0% found this document useful (0 votes)
7K views6 pages

Controlador de Temperatura xmtg818

The document provides an instruction manual for the XMTG-818(T) intelligence digital temperature controller. It has seven input signals for thermocouple and thermo-resistance sensors. It can perform ON/OFF control and PID control, and has a timer function with selectable time units. Users can use the "AT function" to set parameters to satisfy most control needs. The controller has no over-regulation and good anti-interference characteristics. It is widely used in temperature control systems for various industries.

Uploaded by

api-28269646
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Topics covered

  • temperature settings,
  • control period,
  • sampling cycle,
  • relay output,
  • technical specifications,
  • thermocouple,
  • common faults,
  • control cycles,
  • control methods,
  • display precision
0% found this document useful (0 votes)
7K views6 pages

Controlador de Temperatura xmtg818

The document provides an instruction manual for the XMTG-818(T) intelligence digital temperature controller. It has seven input signals for thermocouple and thermo-resistance sensors. It can perform ON/OFF control and PID control, and has a timer function with selectable time units. Users can use the "AT function" to set parameters to satisfy most control needs. The controller has no over-regulation and good anti-interference characteristics. It is widely used in temperature control systems for various industries.

Uploaded by

api-28269646
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Topics covered

  • temperature settings,
  • control period,
  • sampling cycle,
  • relay output,
  • technical specifications,
  • thermocouple,
  • common faults,
  • control cycles,
  • control methods,
  • display precision
  • Introduction and Survey: Provides general overview and brief technical specifications of the XMTG-81(T) digital temperature controller.
  • Internal Parameters: Lists parameter codes, names, settings, and factory explanations for customizing device behavior.
  • Flow Chart and Parameters Setting Method: Outlines a flow chart for parameter setting and a step-by-step guide to entering and modifying settings.
  • Setting Itself and Fault Analysis: Explains the self-setting feature for ease of operation and provides troubleshooting methods for common faults.

XMTG-818(T) intellgence digital temperature controller

(with timer)
Instruction Manual
Survey:
XMTG-818(T) intelligence digital temperature controller ,equipped with single chip and double row
4 -digit LED display, has seven input signals of thermocouple and thermo- resistance for free selection in the
field , ON/OFF control and PID control. It also has time function with selectable time unit of hour/minute or
minute /second . With the parameters set by using function of setting itself(AT function),their control effect can be
satisfied in the most of case. There are characters of no over-regulation and good anti-interference in this type
controller. They are widely used in the temperature automatic control system of machinery, chemical, ceramics,
light industry, metallurgy, petrochemical and heat treatment industry, etc.

Main technical specification


2.1Input type: CU50PT100KEJTS
2.2Basic error: 0.5%F.S1B
2.3Cold end compensating error: 2.0
2.4Time range: 1M59.59H or 1S59.59M
2.5Timing precision: class 0.005
2.6Sampling cycle: 0.5S
2.7The main relay contact outputAC220V/5Aresistance loador AC220V/0.3Ainductive load
2.8Alarm relay and time relay contact outputAC220V/3Aresistance loador AC220V/0.3Ainductive load
2.9Overall dimensionmm4848110
Hole sizemm4444
2.10Power AC85V242V or AC100V250V, 50/60Hz
2.11Working environmenttemperature 050.0, relative humidity 85%RH, without corrode and strong
electromagnetic interference.

Panel and wiring diagram description (consult)

1PV display window: In the normal display state, it displays the measured value; in the parameters
modification state, it displays parameters symbol.
2SV display window: In the normal display state, it displays the countdown time or the temperature set value;
in the parameters modification state, it displays the parameter value.
3ALM1 indicator: When this indicator light on, the ALM1 relay have outputthat is, terminal No.1 and 13 are
connected.

4TE indicatorWhen this indicator light on, the TE relay have outputthat is, terminal No.14 and 13 are
connected.
5AT indicatorWhen the controller is in the setting itself state, the indicator light on.
6OUT indicatorWhen this indicator light on, the relay of control have output (that is,terminals No. 7 and 8 are
connected).
7Function key (SET): Press the key and release it to modify the SP and TE parameters. Press the key for 3
seconds to enter the parameters modification state
8Shift key: In the parameters modification state, press the key to realize the movement of number location ;
9Number reduced key: In the parameters modification, set value modification or manual adjustment state,
press this key to decrease the number .
10Number increased keyIn the parameters modification, set value modification or manual adjustment state,
press this key to increase the number.

