Configuration Directory
700 Communications Directory
800 Additive Directory
Load Arm Directories
100 General Purpose Directory
200 Flow Control Directory
300 Volume Accuracy Directory
700 Communications
Meter Directories
Note: This is a subdirectory under Load Arm.
200 Flow Control Directory
300 Volume Accuracy Directory
400 Temperature/Density Directory
Product Directories
Note: This is a subdirectory under Meter.
100 General Purpose Directory
200 Flow Control Directory
300 Volume Accuracy Directory
400 Temperature/Density Directory
500 Pressure Directory
Recipe Directory
Configuration 000 Arm
Configuration Directory
001 Number of Load Arms
002 Arm 1 Configuration
003 Arm 1 Number of Products
004 Arm 2 Configuration
005 Arm 2 Number of Products
020 Number of Additive Injectors
Configuration 001 Number of Load
Arms
This parameter defines the number of load arms
associated with this AccuLoad. Valid entries are 1 or
2.
Fatal: Entry is out of specified range.
Help: Enter the number of load arms associated with
this AccuLoad.
Configuration 002 Arm 1
Configuration
Section VI Program Codes
This parameter determines the functionality of Arm
1. The factory default is "straight product."
Selections are as follows:
(0) Straight Product Arm
(1) Sequential Blending Arm
(2) Ratio Blending Arm
Help: Select the configuration for this load arm:
Straight Product, Sequential Blender or Ratio
Blender.
Configuration 003 Arm 1 Number of
Products
Help: Enter the number of products associated with
this load arm.
Configuration 020 Number of
Injectors
This parameter defines the number of additive
injectors that will be used with this AccuLoad. Valid
entries are 0 to 12.
Fatal: Entry out of specified range.
Help: Enter the number of additive injectors
associated with this AccuLoad.
This parameter defines the number of products
assigned to this arm. Valid entries are 1 to 4. The
factory default is "4."
Configuration 100 Pulse Input
Directory
Help: Enter the number of products associated with
this load arm.
102 Transmitter Integrity
103 Pulse Input 3 Function
104 Pulse Input 3 Arm
105 Pulse Input 3 Meter
107 Pulse Input 4 Function
108 Pulse Input 4 Arm
109 Pulse Input 4 Meter
111 Pulse Input 5 Function
112 Pulse Input 5 Arm
113 Pulse Input 5 Meter
115 Pulse Input 6 Function
116 Pulse Input 6 Arm
117 Pulse Input 6 Meter
Configuration 004 Arm 2
Configuration
This parameter determines the functionality of Arm
2. The factory default is "straight product."
Selections are as follows:
(0) Straight Product Arm
(1) Sequential Blending Arm
Help: Select the configuration for this load arm:
Straight Product or Sequential Blender.
Note: On the AccuLoad III with ALD1, this entry is not available if
arm 1 is programmed for ratio blending. This entry is not available
on ALS1 firmware.
Configuration 005 Arm 2 Number of
Products
This parameter defines the number of products
assigned to this arm. Valid entries are 1 to 4. The
factory default is "4." This entry is not available on
ALS1 firmware.
Critical: Block valves required for all products.
Fatal: Entry is out of specified range.
75
101 Pulse Input Channel Selection
Configuration 101 Transmitter
Channel Selection
This parameter defines the transmitter type used
with AccuLoad III. The two types available are Single
(Channel A only) and Dual (Channel A and B).
Selections are as follows:
(0) Single channel
(1) Dual channel
Help: Select a single or dual pulse transmitter, PIB
PT1 (1(+), 2(-) for single channel or A, (3(+), 4(-) for
channel B
MN06118L Issue/Rev. 0.5 (4/02)
Configuration 102 Meter Pulse
Transmitter Integrity
This parameter defines whether or not transmitter
integrity is in effect if a dual channel transmitter is
selected for use. Transmitter integrity uses the
inverse pulses to determine if there is an integrity
problem with the transmitter. This feature is only
used with the Smith Meter dual pulse transmitter
PPST or the GPST. Selections are as follows:
(0) No - No transmitter integrity
(1) Yes - Transmitter integrity
Critical: Transmitter integrity not available with
single channel.
Help: If Yes, /A input to pulse input 3 required. PIB
PT1:5(+), 6(-)
Configuration 103 Pulse Input 3
Function
Pulse input #3 function can be definedassigned to
be one of the following functions. Selections are as
follows:
(0) N/A
(1) Metered Injector #1
(2) Metered Injector #2
(3) Frequency Densitometer
A Metered Injector is a direct input from an additive
injector system that contains no control electronics;
hence, the interface consists of an injecting solenoid
input and a meter pulse output. This input is used as
a meter input for the injector and is connected to the
injectors meter pulse output.
Critical: This input not available with dual channel
pulse input.
Help: Select function for In 3, PIB PT1:5(+), 6(-)
Configuration 104 Pulse Input 3
Arm
Pulse input #3 arm can be defined to beassigned to
one of the following arms. Selections are as follows:
(0) Arm 1
(1) Arm 2
Critical: Load arm not configured. (Load Arm 2 not
available on ALS1 firmware.)
Help: Specify which arm this input is associated
with.
Configuration 105 Pulse Input 3
Meter
Pulse input #3 meter can be defined to beassigned
to one of the following meters. Selections are as
follows:
(0) Meter 1
(1) Meter 2
Critical: Meter not configured.
Help: Specify which meter this input is associated
with.
Configuration 107 Pulse Input 4
Function
Pulse input #4 can be defined to be assigned to one
of the following functions. Selections are as follows:
(0) N/A
(1) Metered Injector #1
(2) Metered Injector #2
(3) Frequency Densitometer
A Metered Injector is a direct input from an additive
injector system that contains no control electronics;
hence, the interface consists of an injecting solenoid
input and a meter pulse output. This input is used as
a meter input for the injector and is connected to the
injectors meter pulse output.
Critical: This input not available with dual channel
and two arms.
Help: Select function for In 4, PIB PT1:7(+),8(-)
Configuration 108 Pulse Input #4
Arm
Section VI Program Codes
Pulse input #4 arm can be defined to beassigned to
one of the following arms. Selections are as follows:
(0) Arm 1
(1) Arm 2
Critical: Load arm not configured.
Help: Specify which arm this input is associated
with.
Configuration 109 Pulse Input 4
Meter
Pulse input #4 meter can be defined to beassigned
to one of the following meters. Selections are as
follows:
(0) Meter 1
(1) Meter 2
Critical: Meter not configured.
Help: Specify which meter this input is associated
with.
Configuration 111 Pulse Input 5
Function
Pulse input #5 can be defined to beassigned to one
of the following functions. Selections are as follows:
(0) N/A
(1) Metered Injector #1
(2) Metered Injector #2
(3) Frequency Densitometer
A Metered Injector is a direct input from an additive
injector system that contains no control electronics;
hence, the interface consists of solelysolely of an
injecting solenoid input and a meter pulse output.
This input is used as a meter input for the injector
and is connected to the injectors meter pulse output.
Critical: This input not available with dual channel
and two arms.
Help: Select function for In 5, PIB PT1:9(+),10(-)
77
Configuration 112 Pulse Input #5
Arm
Pulse input #5 arm can be defined to beassigned to
one of the following arms. Selections are as follows:
(0) Arm 1
(1) Arm 2
Critical: Load arm not configured. (Load arm 2 not
available on ALS1 firmware.)
Help: Specify which arm this input is associated
with.
Configuration 113 Pulse Input 5
Meter
Pulse input #5 meter can be defined to beassigned
to one of the following meters. Selections are as
follows:
(0) Meter 1
(1) Meter 2
Critical: Meter not configured.
Help: Specify which meter this input is associated
with.
Configuration 115 - Pulse Input 6
Function
Pulse input #6 can be defined to beassigned to one
of the following functions. Selections are as follows:
(0) N/A
(1) Metered Injector #1
(2) Metered Injector #2
(3) Frequency Densitometer
A Metered Injector is a direct input from an additive
injector system that contains no control electronics;
hence, the interface consists of solelyof an injecting
solenoid input and a meter pulse output. This input is
used as a meter input for the injector and is
connected to the injectors meter pulse output.
MN06118L Issue/Rev. 0.5 (4/02)
Critical: This input not available with dual channel
and two arms.
Help: Select function for In 6, PIB PT1:11(+),12(-)
Configuration 116 Pulse Input #6
Arm
Pulse input #6 arm can be defined to beassigned to
one of the following arms. Selections are as follows:
(0) Arm 1
(1) Arm 2
Critical: Load arm not configured. (Load arm 2 not
available on ALS1 firmware.)
Help: Specify which arm this input is associated
with.
Configuration 117 Pulse Input 6
Meter
Pulse input #6 meter can be defined to be assigned
to one of the following meters. Selections are as
follows:
(0) Meter 1
(1) Meter 2
Critical: Meter not configured.
Help: Specify which meter this input is associated
with.
Configuration 200 Pulse Output
Directory
Meter 1 or Arm 1 Pulses
201 Pulse Output 1 Function
202 Pulse Output 1 Pulse/Volume
203 Pulse Output 1 Pulse Units
204 Pulse Output 1 Maximum Frequency
Meter 2 or Arm 2 Pulses
205 Pulse Output 1 Function
206 Pulse Output 2 Pulse/Volume
207 Pulse Output 2 Pulse/Units
208 Pulse Output 2 Maximum Frequency
Configuration 201 - Pulse Output 1
Function
This program code allows a pulse output to be
defined. The output will be active when flow is active
during a batch, and represents volume. The number
of pulses is determined by Configuration 202
Pulse/Volume, and volume type is determined by
Configuration 203 Pulse Out Units. Selections are
as follows:
(0) Not used
(1) Load Arm 1 Out
(2) Load Arm 2 Out (No Entry: Only one load
arm, ratio blending; ALS1 firmware)
(3) Meter 1 Out
(4) Meter 2 Out (No Entry; Only one load arm
configured for straight product or sequential
blending)
Note: Available options will vary based on arm configurations.
Help: Select function for this pulse output, KDC
TB4:7(+),8(-)
Configuration 202 - Pulse Output 1
Pulse/Volume
This parameter defines the pulse output resolution,
the number of pulses per unit of volume to be
generated (e.g., 0.1 will output 1 pulse for every 10
units of volume). The range of this parameter is 0.00
999.99.
No-entry if corresponding Pulse Output Function =
Not Used
Help: Enter output pulses per unit of volume
Section VI Program Codes
Configuration 203 - Pulse Output 1
Units
This parameter defines the volume type used to
pace the pulse output. Selections are as follows:
(0) IV (Indicated Volume or Raw)
(1) GV (Gross)
(2) GST (Gross Standard Temperature)
(3) GSV (Gross at Standard Temperature and
Pressure)
(4) Mass
Critical: Selected units not available.
No-entry if corresponding Pulse Output Function =
Not Used
Help: Select volume type for pulse output to be
based on.
Configuration 204 Pulse Output 1
Max Frequency
This entry limits the pulse output frequency for Pulse
Output 1 to a fixed range (0 3500 Hz) to avoid
over-speeding the device attached to the pulse
output. All of the intended pulses will eventually be
transmitted; the total period will be increased if
required to ensure the correct number of pulses is
output. A 0 entry disables this feature.
Fatal: Entry is out of specified range.
Help: Enter frequency that output should be limited
to (0 3500 Hz).
Configuration 205 - Pulse Output 2
Function
This program code allows a second pulse output to
be defined. The output will be active when flow is
active during a batch, and represents volume. The
number of pulses is determined by Configuration
206 Pulse/Volume, and volume type is determined
by Configuration 207 Pulse Out Units. Selections
are as follows:
N/A
Pulse Output
(0) Not Used
79
(1) Load Arm 1 Out
(2) Load Arm 2 Out (No Entry: Only one load
arm or ALS1 firmware)
(3) Meter 1 Out
(4) Meter 2 Out (No Entry: Not a ratio blender.)
Note: Available options will vary based on arm configurations.
Help: Select function for this pulse output, KDC
TB5:7(+),8(-)
Configuration 206 - Pulse Output 2
Pulse/Volume
This parameter defines the pulse output resolution,
the number of pulses per unit of volume to be
generated (e.g., 0.1 will output 1 pulse for every 10
units of volume). The range of this parameter is 0.01
999.99.
Configuration 207 Pulse Output 2
Units
This parameter defines the volume type used to
pace the pulse output. Selections are as follows:
(0) IV (Raw)
(1) GV (Gross)
(2) GST (Gross at Standard Temperature)
(3) GSV (Gross at Standard Temperature and
Pressure)
(4) Mass
Critical: Selected units not available.
No-entry if corresponding Pulse Output Function =
Not Used
Help: Select volume type for pulse output to be
based on.
Configuration 208 Pulse Output 2
Max Frequency
This entry limits the pulse output frequency for Pulse
Output 2 to a fixed range (0 3500 Hz) to avoid
over-speeding the device attached to the pulse input.
All of the intended pulses will eventually be
transmitted; the total period will be increased if
required to ensure the correct number of pulses is
output. A 0 entry disables this feature.
MN06118L Issue/Rev. 0.5 (4/02)
Fatal: Entry is out of specified range.
Help: Enter frequency that output should be limited
to (0 3500 Hz).
Configuration 300 Digital Input
Directory
301, 305, 309, 313, 317, 321, 325, 329, 333, 337,
341 Digital Input Function
302, 306, 310, 314, 318, 322, 326, 330, 334, 338,
342 Digital Input Arm Assignment
304, 308, 312, 316, 320, 324, 328, 332, 336, 340,
344 Digital Input Product
Section VI Program Codes
Configuration 301, 305, 309, 313,
317, 321, 325, 329, 333, 337, 341 Digital Input Function
DC & AC Digital Inputs
301 Digital Input DC #1
KDC TB4:1(+),2(-)
305 Digital Input DC #2
KDC TB4:3(+),4(-)
309 Digital Input DC #3
KDC TB4:5(+),6(-)
313 Digital Input DC #4
EAAI TB4:4(+),5(-)
317 Digital Input DC #5
EAAI TB4:6(+),7(-)
321 Digital Input DC #6
EAAI TB4:8(+),9(-)
325 Digital Input AC #7
EAAI TB2:1 (Com), 2
329 Digital Input AC #8
EAAI TB2:1 (Com), 3
333 Digital Input AC #9
EAAI TB2:1 (Com), 4
337 Digital Input AC #10
EAAI TB2:1 (Com), 5
341 Digital Input AC #11
EAAI TB2:1 (Com), 6
These program codes define the function for a digital
input. Except for General Purpose inputs, duplicate
assignments are not allowed. Inputs 1-6
(Configuration numbers 301, 305, 309, 313, 317,
and 321) are DC inputs, and the rest (7-11,
Configuration numbers 325, 329, 333, 337, and 341)
are AC. Selections are as follows:
(00) N/A
(01) Security Switch Input #1
(02) Security Switch Input #2
(03) Permissive #1
(04) Permissive #2
Permissive #3
1st/2nd(05) First/Second High Flow Switch
(06) Remote Start
(07) Remote Stop
(08) Transaction Reset
(09) General Purpose Input
(10) Piston Injector #1 Feedback
(11) Piston Injector #2 Feedback
(12) Piston Injector #3 Feedback
(13) Piston Injector #4 Feedback
(14) Piston Injector #5 Feedback
(15) Piston Injector #6 Feedback
(16) Piston Injector #7 Feedback
(17) Piston Injector #8 Feedback
81
(18) Piston Injector #9 Feedback
(19) Piston Injector #10 Feedback
(20) Piston Injector #11 Feedback
(21) Piston Injector #12 Feedback
(22) Ticket Printer Tray Switch
(23) Block Valve Feedback
Critical: Input assignments must be unique [except
general purpose inputs]
Critical: Input assignments do not match type
[injector feedbacks only]
Critical: No digital output assigned for this injector
[injector feedbacks only]
Critical: Block valves used with sequential blending
only.
Help: Select function for this (DC/AC) input (plus
terminal connection)
Configuration 302, 306, 310, 314,
318, 322, 326, 330, 334, 338, 342
Digital Input Arm Assignment
DC & AC Digital Inputs
302 Digital Input DC #1
KDC TB4:1(+),2(-)
306 Digital Input DC #2
KDC TB4:3(+),4(-)
310 Digital Input DC #3
KDC TB4:5(+),6(-)
314 Digital Input DC #4
EAAI TB4:4(+),5(-)
318 Digital Input DC #5
EAAI TB4:6(+),7(-)
322 Digital Input DC #6
EAAI TB4:8(+),9(-)
326 Digital Input AC #7
EAAI TB2:1 (Com), 2
330 Digital Input AC #8
EAAI TB2:1 (Com), 3
334 Digital Input AC #9
EAAI TB2:1 (Com), 4
338 Digital Input AC #10
EAAI TB2:1 (Com), 5
342 Digital Input AC #11
EAAI TB2:1 (Com), 6
Assign the associated digital input to one of the two
load arms. Selections are as follows:
(0) Arm 1
(1) Arm 2
Some digital input functions are system-based and
the arm entry is not used. It will not appear on the
AccuLoad Program Mode menus in these cases.
MN06118L Issue/Rev. 0.5 (4/02)
These functions include Security inputs, General
Purpose inputs, Piston Injector Feedback inputs and
remote Stop inputs.
Critical: Load arm not configured.
Critical: Input assignments must be unique [except
general purpose inputs]
Critical: Input assignments do not match type
[injector feedbacks only]
Critical: No digital output assigned for this injector
[injector feedbacks only]
Help: Select function for this (DC/AC) input (plus
terminal connection)
Help: Select the arm this input is associated with.
Section VI Program Codes
Configuration 304, 308, 312, 316,
320,324, 328, 332, 336, 340, 344
Digital Input Product
DC & AC Digital Inputs
304 Digital Input DC #1
KDC TB4:1(+),2(-)
308 Digital Input DC #2
KDC TB4:3(+),4(-)
312 Digital Input DC #3
KDC TB4:5(+),6(-)
316 Digital Input DC #4
EAAI TB4:4(+),5(-)
320 Digital Input DC #5
EAAI TB4:6(+),7(-)
324 Digital Input DC #6
EAAI TB4:8(+),9(-)
328 Digital Input AC #7
EAAI TB2:1 (Com), 2
332 Digital Input AC #8
EAAI TB2:1 (Com), 3
336 Digital Input AC #9
EAAI TB2:1 (Com), 4
340 Digital Input AC #10
EAAI TB2:1 (Com), 5
344 Digital Input AC #11
EAAI TB2:1 (Com), 6
402,406,410,414,418,422,426,430,434,438,442,446,
450,454 Digital Output Arm Assignment
403,407,411,415,419,423,427,431,435,439,443,447,
451,455 Digital Output Meter Assignment
404,408,412,416,420,424,428,432,436,440,444,448,
452,456 Digital Output Product Assignment
Assign a product to one of the digital input functions
from the list above. Selections are as follows:
(0) Product 1
(1) Product 2
(2) Product 3
(3) Product 4
These entries can only be configured for a
Sequential Blending arm.
Critical: Load arm not configured.
Critical: Input assignments must be unique [except
general purpose inputs]
Critical: Input assignments do not match type
[injector feedbacks only]
Critical: No digital output assigned for this injector
[injector feedbacks only]
Help: Select function for this (DC/AC) input (plus
terminal connection)
Help: Select the arm this input is associated with.
Configuration 400 Digital Output
Directory
401,405,409,413,417,421,425,429,433,437,441,445,
449,453 Digital Output Function
83
MN06118L Issue/Rev. 0.5 (4/02)
Configuration 401, 405, 409, 413,
417, 421, 425, 429, 433, 437, 441,
445, 449, 453 Digital Output
Function
DC & AC Digital Outputs
401 Digital Output DC #1
KDC TB5:1(+),2(-)
405 Digital Output DC #2
KDC TB5:3(+),4(-)
409 Digital Output DC #3
KDC TB5:5(+),6(-)
413 Digital Output AC #4
EAAI TB3: 1,2
417 Digital Output AC #5
EAAI TB3: 3,4
421 Digital Output AC #6
EAAI TB3: 5,6
425 Digital Output AC #7
EAAI TB3: 7,8
429 Digital Output AC #8
EAAI TB3: 9,10
433 Digital Output AC #9
EAAI TB3: 11,12
437 Digital Output AC #10
EAAI TB7: 1,2
441 Digital Output AC #11
EAAI TB7: 3,4
445 Digital Output AC #12
EAAI TB7: 5,6
449 Digital Output AC #13
EAAI TB7: 7,8
453 Digital Output AC #14
EAAI TB7: 9,10
This program code defines the function of a digital
output. Except for General Purpose outputs,
duplicate assignments are not allowed. If a valve is
being configured, both Upstream and Downstream
Solenoids must be assigned. Outputs 1 3
(Configuration numbers 401, 405, and 409) are DC,
the remaining (4 14, Configuration numbers 413,
417, 421, 425, 429, 433, 437, 441, 445, 449, and
453) are AC.
