TP48300B-X6X0 & TP48600B-X6X0
V300R001
User Manual
Issue
02
Date
2012-12-04
HUAWEI TECHNOLOGIES CO., LTD.
Copyright Huawei Technologies Co., Ltd. 2012. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.
Trademarks and Permissions
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Huawei Technologies Co., Ltd.
Address:
Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China
Website:
http://www.huawei.com
Email:
support@huawei.com
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
TP48300B-X6X0 & TP48600B-X6X0
User Manual
About This Document
About This Document
Purpose
This document describes the TP48300B-X6X0 & TP48600B-X6X0 in terms of its features,
structure, components, installation, commissioning, and maintenance.
Intended Audience
This document is intended for:
Sales engineers
Technical support personnel
Maintenance personnel
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol
Description
Alerts you to a high risk hazard that could, if not avoided,
result in serious injury or death.
Alerts you to a medium or low risk hazard that could, if not
avoided, result in moderate or minor injury.
Alerts you to a potentially hazardous situation that could, if not
avoided, result in equipment damage, data loss, performance
deterioration, or unanticipated results.
Provides a tip that may help you solve a problem or save time.
Provides additional information to emphasize or supplement
important points in the main text.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
ii
TP48300B-X6X0 & TP48600B-X6X0
User Manual
About This Document
Change History
Changes between document issues are cumulative. The latest document issue contains all the
changes made in earlier issues.
Issue 02 (2012-12-04)
Port description is modified.
Issue 01 (2011-12-26)
This issue is the first official release.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
iii
TP48300B-X6X0 & TP48600B-X6X0
User Manual
Contents
Contents
About This Document .................................................................................................................... ii
1 Overview......................................................................................................................................... 1
1.1 Designation Explanation .................................................................................................................................. 1
1.2 Typical Application .......................................................................................................................................... 1
1.3 Features ............................................................................................................................................................ 2
1.4 Structure ........................................................................................................................................................... 3
2 Component Description............................................................................................................... 5
2.1 Cabinet ............................................................................................................................................................. 5
2.1.1 Appearance .............................................................................................................................................. 5
2.1.2 Features ................................................................................................................................................... 6
2.2 Rectifier ............................................................................................................................................................ 6
2.2.1 Appearance .............................................................................................................................................. 6
2.2.2 Panel........................................................................................................................................................ 7
2.2.3 Protection Mechanisms ........................................................................................................................... 8
2.2.4 Features ................................................................................................................................................... 8
2.3 Monitoring Unit ............................................................................................................................................... 8
2.3.1 Introduction ............................................................................................................................................. 8
2.3.2 PMU ...................................................................................................................................................... 10
2.3.3 UIM....................................................................................................................................................... 12
2.3.4 SNMP Module (Optional) ..................................................................................................................... 15
2.3.5 Querying alarms .................................................................................................................................... 15
2.3.6 Remote Software Upgrade .................................................................................................................... 17
3 Safety Precautions ....................................................................................................................... 20
3.1 Overview ........................................................................................................................................................ 20
3.2 Local Safety Regulations ............................................................................................................................... 20
3.3 Grounding Requirements ............................................................................................................................... 20
3.4 Human Safety ................................................................................................................................................. 21
3.5 Equipment Safety ........................................................................................................................................... 21
3.6 Electrical Safety ............................................................................................................................................. 21
4 Installation And Commissioning ............................................................................................ 24
5 Maintenance ................................................................................................................................. 25
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
iv
TP48300B-X6X0 & TP48600B-X6X0
User Manual
Contents
5.1 Routine Maintenance...................................................................................................................................... 25
5.2 Common Faults .............................................................................................................................................. 26
5.3 Troubleshooting Components......................................................................................................................... 32
5.4 Component Replacment ................................................................................................................................. 34
A Technical Specifications ........................................................................................................... 39
B LCD Menu ................................................................................................................................... 42
C Acronyms and Abbreviations .................................................................................................. 47
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
TP48300B-X6X0 & TP48600B-X6X0
User Manual
1 Overview
Overview
1.1 Designation Explanation
The TP48300B-X6X0 & TP48600B-X6X0 are alternating current (AC)-to-direct current (DC)
indoor power system and supply power to -48 V series communications equipment. The
TP48300B-X6X0 & TP48600B-X6X0 use 50 A rectifiers. The TP48300B-X6X0 provides a
maximum current of 300 A, and the TP48600B-X6X0 provides a maximum current of 600 A.
The TP48300B-X6X0 supports dual live wire (L1, L2, PE) AC input, and the
TP48600B-X6X0 supports three-phase-four-line (L1, L2, L3, PE) AC input.
1.2 Typical Application
The TP48300B-X6X0 & TP48600B-X6X0, AC power source, automatic transfer switch
(ATS), and storage batteries are combined to form a site power supply solution. Figure 1-1
shows the position of the TP48300B-X6X0 & TP48600B-X6X0 in a typical site solution.
Figure 1-1 Position of the TP48300B-X6X0 & TP48600B-X6X0 in a typical site solution
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
TP48300B-X6X0 & TP48600B-X6X0
User Manual
1 Overview
1.3 Features
The TP48300B-X6X0 & TP48600B-X6X0 support easy installation, intelligent hibernation,
network Management over the NetEco, and wide range of AC input voltage.
Easy Installation
The power monitoring unit (PMU) and rectifier are hot-swappable. This facilitates the system
installation, saves maintenance time, and reduces the operational expenditure (OPEX).
Intelligent Hibernation
The rectifier efficiency increases in proportion to the load power. When the total load power is
low, certain rectifiers can be hibernated to improve the load power of running rectifiers and
increase the rectifier efficiency. This facilitates energy conversation.
rectifiers should be hibernated in turn to ensure the same aging degree. When the started
rectifier with the longest running time in total runs for 7 days (by default) more than the
hibernated rectifier with the longest running time in total, start all rectifiers for 2 hours and
then hibernate the rectifiers with long running time.
High Efficiency
The TP48300B-X6X0 & TP48600B-X6X0 use rectifiers with a 91.5% efficiency record.
Low Imbalance Degree of Current Equalization
The imbalance degree of current equalization for rectifiers is less than 5%.
Remote Management
OPEX is reduced when the TP48300B-X6X0 & TP48600B-X6X0 performs comprehensive
power management and battery management functions by connecting to the element
management system (EMS).
Wide Range of AC Input Voltage
The AC input voltage of the TP48300B-X6X0 & TP48600B-X6X0 ranges from 85 V AC to
300 V AC phase voltage.
High-Level Regulatory Design
The TP48300B-X6X0 & TP48600B-X6X0 complies with Conformite Europeenne (CE)
standards, the power distribution components comply with CE standards, and the rectifier
complies with underwriters laboratory (UL), CE, and Technical Watch-Over Association
(TUV) standards.
Low Noise
The noise specifications comply with ETSI EN 300 753 Class 4.1 (rural environment).
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
TP48300B-X6X0 & TP48600B-X6X0
User Manual
1 Overview
Periodic Battery Test
The periodic battery test is used to test battery aging. The test allows storage batteries to be
fully charged automatically and then to discharge till the voltage reaches the value of Test End
Volt. The test is performed periodically (every 120 days by default).
1.4 Structure
Figure 1-2 shows the TP48300B-X6X0 & TP48600B-X6X0 interior.
