F6 Series, 2-Way, HDU Butterfly Valve
Resilient Seat, 304 Stainless Disc
50 psi bubble tight shut-off
Long stem design allows for 2 insulation
Valve face-to-face dimensions comply with API 609 & MSS-SP-67
Completely assembled and tested, ready for installation
Application
These valves are designed to meet the needs of HVAC and commercial
applications requiring bubble tight shut-off for liquids. Typical applications
include chiller isolation, cooling tower isolation, change-over systems, large
air handler coil control, bypass and process control applications. The large
Cv values provide for an economical control valve solution for larger flow
applications. Designed for use in Victaulic piping systems when mated to
Victaulic 41 series flange nipples.
Jobsite Note
Valves should be stored in a weather protected area prior to construction.
Complete installation recommendations can be found in Belimos Installation
and Maintenance Instructions for F6HDU Butterfly Valves.
800-543-9038 USA
10
.06
.10
.20
.30
.50
.80
2
3
4
20
3
6
9
17
29
45
89
151
234
30
7
12
18
36
61
95
188
320
495
200 F6200HDU
250 F6250HDU
300 F6300HDU
40
15
25
39
78
133
205
408
694
1072
866-805-7089 CANADA
50
27
45
70
139
237
366
727
1237
1911
MOD
60
44
75
116
230
392
605
1202
2047
3062
70
70
119
183
364
620
958
1903
3240
5005
80
105
178
275
546
930
1437
2854
4859
7507
GK Series
3136 1202 8
5340 2047 10
8250 3062 12
DKR
150 F6150HDU
Electronic
Fail-Safe
SY Series
DR
Cv
115
196
302
600
1022
1579
3136
5340
8250
Size
2
2
3
4
5
6
8
10
12
1579 605
GM Series
Valve
F650HDU
F665HDU
F680HDU
F6100HDU
F6125HDU
F6150HDU
F6200HDU
F6250HDU
F6300HDU
Cv
Cv
90 60
115 44
196 75
302 116
600 230
1022 392
Valve
Nominal Size Type
Suitable Actuators
DN
IN [mm] 2-way Spring
Non-Spring
2
50 F650HDU
2 65 F665HDU
3
80 F680HDU
4
100 F6100HDU
5
125 F6125HDU
AM
Series
ductile iron ASTM A536
epoxy powder coated
304 stainless steel
EPDM
416 stainless steel
EPDM
RPTFE
-22F to 250F [-30C to 120C]
ASME/ANSI Class 125
50 psi
10:1 (for 30 to 70 range)
12 FPS
bubble tight
chilled, hot water, 60% glycol
modified equal percentage
82
2 to 12
for use with ANSI Class 125/150 flanges
AF
Series
Technical Data
Service
Flow characteristic
Controllable flow range
Sizes
Type of end fitting
Materials
Body
Body finish
Disc
Seat
Shaft
O-ring
Bushings
Media temperature range
Body pressure rating
Close-off pressure
Rangeability
Maximum velocity
Leakage
ON/OFF
90
115
196
302
600
1022
1579
3136
5340
8250
203-791-8396 LATIN AMERICA / CARIBBEAN
F6 Series, 2-Way, HDU Butterfly Valve
Resilient Seat, 304 Stainless Disc
A
1.65
B
9.00
C
9.00
D(Max)
19.50
BHC
4.75
No. of Holes
4
Lug Bolt
5/8-11 UNC
Actuator
AF
F665HDU
196
75
1.81
9.00
9.00
20.00
5.50
5/8-11 UNC
F680HDU
302
116
1.81
9.00
9.00
20.50
6.00
5/8-11 UNC
600
230
2.05
9.00
9.00
21.00
7.50
5/8-11 UNC
1022
392
2.19
9.00
9.00
22.00
8.50
3/4-10 UNC
F6100HDU
600
230
2.05
8.00
8.00
17.00
7.50
5/8-11 UNC
F6125HDU
1022
392
2.19
8.00
8.00
17.50
8.50
3/4-10 UNC
F6150HDU
1579
605
2.19
8.00
8.00
22.50
9.50
3/4-10 UNC
F650HDU
115
44
1.65
7.00
7.00
15.00
4.75
5/8-11 UNC
F665HDU
196
75
1.81
7.00
7.00
15.50
5.50
5/8-11 UNC
F680HDU
302
116
1.81
7.00
7.00
16.00
6.00
5/8-11 UNC
F6100HDU
600
230
2.05
8.00
8.00
17.00
7.50
5/8-11 UNC
F6125HDU
1022
392
2.19
8.00
8.00
17.50
8.50
3/4-10 UNC
F6150HDU
1579
605
2.19
8.00
8.00
22.50
9.50
3/4-10 UNC
F6150HDU
F650HDU
F665HDU
F680HDU
F6100HDU
F6125HDU
F6150HDU
F6200HDU
F6250HDU
F6300HDU
6
2
2
3
4
5
6
8
10
12
1579
115
196
302
600
1022
1579
3136
5340
8250
605
44
75
116
230
392
605
1202
2047
3062
2.19
1.65
1.76
1.78
2.05
2.19
2.19
2.37
2.67
3.01
6.00
4.25
4.25
4.25
8.00
8.00
8.00
8.00
8.00
8.00
4.00
4.25
4.25
4.25
13.00
13.00
13.00
13.00
13.00
13.00
18.00
15.50
16.00
16.25
22.00
22.50
23.00
24.25
25.50
27.25
9.50
4.75
5.50
6.00
7.50
8.50
9.50
11.75
14.25
17.00
8
4
4
4
8
8
8
8
12
12
3/4-10 UNC
5/8-11 UNC
5/8-11 UNC
5/8-11 UNC
5/8-11 UNC
3/4-10 UNC
3/4-10 UNC
3/4-10 UNC
7/8-9 UNC
7/8-9 UNC
Dimension A is compressed, add .125 for relaxed state.