(00) N/A
(01) Alarm Output Relay #1
(02) Alarm Output Relay #2
(03) Pump
(04) Control Valve Upstream Solenoid
(05) Control Valve Downstream Solenoid
(06) Additive #1 Pump
(07) Additive #2 Pump
(08) Additive #3 Pump
(09) Additive #4 Pump
(10) Additive #5 Pump
(11) Additive #6 Pump
(12) Additive #7 Pump
(13) Additive #8 Pump
(14) Additive #9 Pump
(15) Additive #10 Pump
(16) Additive #11 Pump
(17) Additive #12 Pump
(18) Piston Injector #1
(19) Piston Injector #2
(20) Piston Injector #3
(21) Piston Injector #4
(22) Piston Injector #5
(23) Piston Injector #6
(24) Piston Injector #7
(25) Piston Injector #8
(26) Piston Injector #9
(27) Piston Injector #10
(28) Piston Injector #11
(29) Piston Injector #12
(30) Metered Injector #1 Solenoid Control Out
(31) Metered Injector #2 Solenoid Control Out
(32) General Purpose Output
(33) Block Valve
(34) Stop Relay
Critical: Input assignments must be unique [except
general purpose inputs]
Critical: Input assignments do not match type
[injector feedbacks only]
Critical: No digital output assigned for this injector
[injector feedbacks only]
Critical: Block valves used with sequential blending
only.
Help: Select function for this (DC/AC) input (plus
terminal connection)
Configuration 402, 406, 410, 414,
418, 422, 426, 430, 434, 438, 442,
446, 450, 454 Digital Output Arm
Assignment
DC & AC Digital Outputs
402 Digital Output DC #1
KDC TB5:1(+),2(-)
406 Digital Output DC #2
KDC TB5:3(+),4(-)
410 Digital Output DC #3
KDC TB5:5(+),6(-)
414 Digital Output AC #4
EAAI TB3: 1,2
418 Digital Output AC #5
EAAI TB3: 3,4
422 Digital Output AC #6
EAAI TB3: 5,6
426 Digital Output AC #7
EAAI TB3: 7,8
430 Digital Output AC #8
EAAI TB3: 9,10
434 Digital Output AC #9
EAAI TB3: 11,12
Section VI Program Codes
438 Digital Output AC #10
442 Digital Output AC #11
446 Digital Output AC #12
450 Digital Output AC #13
454 Digital Output AC #14
EAAI TB7: 1,2
EAAI TB7: 3,4
EAAI TB7: 5,6
EAAI TB7: 7,8
EAAI TB7: 9,10
This entry defines the arm associated with the digital
output function. Selections are as follows:
(0) Arm 1
(1) Arm 2
Critical: Load arm not configured.
Critical: Input assignments must be unique [except
general purpose inputs]
Critical: Input assignments do not match type
[injector feedbacks only]
Critical: No digital output assigned for this injector
[injector feedbacks only]
Help: Select function for this (DC/AC) input (plus
terminal connection)
Help: Select the arm this input is associated with.
This entry defines the meter associated with the
output function. Selections are as follows:
(0) Meter 1
(1) Meter 2
This entry is only valid for a Ratio Blending arm. (In
other configurations, only Meter 1 exists for the arm;
hence, the arm entry determines which meter is
intended.)
Critical: Load arm not configured.
Critical: Input assignments must be unique [except
general purpose inputs]
Critical: Input assignments do not match type
[injector feedbacks only]
Critical: No digital output assigned for this injector
[injector feedbacks only]
Help: Select function for this (DC/AC) input (plus
terminal connection)
Help: Select the arm this input is associated with.
Configuration 403, 407, 411, 415,
419, 423, 427, 431, 435, 439, 443,
447, 451, 455 Digital Output Meter
Assignment
DC & AC Digital Outputs
403 Digital Output DC #1
KDC TB5:1(+),2(-)
407 Digital Output DC #2
KDC TB5:3(+),4(-)
411 Digital Output DC #3
KDC TB5:5(+),6(-)
415 Digital Output AC #4
EAAI TB3: 1,2
419 Digital Output AC #5
EAAI TB3: 3,4
423 Digital Output AC #6
EAAI TB3: 5,6
427 Digital Output AC #7
EAAI TB3: 7,8
431 Digital Output AC #8
EAAI TB3: 9,10
435 Digital Output AC #9
EAAI TB3: 11,12
439 Digital Output AC #10
EAAI TB7: 1,2
443 Digital Output AC #11
EAAI TB7: 3,4
447 Digital Output AC #12
EAAI TB7: 5,6
451 Digital Output AC #13
EAAI TB7: 7,8
455 Digital Output AC #14
EAAI TB7: 9,10
85
MN06118L Issue/Rev. 0.5 (4/02)
Configuration 404, 408, 412, 416,
420, 424, 428, 432, 436, 440, 444,
448, 452, 456 - Digital Output
Product Assignment
DC & AC Digital Outputs
404 Digital Output DC #1
KDC TB5:1(+),2(-)
408 Digital Output DC #2
KDC TB5:3(+),4(-)
412 Digital Output DC #3
KDC TB5:5(+),6(-)
416 Digital Output AC #4
EAAI TB3: 1,2
420 Digital Output AC #5
EAAI TB3: 3,4
424 Digital Output AC #6
EAAI TB3: 5,6
428 Digital Output AC #7
EAAI TB3: 7,8
432 Digital Output AC #8
EAAI TB3: 9,10
436 Digital Output AC #9
EAAI TB3: 11,12
440 Digital Output AC #10
EAAI TB7: 1,2
444 Digital Output AC #11
EAAI TB7: 3,4
448 Digital Output AC #12
EAAI TB7: 5,6
452 Digital Output AC #13
EAAI TB7: 7,8
456 Digital Output AC #14
EAAI TB7: 9,10
Assign a product to one of the digital output
functions from the list above. Selections are as
follows:
(0) Product 1
(1) Product 2
(2) Product 3
(3) Product 4
These entries are used only if the entry for the
related Digital Output Function is Block Valve
Feedback.
Critical: Load arm not configured.
Critical: Input assignments must be unique [except
general purpose inputs]
Critical: Input assignments do not match type
[injector feedbacks only]
Critical: No digital output assigned for this injector
[injector feedbacks only]
Help: Select function for this (DC/AC) input (plus
terminal connection)
Help: Select the arm this input is associated with.
Configuration 600 Analog I/O
Directory
601,611,621,631,641,651 Analog I/O Function
602,612,622,632,642,652 Analog I/O Arm
Assignment
603,613,623,633,643,653 Analog I/O Meter
Assignment
605,615,625,635,645,655 Analog I/O Type
606/607,616/617,626/627,636/637,646/647,656/657
Analog I/O Calibration Counts
608/609,618/619,628/629,638/639,648/649,658/659
Analog I/O High/Low Values
610,620 Analog I/O RTD Offset
Configuration 601, 611, 621, 631,
641, 651 - Analog I/O Function
These program codes define the function of the
analog inputs. Selections are as follows:
(0) N/A
(1) Temperature
(2) Density
(3) Pressure
(4) Analog Valve Out
(5) Flow Rate Out
Critical: I/O assignments must be unique.
Help: Select function for this analog I/O.
Configuration 602, 612, 622, 632,
642, 652 Analog I/O Arm
Assignment
This entry defines the arm associated with the
Analog I/O point. Selections are as follows:
(0) Arm 1
(1) Arm 2
Critical: I/O assignments must be unique.
Critical: Load arm not configured.
Help: Select the arm this I/O is associated with.
Configuration 603, 613, 623, 633,
643, 653 Analog I/O Meter
Assignment
Section VI Program Codes
This entry defines the meter associated with the
Analog I/O point. Selections are as follows:
(0) Meter 1
(1) Meter 2
This entry is only valid for a Ratio Blending arm. (In
other configurations, only Meter 1 exists for the arm;
hence, the arm entry determines which meter is
intended.)
Critical: Meter not configured.
Help: Select the meter this I/O is associated with.
87
MN06118L Issue/Rev. 0.5 (4/02)
Configuration 605, 615, 625, 635,
645, 655 - Analog I/O Type
values are assigned based on the values from the
label on the Analog Input/Output Modules, maximum
accuracy will be attained.
Analog Inputs & Outputs
605 Analog I/O #1
EAAI TB5:1(RTD+),
2(SIG+),3(SIG-),4(RTD-)
615 Analog I/O #2
EAAI TB5:5(RTD+),
6(SIG+),7(SIG-),8(RTD-)
625 Analog I/O #3
EAAI TB5:9(RTD+),
10(SIG+),11(SIG-),
12(RTD-)
635 Analog I/O #4
EAAI TB5:13(SIG+),
14(SIG-)
645 Analog I/O #5
EAAI TB5:15(SIG+),
16(SIG-)
655 Analog I/O #6
EAAI TB5:17(SIG+),
18(SIG-)
Critical: Cal1 must be less than Cal2
Help: Enter count value indicated on module.
Default = 12288
These program codes define the type of analog
module used. Selections are as follows:
(0) NA
(1) 4 20 mA Input
(2) 1 5 VDC Input
(3) RTD
(4) 4 20 mA Output
(5) 1 5 VDC Output
Only Analog Inputs #1 and #2 can be RTDs.
Critical: Function and Type must both be input or
output.
Critical: Analog type must be programmed.
Fatal: RTDs available on I/O's 1 and 2 only.
Help: Select Module type for this function (plus
terminal connection)
Configuration 606, 616, 626, 636,
646, 656 - Analog I/O Calibration 1
Counts
These program codes are used to calibrate the
analog input module. Calibration factors can be
found on the top label of the input modules. The
range of these parameters is 0 to 65535. Calibration
1 Counts must be less than Calibration 2 Counts.
Factory default calibration is 12288. When these
Configuration 607, 617, 627, 637,
647, 657 - Analog I/O Calibration 2
Counts
These program codes are used to calibrate the
analog input module. Calibration factors can be
found on the top label of the input modules. The
range of these parameters is 0 to 65535. Calibration
2 Counts must be greater than Calibration 1 Counts.
The factory default value is 53248. When these
values are assigned based on the values from the
label on the Analog Input/Output Modules, maximum
accuracy will be attained.
Critical: Cal1 must be less than Cal2
Help: Enter count value indicated on module.
Default = 53248
Configuration 608, 618, 628, 638,
648, 658 - Analog I/O Low Value
These program codes are used to define the lower
ranges of the analog input, expressed as
engineering values corresponding to the defined
function of the input. The Low entry represents the
engineering value at 4mA (or 1v for a V-In module)
and the High entry represents the engineering value
at 20mA (or 5v). The range of these parameters is 0
to 99999.99. The Low Value must be less than High
Value.
Note: These entries are not valid if a RTD temperature probe is
selected as the Transducer Type for that input
Critical: Low value must be less than high value
(unless density input and units are API
Fatal: Entry is out of specified range.
Help: Enter value @4mA/1V.
Configuration 609, 619, 629, 639,
649, 659 - Analog I/O High Value
These program codes are used to define the lower
and upper ranges of the analog input, expressed as
engineering values corresponding to the defined
Section VI Program Codes
function of the input. The Low entry represents the
engineering value at 4mA (or 1v for a V-In module)
and the High entry represents the engineering value
at 20mA (or 5v). The range of these parameters is
0 to 9999.99. The High Value must be greater than
the Low Value.
Note: These entries are not valid if a RTD temperature probe is
selected as the Transducer Type for that input
Critical: Low value must be less than high value
(unless density input and units are API
Fatal: Entry is out of specified range.
Help: Enter value @20mA/5V.
Configuration 610, 620 - RTD Offset
This parameter is used to correct the reading of the
RTD input by a fixed amount. The range of this
program code is 9.9 to 9.9.
Help: Offset zeroes out RTD probe error.
Note: This offset is applied to inputs configured as an RTD only.
No-entry if corresponding Analog Type is not RTD.
System 100 General Purpose
Directory
Date and Time
Units and Identifiers
Timeouts
Display and Control
Security
101 Date
102 Time
111 Flow Rate Time
112 Flow Rate Descriptor
121 Dynamic Display Timeout
122 Auto Reset Timer
131 Decimal/Comma Select
132 Start Key Disable
133 Default/Translated Literals
134 Transaction ID
135 Transaction ID Message
136 Number of Batches/Transaction
151 Level 1 Access Code
89
152 Level 2 Access Code
153 Level 3 Access Code
154 Level 4 Access Code
155 Level 5 Access Code
156 Security Input 1 Access Level
157 Security Input 2 Access Level
Date and Time
System 101 - Date
This entry allows the operator to set the date on the
AccuLoad. To change the date, enter the correct
month next to the cursor and press ENTER. Move to
the next selection, enter the correct day next to the
cursor, and press ENTER. Move to the next
selection, enter the correct year next to the cursor,
and press ENTER. When the month, day, and year
have been entered, move to "Accept New Date" and
press ENTER. The new date has been accepted.
Month
Day
Year
Accept New Date
System 102 Time
A correction or change to the time can be made
through this entry. Set the time by moving the cursor
to the hour, pressing ENTER, entering the correct
hour, and pressing ENTER again. This step is
repeated for the minutes setting. Once the hour and
minute have been set, the time type is selected.
Pressing ENTER will display the following:
TimeType
>
MIL
Mil
AM
PM
Select the proper designation by moving the arrow
and press ENTER. To accept the new time, move
the cursor to Accept New Time and press "ENTER."
The time has been accepted and the screen reverts
MN06118L Issue/Rev. 0.5 (4/02)
back to the Date and Time display. Selections are as
follows:
Hours
Min
Time Type
Accept New Time
Fatal: Entry out of range
System 111 - Flow Rate Time
This parameter is used to define the time units used
to compute the flow rate. Selections are as follows:
(0) Per minute
(1) Per hour
Fatal: Entry out of range.
Help: Enter the time base for flow rate calculation
and display.
Section VI Program Codes
System 112 - Flow Rate Descriptor
System 131 - Decimal/Comma Select
This
parameter
allows
a
three-character
alphanumeric message to serve as the flow rate unit
identifier (for example, GPM, LPM, BPH). The
available characters are as follows:
This parameter specifies whether a decimal or a
comma is to be used to separate the whole and
fractional parts of numeric data. The comma is
typically used in European markets. The selected
delimiter is used in the program mode and on run
screens and dynamic displays local to AccuLoad III,
in host communications, and on delivery reports.
Selections are as follows:
ABCDEFGHIJKLMNOPQRSUVWXYZ#*
abcdefghijklmnopqrstuvwxyz&
@
0 1 2 3 4 5 6 7 8 9 < > ( ) ? ! . , - / + = _ END
Help: Enter a three-character entry to be displayed
while flow rate is displayed.
System 121 - Dynamic Display
Timeout
This program code defines the amount of time, in
seconds, that dynamic displays will remain displayed
before AccuLoad III returns to the run or ready
screen. A zero entry for this program code will cause
the dynamic display to remain indefinitely, until the
operator presses CLEAR. The range of this
parameter is 0 99 seconds.
Help: Enter time in seconds before dynamic display
timeout. Zero allows displays to remain indefinitely.
System 122 - Auto Reset Timer
This program code defines the amount of time, in
minutes, before AccuLoad III will return to the ready
screen in the absence of key input by the operator.
The auto reset feature will remove AccuLoad III from
the program mode or end transactions in progress
when this parameter is set to a non-zero value. The
clock starts after each keystroke (unless flowing). If
another keystroke is not made in the time set in this
code, the unit will revert to the Ready display. Also, if
the driver's load has been completed and he hasn't
ended the transaction, the AccuLoad will return to
the Ready mode after the time has expired. The
range of this parameter is 0 99 minutes. An entry
of 0 disables this feature.
Help: Enter time in minutes with no operator activity
before AccuLoad resets to Ready Mode. Zero
disables this feature.
91
(0) Decimal
(1) Comma
Help: Select delimiter between whole and fractional
numbers.
System 132 - Start Key Disable
This
one-digit
program
code
allows
the
enabling/disabling of the local "START" key and
remote start input. When the local "START" key is
disabled, it will not function at the AccuLoad III. The
only method for starting a batch will be through the
communication remote start command. Selections
are as follows:
(0) No (Enabled)
(1) Yes (Disabled)
Note: If the local "START" key is disabled at the AccuLoad III and
communications is in polling only, the AccuLoad III will not be able
to start a transaction until the parameters are properly set.
Note: The "START" Key Enabled selection will not prohibit starting
the batch via communications.
Help: If "START" key is disabled, and no comm
control is defined, transactions cannot be started.
System 133 - Default/Translated
Literals
This parameter allows the user to initialize all the
displays used in the AccuLoad III to either the default
(factory literals) or the translated literals. Translated
literals are only available if the translation has been
completed in the AccuMate and downloaded to the
AccuLoad. Selections are as follows:
(0) Default literals
MN06118L Issue/Rev. 0.5 (4/02)
(1) Translated literals
Help: Select factory-programmed default literals or
literals translated via AccuMate.
System 134 - Transaction ID
This nine-digit security number provides an
additional security level for operation of the
AccuLoad III. If this code is programmed with any
number other than 000000000, the driver or operator
is required to enter this security ID before a
transaction can be started. A 0 entry disables this
feature.
Help: Enter a nine-digit translation ID. Zero disables
this feature.
System 135 - Transaction ID Message
This code allows a 28-character alphanumeric entry
to prompt during the preset operations to enter a
security ID. This message should not be
programmed as blanks. If programmed as blanks,
when the operator presses "SET" the display will go
blank. The data entry allows the following characters
to be selected as part of the prompt:
ABCDEFGHIJKLMNOPQRSTUVW
XYZ#*
abcdefghijklmnopqrstuvwxyz&
@
0 1 2 3 4 5 6 7 8 9 < > ( ) ? ! . , - \ / + = END
No-entry if Transaction ID is zero
Help: Enter message to prompt for translation ID at
start of transaction.
System 136 - Number of
Batches/Transaction
This program code provides the operator with the
capability of setting the loading position up for the
number of batches allowed per transaction. The
range of this entry is from 1 to 10.
Fatal: Entry out of specified range.
Help: Enter the number of batches per transaction.
Warning: Changing this value will clear transaction
storage. Re-entering the same number will not clear
local storage because the size of the transaction
hasn't changed. Do not use System Code 136 to
purge transactions; the Erase Transaction Log has
been provided for this purpose. For more information
on Erase Transaction Log, refer to "Section V
Diagnostics" in this manual.
System 137 Powerfail Alarm
This program code provides the operator with the
capability of either enabling or disabling the
powerfail alarm. The powerfail alarm is a diagnostic
alarm that is not clearable through communications.
The factory default for this parameter is "enable."
Selections are as follows:
(0) Enable
(1) Disable
System 151, 152, 153, 154, 155 Access Code
These four-digit numbers permit entry into the
AccuLoad III's Program or Weights and Measures
program codes. The access codes must be entered
through the AccuLoad III keypad after the Program
Mode security contact has been closed (if a security
contact has been programmed and wired to a
switch). If this contact has not been closed, the
AccuLoad III will not allow entry into the Program
Mode. Once the security is set up for the parameters
in the unit the operator must enter the program mode
at the level assigned to the parameter(s) that are to
be changed. The range of these entries is from 0 to
9999.
Critical: Duplicate access codes are not permitted
Help: Enter Access Code for this security level.
Note: These access codes must be programmed in order,
beginning with security level 1. Intermediate levels cannot be
skipped.
Note: The operator must enter Program Mode at the highest
programmed security level to obtain access to these access
codes.
Section VI Program Codes
System 156, 157 - Security Input
Access Level
These entries are used to assign the relay to the
level of access code. For instance, if a parameter is
assigned level 1 access code and the security input
is assigned level 2 that parameter can be changed
without the switch being closed. If the parameter is
assigned level 2 access code then both the access
code and the switch closed would be needed to
change the parameter. The range of these entries is
from 0 to 5.
Critical: Access level not assigned
No-entry if digital input not programmed as security
input
Help: Select access level (1 5) to be associated
with this security input.