Figure 1-2 TP48300B-X6X0 & TP48600B-X6X0 interior
(1) Positive DC output
busbar
(4) Battery route DC
Contactor
(7) AC input circuit breaker
(10) Battery low voltage
disconnection(BLVD)
circuit breaker
Issue 02 (2012-12-04)
(2) Battery fuse
(5) Battery switch
(8) Load low voltage
disconnection (LLVD) fuse
(11) PMU
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
(3) Load low voltage disconnection
(LLVD) DC Contactor
(6) Space for rectifier
(9) LLVD circuit breaker
(12) User interface module (UIM)
TP48300B-X6X0 & TP48600B-X6X0
User Manual
(13) Ground busbar
Issue 02 (2012-12-04)
1 Overview
(14) AC surge protection device
(SPD)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
TP48300B-X6X0 & TP48600B-X6X0
User Manual
2 Component Description
Component Description
2.1 Cabinet
2.1.1 Appearance
The TP48300B-X6X0 & TP48600B-X6X0 cabinet is made of steel. Dimensions (H x W x D)
of the TP48300B-X6X0 & TP48600B-X6X0 cabinet are 1600 mm x 600 mm x 450 mm
(62.99 in. x 23.62 in. x 17.72 in.).
Figure 2-1 shows the TP48300B-X6X0 & TP48600B-X6X0 cabinet.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
TP48300B-X6X0 & TP48600B-X6X0
User Manual
2 Component Description
Figure 2-1 TP48300B-X6X0 & TP48600B-X6X0 exterior
2.1.2 Features
The TP48300B-X6X0 & TP48600B-X6X0 cabinet has the following features:
All operations can be performed from the front of the cabinet.
The cabinet can be shipped together with boards.
2.2 Rectifier
2.2.1 Appearance
The rectifier converts AC power into stable -48 V DC power. The TP48300B-X6X0 can be
configured with 6 rectifiers based on the actual load power. The TP48600B-X6X0 can be
configured with 12 rectifiers based on the actual load power.
Figure 2-2 shows the rectifier.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
TP48300B-X6X0 & TP48600B-X6X0
User Manual
2 Component Description
Figure 2-2 rectifier
2.2.2 Panel
The rectifier panel provides the power light emitting diode (LED), protection LED, and fault
LED. Figure 2-3 shows the rectifier panel.
Figure 2-3 rectifier panel
(1) Power LED
(2) Protection LED
(3) Fault LED
Table 2-1 LED description
LED
Color
Normal
Status
Abnormal
Status
Exception Causes
Power
LED
Green
Steady
on
Off
The mains supply fails due to no
AC input, AC input overvoltage, or
AC input undervoltage.
The rectifier has no power output.
Overtemperature shutdown occurs.
The rectifier hibernates.
Protection
LED
Yellow
Off
Steady on
In this case, the protection LED is
on.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
TP48300B-X6X0 & TP48600B-X6X0
User Manual
2 Component Description
LED
Color
Normal
Status
Abnormal
Status
Exception Causes
Fault LED
Red
Off
Steady on
The rectifier has no power output due
to output overvoltage shutdown, fan
failure, overtemperature shutdown, or
rectifier failure. If the unavailable
power output is caused by a mains
supply failure due to AC input
absence, AC input overvoltage, or AC
input undervoltage, the fault LED does
not illuminate, either.
2.2.3 Protection Mechanisms
The TP48300B-X6X0 & TP48600B-X6X0 supports the following protection mechanisms:
Input overvoltage protection
Input undervoltage protection
Input overcurrent protection
Output overvoltage protection
Output short circuit protection
Output current limiting protection
Overtemperature protection
2.2.4 Features
The rectifier provides the following features:
High power density
Stable operation
Intelligent hibernation
Hot swappable
2.3 Monitoring Unit
2.3.1 Introduction
In the middle is the PMU, on the left are the BLVD switch and AC detection board, and on the
right is the UIM. Figure 2-4 shows the monitoring unit subrack.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
TP48300B-X6X0 & TP48600B-X6X0
User Manual
2 Component Description
Figure 2-4 Monitoring unit subrack
Table 2-2 lists the structural specifications of the monitoring unit subrack.
Table 2-2 Structural specifications of the monitoring unit subrack
Item
Description
Dimensions (H x W x D)
86.1 mm x 442 mm x 226 mm (3.89 in. x 17.40 in. x 8.90 in.)
Installation scenario
19-inch rack
Maintenance mode
Maintained from the front
The monitoring unit consists of a PMU, a UIM, an AC detection board, an SNMP module
(optional), and a monitoring signal transfer board. Table 2-3 describes these components.
Table 2-3 Component description
Component
Description
Monitoring signal
transfer board
The monitoring signal transfer board is vertically installed in the
innermost of the monitoring unit subrack, and provides conversion
ports for the PMU, UIM, and other components of the
TP48300B-X6X0 & TP48600B-X6X0. The monitoring signal
transfer board connects to the power distribution with mechanical
switch (PDM), AC detection board, and power subrack over cables
and to the UIM and function extended board over 96-pin
connectors.
PMU
The PMU, which is hot-swappable, connects to the monitoring
signal transfer board over a 125-pin connector to perform
monitoring functions.
UIM
The UIM provides various ports such as the temperature and
humidity detection port, Boolean value input port, dry contact
output, and communications port. The UIM connects to the
monitoring signal transfer board over a 96-pin connector.
AC detection board
The AC detection board detects single-phase AC voltage and passes
signals to the monitoring signal transfer board over a cable.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
TP48300B-X6X0 & TP48600B-X6X0
User Manual
2 Component Description
Component
Description
SNMP module
(optional)
The RS485/232 port is connected to the fast Ethernet (FE) port on
the SNMP module for remote management and management of the
TP48300B-X6X0 & TP48600B-X6X0.
2.3.2 PMU
NOTE
All ports in this manual are protected by a security mechanism.
The PMU manages the TP48300B-X6X0 & TP48600B-X6X0 and storage batteries by
communicating with the host over an RS485/232 port. It detects power distribution and
generates alarms for power distribution failures. It also reports spare boolean values, ambient
temperatures and humidity status, battery temperatures, and spare analog parameters. Spare
boolean values and detection results from sensors are transferred to the PMU over the
monitoring signal transfer board and UIM.
The PMU implements local management, remote communication, and alarming functions. It
communicates with the element network system (EMS) by using the RS485 or RS232
protocol. It can also communicate with third-party equipment. The PMU can be connected to
a modem or an SNMP module.
The liquid crystal display (LCD) of the PMU displays operating parameters about the AC
power supply, DC power supply, rectifiers, and storage batteries. It also displays the operating
status and alarm status of the TP48300B-X6X0 & TP48600B-X6X0. You can set parameters
and control functions on the LCD using the four buttons on the PMU panel.
Figure 2-5 shows the PMU panel.
Figure 2-5 PMU panel
Table 2-4 lists the structural specifications of the PMU.
Table 2-4 Structural specifications of the PMU
Item
Specifications
Weight
2 kg (4.41 lb)
Dimensions (H x W x D)
40.8 mm x 100 mm x 205.3 mm (1.61 in. x 3.94 in. x 8.08 in.)
Table 2-5 describes the buttons on the front panel.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
10
TP48300B-X6X0 & TP48600B-X6X0
User Manual
2 Component Description
Table 2-5 Button description
Button
Description
or
Allows you to view menu items and set the value of a menu item.