Internal parameters
Series Code

Name

Temperature
setting value

Timing setting

Temperature
alarm value

3
4
5

Proportion modulus
Integral time
Differential time

Setting range
Determined by
P-SL and P-SH
1S5959M
1M5959H

0200.0
03000
0200

Setting itself

ON or OFF

Control period

2120S

9
10

Main control
return difference
Temperature alarm
return difference
Sensor error
amendment

0.1100.0
0.1100.0
20.0

050
11

Filt modulus

12

Code lock

It can time only after terminals No.11 and


12( "RESET") are short connected

Upper limit alarm


is determined by To set for the upper limit alarm, or the
P-SL,P-SH;
following alarm temperature value.
following alarm:
0.0100.0

explaining
Ex-Factory
Please refer to 6.2 The second
50
setting area

050

When P=0,the controller is under ON/OFF


control

ONopen function of setting itself;


OFFclose function of setting itself
Please refer toSetting itself
Set the relay control cycle, ON/OFF
control is meaningless.
Only have meaning when main control
output is ON/OFF (P=0)
Use for alarm contact output return
difference setting
When the sensor have error, it is used for
correction.
It is the software filter constant of
measurement sampling.The constant ,the
measurement antijamming capability ,
but the measurement and system time
0,all the parameters can be revised;
1,only the SP and TE can be revised;
1,all the parameters can not be
revised

10
100

15.0
240
30
OFF
10
1.0
1.0
0

20
0

13

14
15
16
17
18
19
20
21
22

23
24

Input type
Max. temperature range
CU50
-50.0150.0/-58.0302.0
CU50
PT100
-199.9600.0/-199.91112
Input type
PT100( )
K
-30.01300/-22.02372
K E
E
-30.0700.0/-22.01292
J T
J
-30.0900.0/-22.01652
S
T
-199.9400.0/-199.9752.0
S
-30.01600/-222912
The max. value of

They are used to reset proper temperature


temperature range
range as per userapplication.
As for the Max. temperature range for
The min. value of

different inputs, please refer to Sn,


temperature range
P-SHP-SL
OUTL100.0
Can
serve
as low and high output limiter.
The max. value
Meaningless when manual and ON/OFF
of allowable output
control(unit:%)
0.0OUTH
The min. value
of allowable output
Alarm output
01
0: upper limit alarm
definition
1: following alarm
Time unit choice
01
0: minute and second display
1: hour and minute display
System function
ON/ OFF
OFF: reverse control (heating control)
choice
ON: positive control (cooling control)
Output type
SSR or RLP
SSR: solid state relay output
RLP: relay output
power output of
0100
Soft start function( that is, first output
switching on
electric power coefficient.) (unit:%)
Fahrenheit and
degree centigrade
or
C
F
selecting
Display precision
ON or OFF
ONhave radix point;
OFFhave not radix point

1300
0
100.0
0.0
0
0
OFF
RLP
0
C
OFF

25

Time function
selection

03

0common temperature control(with one


alarm)without timing function( It should be
set to be 0 when you use AT function).
1 Connect terminal 11 and 12( RESET),
the meter start timing when it reaches the
setting temperature . The TE relay will
output after reaching setting time. The
controlleroutput relay keep on same
working situation(keep on heating)
2Connect terminal 11 and 12( RESET),
the meter start timing when it reaches the
setting temperature. The TE relay will
output after reaching the setting
time,Meanwhile, the controlleroutput
relay operate to stop heating
3 temperature control with one
alarmtime relay In this case,
temperature controller and time relay are
working respectively.
a).Temperature controller: It control
temperature normally.
b).Time relay: It works as follows: Connect
terminal 11 and 12( RESET), Timer start
timing(countdown) the terminal TE will be
connected and give out an alarm(you may
install buzzer in TE ) after time is up.
Disconnect terminal 11 ans 12 for reset.
Connect terminal 11 and 12(RESET) again,
it will do same as the above.
Note: If the time function is changed, the
new time function will be effected after
switching on meter again.

Flow chart

Parameters setting method:


6.1The first setting areaParameters setting
Power on controller first, then ,press the SET key 3 seconds to enter into the first setting area, the controller
will display the parameter code 225 in the upper row window and display the parameter value in the low row,
Press the or W key to adjust the parameter value, then press the SET key to save the data and enter into the
next parameter for setting, Keep pressing the SET key to exit quickly or press SET + keys to exit directly. If no
operation within 10 seconds during setting, it will save the data and withdraw from the setting state automatically.
6.2The second setting areatemperature and time setting
Power on controller first, then ,press the SET key and release it to enter into the second setting area, you can
modify the settinng value according to the above method, and then press SET key to display the time setting
parameter , modification method ibid.