System 300 Volume Accuracy
Directory
301 Volume Units
302 Mass Units
303 Volume Descriptor
304 Mass Descriptor
311 Maximum Preset
312 Minimum Preset
313 Auto Preset
314 Auto Preset Increment
315 Transaction Termination
316 Recipes per Transaction
321 Auto Prove Select
322 Proving Mode
331 Blank Downcounter
332 Preset Volume Type
333 Delivery Volume Type
334 Display Resolution
System 301 - Volume Units
This parameter selects the volume units used to
measure product delivery. The factory default is
"Gallons." Selections are as follows:
93
(0) Gallons
(1) Barrels
(2) Dekaliters
(3) Liters
(4) Cubic Meters
Help: Select volume units. These are used to select
proper conversion factors for calculations
System 302 - Mass Units
This parameter defines the mass units used for
product measurement. The factory default is
"Pounds." Selections are as follows:
(0) Pounds
(1) Kilograms
(2) US Tons
(3) Metric Tons
(4) Long Tons
Help: Select mass units. These are used to select
proper conversion factors for calculations
System 303 Volume Descriptor
This code allows a four-character entry message to
serve as the display unit identifier of the volumetric
measurement units that will be displayed on the
display and the reports. The data entry allows the
following characters to be selected as part of the
display unit prompt:
ABCDEFGHIJKLMNOPQRSTUV
WXYZ#*
abcdefghijklmnopqrstuvwxyz&
@
0 1 2 3 4 5 6 7 8 9 < > ( ) ? ! . , - / + = END
Help: Enter an alphanumeric volume descriptor to
be used on displays and reports
System 304 Mass Descriptor
This code allows a four-character entry message to
serve as the display unit identifier for the mass of the
product to be used on displays and reports. The data
MN06118L Issue/Rev. 0.5 (4/02)
entry allows the following characters to be selected
as part of the display unit prompt:
ABCDEFGHIJKLMNOPQRSTUV
WXYZ#*
abcdefghijklmnopqrstuvwxyz&
@
0 1 2 3 4 5 6 7 8 9 < > ( ) ? ! . , - / + = END
Help: Enter an alphanumeric mass descriptor to be
used on displays and reports.
System 311 Maximum Preset
This six-digit entry establishes the largest volume
that can be preset. An error message appears:
"Preset batch volume exceeds the maximum
permitted. PRESS 'CLEAR' TO CONTINUE" will be
displayed on any attempt to start a batch with more
than the maximum preset value. The range of this
entry is 0 to 999999 units. The factory default is "0".
Note: "0" disables the maximum preset volume.
Help: Enter maximum preset volume allowed for any
batch.
System 312 Minimum Preset
This six-digit entry will allow for the setting of the
minimum preset amount. An error message, "Fatal:
Preset batch volume is below the minimum required"
is displayed. "PRESS "CLEAR" TO CONTINUE" will
be displayed on any attempt to start a batch with
less than the minimum preset value. The range of
this entry is 0 to 999999 units. The factory default is
"0".
Note: "0" disables the minimum preset volume
Help: Enter minimum preset volume allowed for any
batch
Section VI Program Codes
System 313 Auto Preset
This six-digit program code allows the operator to
select the Auto Preset mode of operation for the
AccuLoad III. An entry of 0 disables this function and
the preset amount used in the Run Mode will have to
be either manually entered by the driver or entered
through communications. An entry other than 0 (i.e.,
1000) will result in the preset amount programmed in
this code being used in the Run Mode. The
AccuLoad III would preset automatically 1,000 each
time the "SET" button is pressed. The factory default
is "0".
System 315 - Transaction
Termination
This program code defines the primary method used
to terminate a transaction. Communications can
always be used to terminate a transaction if
AccuLoad III is programmed for Poll & Authorize or
Remote Control operations. The factory default is
"PRINT key." Selections are as follows:
Note: "0" disables the Auto Preset.
Help: Select auto preset: a starting point for batch
preset amounts
System 314 - Auto Preset Increment
This five-digit program code allows the operator to
program a volume to be used as an incremental
increase for the Auto Preset. The range of this entry
is from 0 to 99999. The factory default is "0".
Example: Auto Preset is programmed for 1,000
units and the Auto Preset increment is programmed
for 100 units. When the driver/operator approaches
the AccuLoad III and goes through the necessary
steps to get to the Preset Display.
Where:
Premium
P
1000
Gal
=
=
=
=
Programmed Product Name
Preset
Volume programmed for Auto Preset
Units of measurement
Driver presses "SET". Volume will increment 100
units to 1100.
Driver presses "SET" again the volume will
increment another 100 units to 1200.
Driver continues pressing "SET" until the volume of
product required is reached (i.e., 2000 gal).
Help: Enter amount to increment the auto preset
volume with each press of the "SET" key.
95
(0) Print key - For transactions that may be
remotely authorized and terminated by the
"PRINT" key: The ticket printer tray switch is
ignored. The "PRINT" key is used to end the
transaction.
(1) Communications control only - For
transactions that will be authorized and
terminated
remotely
(i.e.,
through
communications): The "PRINT" key is disabled
and the ticket printer tray switch is ignored.
(2) Transaction reset input - For transactions
that will be authorized and terminated by a
master reset input: The "PRINT" key is disabled.
The ticket printer tray input is used to authorize
and end the transaction.
(3) Printer Tray Switch Input - For transactions
that will be authorized and terminated by a
switch input from a load printer: The "PRINT"
key is disabled. The switch input, when active,
authorizes the AccuLoad to load. When the input
deactivates, the transaction is ended and the
AccuLoad will not allow loading to continue or
start again until the input is activated again (a
ticket is put in the printer).
Critical: No comm port selected for communications
control
Critical: No transaction reset input configured
Help: Select how a transaction will be terminated.
System 316 Recipes per
Transaction
This program code provides the operator with the
capability of setting the loading position up to allow
only single recipe transactions or to allow multiple
MN06118L Issue/Rev. 0.5 (4/02)
recipes per transaction. If programmed for a single
recipe, the AccuLoad III will only prompt the driver
for a recipe at the beginning of the transaction. The
driver can load multiple batches of the recipe but
only that recipe for the transaction. If programmed
for multiple recipes, the driver will be prompted for
the recipe at the beginning of each batch. The
factory default is "Multiple." Selections are as
follows:
(0) Single Recipe per Transaction
(1) Multiple Recipes per Transaction
Help: Select single or multiple recipes per
transaction
System 321 - Auto Prove Select
This parameter is used to enable or disable the
Automated Proving Mode. The default for this
program code will be disabled. Select one of the
three security options to enable the automated prove
and associated security. Once selected and the
security activated, the beginning of the next
transaction will launch the auto prove. Once the
prove is completed and the meter factor calculated
the operator has the choice of downloading the
calculated meter factor into the software or ignoring
it. The factory default is "Disabled." Selections are
as follows:
(0) Disabled
(1) Security input not required
(2) Security 1 input required
(3) Security 2 input required
Critical: Security input not configured
Help: Select security level required for auto proving
or disable auto proving.
Note: Auto proving is described in Section II Operations.
System 322 - Proving Counters
This parameter defines whether AccuLoad III is
operating in a proving mode. The factory default is
"Not Proving." Selections are as follows:
(0) Not proving - This is the normal operating
mode where a preset volume is set and the flow
of product is started and stopped.
(1) Proving - In this mode the AccuLoad III
operates as in the Run Mode, except the preset
and delivery counters both count up and go to
tenths resolution. Volume preset and delivery
units are in the volume units selected in the
display units select code.
Help: Set downcounter to upcounter when proving.
System 331 Run Display
This code allows the operator to program the Run
Display options to be used in his application. The
factory default is "Default Display." Selections are as
follows:
(0) Default Display
(1) Blank Downcounter
(2) US Weights and Measures Display
Note: This option will have no effect while the AccuLoad III is in
the proving mode.
Help: Select the desired information to be shown on
the delivery screen.
Section VI Program Codes
System 332 Preset Volume Type
This program code selects the volume type used to
enter the preset value. This volume type is also used
for the downcounter display. The factory default is
"IV." Selections are as follows:
System 400 Temperature/Density
Directory
401 Temperature Units
402 Reference Temperature
411 Density Units
(0) Indicated volume (IV)
(1) Gross volume (GV)
(2) GST volume (GST)
(3) GSV volume (GSV)
(4) Mass
Critical: Selected units not available
Help: Preset volume type
System 333 Delivery Volume Type
This code establishes how the delivery volume
display will appear during operation. Five possible
selections are available that are dependent on the
needs of the operation. The factory default is "IV."
Selections are as follows:
(0) Indicated volume (IV)
(1) Gross volume (GV)
(2) GST volume (GST)
(3) GSV volume (GSV)
(4) Mass
Help: Delivery display volume type
System 334 Display Resolution
This program codes selects the resolution that will
be used by AccuLoad III for the delivery upcounter
and downcounter during normal operations. The
factory default is "Whole." Selections are as follows:
(0) Whole units
(1) Tenths
(2) Hundredths
Help: Select display resolution in whole, tenths, or
hundredths
97
MN06118L Issue/Rev. 0.5 (4/02)
System 401 - Temperature Units
This program code selects the temperature scale
used by AccuLoad III. The factory default is "NA".
Selections are as follows:
(0) N/A
(1) Fahrenheit
(2) Celsius
Note: A zero entry, signifying No Temperature Selected,
will cause all temperature-related program codes to be
removed from the menus in Program Mode.
Help: Select temperature units
System 402 - Reference Temperature
The actual uncompensated volume throughput is
temperature compensated to its equivalent volume
at this four-digit reference temperature in tenth
degrees. The most common reference temperatures
are 60.0 Deg. F and 15.0 Deg. C. The range of this
entry is 0.0 to 999.9.
No-entry if Temperature Units = Not Used
Help: Used as base for correction of liquid volume
System 411 - Density Units
This selection is used to establish which density
scale will be used if there is a densitometer installed.
It is used to convert volume to mass. Selections are
as follows:
(0) Not Used
(1) API
(2) Lb/Ft3 (Pound/Cubic Feet)
(3) Kg/M3 (Kilograms/Cubic Feet)
Note: When using temperature compensation, a value (API,
Lb/Ft3, or Kg/M3) must be entered in this parameter.
Help: Select density units. These are used for a live
density input and for mass calculation
System 500 Pressure Directory
501 Pressure Units
System 501 - Pressure Units
This parameter defines the pressure units used by
AccuLoad III. The factory default is "NA". Selections
are as follows:
(0) N/A
(1) PSI
(2) Bar
(3) Kg/cm2 (Kilograms/square centimeter)
(4) Kpa (kilopascals)
Note: If "not used" is selected, signifying no pressure
transducer installed, any associated parameters will be
removed from the menus in Program Mode.
Help: Select units of pressure
System 600 Alarm Configuration
Directory
601 - Run/Ready Clearable Alarms
602 - Additive Communications Alarm
603 - Back-pressure Alarm
604 - Communications Alarm
605 - Density Transducer Alarm
606 - Additive Feedback Alarm
607 - High Density Alarm
608 - High Flow Alarm
609 - High Pressure Alarm
610 - High Temperature Alarm
611 - Low Additive Alarm
612 - Low Density Alarm
613 - Low Flow Alarm
614 - Low Pressure Alarm
615 - Low Temperature Alarm
616 - Too Many Additive Pulses Alarm
617 - No Additive Pulses Alarm
618 - Overrun Alarm
619 - Transmitter Integrity Alarm
620 - Pressure Transducer Alarm
621 - Pulse Security Alarm
622 - Additive Frequency Alarm
623 - Shared Printer Alarm
624 - Temperature Transducer Alarm
625 - Valve Fault Alarm
626 - Additive Unauthorize Failed Alarm
627 - Zero Flow Alarm
628 - Additive Injector Error
629 - Over-Rev Metered Injector
630 - Additive Clean Line
631 - Injector Command Rejected
632 - Ticket Alarm
633 - CIVACON Monitor Communications Alarm
634 - Clean Line Alarm
Section VI Program Codes
635 - Block Valve Alarm
636 - Blend High Alarm
637 - Blend Low Alarm
638 - Product Overrun
639 - Product Zero Flow
640 - Unauthorized Flow
641 - PTB Printer Failure Alarm
642 - Turbine Meter Alarm
671 - User Alarm 1
672 - User Alarm 2
673 - User Alarm 3
674 - User Alarm 4
675 - User Alarm 5
676 User Alarm 6
677 User Alarm 7
678 User Alarm 8
679 User Alarm 9
680 User Alarm 10
686 User Alarm 1 Message
687 User Alarm 2 Message
688 User Alarm 3 Message
689 User Alarm 4 Message
690 User Alarm 5 Message
691 User Alarm 6 Message
692 User Alarm 7 Message
693 User Alarm 8 Message
694 User Alarm 9 Message
695 User Alarm 10 Message
These parameters allow the actions of each alarm to
be configured. Multiple options selected from the
following list may be configured for each alarm.
Selections are as follows:
(1) Allow run/ready clearing
(2) Energize alarm output 1
(4) Energize alarm output 2
Note: Through Communications, add to get combination of
desired options (i.e., 7 would set up all three options.)
602 AC: Additive Communications
Failure Alarm - Indicates a failure on the
master/slave communications line between the
AccuLoad III and the Additive Injector Subsystem
603 BP: Back-pressure Alarm - Indicates
insufficient pressure in the system to maintain the
minimum back-pressure flow rate entry.
604
CM:
Communications
Alarm -
Indicates a failure on one of the communication
channels.
605 DR: Density Transducer Alarm Indicates a failure or an out-of-range condition.
606 FA: Additive Feedback Error
Alarm - Indicates that the additive feedback has
exceeded the programmed number of errors.
System 601 - Run/Ready Alarm
Clearing
This parameter defines the number of alarms that
can be cleared in the Run and Ready modes without
the requirement of entering a passcode. Alarms
must be configured to be clearable in the Run/Ready
mode. When this number of alarms has been
cleared, subsequent alarms require a passcode
entry to clear, even though they are programmed for
Run/Ready mode clearing. The range of this entry is
0 to 20.
System 602 to 680to 640 and 671 to
680 - Alarm Configuration
99
607 HD: High Density Alarm - Indicates
the density transducer is out of range of the high
alarm setting.
608 HF: High Flow Alarm - Indicates that
the flow rate has exceeded the flow limit set in the
excess high flow program code for more than 4
seconds.
609 HP: High Pressure Alarm - Indicates
that the pressure transducer is out of range of the
high pressure setting.
610 HT: High Temperature Alarm Indicates that the temperature probe or transducer is
out of range of the high temperature setting.
MN06118L Issue/Rev. 0.5 (4/02)
611 KA: Low Additive Alarm - Indicates
that not enough additive was injected during one
cycle or an average of several cycles.
612 LD: Low Density Alarm - Indicates
that the density transducer is out of range of the low
alarm setting.
613 LF: Low Flow Alarm - Indicates that the
flow rate was at or below the minimum flow rate
established by the minimum flow limit program code
for longer than eight seconds.
614 LP: Low Pressure Alarm - Indicates
that the pressure transducer is out of range of the
low alarm setting.
615 LT: Low Temperature Alarm Indicates that the temperature probe or transducer is
out of range of the low alarm setting.
616 MA: Excess Additive Pulses
Alarm - Indicates that too many additive flow meter
pulses were detected.
617 NA: No Additive Pulses Alarm Indicates that the additive flow meter's pulses were
not detected
618 OA: Overrun Alarm - Indicates that the
622 RA: Additive Frequency Alarm The additive volume is too high for the rate selected;
a second dose of additive is being requested before
delivery of the first dose completes.
623 SP: Shared Printer Alarm - Indicates
an output was attempted to the shared printer, but
was unsuccessful because the shared printer
remained busy longer than the programmed shared
printer out alarm timer.
624 TP: Temperature Transducer
Alarm - Indicates a temperature transducer failure
or an out-of-range condition (less than 2 mA/0.5
vdc/52.11 Ohms or greater than 23 mA/5.5
vdc/220.88 Ohms).
625 VF: Valve Fault Alarm - Indicates that
the valve did not close within the time allowed by the
valve fault timeout program code after receiving the
signal to close.
626 UA: Additive Unauthorize Failed
Alarm - The unauthorize command failed at the
end of the batch for an additive. Authorization may
have to be removed manually (by power cycling the
additive system) to prevent unwanted additive in
subsequent batches/transactions.
volume delivered exceeded the preset amount by at
least the number of units programmed in the overrun
alarm code.
627 ZF: Zero Flow Alarm - Indicates that
619 XA: Transmitter Integrity Alarm -
628 GA: Additive Injector Error Alarm
Indicates a collision on the incoming pulse stream.
620 PR: Pressure Transducer Alarm
Indicates a pressure transducer failure or an out-ofrange (less than 2 mA/0.5 Vdc or greater than 23
mA/5.5 Vdc) condition.
621 PS: Pulse Security Alarm - Indicates
an out of sequence error in the A - B pulse stream.
If this alarm occurs, the batch must be reset using
one of the methods in System 322. Pressing CLEAR
as a run clearable alarm will open the valve, but as
soon as pulses start, the PS alarm will reoccur and
again shut down the valve.
the Zero Flow Timer has expired and the AccuLoad
has not detected any flow in the system.
Indicates that there is an additive injector error.
629 OR: OverRev Metered Injector
Alarm Indicates that the meter on the metered
injector has exceeded
frequency.
its
specified
maximum
630 CA: Additive Clean Line Alarm
Indicates that an insufficient amount of additive-free
product was delivered at the end of the load. (This is
usually due to ending the batch prematurely.)
631 CR: Injector Command Rejected
Alarm Indicates that the command from the
AccuLoad to the injector was rejected.
Section VI Program Codes
632 TK: Ticket Alarm Indicates a removal of the
ticket from the Load Printer was tried during the
batch. When the alarm is received, press PRINT to
clear the transaction.
a correct response from a PTB printer after
sending data to be printed. The AccuLoad III
will continue to re-send the data to the printer
until the communications port timeout setting
expires, at which time the PTB printer alarm is
set.
633 CV: CIVACON Communication Failure
Alarm Indicates a failure on the communications
642 TM: Turbine Meter Alarm Indicates that
line between the AccuLoad III and the C IVACON
Grounding/Overfill System.
634 CL: Clean Line Alarm Indicates that the
clean line volume delivered has under-run the clean
line volume programmed by at least the amount of
the clean line alarm limit.
635 BV: Block Valve Alarm Indicates that the
block valve did not open or close as signaled by the
AccuLoad III.
636 BH: Blend High Alarm Indicates that the
blend tolerance has been exceeded and the product
being delivered is over the volume required for the
batch.
637 BL: Blend Low Alarm Indicates that the
blend tolerance has not been met and the product
being delivered is under the volume required for the
batch.
638 OA: Product Overrun Alarm Indicates
that the product delivered exceeds the preset
amount by at least the number of units programmed
in the overrun alarm code.
639 ZF: Product Zero Flow Alarm Indicates
that the Zero Flow Timer has expired and the
AccuLoad has not detected any flow of this product.
640 UF: Unauthorized Flow Alarm Indicates
that unauthorized flow was detected for the product.
Unauthorized flow is when the AccuLoad III receives
pulses from a product or products that have not been
signaled to flow.
641 PP: PTB Printer Alarm The PTB printer
alarm is set when the AccuLoad III fails to get
101
the turbine meter signature has changed, and the
meter should be proved. This alarm is displayed
when the AccuLoad detects a statistically significant
variation in 4 out of 10 updates.
System 686 to 695 - User Alarm
Messages
This program code permits the entry of an 18character text entry identifying an alarm condition.
User alarms can be set through communications or
Boolean/algebraic equations.
For more information about alarm messages and
their equivalent in Blend-Pak injectors, AccuTrollers,
Mini-Pak injectors, and metered injectors, refer to
Appendix III Alarms.