Enter
Enters the main menu from the standby screen, enters a submenu from the
main menu, or saves the settings of a submenu item.
Cancel
Returns to the previous menu without saving the settings of the current menu
item.
NOTE
The backlight turns off if the liquid crystal display (LCD) of the CPMU01 is left unattended for eight
minutes. The standby screen is displayed if the LCD is left unattended for five minutes.
On the standby screen, press +Enter to decrease the LCD contrast, and press +Enter to increase
the LCD contrast.
The preset customer password is 0#, and Huawei engineer password is11#.
The PMU supports environment monitoring, alarm management, battery management,
rectifier management, and power distribution management on its LCD or the EMS.
Table 2-6 PMU functions
Function
Description
Battery
management
Load high temperature disconnection
Battery high temperature disconnection
Battery boost charge management
Battery floating charge management
Battery discharge test
Battery temperature compensation
AC input voltage detection
Load current detection
Battery string current detection
DC busbar voltage detection
Battery temperature detection
Ambient humidity detection
Ambient temperature detection
Spare analog parameter detection
Remote
detection
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
11
TP48300B-X6X0 & TP48600B-X6X0
User Manual
2 Component Description
Function
Description
Remote
management
rectifier startup and shutdown
rectifier boost charge and floating charge
rectifier voltage adjustment
rectifier current limiting
Battery connection and disconnection
Current limiting for storage batteries when the diesel generator (D.G.)
is started
Buzzer control
Dry contact outputs (including one dry contact output for detecting the
D.G.)
Remote
communication
Mains fault; mains overvoltage and undervoltage; DC overvoltage and
undervoltage; load fuse blown; charge overcurrent; battery disconnection
(by the EMS or due to overtemperature or undervoltage); overhigh
ambient temperature; over low ambient temperature; No. n rectifier fault;
No. n rectifier protection; rectifier output current reporting; battery loop
broken; SPD fault; door status sensor alarm; water sensor alarm; smoke
sensor alarm; Boolean value input
The PMU panel has a RUN indicator and an ALM indicator, which show the working status
of the TP48300B-X6X0 & TP48600B-X6X0. In addition, the PMU has a buzzer. Table 2-7
describes the indicators on the PMU panel.
Table 2-7 Indicators on the PMU
Indicator
Status
Description
RUN indicator
(green)
Off
The PMU is faulty.
Steady on
The PMU is running properly but is not communicating
with the communications equipment.
Blinking
The PMU is running properly and the PMU
communicates with Huawei communications equipment
normally.
Steady on
If the ALM indicator is steady on and the buzzer beeps,
a major alarm is generated.
ALM indicator
(red)
2.3.3 UIM
The UIM provides sensor detection ports, Boolean value input ports, dry contact outputs, and
a communications port.
Figure 2-6 shows the UIM panel.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
12
TP48300B-X6X0 & TP48600B-X6X0
User Manual
2 Component Description
Figure 2-6 UIM panel
Table 2-8 Ports on the UIM
Port Type
Silk Screen
Description
Remarks
Sensor port
WATER
Used to detect water
TEM_HUM
Used to detect the
ambient temperature
and humidity
AIN
05 V spare analog
parameters
SMOKE
Used to detect smoke
GATE
Used to detect door
TEM_BAT
Used to detect the
battery temperature
DIN1
Boolean value input 1
Reserved
DIN2
Boolean value input 2
Reserved
DIN3
Boolean value input 7
Reserved
Status1
Used to detect D.G.
status 1
Detecting D.G. startup or
stopping
Status2
Boolean value input 6
Reserved
ALM1
AC power failure
Default alarm
ALM2
DC undervoltage
Default alarm
ALM3
rectifier fault
Default alarm
ALM4
SPD fault
Default alarm
ALM5
Fuse blown
Default alarm
ALM6
Battery protection
Default alarm
AC_SPD
Used to detect AC SPD
faults
Boolean value
detection port
Dry contact
output
SPD detection
port
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
13
TP48300B-X6X0 & TP48600B-X6X0
User Manual
Port Type
Communications
port
2 Component Description
Silk Screen
Description
Remarks
DC_SPD
Used to detect DC SPD
faults
Reserved
COM_485/232
Used to communicate
with the EMS
Table 2-9 Pin defination
Silk Screen
Pin
Pin defination
WATER
12V
WATER
AGND_OUT
NULL
24V
VBTEM1
24V
VHUM
SIM4
AGND_OUT
24V
SMOKE
24V
DOOR
12V
JTD1
12V
JTD2
12V
JTD7
12V
JTD3
12V
JTD4
VBTEM1
TEM_HUM
AIN
SMOKE
GATE
DIN1
DIN2
DIN3
AC_SPD
DC_SPD
TEMBAT
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
14
TP48300B-X6X0 & TP48600B-X6X0
User Manual
Silk Screen
2 Component Description
Pin
Pin defination
24V
2.3.4 SNMP Module (Optional)
The SNMP module is used to establish a communication channel between the
TP48300B-X6X0 & TP48600B-X6X0 and an EMS. The SNMP module is a converter which
converts the RS485 or RS232 protocol to the TCP/IP protocol. The SNMP module remotely
manages the AC/DC converter cabinet that cannot be connected to the Ethernet. If the
network is connected, you can use any computer having an EMS or Web browser installed to
manage the power system by using the SNMP module.
The SNMP module is optional for the TP48300B-X6X0 & TP48600B-X6X0 and can be
installed in the power supply cabinet but not in the monitoring unit subrack.
Figure 2-7 shows the network diagram for the SNMP module.
Figure 2-7 Network diagram for the SNMP module
2.3.5 Querying alarms
When a major alarm is generated on the TP48300B-X6X0 & TP48600B-X6X0, the red ALM
indicator on the CPMU01 will be steady on and the buzzer will beep. Troubleshoot the fault
based on the alarms displayed on the CPMU01. For details about how to rectify the fault, see
Table 5-2. For details about menus on the CPMU01, see B LCD Menu. After the current
alarm is cleared, the ALM indicator on the CPMU01 turns off and the buzzer stops beeping.
All alarms can be queried in the alarm history.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
15
TP48300B-X6X0 & TP48600B-X6X0
User Manual
2 Component Description
Figure 2-8 Querying alarms on the CPMU01 panel
Figure 2-9 Querying alarms on the NetEco net work management UI
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
16
TP48300B-X6X0 & TP48600B-X6X0
User Manual
2 Component Description
2.3.6 Remote Software Upgrade
When the TP48300B-X6X0 & TP48600B-X6X0 is used a Simple Network Management
Protocol (SNMP) module, you can upgrade software of the TP48300B-X6X0 &
TP48600B-X6X0 remotely on the NetEcoV1.2 network management UI. For details about the
NetEco, See the NetEco Help. To upgrade software remotely, perform the following steps:
Step 1 Upload the target version file of the controller from a PC to the server.
Choose Software > Software Browser.
On the Software Browser tab page, click Transfer and then click From Client to Server
In the Select Software File dialog box, click Select.
Select the save path for the target version file of the controller on the PC, and then click OK.
In the Select Software File dialog box, click Confirm. Then the system starts transferring the
target version file.
Step 2 View the progress for transferring the target version file of the controller.
Choose Software > Software Browser in the NetEco main window.
On the Software Browser tab page, click the Server tab. Then you can view the progress for
transferring the target version file of the controller in the lower part of the tab page.