Setting itself
When the meter is used at first or the control performance is worse after the condition changes, it is necessary
to use this function of setting itself to set the parameters ,such as P ID,etc.so as to avoid the trivial job of
manual operation which can not reach perfect effect in the past. The time of setting itself depends on working
condition. Take temperature control (reverse/heating ) for example, the method are as below After setting the
desired setting value of temperature, set HY to be 0.51.0, set Int to be 0 (it is status of temperature control
without timer), set AT to be ONAT lamp starts glittering, the meter enters into the status of setting itself, and
the control method is ON/OFF in this timeAfter three times vibration, it will automatically save PID parameter,
AT lamp goes out, the process of setting itself is over.
Note If the power goes off during setting, it will restart setting after switching on the meter next time. It is
because the meter has memory function,
If the setting should be stopped and exited artificially during setting,, set AT to be OFF, then it can
exit, but ,In this case, the setting result will be of no effect.

Fault analysis and clearance


XMTG-818(T) controller with advanced production process, has the strict test before leaving factory, it
improve the reliability of the controller. The usual fault is caused by the wrong operation or parameter setting. If
you find the fault couldnt be cope with, please record it, and contact with the agent or us. Sheet 8-1 is the usual
fault of XMTG-818(T) in the daily application
Sheet 8-1 clearance for common fault
Fault symptom

Causes analysis

Clearance

Abnormal power

1Poor contact of power cord


2Power switch does not close
well

Check the power

Signal display do not


correlate with the facts.
displayHHorLL

1Sensor model mismatch


2Wrong signal connection

1Check sensor model and


controllerinterior input
parameter
2Check signal wire

Abnormal output
control

1Wrong connecting output wire


2Reset terminals are not
connected

1Check output connection


2Check Reset terminals

Note: Our company will continue to improve product technology, design specification. If change, please
subject to the material object, without notice.

Common questions

Powered by AI

The setting itself function (AT function) in the XMTG-818(T) controller automatically adjusts the P, I, and D parameters to optimize control performance. When activated, the controller enters an ON/OFF control mode, and after three cycles, it saves the optimal values for these parameters. This reduces the need for manual adjustments, ensuring the controller adapts to changing conditions for optimal performance. The process can restart automatically if interrupted, thanks to the controller's memory function .

The 'Alarm output definition' parameter is used to configure the type of alarm output based on the specific needs of an application. It provides two options: '0' for upper limit alarms and '1' for following alarms. This parameter is crucial in applications requiring specific alarms to alert operators to operational limit breaches or changes .

The XMTG-818(T) controller achieves anti-interference capabilities through its design, which includes a software filter constant known as the 'Filt modulus'. Increasing this constant improves measurement anti-jamming capability at the cost of reduced measurement and system time, allowing the controller to maintain accurate readings even in environments with strong electromagnetic interference .

The XMTG-818(T) controller manages timing functions with selectable time units configured as either hour/minute or minute/second. The time settings range from 1M to 59.59H or 1S to 59.59M, depending on the time unit choice. This flexibility allows the controller to adapt to various timing requirements in different applications .

The XMTG-818(T) controller can accommodate input types CU50, PT100, K, E, J, T, and S. The corresponding temperature ranges are: CU50 (-50.0 to 150.0℃), PT100 (-199.9 to 600.0℃), K (-30.0 to 1300℃), E (-30.0 to 700.0℃), J (-30.0 to 900.0℃), T (-199.9 to 400.0℃), and S (-30.0 to 1600℃).

The XMTG-818(T) controller handles sensor errors by using the 'Sensor error amendment' parameter, which allows for correction within a range of ±20.0. This ensures accurate temperature readings despite potential sensor inaccuracies .

The primary functions of the XMTG-818(T) intelligence digital temperature controller include performing ON/OFF and PID control with a time function that offers selectable time units. It is equipped with seven input signals for free selection in the field. This controller does not suffer from over-regulation, possesses good anti-interference characteristics, and can autonomously set parameters to optimize control effects. It is commonly used in machinery, chemical, ceramics, light industry, metallurgy, petrochemical, and heat treatment industries .

The AT indicator on the XMTG-818(T) controller lights up when the device is in the setting itself state. This indicates that the controller is actively adjusting its parameters (P, I, D) to optimize its control strategy .

The time function selection impacts how the XMTG-818(T) controller utilizes its output relays by configuring operation modes, such as: 0 for common temperature control, 1 for starting timing after reaching the set temperature while maintaining heating, 2 for outputting relay to stop heating after timing, and 3 for independent operation of the temperature controller and time relay. This function allows customization of operational schedules and relay behaviors based on specific application needs .

The 'Control period' parameter on the XMTG-818(T) controller, set between 2 and 120 seconds, determines the relay control cycle duration. Under ON/OFF control settings, this parameter is meaningless as it exclusively impacts the PID control mode by adjusting the frequency of control action executions, thereby influencing system response times and stability .

You might also like