System 700 Communications
Directory
701 Load Arm 1 Address
702 Load Arm 2 Address
703 Comm Port 1 Function
704 Comm Port 1 Baud Rate
705 Comm Port 1 Data/Parity
706 Comm Port 1 Control
707 Comm Port 1 Timeout
708 Comm Port 2 Function
709 Comm Port 2 Baud Rate
710 Comm Port 2 Data/Parity
711 Comm Port 2 Control
712 Comm Port 2 Timeout
713 Comm Port 3 Function
714 Comm Port 3 Baud Rate
715 Comm Port 3 Data/Parity
716 Comm Port 3 Control
717 Comm Port 3 Timeout
718 Comm Port 4 Function
719 Comm Port 4 Baud Rate
MN06118L Issue/Rev. 0.5 (4/02)
720 Comm Port 4 Data/Parity
721 Comm Port 4 Control
722 Comm Port 4 Timeout
731 Comm Link Programming
732 Modbus Endian Protocol
741 Prompts Used
742 Prompt Timeout
743 Prompt 1 Message
744 Prompt 1 Input Type
745 Prompt 1 Length
746 Prompt 2 Message
747 Prompt 2 Input Type
748 Prompt 2 Length
749 Prompt 3 Message
750 Prompt 3 Input Type
751 Prompt 3 Length
752 Prompt 4 Message
753 Prompt 4 Input Type
754 Prompt 4 Length
755 Prompt 5 Message
756 Prompt 5 Input Type
757 Prompt 5 Length
System 701 Load Arm 1 Address
This parameter defines the communications address
associated with this Load Arm. For multiple
AccuLoads on a shared communications line, all
addresses must be unique. The range of this entry is
01 to 99.
Critical: Address must not be zero.
Help: Enter a unique communication address for this
load arm.
System 702 Load Arm 2 Address
This parameter defines the communications address
associated with this Load Arm. For multiple
AccuLoads on a shared communications line, all
addresses must be unique. The range of this entry is
01 to 99.
Critical: Address must not be zero.
Help: Enter a unique communication address for this
load arm.
System 703, 708, 713, 718 - Comm
Port Function
This program code defines the function of the
communications port. The factory default is
"Minicomp Host" on comm port 1. Selections are as
follows:
(0) Not used - This communications port is not
selected for use.
(1) Terminal host communications - This communications port communicates with a terminal
type device using a simplified communications
protocol.
(2) Minicomputer host communications - This
communications port communicates with a
minicomputer type device using a sophisticated
and secure communications protocol.
(3) Modbus host communications
(4) Printer - Permits the AccuLoad III through
this communication port to automatically output
an end of a transaction report to a printer
connected to the AccuLoad III.
(5) Shared printer - Same as number (4) above
except the output report will go to a shared
printer connected to one or more AccuLoad IIIs.
(6) Smart injector control - Permits the
AccuLoad III through this communication port to
communicate with and control up to twelve smart
additive injector systems.
(7) CIVACON Monitor Permits the AccuLoad III
through this communication port to communicate
with the CIVACON Grounding and Overfill System.
Certain restrictions apply:
Shared printing is only possible on port 1.
Port 4 may only be a printer or smart injector
control.
Only one port can be configured for smart
injector control
A maximum of two ports may be configured for
printer/shared printer
A maximum of two ports may be configured for
host communications functions.
Only one port can be used for CIVACON interface.
The proper communications port control must be
configured for the selected function.
Section VI Program Codes
See System 706, 711, 716, 721 Control for port
control options.
Critical: Function conflicts with Port Control.
Critical: Permissive input must be configured with
CIVACON.
Help: KDC TB1:(232:1(TX), 2(RX), 3(RTS), 4(CTS),
5(COM)), (485:6(TX+), 7(TX-), 8(RX+), 9(RX-),
10(COM)
System 704, 709, 714, 719 - Baud
Rate
This parameter sets the speed of the associated
communications port. The factory default is "38400."
Selections are as follows:
(0) 1200 baud
(1) 2400 baud
(2) 4800 baud
(3) 9600 baud
(4) 19200 baud
(5) 38400 baud
Help: Select the baud rate for this communications
port
System 706, 711, 716, 721 - Control
This program code defines the level of control the
associated communications port commands. Polling
Only, Poll and Authorize, and Remote Control are
valid with host communications options. XON/XOFF
is valid with printer options. Only one port can have
transaction control. The factory default is "Poll &
Program." Selections are as follows:
System 705, 710, 715, 720 Data/Parity
This parameter defines the number of data bits and
parity used by the associated communications port.
Unless indicated otherwise, one stop bit is used. The
factory default is "8/None." Selections are as follows:
(0) 7 bits No Parity
(1) 7 bits Odd Parity
(2) 7 bits Even Parity
(3) 8 bits No Parity
(4) 8 bits Odd Parity
(5) 8 bits Even Parity
(6) 8 bits No Parity, 2 Stop bits
Help: Select the data format: number of bits per
character and type of parity
103
(0) N/A No communications. AccuLoad III
operates as standalone preset.
(1) Polling Only No transaction control,
display control or programming allowed via this
port. Able to read program code values and run
data from the unit. Loading as above.
(2) Poll & Authorize Full programming/
prompting control. Transaction control type 1
requiring authorization from host. Allows use of
AccuLoad III communications commands such
as AU-Authorize Transaction and AP-Authorize
Transaction and Preset for host authorization.
Designed for terminals where the driver enters
desired preset volume after authorization.
(3) Remote Control Full programming and
prompting control. Transaction control type 2
(also requiring authorization from host) Allows
use of SB Set Batch to enter the preset
remotely and EB to end the batch remotely. This
is designed for pre-dispatch operations where
the driver has limited input during the load
process and the preset is host-controlled.
(4) Xon/Xof For printer ports only. Xon/Xoff
flow control.
(5) Poll & Program For use with
demonstration/AccuMate ports. Allows full
program access but does not affect transaction
control (acts like a standalone unit).
(6) PTB-FX Security level designed to support
PTB Weights and Measures Agency-approved
printer interface.
(7) PTB-LQ Security level designed to support
PTB Weights and Measures Agency-approved
printer interface.
MN06118L Issue/Rev. 0.5 (4/02)
Critical: Comm port not configured for host
communications
Critical: Comm port not configured for printer
Critical: Only one comm port may be configured for
control
No-entry if corresponding function is not used
Help: Select the degree of control for this
communications port
System 707, 712, 717, 722 - Timeout
These three-digit codes allow the operator to specify
the amount of time, in seconds, before aborting a
communications transfer that has halted. The
communications alarm will then be set. This entry is
also used to abort a printout if waiting for a shared
printer on an XON from a printer. If the timer expires
waiting for a shared printer, the shared printer alarm
will be set. The range of this entry is from 0 to 999
seconds.
Help: Enter elapsed time in seconds of comm fail
before signaling an alarm
System 731 - Comm Link
Programming
This program code defines which program code
parameters
can
be
modified
through
communications by the access level assigned to
those parameters. The factory default is "Level 1
Access." Selections are as follows:
(0) Alarm Clearing Only - This selection allows
only the alarms to be reset (cleared) through
communications.
(1) Level 1 Access Parameters This selection
allows only the parameters that are assigned
level 1 access to be changed through
communications.
(2) Level 2 Access Parameters This selection
allows only the parameters that are assigned
levels 1 and 2 access to be changed through
communications.
(3) Level 3 Access Parameters This selection
allows only the parameters that are assigned
levels 1 through 3 access to be changed through
communications.
(4) Level 4 Access Parameters This selection
allows only the parameters that are assigned
levels 1 through 4 access to be changed through
communications.
(5) Level 5 Access Parameters This selection
allows all parameters to be changed through
communications.
Help: Select program mode groups modifiable via
communications
System 732 - Modbus Endian
Protocol
This program code defines the byte order for floating
point values returned by Modbus communications.
AccuLoad III supports three variations of the Modbus
protocol. The factory default is "Big." Selections are
as follows:
(0) Big endian bytes are ordered most
significant first
(1) Little 8 endian bytes are ordered least
significant first
(2) Little 16 endian words are ordered least
significant first
No-entry if no comm port set up for Modbus
Help: Select modbus data format (affects floating
point numbers)
System 741 - Prompts Used
This program code defines the number of local
prompts configured at AccuLoad III. These prompts
are presented to the operator prior to the preset
prompt. The data entered by the operator is stored
by AccuLoad III and can be printed on a Bill of
Lading and retrieved through communications. The
range of this program code is 0 to 5.
Help: Zero entry disables this feature
System 742 - Prompt Timeout
This two-digit code defines the amount of time, in
seconds, that a local prompt will remain displayed at
AccuLoad III before the prompting sequence is
aborted and AccuLoad III returns to the ready
screen. The range of this parameter is 0 to 99
Section VI Program Codes
seconds. If set to zero, AccuLoad III will wait
indefinitely for data entry in response to a prompt.
The factory default is "0".
Help: Enter time, in seconds, for display of prompt
messages
System 743, 746, 749, 752, 755 Prompt Message
This program code defines the 28-character text
entry displayed to the operator as one of the five
local prompts. It is important to not leave this
message as all blanks, as a blank screen will be
presented to the operator if this prompt is activated.
Help: Enter prompt message to be displayed at start
of transaction
System 744, 747, 750, 753, 756 Prompt Input Type
This parameter defines whether numeric data
entered in response to a local prompt will echo to the
screen or display Xs in place of digits as a security
feature. (Revision 4 and above firmware allows a 20character alphanumeric response.) The factory
default is "Numeric." Selections are as follows:
(0) Numeric
(1) Hidden
(2) Alphanumeric (Revision 4 and above firmware only)
Help: Select whether response to prompt should be
displayed or hidden
System 745, 748, 751, 754, 757 Prompt Length
This program code defines the maximum length of a
response to a local prompt. The range of this entry is
0 to 9 for numeric or hidden entries. Revision 4 and
above firmware allows a 20-character alphanumeric
response for visible entries.
Note: Codes 745, 748, 751, 754, and 757 are associated with
codes 743, 746, 749, 752, and 755 respectively.
No-entry if Prompts Used = 0
105
Help: Set maximum length for prompt response
System 800 Additive Directory
801 Additive Selection Method
802 Additive Pacing Units
803 Additive Stop Option
804 Additive Stop Volume
805 Additive 1 Type
806 Additive 1 Plumbing
807 Additive 1 Arm
808 Additive 2 Type
809 Additive 2 Arm
810 Additive 2 Plumbing
811 Additive 3 Type
812 Additive 3 Arm
813 Additive 3 Plumbing
814 Additive 4 Type
815 Additive 4 Arm
816 Additive 4 Plumbing
817 Additive 5 Type
818 Additive 5 Arm
819 Additive 5 Plumbing
820 Additive 6 Type
821 Additive 6 Arm
822 Additive 6 Plumbing
823 Additive 7 Type
824 Additive 7 Arm
825 Additive 7 Plumbing
826 Additive 8 Type
827 Additive 8 Arm
828 Additive 8 Plumbing
829 Additive 9 Type
830 Additive 9 Arm
831 Additive 9 Plumbing
832 Additive 10 Type
833 Additive 10 Arm
834 Additive 10 Plumbing
835 Additive 11 Type
836 Additive 11 Arm
837 Additive 11 Plumbing
838 Additive 12 Type
839 Additive 12 Arm
840 Additive 12 Plumbing
841 Smart Injector 1 Address
MN06118L Issue/Rev. 0.5 (4/02)
842 Smart Injector 2 Address
843 Smart Injector 3 Address
844 Smart Injector 4 Address
845 Smart Injector 5 Address
846 Smart Injector 6 Address
847 Smart Injector 7 Address
848 Smart Injector 8 Address
849 Smart Injector 9 Address
850 Smart Injector 10 Address
851 Smart Injector 11 Address
852 Smart Injector 12 Address
861 Metered Injector 1 K Factor
862 Metered Injector 1 Meter Factor
863 Injector 1 High Tolerance
864 Injector 1 Low Tolerance
865 Injector 1 Maximum Tolerance Error
866 Metered Injector 2 K Factor
867 Metered Injector 2 Meter Factor
868 Injector 2 High Tolerance
869 Injector 2 Low Tolerance
870 Injector 2 Maximum Tolerance Error
881 Additive Injection Unit Descriptor
882 Additive Totals Units Descriptor
883 Injection/Totalization Conversion Factor
884 Clean Line Additive
885 Piston Injector Feedback Errors
System 802 - Additive Pacing Units
This program code selects the volume type used to
pace the additive injectors. The factory default is
"GV." Selections are as follows:
Critical: Selected units not available
Help: Select the product volume type used in the
determination of injection points
System 803 - Additive Stop Option
This parameter defines when the additive injection
will stop for each batch and whether or not the rate
will be recalculated so that the total amount of
additive expected for the preset volume will be
delivered before the downcounter reaches the
volume in System 804 Additive Stop Volume. The
factory default is "Batch." Selections are as follows:
System 801 - Additive Selection
Method
This parameter defines how additives will be
selected on a batch basis. Additives will be as
defined in the recipe, or a subset of those additives
defined selected by the operator at the keypad prior
to entering the preset volume. The factory default is
"Auto." Selections are as follows:
(0) Automatic - For auto selection of the
injectors. All the injectors that are programmed
will automatically pulse when the unit is loading.
(1) Transaction Manual selection of the
injectors at the start of the transaction
(2) Batch Manual selection of the injectors at
the start of each batch
Help: Select how injectors are chosen,
automatically, at transaction start, or at batch start
(0) Indicated volume (IV)
(1) Gross volume (GV)
(2) GST volume (GST)
(3) GSV volume (GSV)
(4) Mass
(0) End of Batch Stop volume is ignored.
Additive is delivered until end of batch
(1) No recalculation Additive is delivered as
above but injection halts when only stop volume
remains
(2) Recalculation - Proper additive volume for
entire preset volume is "squeezed" so that the
correct additive amount for preset is delivered
when the stop volume is reached.
Help: Injections may stop at the end of a batch or at
the additive stop volume with or without recalculation
of the inject rate
System 804 - Additive Stop Volume
This three-digit entry allows the operator to select
the volume of product remaining to be delivered
when the additive injectors will be shut down. This
code is used only in conjunction with Injector Option
Section VI Program Codes
1 and 2 of parameter 803. The range of this code is
0 to 999 units of volume.
Help: Enter the volume left to be delivered before
injector shutdown (in preset volume type).
System 805, 808, 811, 814, 817, 820,
823, 826, 829, 832, 835, 838 Additive Types
These program codes define the type of additive
injector installed at that injector position. AccuLoad
III supports a mixed implementation of additive
injector types. Selections are as follows:
(0) N/A
(1) Piston
(2) Piston with Feedback
(3) Titan
(4) Blend-Pak
(5) MiniPak
(6) Smith Smart
(7) Metered Injector
(8) Add-Pak
Critical: Metered injector pulse input not configured
Critical: Injector I/O does not match type
assignment
Critical: No comm port configured for smart additive
control
Critical: No injector address assigned
Critical: Injectors 1 and 2 cannot be Add-Pak
Help: Select the type of injector for this additive.
Note: The Add-Pak option is only available on Rev. 3 and above
firmware.
107
MN06118L Issue/Rev. 0.5 (4/02)
System 806, 809, 812, 815, 818, 821,
824, 827, 830, 833, 836, 839 Additive Arm
These entries specify the arm with which the
associated additive injector is used. Selections are
as follows:
(0) Arm 1
(1) Arm 2
System 807, 810, 813, 816, 819, 822,
825, 828, 831, 834, 837, 840
Additive Plumbing
Additive Injector selections available dependent
upon code 020.
This multiple selection (bit mapped) entry allows the
operator to select which meter(s) the injector is
plumbed into in a ratio blending application.
Selections are as follows:
(0) Meter 1
(1) Meter 2
No Entry: No ratio blending
System 841 to 852 - Smart Injector
Address
This parameter is used with any smart injector type
and defines the communications address for the
associated injector. When more than one injector is
installed at AccuLoad III, injector addresses must be
unique. The range of this program code is 0 to 999.
Critical: If AICB Board #1 is present, then no
injector may have address 100 through 110.
Help: Enter the communications address for this
smart injector
No Entry: Corresponding injector type = Add-Pak
System 861, 866 - Metered Injector K
Factor
This seven-digit code defines the nominal number of
pulses from a meter for one unit of registration. The
value must be between 0.001 and 9999.999.
Critical: Metered injector pulse input not configured
Fatal: Entry must not be zero
No-entry if Pulse Input not configured for metered
injector
Help: Enter the K factor in pulses per unit volume for
the metered injector.
Section VI Program Codes
System 862, 867 - Metered Injector
Meter Factor
The range of this entry is 0 to 99.9. The factory
default is "0".
The meter factor for the additive meters that are
being controlled directly by the AccuLoad are
programmed in these parameters. If the additives
are being controlled through communications and
ancillary equipment, no value should be
programmed in these parameters. Additive meter
number one is programmed in code 853 and additive
meter number two is programmed in code 854. The
range of these entries is 0.0000 to 9.9999. Meter
factor equals the actual volume times the current
meter factor times the k factor, all divided by the
input pulses. The factory default is "0.0000".
Help: Enter the percent below the averaged amount
before an error is counted
Critical: Metered injector pulse input not configured
Critical: No-entry if Pulse Input not configured for
metered injector
Help: Enter the meter factor for the metered injector
System 863, 864, 865, 868, 869, 870
Injector Tolerances
863 Injector #1 High Tolerance
868 Injector #2 High Tolerance
These parameters allow a percentage entry in two
whole digits followed by one decimal place for the
amount the actual injected volume can surpass the
average volume required to meet the additive needs.
The range of this entry is 0 to 99.9. The factory
default is "0".
Help: Enter the percent above the averaged amount
before an error is counted
864 Injector #1 Low Tolerance
869 Injector #2 Low Tolerance
These parameters allow a percentage entry in two
whole digits followed by one decimal place for the
amount the actual injected volume can be under the
average volume required to meet the additive needs.
109
MN06118L Issue/Rev. 0.5 (4/02)
865 Injector #1 Maximum Tolerance Errors
870 Injector #2 Maximum Tolerance Errors
These parameters allow the operator to set up how
many times during the batch that the high and low
tolerance percentages can be exceeded before an
alarm is set. The range of this entry is from 0 to 99.
The factory default is "0".
Help: Enter the maximum number of tolerance
errors allowed before an alarm is set.
System 881 Additive Injection Units
Descriptor
This code allows a three-character entry message to
serve as the additive injection units identifier for the
injected products, such as cc or oz. The data entry
allows the following characters to be selected:
ABCDEFGHIJKLMNOPQRSTUV
WXYZ#*
abcdefghijklmnopqrstuvwxyz&
@
0 1 2 3 4 5 6 7 8 9 < > ( ) ? ! . , - / + = _ END
Help: Enter a description for additive injector units.
System 882 - Additive Totals Units
Descriptor
This program code is a 3-character text entry used
to define the units in which additive injector volumes
are totaled.
Help: Enter a descriptor for additive totals units.
System 883 - Injection/Totalization
Conversion Factor
This parameter is used to convert injection units to
totals units. This parameter is an exponential entry.
The AccuLoad III uses this formula for the
conversion:
Volume in Injector units / Conversion factor =
Volume in Totals Units
Example: If injection units are in cc., and injector
totals are to be displayed in liters, the value would be
1000. (1.00 e+03).
Help: Enter the number of injection units in each add
totals unit (e.g., number of cc's per gallon).
System 884 Clean Line Additive
This entry determines the tolerance for the additive
stop volume. If the batch is ended before the
programmed stop volume has been completely
delivered, this entry determines if an alarm will
occur. An alarm will occur at batch end if the volume
delivered since the last injection is short of the stop
volume by more than this entry. An entry of 0
disables the alarm.
Help: Set the tolerance allowed for underrun of
additive stop volume. Zero disables add clean line
alarm.
System 885 - Piston Injector
Feedback Errors
This parameter is used with piston injectors with
feedback only. It defines the number of missed
feedback signals that can occur before an additive
feedback alarm occurs. The range is 0 to 9.
Help: Enter the maximum number of feedback
errors allowed for a piston injector before alarming
System 891, 896, 901, 906, 911, 916,
921, 926, 931, 936 Add-Pak Injector
K Factor
This seven-digit numeric entry defines the nominal
number of pulses from an Add-Pak for one unit of
registration. The value must be between 0.001 and
9999.999.
Fatal: Entry must not be zero
Critical: Metered injector pulse input not configured
No-entry if Pulse Input not configured for Add-Pak
Help: Enter the K factor in pulses per unit volume for
the metered injector.
Note: These program codes are only available on Rev. 3 and
above firmware.
System 892, 897, 902, 907, 912, 917,
922, 927, 932, 937 Add-Pak Injector
Meter Factor
The meter factor for the Add-Paks that are being
controlled directly by the AccuLoad are programmed
Section VI Program Codes
in these parameters. If the Add-Paks are being
controlled through communications and ancillary
equipment, no value should be programmed in these
parameters. The range of these entries is 0.0000 to
9.9999. Meter factor equals the actual volume times
the current meter factor times the k factor, all divided
by the input pulses. The factory default is "0.0000".