Step 3 Create a task for upgrading the controller software.
Choose Software > Upgrade Task Management in the NetEco main window.
On the Upgrade Task Management tab page, click Create.
In the Site Upgrade Wizard dialog box, enter a task name in Task Name and set Upgrade
Type to Upgrade Version.
Choose the home site of the controller to be upgraded in the navigation tree. Click
add the site to the list shown in the following figure on the right. Then click Next.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
to
17
TP48300B-X6X0 & TP48600B-X6X0
User Manual
2 Component Description
Check that the home site and target version of the controller are correct. Click Finish to start
the upgrade.
Step 4 View the progress for upgrading the controller software.
Choose Software > Upgrade Task Management in the NetEco main window.
On the Upgrade Task Management tab page, click Controller in the navigation tree. Then
you can view the progress of all current tasks in the right pane.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
18
TP48300B-X6X0 & TP48600B-X6X0
User Manual
2 Component Description
Step 5 Verify whether the upgrade is successful.
Choose Software > Software Browser in the NetEco main window.
On the Software Bowser tab page, click the Site tab and select the home site of the target
controller.
On the Version tab page on the right of the Site tab page, you can view the current software
version of the controller.
----End
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
19
TP48300B-X6X0 & TP48600B-X6X0
User Manual
3 Safety Precautions
Safety Precautions
3.1 Overview
CAUTION
To minimize the risk of personal injury and damage to equipment, read and follow all the
precautions in this document before performing any installation or maintenance. The "NOTE",
"CAUTION", and "WARNING" marks in other documents do not represent all the safety
instructions. They are only supplements to the safety instructions. Only trained and qualified
personnel are allowed to install, operate, and maintain Huawei equipment, and they must
understand basic safety precautions to avoid hazards.
To ensure safety of humans and the equipment, pay attention to the safety symbols on the
equipment and all the safety instructions in this document. Huawei will not be liable for any
consequence caused by the violation of the safety operation regulations and design,
production, and usage standards.
NOTE
The safety precautions described in this section are also applicable to other Huawei equipment.
3.2 Local Safety Regulations
When operating Huawei equipment, you must follow the local laws and regulations. The
safety instructions in this document are only supplements to the local laws and regulations.
3.3 Grounding Requirements
Equipment to be grounded must meet the following requirements:
When installing the device, always make the ground connection first and disconnect it at
the end.
Do not damage the ground conductor or operate the device in the absence of a properly
installed ground conductor. Conduct the electrical inspection carefully.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
20
TP48300B-X6X0 & TP48600B-X6X0
User Manual
3 Safety Precautions
The device (or system) must be connected permanently to the protection ground before
an operation. Before operating the device, check the electrical connection of the device
to ensure that it is securely grounded.
3.4 Human Safety
Do not operate the device or cables during lightning strikes.
To avoid electric shock, do not connect safety extra-low voltage (SELV) circuits to
telecommunication network voltage (TNV) circuits.
Before operating the device, wear electrostatic discharge (ESD) clothes, ESD gloves, and
an ESD wrist strap.
Do not wear jewelry or watches when you operate the device.
In the case of fire, immediately leave the building or the equipment room, and turn on
the fire alarm bell or make an emergency call. Do not enter a building that is on fire.
The temperature of some equipment parts may be rather high. Do not touch the surface
of such equipment parts to avoid getting burn.
3.5 Equipment Safety
The device must be fixed securely on the floor or to other immovable objects such as
walls and mounting racks before operation.
Do not block the ventilation while the device is operating.
Tighten the thumbscrews by using a tool after initial installation and subsequent access
to the panel.
After the installation, remove packing materials from the equipment area.
3.6 Electrical Safety
High Voltage
DANGER
The high voltage power supply provides power for the device operation. Direct or indirect
contact (through damp objects) with high voltage and AC mains supply may result in fatal
danger.
Non-standard and incorrect high voltage operations may result in fire and electric shock.
The personnel who install the AC facility must be qualified to perform high voltage and
AC operations.
You must abide by the local rules and regulations when bridging and wiring AC cables.
During the installation of the AC power supply facility, follow the local safety
regulations.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
21
TP48300B-X6X0 & TP48600B-X6X0
User Manual
3 Safety Precautions
Dedicated tools must be used during high voltage and AC operations. Avoid using
ordinary tools.
When the operation is performed in a damp environment, ensure that the device is dry.
When water is found in the rack or the rack is damp, switch off the power supply
immediately.
High Electrical Leakage
Ground the device before powering it on. Otherwise, personal injury or device damage
may be caused by high leakage current.
If a "high electrical leakage" tag is present on the power terminal of the device, you must
ground the device before powering it on.
Do not install or remove power cables when the device is on. Transient contact between
the core of the power cable and the conductor may generate electric arcs or sparks, which
may cause fire or hurt human eyes.
Before installing or removing the power cable, turn off the power switch.
Before connecting a power cable, check that the label on the power cable is correct.
Power Cable
Power Output
All output circuits are evaluated as SELV circuits.
CAUTION
Outputs are energy hazards (>240 VA)
Electrostatic Discharge
CAUTION
The static electricity generated by human bodies may damage the electrostatic-sensitive
components on boards, for example, the large-scale integrated (LSI) circuits.
Human body movement, friction between human bodies and clothes, friction between
shoes and floors, or handling of plastic articles causes static electromagnetic fields on
human bodies. These static electromagnetic fields cannot be eliminated until the static is
discharged.
To prevent electrostatic-sensitive components from being damaged by the static on
human bodies, you must wear a well-grounded ESD wrist strap when touching the
device or handling boards or application-specific integrated circuits (ASICs).
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
22
TP48300B-X6X0 & TP48600B-X6X0
User Manual
3 Safety Precautions
Figure 3-1 shows how to wear an ESD wrist strap.
Figure 3-1 Wearing an ESD wrist strap
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
23
TP48300B-X6X0 & TP48600B-X6X0
User Manual
4 Installation And Commissioning
Installation And Commissioning
The detailed installation and commissioning refer to the TP48300B-X6X0 Quick Installation
Guide (V300R001) and TP48600B-X6X0 Quick Installation Guide (V300R001).
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
24
TP48300B-X6X0 & TP48600B-X6X0
User Manual
5 Maintenance
Maintenance
5.1 Routine Maintenance
The TP48300B-X6X0&TP48600B-X6X0 is maintained every six months. If faults are
identified, rectify them immediately.
Table 5-1 Routine maintenance checklist
Maintenance
Item
Maintenance Task
Check
Whether
Check
Method
Repair When
Measures
Electricity
The voltage
output is
normal.
Using a
multimeter
The battery low
voltage
disconnection
(BLVD)
voltage or load
low voltage
disconnection
(LLVD) voltage
exceeds the
threshold.
For details
about how to
rectify the fault,
See 5.2
Common Faults
Preventive
maintenance
inspection
(PMI)
Indicators are in
normal status.
Observing
indicators
Fault alarms are
generated.
Cabinet
appearance
The paint and
the
electroplated
coating on the
surface of the
cabinet are in
good condition.
Observing the
cabinet
The cabinet
surface is
damaged or
distorted.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
Repaint and
repair the
cabinet.