AF, AM and GM maximum actuator ambient temperature is 122F.
SY maximum actuator ambient temperature is 150F.
Model SY1 does not have handwheel - override is via 8mm wrench on
bottom side of actuator.
50
2*AF
50
50
GK
50
50
2*GK
50
50
AM
50
50
GM
50
50
2*GM/GK
DR/DKR
50
50
50
50
50
50
50
50
50
50
SY1...
SY2...
SY3...
SY4...
Flow Pattern
100
Dimensions
% OF MAXIMUM FLOW
90
Application Notes
1. Valves are rated at 50 psi differential pressure in the closed position.
2. Valves are furnished with lugs tapped for use with ANSI Class 125/150
flanges. Installation flanges and hardware are not included.
3. 2-way assemblies are furnished assembled and tested, ready for installation.
4. Dimension D allows for actuator removal without the need to remove the
valve from the pipe.
5. Weather shields are available, dimensional data upon request.
6. Dual actuated valves have actuators mounted on a common valve shaft.
7. Belimo SY Series actuators are NEMA 4X rated.
80
70
60
50
40
30
20
10
10
20
30
40
50
60
70
80
90
100
BF2WUDIM
% OF VALVE OPENING
D
B
C
A
800-543-9038 USA
Non-Spring Return
F6125HDU
50
50
Electronic
Fail-Safe
F6100HDU
Close-Off (PSI)
50
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
O50904 - 02/12 - Subject to change. Belimo Aircontrols (USA), Inc.
Cv 60
44
Spring Return
Maximum Dimensions (Inches)
Valve
Size
Cv 90
2
115
SY...24V Series Non-Spring Return Actuator
Tecnhincal Data - 24 VAC
Application:
The SY actuators are NEMA 4X rated and designed to meet
the needs of HVAC and Commercial applications. Offered on
Belimo standard and high performance valve series, these
actuators are available for on/off and modulating applications.
Depending on the application, they are available in 24 VAC/
VDC, 120 VAC and 230 VAC.
O50904 - 02/12 - Subject to change. Belimo Aircontrols (USA), Inc.
Technical Data
Electrical connection
conduit connector,
screw terminals
Motor protection
H Class insulation (SY-1),
F Class (SY-25)
Gear train
high alloy steel gear sets, self locking
Operating range
(SY-24) on/off, floating point
(SY...24MFT) 2-10 VDC, 4-20 mA,
0-10 VDC
Sensitivity
(SY24MFT) 0.4 mA/200mV
Reversal hysteresis
(SY24MFT)1.0 mA/500mV
Feedback
(SY24MFT) 2-10 VDC
Angle of rotation
90
Direction of rotation
reversible
Position indication
top mounted domed indicator
Internal humidity control
resistive heating element
Auxiliary switches
factory set for 5 and 85 change of state
SY1: (2) SPDT, min 1 mA, 24 VAC; max
3A, 250 VAC.
SY2-12: (2) SPDT, min 1 mA, 24 VAC;
max 5A, 250 VAC.
Ambient temperature
-22F to +150F [-30C to +65C]
Humidity range
up to 95%
Housing type
IP67, NEMA 4X
Housing material
die cast aluminum alloy
Agency listings
ISO, CE, cCSAus
Power Supply
24 VAC/VDC 50/60Hz, single phase
Duty Cycle
Torque
Speed
Power
Consumption
On/Off
MFT
Override
Weight
35Nm/310 in-lbs
15s
1.8A
30%
75%
8mm Wrench
2.0kg/4.9 lb.
SY2-24(MFT)
90Nm/801 in-lbs
15s
3.0A
30%
75%
Hand Wheel
11kg/24.5 lb.
SY3-24(MFT)
150Nm/1335 in-lbs
22s
3.0A
30%
75%
Hand Wheel
11kg/24.5 lb.
SY4-24(MFT)
400Nm/3560 in-lbs
16s
6.0A
30%
75%
Hand Wheel
22kg/48.5 lb.
SY5-24(MFT)
500Nm/4450 in-lbs
22s
6.5A
30%
75%
Hand Wheel
22kg/48.5 lb.
Model
SY1-24(P)
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
43
SY Series Non-Spring Actuator
Dimensions
D
B
SY-1...
SY-2~6...
B
SY-9~12...
SY-7~8...
B
M40048 - 06/10 - Subject to change. Belimo Aircontrols (USA), Inc.
MODEL
DIM A (MAX)
Add to Dim A for
cover removal
DIM B
DIM C (MAX)
DIM D
Inches [mm]
Inches [mm]
Inches [mm]
Inches [mm]
Inches [mm]
SY1
6.10 [155]
3.94 [100]
4.25 [108]
8mm
SY2~3
10.04 [255]
7.48 [190]
7.87 [200]
12.99 [330]
7.87 [200]
SY4~6
12.40 [315]
8.86 [225]
9.21 [234]
14.96 [380]
11.81 [300]
SY7~8
16.54 [420]
8.86 [225]
9.21 [234]
17.72 [450]
13.39 [340]
SY9~12
23.23 [590]
8.86 [225]
10.24 [260]
18.50 [470]
13.78 [350]
Note: ~ indicates range of actuator i.e., SY2~3 = SY-2 and SY-3
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
39