Fatal: Entry must not be zero
No-entry if Pulse Input not configured for Add-Pak
injector
Help: Enter the meter factor for the metered injector
Note: These program codes are only available on Rev. 3 and
above firmware.
System 893, 898, 903, 908, 913, 918,
923, 933, 938 Injector High
Tolerances
These parameters allow a percentage entry in two
whole digits followed by one decimal place for the
amount the actual injected volume can surpass the
average volume required to meet the additive needs.
The range of this entry is 0 to 99.9. The factory
default is "0".
Help: Enter the percentage that the actual additive
amount may pass the averaged amount before an
error is counted
Note: These program codes are only available on Rev. 3 and
above firmware.
System 894, 899, 904, 909, 914, 919,
924, 929, 934, 939 Injector Low
Tolerances
These parameters allow a percentage entry in two
whole digits followed by one decimal place for the
amount the actual injected volume can be under the
average volume required to meet the additive needs.
The range of this entry is 0 to 99.9. The factory
default is "0".
Help: Enter the percentage that the actual additive
amount may be under the averaged amount before
an error is counted
111
Note: These program codes are only available on Rev. 3 and
above firmware.
895, 900, 905, 910, 915, 920, 925,
930, 935, 940 Maximum Tolerance
Errors
These parameters allow the operator to set up how
many times during the batch that the high and low
tolerance percentages can be exceeded before an
alarm is set. The range of this entry is from 0 to 99.
The factory default is "0".
Help: Enter the maximum number of tolerance
errors allowed before an alarm is set
Note: These program codes are only available on Rev. 3 and
above firmware.
Load Arm General Purpose
Directory
101 Permissive 1 Sense
102 Permissive 1 Message
103 Permissive 1 Restart
104 Permissive 2 Sense
105 Permissive 2 Message
106 Permissive 2 Restart
107 Load Arm ID
Load Arm 101, 104 Permissive
Sense
These parameters define the conditions under which
a defined permissive is expected to be present in
order for loading operations to be allowed.
Selections are as follows:
(0) N/A
(1) Transaction Start - Permissive only checked
immediately after authorization
(2) Continuous - Permissive must be met
continuously during the batch
(3) Start Condition - Permissive must be met
whenever flow is started
(4) Batch Start - Permissive must be met to
start a batch
MN06118L Issue/Rev. 0.5 (4/02)
Load Arm 102, 105 Permissive
Messages
These 28-character text messages will be displayed
to the operator if a permissive sense entry
corresponding with the message is defined but not
present when expected.
Load Arm 103, 106 Permissive
Restart
These parameters will determine how a restart is
initiated after a permissive is lost and then restored.
Selections are as follows:
(0) Manual Start key must be pressed to
restore flow
(1) Automatic Flow will be started
automatically as soon as the permissive is
restored
Load Arm 107 Load Arm ID
This program code is a 28-character text entry used
to identify the load position. It is included on the
AccuLoad's display in Ready mode. The Load Arm
ID can also be included on the delivery report.
Help: Enter an alphanumeric identifier for this load
arm.
Load Arm 108 Flashing Totals
This
program
code
determines
whether
nonresettable total data is displayed at the Ready
screen. This feature is only supported on arms
configured for straight product delivery. The total(s)
displayed will alternate with the "Press Set Key"
message if the unit is authorized for loading;
otherwise, it will appear full-time. Options are as
follows:
(0) None
(1) IV
(2) GV
(3) GST
(4) GSV
(5) Mass
(6) All
If "None" is selected, the display line will be blank if
the arm is not authorized. The display line will show
the message "Press Set Key" when the arm is
authorized.
If a specific volume type is selected, the Ready
screen will display the nonresettable total for the arm
in the volume type specified, alternating with the
"Press Set Key" message if authorized.
If "All" is selected, the Ready screen will cycle
through all of the volume types (as well as the
"Press Set Key" message if the arm is authorized).
IV and GV will always be included. GST and GSV
will be included only if they differ in value from the
next less-compensated volume. The mass
nonresettable total will be included only if it is nonzero.
Note: This parameter is only available on Revision 10 firmware, or
higher.
Load Arm Flow Control Directory
201 Low Flow Start Rate
202 Low Flow Start Volume
203 Low Flow Start Percentage
204 Low Flow Start Condition
205 High Flow Rate
206 Second High Flow Rate
207 Start After Stop Delay
208 Overrun Alarm Limit
209 Zero Flow Timer
210 Valve Delay to Open
211 Pump Delay to Off
212 Valve Fault Timeout
221 Clean Line Volume
222 Clean Line Product
223 Clean Line Alarm Limit
224 Ratio Factor Adjust
225 Ratio Factor Time
226 Block Valve Position
Load Arm 201 - Low Flow Start Rate
This program code designates the flow rate used
during low flow start, i.e. for the volume of product
Section VI Program Codes
defined by the low flow start volume or low flow start
percentage program codes. The range of this
parameter is 0.0 to 9999.9. The factory default is
0.0.
being delivered according to the percentages
assigned in the recipe selected for loading. The
range of this entry is 00001 to 99999 flow units.
Help: Enter the flow rate during low flow start
operation.
Help: Enter the maximum flow rate for digital/analog
valve control operation. A zero entry will not allow
the valve to open.
Load Arm 202 - Low Flow Start
Volume
This parameter defines the volume of product to be
delivered at the low flow start rate. If both low flow
start volume and low flow start percentage are
defined, the larger of the two will be used for low flow
start. The range of this parameter is 0.0 to 9999.9.
The factory default is 0.0.
Help: Enter volume for delivery during low flow start
Load Arm 203 - Low Flow Start
Percentage
This parameter defines the percentage of the preset
volume to be delivered during low flow start. If both
low flow start percentage and low flow start volume
are defined, the larger of the two will be used for low
flow start. The range of this parameter is 0 to 99.
The factory default is 0.0.
Note: "00000" will not allow the valve to open.
Load Arm 206 Second High Flow
Rate
This five-digit entry defines a second high flow rate
for the system, which is selectable by an AC contact
input. This program code is only available if one of
the inputs has been configured for first/second high
flow rate selection. The range of this entry is 00000
to 99999 flow units. This flow rate would be typically
selected for smaller trucks.
Help: Enter the 2nd high flow rate for digital/analog
valve control operation. Zero will not allow valve to
open.
Load Arm 207 - Start After Stop
Delay
Help: Enter percent of preset for delivery during low
flow start
This parameter defines the amount of time, in
seconds, before AccuLoad III will allow flow to be
restarted after flow was stopped during a batch. The
range of this parameter is 0 to 999 seconds. The
factory default is 0.
Load Arm 204 - Low Flow Start
Condition
Help: Enter time in seconds to delay a start after
stop in midload
This parameter defines when AccuLoad III will
deliver product at the low flow start rate. The factory
default is "Always." Selections are as follows:
Load Arm 208 - Overrun Alarm Limit
(0) Always
(1) Start of batch
Help: Select whether low flow start is desired at
batch beginning or at every start
This program code defines the amount of product, in
programmed volume units, that can be delivered
above the preset amount before AccuLoad III
generates an overrun alarm. The range of this
parameter is 0 to 99. An entry of 0 disables the
Overrun Alarm.
Load Arm 205 High Flow Rate
Help: Enter number of units delivered over preset
amount before alarm occurs
This five-digit code sets the high flow rate for the
system. This rate will be divided among the products
Load Arm 209 - Zero Flow Timer
113
MN06118L Issue/Rev. 0.5 (4/02)
This parameter defines the amount of time, in
seconds, that AccuLoad III will ignore a zero flow
condition before commanding the valve to close.
Once this occurs, AccuLoad III will require a start
command before the batch in progress can be
continued. The range of this parameter is 0 to 99
seconds. The factory default is 0.
This three-digit entry establishes the volume of clean
line product to be delivered to fill the pipe/load arm at
the end of every batch. This volume is determined by
calculating the volume of product to fill the pipe/load
arm from the control valve(s) to the end of the
loading arm. The range of this entry is 0 to 999 units.
The factory default is 0.
Help: Enter time in seconds zero flow is ignored
before valve closure. Zero disables this feature.
Help: Enter the volume of clean line product desired
at end of batch.
Load Arm 210 - Valve Delay to Open
Load Arm 222 Clean Line Product
This program code defines the amount of time, in
seconds, before the valve will be commanded to
open after the pump relay is closed. This allows the
pump to pressurize the line, providing for better valve
response. The range of this parameter is 0 to 99
seconds. The factory default is 0.
This one-digit entry selects the product that will be
designated as the clean line product. The clean line
product will be delivered at the end of every batch
whether the designated clean line product is part of
the recipe being delivered or not. The purpose is to
have the line packed with the clean line product at
the end of a delivery. The factory default is "Product
1." Selections are as follows:
Help: Enter time delay in seconds to open valve
after start
Load Arm 211 - Pump Delay to Off
This two-digit entry allows the operator to select a
pump relay delay to off time in seconds. At any time
during a normal or operator-requested stop, the
pump relay will be delayed by the programmed value
in seconds before turning off. This delay will be
overridden in an alarm condition (i.e., no delay to
off). The range of this entry will be 0 to 99 seconds
delay to off.
No-entry if no digital output configured as pump
Help: Enter delay time in seconds to open the pump
relay contact after stop.
(0) Product #1
(1) Product #2
(2) Product #3
(3) Product #4
No-entry if clean line volume set to 0.
Help: Select the product that will be used to fill the
load arm at the end of each batch.
Load Arm 223 Clean Line Alarm
Limit
This two-digit program code allows the setting of the
amount of time that the AccuLoad will ignore flow
after the valve has been commanded to close. The
range of this parameter is 0 to 99 seconds.
This two-digit entry defines the volume of product
that the clean line volume can be short and not
cause an alarm. For example, if the clean line
volume is set for 100 gallons and the maximum
clean line alarm limit is programmed for 5 gallons,
the clean line volume can range between 95 gallons
and 100 gallons without causing an alarm. The
range of this entry is 0 to 99 units. The factory
default is 0.
Help: Enter time in seconds to ignore flow when
valve has been commanded to close. Zero disables
this feature.
No-entry if clean line volume set to 0.
Help: Set tolerance allowed for under-run of clean
line delivery.
Load Arm 221 Clean Line Volume
Load Arm 224 Ratio Factor Adjust
Load Arm 212 Valve Fault Timeout
Section VI Program Codes
This three-digit entry sets the ratio adjustment factor
used to speed up the response of the blend valves to
help maintain the programmed blend ratio during
loading. This factor is used to magnify the difference
between the programmed blend ratio and the current
blend ratio so that the programmed blend ratio can
be achieved more quickly. The value used in this
code must not be zero. The range of this entry is
00.1 to 99.9.
No-entry if ratio blending not selected.
Help: Enter the ratio adjustment factor for the
desired blend flow correction.
Load Arm 225 Ratio Factor Time
This two-digit entry sets the time in seconds
between flow rate adjustments of the control valves.
The value used in this code must not be zero. This
value should be determined based on the hydraulic
conditions that exist for the system. The range of this
entry is 01 to 99 seconds.
No-entry if ratio blending not selected.
Help: Enter the flow rate adjustment time in seconds
for the desired blend flow correction.
Load Arm 226 Block Valve Position
This one-digit entry sets the position of the product
select valve at the end of a transaction or when the
STOP button is pressed. The valve can either be left
open (for relief of thermal expansion) or closed. This
code applies only to electric motor-operated valves.
The factory default is 0. Selections are as follows:
(0) Valve is closed when STOP is pressed and at
the end of the transaction
(1) Valve is open when STOP is pressed and
closed at the end of the transaction
(2) Valve is closed when STOP is pressed and
open at the end of the transaction
(3) Valve is open when STOP is pressed and
open at the end of the transaction.
No-entry if sequential blending not selected.
115
Help: Select the block valve position at the end of a
transaction when STOP is pressed or when stop
state occurs
Load Arm Volume Accuracy Directory
301 Blend Tolerance (Percentage)
302 Blend Tolerance (Volume)
303 Blend Correction
Load Arm 301 Blend Tolerance
(Percentage)
This two-digit program code defines the blend
tolerance allowed for all delivered blends. The range
of this entry is 0.1 percent to 9.9 percent.
This blend tolerance is applied as a percentage of
the total batch delivered. If the delivered amount of
the product is within plus or minus the blend
percentage of the total delivery, no blend alarm will
occur.
A blend tolerance entry of zero allows no tolerance,
causing an alarm to occur unless all components are
delivered exactly.
For example, assume a blend tolerance percentage
of 2%, a preset of 1000 gallons, and a recipe
consisting of 25% of each of the four products. The
presets for each of the products would be 250
gallons. If 1000 gallons are delivered, the calculated
blend tolerance would be 20 gallons (2% of 1000
gallons). If any product delivered less than 230
gallons (250 20) a blend low alarm will be set. If
any product delivered more than 270 gallons (250 +
20), a blend high alarm will be set. (This is true only
if all 1000 gallons are delivered.)
Help: Enter the percentage of total preset to be used
as the blend tolerance.
Load Arm 302 Blend Tolerance
(Volume)
This three-digit code defines the blend tolerance as
a fixed volume. This volume represents the delivered
MN06118L Issue/Rev. 0.5 (4/02)
volume of product over or under the delivered
volume that will be allowed by AccuLoad III without
causing an alarm. The range of this entry is 00.1 to
99.9 units.
Help: Choose the level of blend correction that will
be allowed.
If both a blend tolerance volume and a blend
tolerance percentage are entered, the AccuLoad will
use the larger of the two for a specific batch. It is
recommended that the minimum volume tolerance
be programmed here to override the percentage
applied to very small batches.
701 Report Selection
Help: Enter the volume to be used as the blend
tolerance.
Load Arm 303 Blend Correction
This code establishes the type of Blend Correction
that will be allowed in case of a product overrun.
Three possible selections are available. The factory
default is "No Blend Correction." Selections are as
follows:
(0) No Blend Correction. If a product overrun
occurs during the loading process, which would
cause a blend alarm, no correction will be
allowed and the transaction must be ended.
(1) Self-Corrected Blend. If a product overrun
occurs during the loading process, the
AccuLoad III will automatically try to correct the
blend if the product in error is being loaded as
another component of the blend (i.e., error in
component 2 Regular, Regular also being
loaded as component 5). If the component in
error is not repeated as one of the components
that has not been loaded, the transaction will
have to be ended.
(2) Self-Corrected Blend/Complete Batch. If a
product overrun occurs during the loading
process, the AccuLoad III will automatically try to
correct the blend if the product in error is being
loaded as another component of the blend. If the
component in error is not repeated as one of the
components that has not been loaded, the
driver/operator will have the choice of ending the
batch or completing the loading of the original
preset amount.
Load Arm Communications Directory
702 Summary Report Print Time
703 Summary Report Interval
704 Report Volume Resolution
705 Report Pages
706 Report HM Classification
Load Arm 701 Report Selection
This program code defines which delivery report will
be printed at the completion of a transaction if a
printer function is assigned to one or more
communications ports. The same report will be
printed at each port if multiple ports are configured
for printer options. The factory default is "Default."
Selections are as follows:
(0) Default
(1) User Configured Report 1
(2) User Configured Report 2
Note: The user-configured reports are designed on the AccuMate
and downloaded to the AccuLoad.
Help: Select the report type to be printed
Load Arm 702 Summary Report
Print Time
This entry sets the initial print time of the summary
report. Enter the hours, minutes, and time type (AM,
PM, or military) the summary report is to be printed.
The summary report includes a line per batch for all
transactions run during the time interval specified.
No-entry if no printer configured on any comm port
Help: Enter up to 6 characters of text. Enter time to
print summary report. Time format is HH:MMT,
where T = A,P,M
Load Arm 703 Summary Report
Interval
Section VI Program Codes
This parameter sets the interval that the summary
report will be printed. Once the time of the report has
been set using this parameter, the report would print
based on that initial time and the interval
programmed. The interval is entered in hours with
three digits in whole hours. The range of this entry is
from 0 to 999.
No-entry if no printer configured on any comm port
Help: Enter time interval in hours between printed
reports. Zero entry disables this feature.
Load Arm 704 Report Volume
Resolution
This entry selects the volume resolution to print on
default reports. The factory default is "Whole units."
Selections are as follows:
(0) Whole units
(1) Tenths
(2) Hundredths
Help: Select the volume resolution to print on default
reports
This entry allows the operator to select which
product's Hazardous Materials (HM) Classification
will be printed on the transaction summary page of
the report. The factory default is "Product 1."
Selections are as follows:
(0) Product 1
(1) Product 2
(2) Product 3
(3) Product 4
Help: Select which product's HM class to print on
summary page of default report
Meter Flow Control Directory
201 Valve Type
202 PID Proportional Gain Factor
203 PID Integral Gain Factor
204 PID Derivative Gain Factor
205 PID Interval
206 Zero Flow Alarm Timer
207 Overrun Alarm Limit
208 Flow Adjust Tolerance
209 Flow Adjust Timer
Load Arm 705 Report Pages
This entry selects which pages will be printed on
reports. The factory default is "Batch and transaction
pages." Selections are as follows:
(0) Batch and transaction pages one page per
batch plus a summary page for the transaction
(1) Batch page only one page per batch only;
no transaction summary
(2) Transaction page only transaction
summary only; no batch details
(3) No transaction report printer only used for
summary reports
Help: Select which pages to print for reports
Load Arm 706 Report HM
Classification
117
Meter 201 Valve Type
This parameter selects the type of control valve used
by AccuLoad III. The factory default is "Digital."
Selections are as follows:
(0) Digital
(1) Two-stage
(2) Analog
Note: A two-stage valve is not allowed for ratio blending.
Help: Select the type of valve used
Meter 202 PID Proportional Gain
Factor
This three-digit entry is the PID proportional gain
factor for analog valve control. The range of this
MN06118L Issue/Rev. 0.5 (4/02)
entry is from 0.000 to 999.999. (Used only with
analog valves.)
occurs. The range of this entry is from 0 to 99 units.
An entry of zero disables the overrun alarm.
Help: Enter the PID proportional gain factor for
analog valve control
Help: Enter number of units delivered over preset
amount before alarm occurs
Meter 208 Flow Adjust Tolerance
Meter 203 PID Integral Gain Factor
This three-digit entry is the PID integral gain factor
for analog valve control. The range of this entry is
from 0.000 to 999.999. (Used only with analog
valves.)
Help: Enter the PID integral gain factor for analog
valve control
Meter 204 PID Derivative Gain
Favor
This three-digit entry is the PID derivative gain factor
for analog valve control. The range of this entry is
from 0.000 to 999.999. (Used only with analog
valves.)
Help: Enter the PID derivative gain factor for analog
valve control
Meter 205 PID Interval
This two-digit entry is the time interval in seconds
between PID calculations. The range of this entry is
from 0.0 to 9.9. (Used only with analog valves.)
Help: Enter the time interval in seconds between
PID calculations
Meter 206 Zero Flow Alarm Timer
This parameter defines the percentage of flow rate
tolerance to be used when making flow rate
adjustments. The range of this entry is 0 to 9.9%.
This is intended as a tighter flow tolerance than in
Product 204. This tolerance is only applied when the
flow rate has been adjusted (from low flow to high
flow, or to improve the blend). The purpose of the
tighter tolerance is to more closely achieve the
desired flow rate. Note that this tight tolerance is only
in effect for the time specified in the following
parameter.
Help: Enter flow rate tolerance (percent) to be used
when making flow rate adjustments
No-entry if not a ratio blender.
Meter 209 Flow Adjust Timer
This parameter defines the time duration in seconds
for the flow rate adjustment tolerance to be in effect.
The range of this entry is 0.0 to 99.9 seconds.
Help: Enter the time duration in seconds for the flow
rate adjustment tolerance to be in effect
No-entry if not a ratio blender.
Meter Volume Accuracy Directory
301 K-Factor
This program code defines the amount of time, in
seconds, after which a zero flow condition will
generate an alarm. An entry of zero causes
AccuLoad III to disable the zero flow alarm. The
range of this parameter is 0 to 99 seconds.
302 Dual Pulse Error Count
303 Dual Pulse Error Reset
304 Dual Pulse Flow Rate Cutoff
310 Turbine Meter Blade Count
311 Turbine Diagnostic Tolerance
Help: Enter time in seconds zero flow is ignored
before valve closure
Meter 301 K Factor
Meter 207 Overrun Alarm Limit
This parameter defines the number of units that may
be delivered over the preset amount before an alarm
This program code defines the nominal number of
pulses comprising one unit of volume registration.
The range of this entry is 0.001 to 9999.999.