25
TP48300B-X6X0 & TP48600B-X6X0
User Manual
5 Maintenance
5.2 Common Faults
Table 5-2 Troubleshooting the TP48300B-X6X0&TP48600B-X6X0
Category
Exception Cause
Measures
AC out of phase
The AC input
cable is faulty.
The mains
supply or D.G.
fails.
Check whether the AC input cable is
connected properly. If it is not connected
properly, reconnect it. If the insulation layer
deteriorates, replace the AC input cable.
Use a multimeter to check whether the AC
input voltage is over low and whether an AC
undervoltage alarm (lower than 180 V AC) is
generated. If yes, check whether short circuits
occur in the AC input loop and whether
electrical leakage occurs. If a short circuit or
electrical leakage occurs, replace the AC
input cable.
If the mains supply provides the AC power,
contact the mains supplier. If the D.G.
provides the AC power, check and repair the
D.G. by referring to the D.G. User Manual.
Check whether the AC input cable is
connected properly. If it is not connected
properly, reconnect it.
Check whether the AC power is available. If
the AC power is unavailable, check whether
an open or a short circuit occurs in the AC
input loop. If the AC power is available and
no open or short circuit occurs, contact the
mains supplier. If the D.G. provides the AC
power, check and repair the D.G. by referring
to the D.G. User Manual.
If the AC power is available, check whether
the AC detection cable is connected properly.
If the AC detection cable is connected
properly, replace the AC detection board.
If the power failure does not last long, use
storage batteries to power DC-powered loads.
If the power failure lasts long, use another
power supply.
Check whether the AC overvoltage and
undervoltage alarm thresholds are properly
set on the PMU. If no, adjust them as
required.
If the mains supply provides the AC power,
contact the mains supplier. If the D.G.
provides the AC power, check and repair the
D.G. by referring to the D.G. User Manual.
AC power
failure
AC overvoltage
or undervoltage
The AC input
cable is faulty.
The mains
supply or D.G.
fails.
Issue 02 (2012-12-04)
The alarm
threshold for
AC overvoltage
or undervoltage
is not properly
set on the PMU.
The mains
supply or D.G.
fails.
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
26
TP48300B-X6X0 & TP48600B-X6X0
User Manual
5 Maintenance
Category
Exception Cause
Measures
DC overvoltage
or undervoltage
The alarm
threshold for
DC overvoltage
or undervoltage
is not properly
set on the PMU.
Check whether the DC overvoltage and
undervoltage alarm thresholds are properly
set on the PMU. If no, adjust them as
required.
Reseat all rectifiers one by one when storage
batteries provide power normally. If an
overvoltage alarm is generated when a certain
rectifier is reinserted, replace this rectifier.
The charging
parameters are
not properly set
on the PMU.
Check the charging parameters on the PMU
and reset those that are not properly set.
Check whether faults such as short circuits
occur in the battery loop. If faults occur,
rectify them.
Check the storage batteries and replace faulty
ones.
Check whether the contactor is faulty and
whether the contactor cannot be connected or
disconnected. If the contactor is faulty or the
contactor cannot be connected or
disconnected, replace the contactor.
Check whether the LLVD voltage is
overhigh. If it is overhigh, adjust the voltage
to the normal range.
Check whether the load power is greater than
the configured rectifier power. If yes, add
rectifiers. If the load power exceeds the
maximum power of the TP48300B-X6X0 or
TP48600B-X6X0, decrease the load power.
Check whether the mains supply fails and
whether the battery voltage is below the
BLVD threshold. If the mains supply fails or
the battery voltage is below the BLVD
threshold, contact the mains supplier.
Check whether that BLVD is enabled on the
PMU.
Check whether the battery cables and
connectors are faulty, and replace faulty ones.
Check whether the contactor is faulty and
whether the contactor cannot be connected or
disconnected. If the contactor is faulty or
cannot be connected or disconnected, replace
the contactor.
Overcurrent
charge
Load
disconnection
The contactor is
faulty.
The PMU load
disconnection
voltage is
overhigh.
Battery
disconnection
Issue 02 (2012-12-04)
The battery
loop is faulty.
The load power
is greater than
the maximum
value
configured for
the rectifier,
and this causes
low output
voltage.
The battery
parameters are
not properly set
on the PMU.
The contactor is
faulty.
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
27
TP48300B-X6X0 & TP48600B-X6X0
User Manual
5 Maintenance
Category
Exception Cause
Measures
Battery loop
broken
The battery
loop is faulty.
Check the battery cables and connectors, and
replace faulty ones.
The contactor is
faulty.
Storage
batteries are
faulty.
Check whether the contactor is faulty and
whether the contactor cannot be connected or
disconnected. If the contactor is faulty or
cannot be connected or disconnected, replace
the contactor.
Check the storage batteries and replace faulty
ones.
Check that the alarm threshold for ambient
temperatures is properly set on the PMU.
Check the temperature control system in the
shelter and repair it if necessary. After the
temperature inside the cabinet is adjusted to
the specified range, the alarm is automatically
cleared.
If the alarm persists, repair the temperature
sensor.
Overhigh or over
low ambient
temperature
Faulty ambient
temperature
sensor
Faulty battery
temperature
sensor
The
temperature
inside the
shelter where
the ambient
temperature
sensor is
installed is not
in the normal
range.
The ambient
temperature
sensor is faulty.
The sensor is
not connected
properly.
Check whether the signal cable is properly
connected to the UIM. If no, fasten or replace
the signal cable.
The ambient or
battery
temperature
sensor is faulty.
If the cable is connected properly but the
sensor is faulty, replace the sensor.
If the alarm persists, replace the UIM.
Issue 02 (2012-12-04)
The alarm
threshold for
ambient
temperatures is
not properly set
on the PMU.
The UIM is
faulty.
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
28
TP48300B-X6X0 & TP48600B-X6X0
User Manual
5 Maintenance
Category
Exception Cause
Measures
Overhigh or over
low ambient
humidity
Check that the alarm threshold for ambient
humidity is properly set on the PMU.
Check the shelter for water intrusion. If there
is water in the shelter, remove the water using
a dry cotton cloth or dehumidifier.
If the humidity in the cabinet is adjusted to
the specified range but the alarm persists,
check and repair the humidity sensor.
Faulty ambient
humidity sensor
Overhigh or over
low battery
temperature
The humidity
inside the
shelter that
houses the
humidity sensor
is not in the
normal range.
The humidity
sensor is faulty.
The sensor is
not connected
properly.
Check whether the signal cable is properly
connected to the monitoring backplane. If no,
fasten or replace the signal cable.
The humidity
sensor is faulty.
If the cable is connected properly but the
sensor is faulty, replace the sensor.
The monitoring
backplane is
faulty.
If the alarm persists, replace the monitoring
backplane.
The battery
cabinet is under
an
overtemperature
condition.
Check that the alarm threshold for battery
temperatures is properly set on the PMU.
Check whether the temperature inside the
battery cabinet is overhigh. If it is, lower the
temperature inside the battery cabinet. The
alarm is automatically cleared after the
temperature lowers to the proper range.
Check the charge current. If the charge
current is overhigh, change the charge mode
from boost charge to floating charge and
check whether the charge current lowers. If
the charge current is still overhigh, reduce the
charge current. If the overtemperature
condition persists, check the storage batteries
and replace faulty ones.
Close the cabinet door.
If the alarm persists after the cabinet door is
closed, check and repair the door status
sensor.
If the door status sensor is not faulty, replace
the monitoring backplane.