Section VI Program Codes
Critical: Security level for parameter must be at top
2 levels. [Revision 5 and above firmware only]
Help: Enter the number of pulses required for one
unit of registration
programmed accurately if any turbine meter
diagnostics are to be performed. It is not used and
should be programmed to 0 if the meter is any other
type. The range of this entry is 0 to 99.
Meter 302 - Dual Pulse Error Count
Help: Enter the number of blades for turbine meter
diagnostics
This program code defines the number of error
counts that may be received from a dual pulse
comparator without causing a pulse security alarm.
The range of this parameter is 0 to 999. The factory
default is 0.
Help: Enter the number of dual pulse errors allowed
before alarm
Meter 303 - Dual Pulse Error Reset
This program code defines the conditions under
which the dual pulse error count will be reset. The
factory default is "No reset." Selections are as
follows:
(0) No reset
(1) Reset at end of transaction
(2) Reset on power-up
(3) Reset at end of transaction and power-up
Note: Clearing a pulse security alarm does not reset the error
count.
Help: Select how dual pulse error count is reset
Meter 304 - Dual Pulse Flow Rate
Cutoff
This parameter defines the flow rate below which
dual pulse errors will not be counted. The range of
this entry is 0 to 9999. The factory default is 0.
Help: Enter the flow rate at which dual pulse error
counts will be counted
Meter 310 Number of Turbine
Blades
This two-digit entry should be programmed to the
number of blades/buttons present on the rotor for a
turbine type meter. It is required that this entry be
119
Meter 311 Turbine Meter Diagnostic
Tolerance
This parameter defines the degree of turbine meter
diagnostic tolerance. The stricter the tolerance, the
greater the chance of the turbine meter diagnostic
causing an alarm. The factory default is "Most Lax."
Selections are as follows:
(0) Most lax
(1) Lax
(2) Normal
(3) Strict
(4) Most strict
Help: The stricter the tolerance, less variation will
result in an alarm
Meter Temperature/Density Directory
401 Densitometer Type
407 S-Mass A Coefficient
408 S-Mass B Coefficient
411 Solartron Calculation Units
412 Solartron DCF
413 Solartron K0
414 Solartron K1
415 Solartron K2
416 Solartron K18
417 Solartron K19
418 Solartron K20a
419 Solartron K20b
420 Solartron K21a
421 Solartron K21b
422 Solartron Tcal
423 Solartron Pcal
441 Sarasota Calculation Units
442 Sarasota DCF
MN06118L Issue/Rev. 0.5 (4/02)
443 Sarasota K
444 Sarasota D0
445 Sarasota T0
446 Sarasota Tcoef
447 Sarasota Tcal
448 Sarasota Pcoef
449 Sarasota Pcal
461 UGC Calculation Units
462 UGC DCF
463 UGC K0
464 UCG K1
465 UCG K2
466 UCG Tc
467 UCG Kt1
468 UCG Kt2
469 UCG Kt3
470 UGC Pc
471 UGC Kp1
472 UGC Kp2
473 UGC Kp3
491 Other Density Calculation Units
492 Other DCF
493 Other A Coefficient
494 Other B Coefficient
495 Other C Coefficient
Meter 401 Densitometer Type
This parameter allows the operator to select the
frequency densitometer used by the meter. The
factory default is "S-Mass." Selections are as
follows:
(0) S-Mass
(1) Solartron
(2) Sarasota
(3) UGC
(4) Other
Help: Select the type of frequency densitometer
used by this meter
Meter 407 - S-Mass A Coefficient
This parameter is used to enter the constant "A" for
the Smith Meter S-Mass meter. The "A" constant is
used in the equation a/T + b where T is the period of
the incoming signal. Suggested values are 1.000E +
7 Kg/m3 for metric units and 6.242797E + 5 for lb/ft 3.
This value is entered as 0.000000E + 00.
No-entry if this isn't an S-Mass Densitometer.
Help: Enter the "A" coefficient to be used for density
calculation.
Meter 408 - S-Mass B Coefficient
This parameter is used to enter the offset error "B" to
correct the density by this fixed value. This value is
used in the equation a/T + b where T is the period of
the incoming signal. This value is entered as
0.000000E + 00.
No-entry if this isn't an S-Mass Densitometer.
Help: Enter the "B" coefficient to be used for density
calculation.
Meter 411 - Solartron Calibration
Units
This entry allows the user to select the calibration
units used for the Solartron Densitometer. Selections
are as follows:
(0) English (Fahrenheit, PSI, Lb/Ft3)
(1) Metric (Celsius, Bar, Kg/m3)
No-entry if this isn't a Solartron Densitometer.
Help: Select calibration certificate units: English
(Fahrenheit, PSI, Lb/Ft3), metric (Celsius, Bar,
Kg/m3).
Meter 412 - Solartron DCF
This entry allows the operator to enter the density
correction factor for computing the calculated density
from the actual density. The range of this entry is
from 9.9999 to 9.9999.
No-entry if not selected as installed densitometer
type
Help: Enter the density correction factor
Meter 413 - Solartron K0
Section VI Program Codes
This entry allows the operator to enter the Constant
K0 from the Solartron densitometer. Enter the base
number (six digits) and two digits for the exponent.
No-entry if this isn't a Solartron Densitometer.
Help: Enter pressure coefficient data from calibration
certificate.
No-entry if this isn't a Solartron Densitometer.
Help: Enter constant from calibration certificate.
Meter 419 - Solartron K20b
Meter 414 - Solartron K1
This entry allows the operator to enter the Constant
K1 from the Solartron densitometer. Enter the base
number (six digits) and two digits for the exponent.
No-entry if this isn't a Solartron Densitometer.
Help: Enter constant from calibration certificate.
Meter 415 - Solartron K2
This entry allows the operator to enter the Constant
K2 from the Solartron densitometer. Enter the base
number (six digits) and two digits for the exponent.
No-entry if this isn't a Solartron Densitometer.
Help: Enter constant from calibration certificate.
Meter 416 - Solartron K18
This entry allows the operator to enter the Constant
K18 from the Solartron densitometer. Enter the base
number (six digits) and two digits for the exponent.
No-entry if this isn't a Solartron Densitometer.
Help: Enter temperature coefficient data from
calibration certificate.
This entry allows the operator to enter the Constant
K20b from the Solartron densitometer. Enter the base
number (six digits) and two digits for the exponent.
No-entry if this isn't a Solartron Densitometer.
Help: Enter pressure coefficient data from calibration
certificate.
Meter 420 - Solartron K21a
This entry allows the operator to enter the Constant
K21a from the Solartron densitometer. Enter the base
number (six digits) and two digits for the exponent.
No-entry if this isn't a Solartron Densitometer.
Help: Enter pressure coefficient data from calibration
certificate.
Meter 421 - Solartron K21b
This entry allows the operator to enter the Constant
K21b from the Solartron densitometer. Enter the base
number (six digits) and two digits for the exponent.
No-entry if not selected as installed densitometer
type.
Help: Enter pressure coefficient data from calibration
certificate.
Meter 417 - Solartron K19
Meter 422 - Solartron Tcal
This entry allows the operator to enter the Constant
K19 from the Solartron densitometer. Enter the base
number (six digits) and two digits for the exponent.
This entry allows the operator to enter the
temperature that the densitometer was calibrated at
the factory. The range of this entry is 9999.999 to
9999.999 (limit of three decimal points).
No-entry if this isn't a Solartron Densitometer.
Help: Enter temperature coefficient data from
calibration certificate.
Meter 418 - Solartron K20a
This entry allows the operator to enter the Constant
K20a from the Solartron densitometer. Enter the base
number (six digits) and two digits for the exponent.
121
No-entry if not selected as installed densitometer
type
Help: Enter temperature calibration value
Meter 423 - Solartron Pcal
MN06118L Issue/Rev. 0.5 (4/02)
This entry allows the operator to enter the pressure
that the densitometer was calibrated at the factory.
The range of this entry is 9999.999 to 9999.999
(limit of three decimal places).
No-entry if not selected as installed densitometer
type
Help: Enter pressure calibration value.
Meter 441 - Sarasota Calibration
Units
This entry allows the user to select the calibration
units used for the Sarasota Densitometer. The
factory default is "English." Selections are as follows:
(0) English (Fahrenheit, PSI, Lb/Ft3)
(1) Metric (Celsius, Bar, Kg/m3)
No-entry if pulse input is not configured for Sarasota
densitometer
Help: Select calibration certificate units: English
(Fahrenheit, PSI, Lb/Ft3), metric (Celsius, Bar,
Kg/m3).
Meter 442 - Sarasota DCF
This entry allows the operator to enter the density
correction factor for computing the calculated density
from the actual density. The range of this entry is
from 9.9999 to 9.9999.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for Sarasota
densitometer
Help: Enter the density correction factor.
Meter 443 - Sarasota K
This entry allows the operator to enter the calibration
constant for the spool on the Sarasota densitometer.
The range of this entry is from 9.999999 to
9.999999.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for Sarasota
densitometer
Help: Enter constant from calibration certificate.
Meter 444 - Sarasota D0
This entry allows the operator to enter the constant
D0 from the Sarasota densitometer. The range of this
entry is from 9999.999 to 9999.999.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for Sarasota
densitometer
Help: Enter constant from calibration certificate.
Meter 445 - Sarasota T0
This entry allows the operator to enter the T 0
constant from the Sarasota densitometer. This
constant is in microseconds. The range of this entry
is
from
9999.999 to 9999.999.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for Sarasota
densitometer
Help: Enter constant from calibration certificate.
Meter 446 - Sarasota Tcoef
This entry is used for entering the temperature
coefficient constant from the Sarasota densitometer
in microseconds/degree F. The range of this entry is
from 9.999999 to 9.999999.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for Sarasota
densitometer
Help: Enter temperature coefficient data from
calibration certificate
Meter 447 - Sarasota Tcal
This entry allows the operator to enter the
temperature that the densitometer was calibrated at
the factory. The range of this entry is from
9999.999 to 9999.999.
No-entry if not selected as installed densitometer
type
Section VI Program Codes
No-entry if pulse input is not configured for Sarasota
densitometer
Help: Enter temperature calibration value
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for UGC
densitometer
Meter 448 - Sarasota Pcoef
Meter 462 - UGC DCF
This entry is used for entering the pressure
coefficient constant from the Sarasota densitometer
in microseconds/PSIG. The range of this entry is
from
9.999999 to 9.999999.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for Sarasota
densitometer
Help: Enter pressure coefficient data from calibration
certificate.
Meter 449 - Sarasota Pcal
This entry allows the operator to enter the pressure
that the densitometer was calibrated at the factory.
The range of this entry is from 9.999999 to
9.999999.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for Sarasota
densitometer
Help: Enter pressure calibration value.
UGC Densitometer
Meter 461 - UGC Calibration Units
This entry allows the user to select the calibration
units used for the UGC Densitometer. The factory
default is "English." Selections are as follows:
(0) English (Fahrenheit, PSI, gr/cc)
(1) Metric (Celsius, Bar, gr/cc)
Help: Select calibration certificate units: English
(Fahrenheit, PSI, gr/cc), metric (Celsius, Bar, gr/cc).
123
This entry allows the operator to enter the density
correction factor for computing the calculated density
from the actual density. The range of this entry is
from 9.9999 to 9.9999.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for UGC
densitometer
Help: Enter the density correction factor.
Meter 463 - UGC K0
This entry allows the operator to enter the Constant
K0 from the UGC densitometer. Enter the base
number (six digits) and then two digits for the
Exponent.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for UGC
densitometer
Help: Enter constant from calibration certificate
Meter 464 - UGC K1
This entry allows the operator to enter the Constant
K1 from the UGC densitometer. Enter the base
number (six digits) and then two digits for the
Exponent.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for UGC
densitometer
Help: Enter constant from calibration certificate
Meter 465 - UGC K2
MN06118L Issue/Rev. 0.5 (4/02)
This entry allows the operator to enter the Constant
K2 from the UGC densitometer. Enter the base
number (six digits) and then two digits for the
Exponent.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for UGC
densitometer
Help: Enter constant from calibration certificate.
Meter 466 - UGC Tc
This entry allows the operator to enter the
temperature that the densitometer was calibrated at
the factory. The range of this entry is from
999.9999 to 999.9999.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for UGC
densitometer
Help: Enter temperature calibration value.
Meter 467 - UGC Kt1
This entry allows the operator to enter the Constant
Kt1 from the UGC densitometer. Enter the base
number (six digits) and then two digits for the
Exponent.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for UGC
densitometer
Help: Enter constant from calibration certificate.
Meter 468 - UGC Kt2
This entry allows the operator to enter the Constant
Kt2 from the UGC densitometer. Enter the base
number (six digits) and then two digits for the
Exponent.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for UGC
densitometer
Help: Enter constant from calibration certificate.
Meter 469 - UGC Kt3
This entry allows the operator to enter the Constant
Kt3 from the UGC densitometer. Enter the base
number (six digits) and then two digits for the
Exponent.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for UGC
densitometer
Help: Enter constant from calibration certificate.
Meter 470 - UGC Pc
This entry allows the operator to enter the pressure
that the densitometer was calibrated at the factory.
The range of this entry is from 999.9999 to
999.9999.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for UGC
densitometer
Help: Enter pressure calibration value.
Meter 471 - UGC Kp1
This entry allows the operator to enter the Pressure
Constant Kp1 from the UGC densitometer. Enter the
base number (six digits) and then two digits for the
Exponent.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for UGC
densitometer
Help: Enter constant from calibration certificate.
Meter 472 - UGC Kp2
This entry allows the operator to enter the Constant
Kp2 from the UGC densitometer. Enter the base
number (six digits) and then two digits for the
Exponent.
Section VI Program Codes
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for UGC
densitometer
Help: Enter constant from calibration certificate.
125
MN06118L Issue/Rev. 0.5 (4/02)
Meter 473 - UGC Kp3
This entry allows the operator to enter the Constant
Kp3 from the UGC densitometer. Enter the base
number (six digits) and then two digits for the
Exponent.
No-entry if not selected as installed densitometer
type
No-entry if pulse input is not configured for UGC
densitometer
Help: Enter constant from calibration certificate.
Other Densitometers
Meter 491 - Other Densitometer
Calibration Units
This entry allows the user to select the calibration
units used for the Solartron Densitometer. The
factory default is "English." Selections are as follows:
(0) English (Fahrenheit, PSI, Lb/Ft3)
(1) Metric (Celsius, Bar, Kg/m3)
No-entry if not configured for "other densitometer"
Help: Select calibration certificate units: English
(Fahrenheit, PSI, Lb/Ft3), metric (Celsius, Bar,
Kg/m3).
Meter 492 - Other DCF
This entry allows the operator to enter the density
correction factor for computing the calculated density
from the actual density. The range of this entry is
from 9.9999 to 9.9999.
No-entry if not selected as installed densitometer
type
No-entry if not configured for "other densitometer"
Help: Enter the density correction factor.
Where: T is the period of the incoming signal and a,
b, and c are the programmed constants.
Nine digits must be entered for constant a. The first
seven digits represent the base number and the last
two numbers represent the exponent. The +/- key
may be used to set the sign of the base and the
exponent field.
No-entry if not selected as installed densitometer
type
Help: Enter the "A" coefficient to be used for density
calculation.
Meter 494 - Other B Coefficient
This parameter allows the operator to enter the
constant b by which the density is calculated
according to the following formula:
Density = aT2 + bT + c
Where: T is the period of the incoming signal and a,
b, and c are the programmed constants.
Nine digits must be entered for constant b. The first
seven digits represent the base number and the last
two numbers represent the exponent. The +/- key
may be used to set the sign of the base and the
exponent field.
No-entry if not selected as installed densitometer
type
Help: Enter the "B" coefficient to be used for density
calculation.
Meter 495 - Other C Coefficient
This parameter allows the operator to enter the
constant "c" by which the density will be calculated
according to the following formula:
Density = aT2 + bT + c
Meter 493 - Other A Coefficient
This code allows the operator to enter the constant
a by which the density will be calculated according
to the following formula:
Density = aT2 + bT + c
Where: T is the period of the incoming signal and a,
b, and c are the programmed constants.
Nine digits must be entered for constant c. The first
seven digits represent the base number and the last
two numbers represent the exponent. The +/- key
Section VI Program Codes
may be used to set the sign of the base and the
exponent field.
No-entry if not selected as installed densitometer
type
Help: Enter the "C" coefficient to be used for density
calculation.
127
MN06118L Issue/Rev. 0.5 (4/02)
Product 100 General Purpose
Directory
101 Product ID
102 HM Classification
103 HM Classification
Product 101 - Product ID
This code allows a nine-character entry message to
serve as a product identifier. The data entry will
allow the following characters to be selected as part
ID:
ABCDEFGHIJKLMNOPQRSTUV
WXYZ#*
abcdefghijklmnopqrstuvwxyz&
@
0 1 2 3 4 5 6 7 8 9 < > ( ) ? ! . , - / + = _ END
Help: Enter an alphanumeric ID to describe the
product.
Product 102, 103 HM Classification
The Hazardous Materials (HM) Classification is a 60character message divided between two program
parameters. The data entry will allow the following
characters to be selected as part of the
classification:
ABCDEFGHIJKLMNOPQRSTUV
WXYZ#*
abcdefghijklmnopqrstuvwxyz&
@
0 1 2 3 4 5 6 7 8 9 < > ( ) ? ! . , - / + = _ END
Help: Enter the first thirty characters of the
Hazardous Materials Classification.
Help: Enter the last thirty characters of the
Hazardous Materials Classification.
Product 200 Flow Control Directory
201 Minimum Flow Rate
202 High Flow Rate
203 Second High Flow Rate
204 Flow Tolerance Percentage
205 Flow Tolerance Rate
206 First Trip Volume
207 Second Trip Volume
208 Second Trip Auto Adjust
209 Excess High Flow Rate
210 Low Flow Rate Alarm Limit
211 Block Valve Delay to Open
212 Block Valve Delay to Close
Product 201 Minimum Flow Rate
This four-digit entry defines the lowest programmed
(final stage) flow rate for the product. This will be the
flow rate when the valve is signaled to close at the
completion of a preset. The range of this entry is
from 0 to 9999 units per time measurement.
Help: Enter the minimum flow rate for digital valve
control operation
Product 202 High Flow Rate
This five-digit code defines the maximum flow rate
being controlled for this product during loading. The
range of this entry is 0 to 99999 flow units. The
factory default is zero.
Help: Enter the maximum flow rate for digital valve
control operation. A zero entry will not allow the valve
to open
Product 203 Second High Flow Rate
This five-digit entry defines a second high flow rate
that is selectable by an AC contact input. This
program code is not used when a two-stage valve
has been selected. The range of this entry is 0 to
99999 flow units. If zero is entered, second high flow
is disabled. This flow rate would normally be used in
situations where the size of the trucks vary and a
lower high flow rate is needed for the smaller trucks.
Help: Enter the second high flow rate for digital
valve control operation. A zero entry will not allow
the valve to open.
Product 204 Flow Tolerance
Percentage
Section VI Program Codes
This single-digit entry designates the percentage of
the currently requested flow rate that the flow rate
may vary before the AccuLoad III initiates a valve
correction. The range of this entry is 0 to 9%.
The AccuLoad III will calculate the current flow
tolerance using this percentage and the current flow
rate. This will be compared with the programmed
flow tolerance rate, with the larger of the two
tolerances determining when to adjust the valve.
129
MN06118L Issue/Rev. 0.5 (4/02)
Example:
Current Flow Rate 600 GPM
Flow Tolerance 9%
Flow rate can vary 54 GPM (600 GPM x 9% = 54
GPM) without a valve correction signal from the
AccuLoad III.
Help: Enter desired flow rate tolerance as a
percentage of the current flow rate
Product 205 Flow Tolerance Rate
This three-digit code allows for the entry of the
minimum flow rate tolerance in units per time. The
range of this entry is from 0 to 99 units per time.
trip adjustment. For a preset, this is the number of
batches run. The range of this entry is 1 to 9.
This parameter provides the operator an automatic
method of adjusting the final trip point of the valve.
The use of this parameter is ideal when starting up
the system or when system hydraulics are changed
during maintenance. The AccuLoad III will
automatically set up the final (second) trip point
when this parameter is used.
If for some reason the system parameters change
and the final trip point needs adjusted, the operator
must enter Program Mode and reset the auto adjust
to again automatically adjust the final stage trip point
The AccuLoad III will calculate the current flow
tolerance using this percentage and the current flow
rate. This will be compared with the programmed
flow tolerance rate, with the larger of the two
tolerances determining when to adjust the valve.