Door status
sensor alarm
Issue 02 (2012-12-04)
The alarm
threshold for
ambient
humidity is not
set properly on
the PMU.
The alarm
threshold for
battery
temperatures is
not properly set
on the PMU.
The charge
current of
storage batteries
is overhigh.
The battery
temperature
sensor is faulty.
The cabinet
door is open.
The door status
sensor is faulty.
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
29
TP48300B-X6X0 & TP48600B-X6X0
User Manual
5 Maintenance
Category
Exception Cause
Measures
Water detector
alarm
There is water
in the shelter.
The water
sensor is faulty.
Check the shelter for water intrusion. If there
is water in the shelter, remove the water using
a dry cotton cloth or dehumidifier.
If the alarm persists after the water is
removed, check and repair the water sensor.
If the water sensor is not faulty, replace the
monitoring backplane.
Check the shelter for smoke. If there is
smoke, put out the fire immediately and open
the shelter door for ventilation.
If there is no smoke but this alarm persists,
check and repair the smoke sensor.
If the smoke sensor is not faulty, replace the
monitoring backplane.
Check the fault indicator on the rectifier
panel. If the indicator is red, the rectifier is
faulty. Then replace the rectifier.
Disconnect the AC power from the rectifier,
and then restart the rectifier after a period of
time. If the alarm persists, replace the
rectifier.
Smoke sensor
alarm
rectifier fault
rectifier
shutdown
rectifier
protection
Issue 02 (2012-12-04)
There is smoke
in the shelter.
The smoke
sensor is faulty.
The rectifier has
poor contact
with the
subrack.
The rectifier is
faulty.
rectifier enters
the hibernation
mode.
If rectifier enters the hibernation mode, the
power system generates rectifier shutdown
alarm, dont need to deal with it.
The input
voltage to the
rectifier is not
in the normal
range.
A fault occurs
on the rectifier.
Check whether the mains supply voltage is
higher than the rectifier AC overvoltage
threshold (300 V) or lower than the rectifier
AC undervoltage threshold (85 V). If the
power grid is in an overvoltage or
undervoltage condition for a long period of
time, contact the mains supplier to improve
the power grid.
If the input voltage to the rectifier is within
the specified range but this alarm persists,
replace the rectifier.
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
30
TP48300B-X6X0 & TP48600B-X6X0
User Manual
5 Maintenance
Category
Exception Cause
Measures
Communication
failure between
the rectifier and
the PMU
The signal cable
to the rectifier
is not connected
properly.
The rectifier is
not installed in
the subrack.
Check whether the rectifier is installed in the
subrack and whether the rectifier is properly
connected. If the rectifier is not installed in
the subrack, install the rectifier in the correct
position. If the rectifier has poor contact with
the subrack, reseat the rectifier, and ensure
that the rectifier is secured to the subrack.
The rectifier has
poor contact
with the
subrack.
Check whether the communications cable is
properly connected between the rectifier and
the monitoring backplane. If yes, reseat the
rectifier.
A fault occurs
on the rectifier.
If the alarm persists, replace the rectifier.
If the alarm still persists after the rectifier is
replaced, replace the monitoring backplane.
Check whether the load circuit breaker is in
the OFF position. If it is, switch it to the ON
position.
Check whether the load fuse is damaged. Use
a multimeter to measure the voltage at both
ends of the fuse. If the voltage is close to 0 V,
the fuse is normal. Otherwise, the fuse is
blown. Replace the fuse.
If the alarm persists after the fuse is replaced,
check the new fuse. If the new fuse is blown
or the load circuit breaker is automatically
switched to the OFF position, the load power
on this route may be excessive or a short
circuit may occur. In this case, you need to
rectify the fault on this load loop. If the new
fuse functions normally, the alarm loop is
faulty. Then replace the PMU.
Observe the indication window on the AC
surge protection module. If it turns red,
replace the surge protection module. If it does
not turn red, the alarm loop in the PMU is
faulty. Then replace the PMU.
If the alarm persists, replace the monitoring
backplane.
Replace the DC surge protection board.
If the alarm persists after the PMU is
replaced, replace the monitoring backplane.
Load fuse blown
Faulty AC SPD
Faulty DC SPD
Issue 02 (2012-12-04)
The monitoring
backplane is
faulty.
The load fuse is
faulty.
The load circuit
breaker is in the
OFF position.
The AC SPD is
faulty.
The monitoring
backplane is
faulty.
The DC SPD is
faulty.
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
31
TP48300B-X6X0 & TP48600B-X6X0
User Manual
5 Maintenance
If the customer does not require the TP48300B-X6X0 & TP48600B-X6X0 to be managed in in-band
mode, do not connect the TP48300B-X6X0 & TP48600B-X6X0 and the base band unit (BBU) with
an Ethernet cable or an RJ45 communications cable. If the customer requires the TP48300B-X6X0
& TP48600B-X6X0 to be managed in in-band mode, set the capacity of storage batteries on the
EMS.
After a fault is rectified, the corresponding alarm is automatically cleared on the PMU and the alarm
information is stored in the alarm history.
The BLVD fuse and LLVD fuse are both called load fuse.
Disconnect the fuse before replacing it. Otherwise, arc sparks may be generated, and this may cause
bodily injury.
After replacing the PMU, reset parameters by referring to the TP48300B-X6X0 Quick Installation
Guide or TP48600B-X6X0 Quick Installation Guide.
The PMU and rectifiers are hot-swappable.
When replacing the monitoring board, take ESD measures such as wearing an ESD wrist wrap.
5.3 Troubleshooting Components
AC SPD
Observe the indication window on the surge protection module. If the indication window
turns red, the surge protection module is damaged. In this case, replace the surge protection
module. If the indication window remains green, the SPD runs properly.
Circuit Breaker
The circuit breaker fault is usually caused by overcurrent or short circuits. Circuit breaker
faults are caused by overcurrent or short circuits. To check whether a circuit break is faulty,
perform the following steps:
Step 1 Switch the circuit breaker to the ON position.
Step 2 Measure the resistance at the two ends of the circuit breaker using a multimeter. If the
resistance is infinity, the circuit breaker is damaged.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
32
TP48300B-X6X0 & TP48600B-X6X0
User Manual
5 Maintenance
DC Contactor
Table 5-3 DC contactor description
Position
Type
Check Method
LLVD route
Normally closed (NC)
(When the contactor is
powered off, the contactor is
closed.)
When there is no voltage on the control
pin of the contactor, use a mulitmeter
to check whether the output pin is in
normal status. For example, if pins 1
and 2 shown in Figure 5-1 have no
voltage, use a multimeter to check the
connection status between pins 3 and 4.
If pins 3 and 4 are disconnected, the
contactor is faulty.
When there is a rated control voltage
on the control pin of the contactor, use
a mulitmeter to check whether the
output pin status of the contactor is
normal. For example, if pins 1 and 2
shown in Figure 5-1 have a rated
control voltage, use a multimeter to
check the connection status between
pins 3 and 4. If pins 3 and 4 are
connected, the contactor is faulty.
When there is no voltage on the control
pin of the contactor, use a mulitmeter
to check whether the output pin of the
contactor is in normal status. For
example, if pins 1 and 2 shown in
Figure 5-1 have no voltage, use a
multimeter to check the connection
status between pins 3 and 4. If pins 3
and 4 are connected, the contactor is
faulty.
When there is a rated control voltage
on the control pin of the contactor, use
a mulitmeter to check whether the
output pin status of the contactor is
normal. For example, if pins 1 and 2
shown in Figure 5-1 have a rated
control voltage, use a multimeter to
check the connection status between
pins 3 and 4. If pins 3 and 4 are
disconnected, the contactor is faulty.
Battery route
(battery fuse
or circuit
breaker route)
Issue 02 (2012-12-04)
Normally open (NO) (When
the contactor is powered off,
the contactor is open.)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
33
TP48300B-X6X0 & TP48600B-X6X0
User Manual
5 Maintenance
Figure 5-1 DC contactor
Rectifier
The rectifier is damaged if either of the following conditions is not met:
The Run indicator of the rectifier is steady on and the Fault indicator is off when the
rectifier does not communicate with the PMU and the input AC voltage is around 220 V.
The rectifier outputs power normally.
The PMU can perform control on the charge mode (boost charge or floating charge) and
current for the rectifier when the rectifier communications cable is properly connected
and the rectifier communicates with the PMU normally.
PMU
If any of the following occurs, the PMU is faulty:
The PMU breaks down or fails to start, or its LCD or keyboard fails.
The PMU does not generate an alarm when a fault occurs in the system.
The PMU generates an alarm (false alarm) when the system runs properly.
Communication between the PMU and all subordinate equipment is interrupted.
The PMU fails to control or monitor all the modules when these modules run properly
and communications cables are connected properly.
The PMU fails to monitor or control AC or DC distribution when AC/DC power is
distributed normally and communications cables are connected properly.
Parameters cannot be set or operating information cannot be viewed on the PMU.
5.4 Component Replacment
Describes how to replace the main components of the power system.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
34
TP48300B-X6X0 & TP48600B-X6X0
User Manual
5 Maintenance
Load disconnection is prohibited when you replace the main components. Take measures to ensure
that important loads are always connected during the replacement. For example, keep the circuit
breaker of important loads set to ON and storage batteries and AC input are not cut off.
If a load must be disconnected, ask for the customer's prior permission.
The rectifier and the PMU are hot-swappable.
For more safety precautions, see Safety Information.
Replacing the rectifier
To replace the rectifier, perform the following steps:
Step 1 Loosen the screws on the rectifier panel using a flat-head screwdriver.
Step 2 Pull the handle of the rectifier outwards, and then remove the rectifier from the plug-in
subrack, as shown in Figure 5-2.
Step 3 Insert the rectifier into the corresponding slot in the plug-in subrack. Then, loosen the screws
on the handle and pull out the handle.
Step 4 Slide the rectifier into the plug-in subrack slowly along the guide rails. Then, lock the handle.
Step 5 Tighten the screws on the handle, as shown in Figure 5-3.
----End
Figure 5-2 Removing the old rectifier
Figure 5-3 Installing the new rectifier
Replacing the PMU
To replace the PMU, perform the following steps:
Step 1 Unscrew the PMU panel using a Phillips screwdriver.
Step 2 Remove the old PMU.
Step 3 Insert a new PMU.
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
35
TP48300B-X6X0 & TP48600B-X6X0
User Manual
5 Maintenance
Step 4 Tighten the screws on the handle.
Step 5 Set parameters on the PMU panel.
----End
Figure 5-4 Replacing the PMU
Replacing the UIM
To replace the UIM, perform the following steps:
Step 1 Remove signal cables from the UIM.
Step 2 Loosen the screws on the UIM panel using a Phillips screwdriver.
Step 3 Pull the UIM outwards.
Step 4 Insert the new UIM.
Step 5 Tighten the screws on the handle.
Step 6 Reinstall the signal cables.
----End
Replacing the AC SPD
To replace the AC SPD, perform the following steps:
Step 1 Remove the faulty SPD.
Step 2 Insert the new SPD.
----End
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
36
TP48300B-X6X0 & TP48600B-X6X0
User Manual
5 Maintenance
Figure 5-5 Replacing the AC SPD
Replacing Circuit breakers
To replace a circuit breaker, perform the following steps:
Step 1 Disconnect the power supply of a circuit breaker. For example, disconnect the DC input and
set the circuit breaker to OFF before replacing the input circuit breaker.
Step 2 Remove the cables or copper bars connected to the circuit breaker using a Phillips screwdriver,
and then wrap the cables or copper bars using black PVC insulation tape to avoid hazards.
Step 3 Press the contact plate at the bottom of the circuit breaker using a flat-head screwdriver. Then,
remove the circuit breaker, as shown in Figure 5-6.
Step 4 Press the contact plate at the bottom of the circuit breaker using a flat-head screwdriver again
to install the new circuit breaker in the correct position. Then, push the contact plate upwards
using the screwdriver.
Step 5 Install the cables or copper bars to the circuit breaker using a Phillips screwdriver in the same
way.
Step 6 Set the circuit breaker to ON and connect power supply of this circuit breaker, as shown in
Figure 5-7.
----End
Figure 5-6 Removing the circuit breaker
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
37
TP48300B-X6X0 & TP48600B-X6X0
User Manual
5 Maintenance
Figure 5-7 Installing the circuit breaker
Replacing a Fuse
To replace a fuse, perform the following steps:
Step 1 Disconnect the fuse loop.
Step 2 Remove the damaged fuse using a fuse extracting unit, as shown in Figure 5-8.
Figure 5-8 Removing a fuse
Step 3 Install a new fuse, as shown in Figure 5-9.
Figure 5-9 Installing a fuse
Step 4 Connect the fuse loop.
----End
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
38
TP48300B-X6X0 & TP48600B-X6X0
User Manual
A Technical Specifications
Technical Specifications
Table A-1 Technical specifications
Category
Item
Specifications
Environmental
conditions
Operating
temperature
Long-term operating temperature: 20C to +50C
(4F to +122F)
Short-term operating temperature: 50 C55C
(122 F131F)
Storage
temperature
40C to +70C (40F to +158F)
Transportation
temperature
40C to +70C (40F to +158F)
Operating
humidity
5%95% RH (non-condensing)
Storage humidity
5%95% RH (non-condensing)
Altitude
0-4000 m (0-13123.2 ft)
When the altitude ranges from 2000 m (6561.6 ft) to
4000 m (13123.2 ft), the operating temperature is
derated by 1C (1.8F) for each additional 200 m
(656.16 ft).
AC input
Input mode
Input voltage
TP48300B-X6X0: dual live wire (L1, L2, PE)
TP48600B-X6X0: three-phase-four-line (L1, L2,
L3, PE)
176 V AC to 290 V AC (corresponding
to the rated power of the rectifier)
90 V AC to 175 V AC (corresponding to
the derated output power of the rectifier)
Issue 02 (2012-12-04)
Input frequency
45 Hz to 66 Hz (50 Hz by default)
Power factor
0.99
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
39
TP48300B-X6X0 & TP48600B-X6X0
User Manual
A Technical Specifications
Category
Item
Specifications
DC output
Output voltage
range
43.2 V DC to 57.6V DC
Default output
voltage
53.5 V DC
AC input
overvoltage
protection
threshold
Overvoltage protection is performed when the
single-phase AC input voltage exceeds the AC input
overvoltage protection threshold (300 V AC by
default).
AC input
overvoltage
recovery
threshold
When the voltage is restored to 290 V AC, the output
resumes.