Note: The batch volumes must be sufficient to allow the
AccuLoad III to reach high flow before the first trip point is
encountered.
Help: Enter a desired flow rate tolerance in units per
time (GPM, BPH, etc.)
This four-digit entry designates the preset volume for
this product remaining on the line when flow slowdown begins. The range of this entry is 0 to 9999
units.
This two-digit entry sets the maximum percentage by
which the flow rate can exceed the product's high
flow rate entry without alarming. This entry must be
greater than the Flow Tolerance entry, except when
a value of zero is entered to disable excess high flow
alarm checking. The excess rate is entered as a
percentage of the product high flow rate. The range
of this entry is 00 through 99 seconds.
Help: Enter preset volume remaining before ramp
down begins
Help: Enter the highest flow rate allowed in percent
above the high flow rate without alarming
Product 207 Second Trip Volume
Product 210 Low Flow Rate Alarm
Limit
Product 206 First Trip Volume
This three-digit entry defines the preset volume (in
tenth of volume units) remaining for this product at
the final valve closure signal for the product. The
range of this entry is 0.0 to 99.9 units.
Help: Enter the preset volume remaining before
valve closure occurs
Product 208 Second Trip Auto
Adjust
This one-digit entry defines the number of batches to
be included in the average used to calculate the final
Help: Enter number of batches to average for auto
second trip value adjustment
Product 209 Excess High Flow Rate
This three-digit entry defines the set point in units
per minute for the low flow alarm. The low flow alarm
will be triggered whenever a flow rate is equal to or
lower than the limit set and is maintained for eight
seconds. The low flow alarm is not triggered in
cases where there is no flow. The range of this entry
is 001 to 999 flow units.
Help: Enter the minimum flow rate allowed without a
low flow alarm
Section VI Program Codes
Product 211 Block Valve Delay to
Open
This program code allows the setting of a time delay
(in seconds) for the opening of the product block
valve prior to delivery of the product. If Block Valve
Security is programmed and the valve does not open
within the programmed delay, a block valve alarm
will be triggered. The range of this entry is 01 to 99
seconds. For example, if the Block Valve Delay to
Open entry is set to 05 seconds, the AccuLoad
would allow 5 seconds for the block valve to open or
else an alarm would be triggered if the valve had not
been opened. If Block Valve Security is not used, the
AccuLoad assumes that the valve has opened after
the programmed delay.
Help: Enter delay time in seconds to open the pump
relay contact after stop
Product 212 Block Valve Delay to
Close
This program code allows setting of a time delay (in
seconds) for the closing of the product block valve
after the product has been delivered. If Block Valve
Security is programmed and the valve does not
close within the programmed delay, a block valve
alarm will be triggered. The range of the entry is 01
to 99 seconds. For example, if the block valve delay
entry were set to 05 seconds once the delivery was
completed, the AccuLoad would allow 5 seconds for
the block valve to close, then an alarm would be
triggered. If Block Valve Security is not used, the
AccuLoad assumes that the valve has closed after
the programmed delay.
Help: Enter time in seconds to ignore flow when
valve has been commanded to close. Zero disables
this feature.
Product 300 Volume Accuracy
Directory
301 Minimum Batch Volume
302 Meter Factor 1
303 Flow Rate 1
304 Meter Factor 2
131
305 Flow Rate 2
306 Meter Factor 3
307 Flow Rate 3
308 Meter Factor 4
309 Flow Rate 4
310 Master Meter Factor
311 Linearized Factor Deviation
312 Meter Factor Variation Select
313 Meter Factor Variation % Change Per Degree
314 Meter Factor Variation Reference Temperature
Product 301 Minimum Batch
Volume
This entry allows for the setting of the minimum
batch size for this product. The range of this entry is
00001 to 99999 units. An error message, "The
minimum preset for this recipe is *. Press clear to
continue," will be displayed. Any attempt to start a
batch with a product volume less than the minimum
batch size for that product will not be allowed.
Note: * indicates the summation of all the minimum batches of
the components of the recipe according to the percentages
programmed for that recipe.
Help: Enter the minimum batch amount allowed for
this product.
Product
Product
Product
Product
302
304
306
308
Meter
Meter
Meter
Meter
Factor
Factor
Factor
Factor
1
2
3
4
If only a single meter factor is used, it must be put
into program code 302. The flow rate selected in
program code 303 or 305 must be set to "0". Under
these conditions any other meter factors
programmed will be ignored. The range of these
entries is 0 to 9.99999.
Note: A zero entry in meter factor 1 will be considered an
invalid entry. Zero entries in the remaining factors will
result in that factor and subsequent factors not being
used. (e.g., if a zero entry is made for factor 2, factors 3
and 4 will not be used.)
Critical: Security level for parameter must be at top
2 levels. [Revision 5 and above firmware only]
Critical: Meter factor varies more than the
Linearized Factor Deviation
MN06118L Issue/Rev. 0.5 (4/02)
Critical: Meter factors must be within 2% of the
master meter factor
Fatal: (302 only) Entry must not be zero
Help: Meter factor = (actual volume x current factor x
k factor)/input pulses.
Product
Product
Product
Product
303
305
307
309
Flow
Flow
Flow
Flow
Rate
Rate
Rate
Rate
1
2
3
4
These five-digit entries are the flow rates at which
the meter factors (codes 302, 304, 306, 308) are
defined beginning with the highest flow rate in
program code 303 and descending to the lowest flow
rate in program code 309. If only one meter factor is
used, program code 303 or 305 must be set at "0".
The range of these entries is 0 to 99999 flow units.
Critical: Security level for parameter must be at top
2 levels. [Revision 5 and above firmware only]
Critical: Flow rates must be entered in descending
order
Critical:
Corresponding
meter
factor
not
programmed
Help: Enter the flow rate corresponding to the meter
factor.
Section VI Program Codes
Product 310 - Master Meter Factor
This program code allows the operator to set a
master meter factor. This six-digit entry will be used
to restrict meter factors one through four (codes 302,
304, 306 and 308), to plus or minus 2% of the
master factor (i.e., the value entered here). This
range restriction applies only to meter factors which
are programmed for use (i.e., meter factor one
always and, if linearizing, all the factors used). Any
attempt to enter a meter factor outside the 2% range,
if installed, will cause a Critical Warning.
In addition, a master factor entry that causes the
current meter factors installed to be out of range will
cause those meter factors which are out of range to
prompt a Critical Message. This critical condition must
be corrected so that all used meter factors are within
the 2% range of the master factor before normal Run
Mode operations can occur. The range of this entry is
0 to 9.99999. Note that an entry of zero disables the
master meter factor.
Critical: Security level for parameter must be at top
2 levels. [Revision 5 and above firmware only]
Critical: Meter factor must be within 2% of the
master meter factor
Help: Restricts programmed meter factors to + or
2% of this master factor
Product 311 - Linearized Factor
Deviation
This code allows the operator to set a maximum
deviation between adjacent meter factors. This three
digit entry will be used to restrict deviation between
the adjacent meter factors in use to plus or minus
the entered percentage (i.e., the value entered here).
Any attempt to enter a meter factor outside the
entered range will cause a Critical Warning.
Also, a linearized factor deviation entry that results in
the current meter factors installed to be out of range
will set a program code alarm. The meter factors that
are out of range will be indicated by a DA alarm. The
meter factors at fault must be corrected so they are
133
within range of the deviation entry before normal Run
Mode operations can occur. The value of the
linearized factor deviation may range from 0 to 9.99%.
Zero disables this feature.
Critical: Security level for parameter must be at top
2 levels. [Revision 5 and above firmware only]
Critical: Meter factor varies more than the
Linearized Factor Deviation
Help: Set the maximum deviation in percent allowed
between adjacent meter factors
Product 312 - Meter Factor Variation
Select
This parameter allows the selection of enabling or
disabling the meter factor variation entries
(calculations). When enabled the AccuLoad III will
calculate and use the meter factors based on the
current temperature of the product. The factory
default is "Disabled." Selections are as follows:
(0) Disabled
(1) Enabled
Critical: Security level for parameter must be at top
2 levels. [Revision 5 and above firmware only]
Help: Enable or Disable the use of meter factor
variation with temperature.
Product 313 - Meter Factor Percent
Change Per Degree Temperature
This four-digit parameter allows the entry of the
meter factor variation with temperature. This entry
represents the meter factor percent change per
degree of temperature. The range of this parameter
is 0.0001 to 0.9999 percent.
This parameter will not appear on the display unless
parameter 312 is enabled.
Critical: Security level for parameter must be at top
2 levels. [Revision 5 and above firmware only]
Fatal: Entry is out of specified range.
MN06118L Issue/Rev. 0.5 (4/02)
Help: Enter the meter factor variation in % change
per degree temperature.
Help:
Select
maintenance
temperature
if
temperature probe is not installed or to override the
probe
Product 314 - Meter Factor Variation
Reference Temperature
Product 402 High Temperature
Alarm Limit
This four-digit code allows the entry of the meter
factor reference temperature. This entry represents
the temperature, in tenths, at which the present
meter factor was determined. The range of this entry
is 000.1 to 999.9 units.
This code allows the entry of a temperature reading
that will cause a high temperature alarm to be
generated. The temperature units will be dependent
on the entry made in the Temperature Scale Select
code. This four-digit entry has a range of 999.9 to
+999.9 degrees F or C.
This parameter will not appear on the display unless
parameter 312 has been enabled.
Critical: Security level for parameter must be at top
2 levels. [Revision 5 and above firmware only]
Fatal: Entry is out of specified range.
Help: Enter reference temperature for the meter
factor percent change per degree.
Product 400 Temperature/Density
Directory
401 Maintenance Temperature
402 High Temperature Alarm Limit
403 Low Temperature Alarm Limit
411 API Table
412 Reference Density
413 High Density Alarm Limit
414 Low Density Alarm Limit
Product 401 Maintenance
Temperature
This code allows the entry of a maintenance
temperature to be used when a temperature probe is
not installed or working, but temperature related
calculations are desired. The temperature units are
dependent on the entry made in the Temperature
Scale Select code. This four-digit entry has a range
of 999.9 to 999.9 temperature units where 999.9
disables the maintenance temperature.
Note: An entry greater than -999.9 will override the
temperature probe or transducer input if installed and will
be used in all calculations where temperature is used.
No-entry if Temperature Units = Not Used
Note: An entry of "+999" will disable the alarm.
Help: Enter temperature that will signal an
alarm for high product temperature
Product 403 Low Temperature
Alarm Limit
This code allows the entry of a temperature reading
that will cause a low temperature alarm to be
generated. The temperature units will be dependent
on the entry made in the Temperature Scale Select
code. This four-digit entry has a range of 999.9 to
+999.9 degrees F or C.
Note: "-999" will disable the alarm.
No-entry if Temperature Units = Not Used
Help: Enter temperature that will signal an alarm for
low product temperature.
Product 411 API Table
This entry selects the API Table and product to be
selected. Selections are as follows:
(0) Not used
(1) 5A
(2) 5B
(3) 5D
(4) 6
(5) 6A
(6)6B
(7) 6C
(8) 6D
(9) 23
(10) 23A
(11) 23B
(12) 23D
(13) 24
Section VI Program Codes
(14) 24A
(15) 24B
(16) 24D
(17) 53
(18) 53A
(19) 53B
(20) 53D
(21) 54
(22) 54A
(23) 54B
(24) 54C
(25) 54D
Critical: Selected API table conflicts with
temperature units
Critical: No density input configured [odd tables
only]
No-entry if Temperature Units = Not Used
Help: Select the API table to be used for
temperature compensation.
Product 412 Reference Density
This code has a constant five-digit entry with a
floating decimal point and the format is based on the
table and product selection. The program code
format and data entry will allow the programmable
entry of the Reference Density when table 54 is
selected, Relative Density when table 24 is selected,
API when table 6 is selected, and temperature
coefficient when a C table is selected. This five-digit
entry represents the reference value used to
calculate the volume correction factor. The range of
this value will vary with the table selection chosen.
Note: When table 6 is selected, the leading digit will be
used to show polarity, + = positive and a - = negative.
Entry range based on table selection.
Table 6 -999.9 to +999.9 API
Table 24
0 to 9.9999 Relative Density
Table 54
0 to 9999.9 Reference Density
C Tables
0 to 0.9999 Percent per Degree
Temperature
135
Note: If the API table selection is changed, the previous
five-digit entry for reference will not be converted. This
value must be re-entered.
The following are examples of the display when
Tables 24, 54 or 6C and 54C are selected.
Table 6B selected: +0.85 API
Table 24 selected: 0.9875 Rel Density
Table 54 selected: 1150.2 Kg/M3
Table 6C or 54C selected: 0.9875 %/Deg. F or Deg. C
No-entry if Density Units = Not Used or if odd API
Table is selected
Help: Enter the product density at reference
temperature or the temperature coefficient (for C
tables).
Product 413 - High Density Alarm
Limit
This code allows the entry of a density reading that
will cause a high-density alarm to be generated. The
units will be dependent on the entry made in the
Density Units Select code. This four-digit entry will
be dependent on the API table selection as follows:
999.9 to +999.9 API
0 to 9999.0 Reference Density
No-entry if Density Units = Not Used
Help: Enter density that will signal an alarm for high
product density.
Product 414 Low Density Alarm
Limit
This code allows the entry of a density reading that
will cause a low-density alarm to be generated. The
units will be dependent on the entry made in the
Density Units Select code (System 403). This fivedigit entry will be dependent on the API table
selection as follows:
999.9 to +999.9 API
0 to 9999.0 Reference Density
MN06118L Issue/Rev. 0.5 (4/02)
No-entry if Density Units = Not Used
Help: Enter density that will signal an alarm for low
product density.
Product 500 Pressure Directory
501 Maintenance Pressure
502 Pressure Coefficient
503 High Pressure Alarm Limit
504 Low Pressure Alarm Limit
511 Differential Pressure
512 Minimum Back-pressure Flow Rate
513 Minimum Back-pressure Flow Rate Timer
514 Back-pressure % Reduction
515 Back-pressure Flow Recovery Pressure
516 Back-pressure Flow Recovery Timer
521 Vapor Pressure Calculation Method
522 Vapor Pressure 1
523 Vapor Pressure Temperature 1
524 Vapor Pressure 2
525 Vapor Pressure Temperature 2
526 Vapor Pressure 3
527 Vapor Pressure Temperature 3
Product 501 Maintenance Pressure
This code allows the entry of a maintenance
pressure to be used when a pressure transmitter is
not installed or working, but pressure-related
calculations are desired. The pressure units will be
dependent on the entry made in the Pressure Scale
Select code (System 501). This five-digit entry has a
range of 0.0 to 9999.9 pressure units. A nonzero
value entered here will override an analog pressure
input.
No-entry if Pressure Units = Not Used
Help: Select maintenance pressure if pressure
probe is not installed or to override probe
the compressibility factor. If, however, API table 6C
or 54C is selected, then a compressibility factor must
be entered here if pressure compensation is desired,
as the AccuLoad has no density with which to
calculate the compressibility factor. The factor is
used as the following: XXXXX equals the factor
entered and it is applied as 0.0000XXXXX.
Note: This value will represent the "F" variable in the CPL
equation.
No-entry if Pressure Units = Not Used
Help: Enter compressibility factor used to calculate
CPL, where 0.0000XXXXX is the compressibility
factor.
Product 503 High Pressure Alarm
Limit
This code will allow for the entry of the pressure
reading that will cause a High Pressure Alarm to be
generated. The pressure units will be dependent on
the entry made in the Pressure Scale Select code.
This four-digit entry has a range of 0 to 9999
pressure units.
No-entry if Pressure Units = Not Used
Help: If pressure exceeds this value an alarm will
occur
Product 504 Low Pressure Alarm
Limit
This code will allow for the entry of the pressure
reading which will cause a Low Pressure Alarm to be
generated. The pressure units will be dependent on
the entry made in the Pressure Scale Select code.
This four-digit entry has a range of 0 to 9999
pressure units.
No-entry if Pressure Units = Not Used
Help: If pressure drops below this value an alarm
will occur
Product 502 Pressure Coefficient
This code will allow for the entry of a Compressibility
Factor that will be used by the system to calculate
the CPL. This entry should be zeroed if a
densitometer is installed or a reference density is
entered. In these cases, the AccuLoad will calculate
Product 511 Differential Pressure
This three-digit entry will allow the operator to select
the delta pressure, in PSIA, bars, kPa or kg/cm 2
(units dependent on the Pressure Units Select
entry). This is the additional pressure to be
Section VI Program Codes
maintained above the vapor or back-pressure. If
AccuLoad III is controlling flow with a two-stage valve,
no alarm is issued and flow is not halted if the
pressure drops below the programmed limit
determined by the vapor pressure and differential
pressure. Therefore, this Differential Pressure feature
should not be used with a two-stage valve. In this
situation, the low-pressure alarm must be set high
enough to ensure that the pressure does not fall
below the product's vapor pressure.
The range of this entry will be 0 to 9999 pressure
units. An entry of 0 will disable pressure control of
the valve by a pressure transducer.
Note: A non-zero entry here will override any other
programmed type of back-pressure flow control.
Help: Enter back-pressure to be maintained above
product vapor pressure
Product 512 - Minimum Backpressure Flow Rate
This four-digit entry will allow the operator to select
the Minimum Back-pressure Flow Rate that will not
cause an alarm. That is, anytime the flow rate is
being controlled because of insufficient backpressure and it falls below this programmed rate, a
back-pressure alarm will be issued and the valve will
be closed. The range of this entry will be 0 to 9999.
Help: Minimum flow rate allowed during backpressure control before alarm.
Product 513 - Minimum Backpressure Flow Rate Timer
This two-digit entry will allow the operator to select
the minimum time, in seconds, allowed for the unit to
achieve a desired flow rate. If the flow rate is not
reached in this time, the flow rate will be lowered by
a percentage because of insufficient back-pressure.
(This percentage may be programmed in the Backpressure Reduction, Code 504). If the flow rate falls
below the back-pressure minimum flow, an alarm will
be issued and the valve will be closed. The range of
this entry will be 0 to 99 seconds.
137
If a differential pressure is entered in Product 511,
this pressure must be attained within this time period
after a flow rate change. If not, the flow rate will be
lowered due to insufficient back-pressure.
Note: This entry is used for Automatic Flow Optimization
(AFO).
Note: "00" disables any back-pressure control (including
the differential pressure method.)
Help: Minimum time in seconds to reach desired
flow rate during back-pressure control.
Product 514 - Back-pressure %
Reduction
This two-digit entry will allow the operator to select
the percentage of flow rate to be used during
insufficient back- pressure conditions or insufficient
flow conditions. (For example, an entry of 90% will
cause the flow rate to be reduced to 90% of the
current rate during insufficient back-pressure
conditions.) The range of this entry is 50 to 90
percent.
Note: This entry is used for Automatic Flow Optimization
(AFO).
Help: In back-pressure control, the flow rate will be
reduced to this percentage of the current flow rate.
Range is 50% to 90%
Product 515 - Back-pressure Flow
Recovery Pressure
This four-digit entry allows the programming of the
amount of pressure above the vapor pressure of the
product that must be read by the AccuLoad III before
it will attempt flow recovery to the programmed high
flow. The range of this entry is from 0 to 9999
pressure units. This parameter is used in conjunction
with a pressure transmitter input. Note that this
pressure must be sufficiently higher than the
differential pressure entered in Product 511 to
prevent flow rate oscillation.
Help: Enter the differential pressure above vapor
pressure to attempt flow recovery
MN06118L Issue/Rev. 0.5 (4/02)
Product 516 - Back-pressure Flow
Recovery Timer
This two-digit entry programs the amount of time the
AccuLoad III will wait to attempt flow rate recovery if
a pressure reading is not available in the system.
The range of this timer is from 0 to 99 minutes. Zero
will disable the flow recovery feature. This parameter
provides a method of flow recovery that does not
require the use of a pressure transmitter input.
Help: Enter the time interval in minutes to attempt
flow recovery.
Product 521 - Vapor Pressure
Calculation Method
This parameter defines the method that the
AccuLoad III will use to calculate the vapor pressure
of a product. Selections are as follows:
(0) Straight Line Approximation (Requires points
of the curve to be entered in codes 522 through
527).
(1) As outlined in GPA TP-15 (Gas Processors
Association Technical Publication 15). (Uses the
reference density of the product in the
calculations).
Critical: GPA-TP15 requires corrected density
[temp. used, API table selected]
Help: Choose vapor pressure calculation method.