AC input
undervoltage
protection
threshold
Undervoltage protection is performed when the
single-phase AC input voltage is below the AC input
undervoltage protection threshold (85 V AC by
default).
AC input
undervoltage
recovery
threshold
When the voltage is restored to 90 V AC, the output
resumes.
DC output
protection
DC output
overvoltage
protection
threshold
58.560.5 V DC
Rectifier
Efficiency
>91.5%( 35%~80% load)
Output power
2900W (176290 V AC)
AC input
protection
1200W (90175 V AC)
Others
Output soft start
At the moment when the rectifier is powered on, the
output voltage rises slowly. The time for voltage rise
is configurable.
Overvoltage
protection
Voltage range: 58.560.5 V DC
Surge protection
If the external voltage is less than 63 V, the
rectifier is in the standby state. If overvoltage
disappears, the rectifier output resumes.
If the external voltage is greater than 63 V for
more than 500 ms, the rectifier experiences a
deadlock.
Level C surge protection
Standard surge discharge current: 20 kA, 8/20
s
Maximum surge discharge current: 40 kA, 8/20 s
MTBF
Issue 02 (2012-12-04)
500,000 hours, at a temperature of 25C (77F)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
40
TP48300B-X6X0 & TP48600B-X6X0
User Manual
A Technical Specifications
Category
Item
Specifications
Structure
Dimensions (H x
W x D)
1600 mm x 600 mm x 450 mm (62.99 in. x 23.62 in.
x 17.72 in.)
Weight
(including
modules)
110 kg (242.55 lb), excluding rectifiers
Protection level
IP20
Installation
Installed on a concrete floor or an ESD floor against
the wall, with a slack of at least 100 mm (3.94 in.)
Maintenance
Operated and maintained from the front
Installation
scenario
Standard 19-inch rack
Table A-2 EMC specifications
Item
Specifications
Electromagnetic
interference
(EMI)
Electronic
magnetic
sensitivity
(EMS)
Issue 02 (2012-12-04)
Conducted
emission
(CE)/Radiated
emission (RE)
In compliance with CISPR 22/EN 55022 class A
Harmonic
In compliance with IEC 61000-3-12
Fluctuation and
blinking
In compliance with IEC 61000-3-11
ESD
Contact discharge 6 kV and air discharge 8 kV
(criterion B)
Contact discharge 8 kV and air discharge 15 kV
(criterion R)
Electrical fast
transient (EFT)
Signal port 1 kV and power port 2 kV (criterion B)
Radiated
susceptibility
(RS)
10 V/m (criterion A)
Conducted
susceptibility
(CS)
Signal port 10 V and power port 10 V (criterion A)
SURGE
Differential mode of the AC power port: 2 kV
(criterion B)
Common mode of the AC power port: 4 kV
(criterion B)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
41
TP48300B-X6X0 & TP48600B-X6X0
User Manual
B LCD Menu
LCD Menu
Figure B-1 Menu hierarchy (to the secondary level) on the LCD screen
Table B-1 Menu Table on the LCD screen
Main
Menu
Second
Menu
Third Menu
Forth Menu
Fifth
Menu
Default
Value
Status
Rectifiers
Rectifiers ID
ID
Voltage
Current
Current limit
Status
Output power
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
42
TP48300B-X6X0 & TP48600B-X6X0
User Manual
Main
Menu
Second
Menu
Forth Menu
Fifth
Menu
Default
Value
Rated
efficiency
Input power
Input current
Rated current
Inner
temperature
Major alarm
Common alarm
History
alarm
Battery test
result
Version
display
Generator
status
Generator 1/2
Management
mode
Start
Rectifier ID
System
settings
Address
Text
RS232
9600
Active alarm
Mainten
ance
Settings
B LCD Menu
Third Menu
Communication
mode
Baud
Date
Time
Battery 2 shunt
Yes
Display
contrast
TP48300B or
TP48600B
System type
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
43
TP48300B-X6X0 & TP48600B-X6X0
User Manual
Main
Menu
Second
Menu
Alarm
settings
B LCD Menu
Third Menu
Forth Menu
Fifth
Menu
Default
Value
IP address
192.168.0.1
Subnet mask
255.255.254.0
Gateway
10.70.199.1
Server port
31220
Server IP
address 1
192.168.0.1
Server IP
address 2
192.168.0.2
Engineering
settings
Modify
Password
None
Initial
parameter
No
Rectifier
sleep
No
Rectifier
exchange
sleep
7days
Rectifier
Minimum
number ON
1pieces
Best
efficiency
point
70%
Fast charge
No
Alarm
Level
DI No.
Mode
Set DI name
Audible
alarm
Yes
Clear history
alarm
No
Alarm
Relate relay
Alarm level
Digital alarm
Alarm control
Relay relate
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
44
TP48300B-X6X0 & TP48600B-X6X0
User Manual
Main
Menu
B LCD Menu
Second
Menu
Third Menu
Forth Menu
Fifth
Menu
Default
Value
AC settings
Over voltage
280V
Under voltage
180V
State measure
Yes
Over voltage
58V
Under voltage
45V
Battery
selection
Battery string
Capacitor 1
400AH
Capacitor 2
Install date
2001-01-01
LLVD enable
Yes
BLVD
enable
Yes
LLVD
44V
BLVD
43V
DC settings
Battery
settings
LVD settings
Charge
Battery test
Float
53.5V
Boost
56.5V
Cycle BC
duration
60days
Current limit
0.10C10
Auto test
Short test
Issue 02 (2012-12-04)
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
Auto
test
enable
Discharge test
Cycle
120days
Test end
voltage
1.9V
Duration
10hours
Test
delay
14days
Test end
voltage
45V
Duration
60minutes
45
TP48300B-X6X0 & TP48600B-X6X0
User Manual
Main
Menu
Second
Menu
Ambient
settings
Generator
Air-condition
Issue 02 (2012-12-04)
B LCD Menu
Third Menu
Forth Menu
Fifth
Menu
Default
Value
Temperature co
efficiency
Temp
compensation
basis
Batt1
Temperature
compensation
80mV/
BHTD
enable
No
BHTD
temperature
53
Low
temperature
alarm
High
temperature
alarm
50
Upper limit
80
Lower limit
-20
Upper limit
80
Lower limit
-20
High alarm
50
Low alarm
Generator
enable
No
Output power
12.5kW
Discharge
depth
30%
Temperature
OFF enable
Yes
Start
temperature
45
OFF
temperature
29
Type
Single-phase
Power
1.0 kW
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
46
TP48300B-X6X0 & TP48600B-X6X0
User Manual
C Acronyms and Abbreviations
Acronyms and Abbreviations
A
AC PDU
Alternating Current Power Distribution Unit
ASIC
Application-Specific Integrated Circuit
ATS
Automatic Transfer Switch
D
DC PDU
Direct Current Power Distribution Unit
E
EMS
Element Management System
I
IEC
International Electrotechnical Commission
L
LED
Light Emitting Diode
LSI
Large-scale Integration
O
OPEX
Operational Expenditure
P
PDU
Issue 02 (2012-12-04)
Power Distribution Unit
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
47
TP48300B-X6X0 & TP48600B-X6X0
User Manual
PMU
C Acronyms and Abbreviations
Power Monitoring Unit
S
SELV
Safety Extra-low Voltage
T
TCU
Issue 02 (2012-12-04)
Temperature Control Unit
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd
48