Product 522, 524, 526 - Vapor
Pressure
These three codes allow the operator to select the
vapor pressures, which are used to define the vapor
pressure versus temperature curve. This curve is
used to calculate the current vapor pressure. The
pressure(s) are defined beginning with the lowest
pressure ascending to the highest pressure. The
range of these entries is 0 to 9999.9 pressure units.
The unit for this entry is dependent on the entry
made in the Pressure Units Select Code. The vapor
pressure calculation, determined from the entries
made here, will be used both for differential backpressure control and in the CPL equation as the "Pe"
entry. Therefore, careful consideration should be
given in determining these points and their accuracy.
Critical: Vapor pressures must be entered in
ascending order
No-entry if Vapor Pressure Calculation Method =
GPA-TP15
Help: Enter vapor pressure at corresponding product
temperature.
Product 523, 525, 527 - Vapor
Pressure Temperature
These three codes, with four-digit entries, allow the
operator to select the temperatures that will be used
to define the vapor pressure versus temperature
curve. This curve is used to calculate the current
vapor pressure. These temperatures correspond
with the vapor pressures. The range of these entries
is
+999 degrees to -999 degrees. The units for these
entries is as programmed in the Temperature Units
Select Code. The vapor pressure calculation,
determined from the entries made here, will be
used both for differential back-pressure control
and in the CPL equation as the "Pe" entry.
Therefore, careful consideration should be
given in determining these points and their
accuracy.
Critical: Corresponding vapor pressure not
programmed
No-entry if Vapor Pressure Calculation Method =
GPA-TP15
Help: Enter product temperature at corresponding
vapor pressure.
Recipe Directory
--01 Recipe Used
--02 Recipe Name
--03 HM Classification
--04 First Product Delivered
--05 First Product Percentage
--06 Second Product Delivered
--07 Second Product Percentage
--08 Third Product Delivered
--09 Third Product Percentage
--10 Fourth Product Delivered
--11 Fourth Product Percentage
Section VI Program Codes
--12 Fifth Product Delivered
--13 Fifth Product Percentage
--14 Injector 1 Volume
--15 Injector 1 Rate
--16 Products Using Injector 1
--17 Injector 2 Volume
--18 Injector 2 Rate
--19 Products Using Injector 2
--20 Injector 3 Volume
--21 Injector 3 Rate
--22 Products Using Injector 3
--23 Injector 4 Volume
--24 Injector 4 Rate
--25 Products Using Injector 4
--26 Injector 5 Volume
--27 Injector 5 Rate
--28 Products Using Injector 5
--29 Injector 6 Volume
--30 Injector 6 Rate
--31 Products Using Injector 6
--32 Injector 7 Volume
--33 Injector 7 Rate
--34 Products Using Injector 7
--35 Injector 8 Volume
--36 Injector 8 Rate
--37 Products Using Injector 8
--38 Injector 9 Volume
--39 Injector 9 Rate
--40 Products Using Injector 9
--41 Injector 10 Volume
--42 Injector 10 Rate
--43 Products Using Injector 10
--44 Injector 11 Volume
--45 Injector 11 Rate
--46 Products Using Injector 11
--47 Injector 12 Volume
--48 Injector 12 Rate
--49 Products Using Injector 12
--50 Clean Line Deduct
(0) Not used
(1) Load Arm 1
(2) Load Arm 2
Critical: Load Arm not configured.
Help: Select whether this recipe is to be enabled for
use or not.
Yes
Recipe x01 - Recipe Used
This program code indicates whether a recipe is
configured for use. Selections are as follows:
139
MN06118L Issue/Rev. 0.5 (4/02)
Recipe x02 - Recipe Name
This program code allows an entry of up to nine
characters. It is used as an identifier of the blend
recipe in the preset display and on the product
receipt ticket. The data entry allows the following
characters to be selected as part of the name:
ABCDEFGHIJKLMNOPQRSTUV
WXYZ#*
abcdefghijklmnopqrstuvwxyz&
@
0 1 2 3 4 5 6 7 8 9 < > ( ) ? ! . , - / + = _END
Help: Enter a nine-character alphanumeric message
to identify this recipe.
Recipe x03 HM Classification
This code assigns a product Hazardous Materials
(HM) Classification to the recipe. This HM
Classification will print on the load ticket for this
recipe. HM Classifications are defined in the
individual product directories. Selections are as
follows:
(0) Product 1
(1) Product 2
(2) Product 3
(3) Product 4
Critical: Product not configured.
Help: Select product HM Class for this recipe.
Recipe x04, x06, x08, x10, x12
Product Delivered
Sequential Blending: These program codes select
the components in the order they are to be delivered
for this recipe. Recipe x04 is the first product to be
delivered, x06 is the second product to be delivered,
x08 is the third product to be delivered, x10 is the
fourth product to be delivered, and x12 is the fifth
product to be delivered. Selections are as follows:
(0) Not Used
(1) Product 1
(2) Product 2
(3) Product 3
(4) Product 4
Help: Select the components in the order to be
delivered for the recipe.
Recipe x05, x07, x09, x11, x13
Product Percentage
These program codes allow for the percentage of
products to be used in a recipe to be defined. The
percentage entered here represents the portion of
the total batch that is to be contributed by this
product. The percentages of the four products (or
five components) must add up to one hundred
percent; otherwise, a critical warning will be issued.
The range of this entry is 000.0 to 100.0, where 0
would mean that this product is not to be included in
the recipe, and 100.0 would mean that the recipe
was to consist entirely of this product.
Ratio Blending: Program code x05 is the percentage
of product 1, code x07 is the percentage of product
2, code x09 is the percentage of product 3, and x11
is the percentage of product 4.
Sequential Blending: Program
percentage of component 1,
percentage of component 2,
percentage of component 3,
percentage of component 4,
percentage of component 5.
code
code
code
code
and
x05
x07
x09
x11
x13
is
is
is
is
is
the
the
the
the
the
Critical: Component percentages must sum to
100%.
Help: SEQ: Enter first component percentage of
batch; RATIO: Enter Product 1 percentage of batch
Recipe x14, x17, x20, x23, x26, x29,
x32, x35, x38, x41, x44, x47
Injector Volume
These six-digit codes define the volume of additive
product that will be injected for each cycle of additive
injector (e.g., an entry of 000.100 shows that one
tenth of a unit of product will be injected each cycle
of the injector). The range of this program code is 0
to 999.999.
Section VI Program Codes
For piston or metered injectors, the units for this
additive volume are as programmed in system code
881. For smart injectors, this is the number
downloaded to the smart injector. The units may be
fixed or programmed on the smart injector.
Code Function
x16
Additive Injector 1
x19
Additive Injector 2
x22
Additive Injector 3
x25
Additive Injector 4
x28
Additive Injector 5
Some additive injectors do not support the full range
that we have offered here. Titan injectors accept only
whole numbers for the volume. Smith Meter and
Gate City injectors (Blend-Pak, Mini-Pak, and
AccuTroller) accept injector volume in tenths. The
AccuLoad III will truncate the entry to the format
required for the smart injector.
x31
Additive Injector 6
x34
Additive Injector 7
x37
Additive Injector 8
x40
Additive Injector 9
Help: Enter the additive volume delivered per
injector cycle.
x43
Additive Injector 10
x46
Additive Injector 11
x49
Additive Injector 12
When using a Smart Additive Injector System the
additive injector volume is downloaded to the
additive injector at the start of each batch.
Recipe x15, x18, x21, x24, x27, x30,
x33, x36, x39, x42, x45, x48
Injector Rate
This parameter is used to define the rate at which
additive is injected into the product stream during
delivery. This is the volume of product per additive
injection, typically 40 gallons or 100 liters. The range
of this program code is 0 to 999 volume units.
Help: Enter the additive injector rate, in product
volume per injection
Recipe x16, x19, x22, x25, x28, x31,
x34, x37, x40, x43, x46, x49
Product Using Injector
This entry is used to select whether this injector is to
be used with this recipe and with which products it
will be used. Each of the twelve possible injectors
may be used with the products being loaded in this
recipe.
Note: When an additive is selected to be paced by more than one
product, the additive output will be the result of the combined
volumes of the products selected.
141
Select the products whose delivered volumes should
be used in pacing this injector.
Help: Select the products using this injector
Recipe 50 Clean Line Deduct
This program code allows the selection of the
product from which the clean line volume (if
installed) is to be deducted. In the Ready Mode,
when a recipe is selected and a preset amount is
entered, the preset is divided among the products
according to the percentages programmed in the
recipe. The clean line volume is deducted from the
preset volume of the product selected here. If the
product selected is not part of this recipe, a critical
warning will be issued. The range of this entry is one
through four.
MN06118L Issue/Rev. 0.5 (4/02)
Note: Zero may be entered if no clean line volume is
installed.
For example, assume a recipe with 50% of products
1 and 2. The clean line is 50 gallons of product 4. A
preset of 1000 gallons is entered. This preset is
divided among products 1 and 2: 500 gallons each.
If product 1 is selected here as the product from
which to deduct clean line, then the product 1 preset
would be 500 50 = 450 gallons. When START is
pressed, products 1 and 2 would deliver 450 gallons
and 500 gallons, respectively. When products 1 and
2 have been delivered, 50 gallons of the clean line
product (product 4) will be delivered.
Help: Select the product the clean line volume is
deducted from
Minimum Recipe Preset (Read Only)
This display shows the minimum volume of this
recipe that can be delivered. This is a read only
program code. When presetting a batch, the entered
preset is compared with the recipe minimum preset
that is displayed here. If the entered preset is less
than the minimum, a warning message will be
displayed and the batch will not be delivered until the
preset amount has been corrected.
The minimum preset is calculated using the
percentages programmed in the recipe and the
minimum product batch or second trip amount
associated with each product. In the formulas below,
if the minimum product batch is less than the second
trip volume, the second trip will be used.
If clean line is not installed:
Minimum Preset =
Minimum Product Batch
% of Product Programmed
The minimum preset is calculated for each product
in the recipe. The greatest value calculated is
displayed here as the Recipe Minimum Preset.
If clean line is installed:
Minimum Preset =
Minimum Product Batch
% of Product Programmed
For the product selected as the product from which
to deduct clean line:
Minimum Preset =
Clean Volume + Minimum Product Batch
% of Product Programmed
The minimum preset is calculated for all products.
The greatest value calculated is displayed here as
the Recipe Minimum Preset.
Product Flow Rates (Read Only)
This read only display shows the calculated flow
rates for this recipe. The flow rates are read, from
left to right, first high flow, second high flow, and low
flow rate. These rates are calculated based on the
percentages of the products in the recipe, the arm
high flow rate and low flow start rates and the
products' minimum and high flow rates. These flow
rates are only displayed for a ratio blender.
Recipe5MinimumPreset60
RecalculatedFlowRates
P1
Hi
450
2nd
P2
Hi
50
2nd
0
0
Lo
Lo
150
0
Section VII Appendix
Appendix I Audit Trail
This Appendix explains the Audit Trail and how to
access it.
The Audit Trail can be viewed when the AccuLoad III
is in the Ready Mode or the Run Mode. When in the
Ready Mode pressing either CLEAR or ENTER will
display the main menu. When the main menu is
displayed choose the Diagnostic Menu by using the
arrow keys on the keypad.
MainMenu
DynamicDisplays
PrintMenu
ProgramModeMenu
DiagnosticsMenu
>
If the AccuLoad is in the Run mode, pressing the
ENTER key will display the Dynamic Display menu
from which the Read Only Diagnostics may be
accessed.
DynamicDisplays
System
Batch
Transaction
Diagnostics
>
The Diagnostics menu that is available through the
Dynamic Display or the main menu consists of the
following options. Move the cursor to the Audit Trail
using the up or down arrow.
Active Alarms
Alarm History
Non-Reset Volumes
Event Log
Transaction Log
Audit Trail
Digital Inputs
Digital Outputs
Analog Inputs
Pulse Inputs
View Turbine Meter Data
Comm Monitor
CIVACON Overfill Monitor
Boolean Algebraic
Software Version
Factory Diagnostics
Audit Trail
The View Only Diagnostics menu provides the
selection "Audit Trail" where audit trail data is
available for viewing. With the arrow in front of "Audit
Trail," pressing ENTER will display the last audit trail
entry that occurred in the AccuLoad.
AuditTrailEntry#226
09/03/99
ProgramModeExit
ThroughKeypad
1NoSecurity
0Disabled
Where 321 is the program code modified
0 is constant (reserved for future use)
00 indicates that it is a system parameter
1 No Security is the old program value and
0 Disabled is the new program value.
17:25:02
AuditTrailEntry#224
The audit trail provides the date, time, and
description of what event occurred. Pressing the up
and down arrows on the keypad will allow the
operator to step through the audit trail.
AuditTrailEntry#225
09/03/99
000321
17:24:58
09/03/99
ProgramModeExit
ThroughKeypad
11:24:45
When finished with the Audit Trail displays pressing
the CLEAR key will return the display to the
Diagnostic menu.
Appendix II - Alarms
Table of Equivalent Error Codes
Blend-Pak Injector From the
Blend-Pak's Point of View
AccuLoad III Equivalent Error Code
Excess Additive
RA: Additive Freqency Alarm
No Additive Flow
NA: No Additive Pulses Alarm
No Fuel Flow
GA: Additive Injector Error
Low Additive
KA: Low Additive Volume
Leaking Solenoid
MA: Excess Additive Pulses
No Activity Time Out
GA: Additive Injector Error
Fuel Flow Switch Failure
GA: Additive Injector Error
Low Flow Switch Failure
GA: Additive Injector Error
Flash Volume Alarm
GA: Additive Injector Error
Mini-Pak Injector/AccuTroller From the
Mini-Pak/AccuTroller's Point of View
AccuLoad III Equivalent Error Code
Additive Cycle Volume Alarm
GA: Additive Injector Error
No Additive Alarm
NA: No Additive Pulses Alarm
Leaking Solenoid
MA: Excess Additive Pulses
Firmware Failure
GA: Additive Injector Error
Section VII Appendix
EEPROM Failure
GA: Additive Injector Error
Metered Injector If this happens
AccuLoad III This alarm occurs
Injections are occurring too fast
OR: Overspeed Injector
No additive pulses are registering
NA: No Additive Pulses Alarm
Out of tolerance high
RA: Additive Frequency Alarm
Out of tolerance low
KA: Low Additive Volume
Leaking solenoid
MA: Excess Pulses
Add-Pak Injector
If this happens
AccuLoad III This alarm occurs
Add-Pak Alarms - Alarms
appearing on the Add-Pak
Injections are occurring too fast
OR: Overspeed Injector
Overspeed Injector
No additive pulses are registering
NA: No Additive Pulses Alarm
No Additive Flow
Out of tolerance high
RA: Additive Frequency Alarm
Excess Additive
Out of tolerance low
KA: Low Additive Alarm
Low Additive
Leaking Solenoid
MA: Excess Pulses
Leaking Solenoid
Titan Injector From the
Titan's Point of View
AccuLoad III Equivalent Error Code
Alarm Low 1
RA: Additive Frequency Alarm
Alarm Low 2
KA: Low Additive Volume
Pulse Detection
NA: No Additive Pulses Alarm
Alarm High
MA: Excess Additive Pulses
Product Pulse Failure
GA: Additive Injector Error
Unclean Product
GA: Additive Injector Error
Injector Alarm Grid on the AccuLoad III
Piston
Piston w/
Feedback
Metered
Titan
Blend-Pak
MiniPak/
AccuTroller
Add-Pak
(AICB)
FA: Additive
Feedback Alarm
N/A
Not displayed
N/A
N/A
N/A
N/A
N/A
AC: Additive
Communications
N/A
N/A
N/A
Not displayed
Not displayed
Not displayed
Not displayed
KA: Low Additive
Volume
N/A
N/A
Not displayed
Alarm Low 2
Low Additive
N/A
Low Additive
MA: Excess
Additive Pulses
N/A
N/A
N/A
High Alarm
Leaking
Solenoid
Leaking
Solenoid
Leaking
Solenoid
NA: No Additive
Pulses Alarm
N/A
N/A
Not displayed
Pulse
Detection
No Additive
Flow
No Additive
No Additive
Flow
RA: Additive
Frequency Alarm
N/A
N/A
Not displayed
Alarm Low 1
Excess
Additive
N/A
Excess
Additive
UA: Add Authorize
Failed
N/A
N/A
N/A
Not displayed
Not displayed
Not displayed
Not displayed
GA: Additive
Injector Error
N/A
N/A
N/A
Varies
Varies
Varies
N/A
OR: Overspeed
Injector
N/A
N/A
Not displayed
N/A
N/A
N/A
Overspeed
Injector
CR: Injector
Command Rejected
N/A
N/A
N/A
Not displayed
Not displayed
Not displayed
Not displayed
AD: Injector Auto
Detect Failed
N/A
N/A
N/A
Not displayed
Not displayed
Not displayed
Not displayed
AccuLoad III
Metered Injector Alarms
OR: Overspeed Metered Injector
This alarm occurs if an injection is attempted before the previous one is complete.
NA: No Additive Pulses Alarm
This alarm occurs if an injection is attempted, but the previous injection is still in progress and no pulses have
been registered.
RA: Additive Frequency Alarm
Section VII Appendix
This alarm occurs when the meter consistently falls out of programmed tolerance a programmed number of times,
and the additive volume is too high.
KA: Low Additive Volume
This alarm occurs when the meter consistently falls out of programmed tolerance a programmed number of times,
and the additive volume is too low.
Appendix III Metered Injector Map on the AccuLoad III with ALS1 and
ALD1 Firmware
Injector #
(AccuLoad)
Communications
Address
Board
J1 Address
Jumper on AICB
Board
Input Point
(AICB)
Output Points
(AICB)
N/A
AccuLoad
N/A
N/A
N/A
N/A
AccuLoad
N/A
N/A
N/A
101
AICB #1
Out
Pump = 1
Solenoid = 2
102
AICB #1
Out
Pump = 3
Solenoid = 4
103
AICB #1
Out
Pump = 5
Solenoid = 6
104
AICB #1
Out
Pump = 7
Solenoid = 8
105
AICB #1
Out
Pump = 9
Solenoid = 10
106
AICB #1
Out
Pump = 11
Solenoid = 12
107
AICB #1
Out
Pump = 13
Solenoid = 14
10
108
AICB #1
Out
Pump = 15
Solenoid = 16
11
109
AICB #1
Out
Pump = 17
Solenoid = 18
12
110
AICB #1
Out
10
Pump = 19
Solenoid = 20
Note: Add-Pak parameters and mappings are fixed and are set automatically.
Note: If one Add-Pak injector is programmed to operate, then all addresses are reserved and may not be used for any other injector for the
entire system in an address bank. Banks are 100 through 110.
Note: When using ALD1 firmware, special attention should be paid to the Configuration 020 parameter (Number of Injectors). This number
provides the number of injectors to be used, starting at Injector #1 and running sequentially to Injector #12. If an injector number is not
programmed, its position is still counted.
Example: Only two injectors are needed and these are Add-Paks. Injector positions 5 and 6 are configured as Add-Pak injectors. The
parameter Configuration 020 must be set to at least 6, since the accounting starts at Injector #1 and continues sequentially to Injector #6.
Injectors 1 through 4 count against this number, even though they are not currently configured.
The following literature can be obtained from FMC Technologies Measurement Solutions, Inc. Literature
Fulfillment at [email protected] or online at www.fmctechnologies.com/measurementsolutions .
When
requesting literature from Literature Fulfillment, please reference the appropriate bulletin number and title.
Section VII Appendix
AccuMate for AccuLoad III
Specification......................................................................................................................... Bulletin SS06032
Installation/Operation........................................................................................................... Bulletin MN06121X
AccuLoad III ALS1 and ALD1
Specification......................................................................................................................... Bulletin SS06030
Installation/Operation........................................................................................................... Bulletin MN06108
AccuLoad III ALS1 and ALD1 Operator Reference..............................................................Bulletin MN06118L
Communications.................................................................................................................. Bulletin MN06119L
Modbus Communications..................................................................................................... Bulletin MN06120
AccuLoad III Upgrade
Specification......................................................................................................................... Bulletin SS06033
Installation............................................................................................................................ Bulletin MN06115
Revisions included in MN06118 Issue/Rev. 0.5 (4/02):
Added Mass Flow Rate displays
Added Load Arm 108 Flashing Totals
Added option for backup communications port
(All changes necessitated by release of Revision 10 firmware)
This document placed in LIMITED distribution1/27/11.