HVAC - Practical Basic Calculation PDF
HVAC - Practical Basic Calculation PDF
2012
www.PDHcenter.com
www.PDHonline.org
Page 2 of 37
www.PDHcenter.com
www.PDHonline.org
Page 3 of 37
www.PDHcenter.com
www.PDHonline.org
Vapor pressure is the pressure exerted by the motion of molecules of water vapor. It is dependent on
the amount of water vapor in the air and the temperature of the air.
Thermodynamics Basic Concepts.
The biggest problem in thermodynamics is the student to learn and recognize heat, work, force,
energy, power and other technical terms. So, it is very important to remember some concepts below:
Cal - The Cal is the standard unit of measurement for heat. The gram calorie, small calorie or calorie
(cal) is the amount of energy required to raise the temperature of one gram of water from 19.5 C to
20.5 C under standard atmospheric pressure of 1.033 Kg/cm (14.7 psi).
Btu - British Thermal Unit. The Btu is the standard unit of measurement for heat. A Btu is defined as
the amount of energy needed to raise the temperature of one pound of water from 58.5F to 59.5F under
standard pressure of 30 inches of mercury (14.7 psi).
Energy Unit Conversions:
Unit
1 Btu
Multiply
0.252
107.7
778.7
0.00396
0.00000116
1000
3.9604
To obtain
kcal
Kgf.m
ft.lbf
Btu
kW.h
cal
Btu
Unit
1W
Multiply
0.001
0.00134
0.0002387
44.2
0.000948
0.000284
To Obtain
kW
hp
kcal/s
ft.lbf/min
Btu/s
ton (refrig)
Unit
Multiply
To Obtain
0.3002
1.055
1.435
106.6
778.8
0.001
0.000239
0.000239
0.000423
1.8
4186.8
4.1868
778.2
ton (refrig)
kW
hp
kgf.m/s
ft.lbf/s
kilojoule/kilogram/C = kJ/(kg.C)
kilocalorie /kilogram/C = kcal/(kg.C)
Btu/pound/F = Btu/(lb.F)
Btu/pound/C = Btu/(lb.C)
Btu/pound/C = Btu/(lb.C)
joule/kilogram/C = J/(kg.C)
kilojoule/kilogram/C = kJ/(kg.C)
pound-force.foot/pound/R
1Cal
1 kcal
Watt is the metric unit for power.
1 Btu/s
1 joule/kilogram/K = J/(kg.K) =
1 joule/kilogram/C = J/(kg.C) =
1 Btu/pound/F = Btu/(lbF)
Page 4 of 37
www.PDHcenter.com
www.PDHonline.org
Obs.:
1 Watt = 1 Watt-Hour = 0.000948 (Btu/s) x 60 x 60 = 3.412 Btu/h
1 Btu/h = 0.293 Watt = 0.000293 kW
Celsius (also known as centigrade) is a temperature scale that is named after the Swedish astronomer
Anders Celsius (17011744), who developed a similar temperature scale two years before his death. Then
nominally, 0 C was defined as the freezing point of water and 100 C was defined as the boiling point of
water, both at a pressure of one standard atmosphere (1.033 Kg/cm).
Fahrenheit is the temperature scale proposed in 1724 by, and named after, the physicist Daniel Gabriel
Fahrenheit (16861736). On the Fahrenheit scale, the freezing point of water was 32 degrees Fahrenheit
(F) and the boiling point 212 F at standard atmospheric pressure (14.7 psi).
Pressure (P) is the force per unit area applied in a direction perpendicular to the surface of an object.
Gauge pressure is the pressure relative to the local atmospheric or ambient pressure.
Torr
(Torr)
pound-force
square
(psi)
Unit
Pascal
(Pa)
bar
(bar)
atmosphere
(atm)
1 Pa
1 N/m
0.00001
0.000009867 0.0075006
0.000145
1 bar
100000
106 dyn/cm2
0.9867
750
14.5
1 at
98066
0.980665
0.968
735.5
14.223
1 atm
101325
1.01325
1 atm
760
14.7
1 torr
133.322
0.013332
0.0013158
1 mmHg
0.0193
1 psi
0.006894
0.068948
0.068046
51.72
1 lbf/in
per
inch
Tons of Refrigeration:
For commercial and industrial refrigeration systems most of the world uses the kilowatt (kW) as the basic
unit refrigeration. Typically, commercial and industrial refrigeration systems are rated in Tons of
Refrigeration (TR).
One Ton of Refrigeration was defined as the energy removal rate that will freeze 1 ton of water at 0 C
(32 F) in one day, or, the amount of heat required to melt 1 ton of ice in 24 hours. The unit's value is
approximately 11,958 Btu/h (3.505 kW), redefined to be exactly:
1 Ton of Refrigeration = 12,000 Btu/h (3.517 kW) = 3024 Kcal/h
Metabolic rate.
Metabolic rate is measured in Met units. A Met is the average amount of heat produced by a sedentary
person (e.g. office work = 1 Met).
1 Met unit corresponds approximately: 360 Btu/h = 90,718 cal/h = 90.718 kcal/h.
Human beings are essentially constant-temperature creatures with a normal internal body temperature of
98.6F. Heat is produced in the body as result of metabolic activity.
Page 5 of 37
www.PDHcenter.com
www.PDHonline.org
If the internal temperature rises or falls beyond its normal range, mental and physical operation is
jeopardized or affected, and if the temperature deviation is extreme, then serious physiological disorders or
even death can result.
Comfort Zone.
The comfort range of temperature during summer varies between 70 to 76F dry bulb temperatures and
45 - 65% relative humidity.
The comfort range during cold winters would be in the range of 65 to 68F dry bulb temperature and
relative humidity of a minimum of 30%.
Heat Transfer.
Conduction is the spontaneous transfer of thermal energy through matter, from higher temperature to
lower temperature, and acts to equalize temperature differences. It is also described as heat energy
transferred from one material to another by direct contact.
Convection is usually the dominant form of heat transfer in liquids and gases. Convection is circulation of
a fluid or gas/air caused by temperature difference. Commonly an increase in temperature produces a
reduction in density.
Evaporation: It is exclusively a cooling mechanism. Evaporative losses become a predominant factor
when ambient temperatures are very high. When surrounding temperature is about 70F, most people lose
sensible heat.
Radiation is the only form of heat transfer that can occur in the absence of any form of medium; it means
heat transfers through a vacuum. Thermal radiation is a direct result of the movements of atoms and
molecules in a material.
Determinants of Thermal Comfort - Dry-bulb Temperature:
Thermal Comfort zone: It is an area plotted on the psychrometric chart. During summer the comfort
range of temperature varies between 70 to 76F dry bulb temperatures and 45 - 65% RH. During cold
winters the comfort condition would be in the range of 65 to 68F dry bulb temperature and relative
humidity of a minimum of 30%.
Humidity: Density of water vapor per unit volume of air is expressed in units of lbs. of water/ft of dry air.
Specific humidity = weight of water vapor per unit weight of dry air, expressed in grains/lb.
Relative Humidity (RH): Human tolerance to humidity variations: in winter is from 20 to 50%; in summer,
the range extends up to 60% @ 75F. High humidity causes condensation problems and reduces body
heat loss by evaporative cooling.
Psychrometrics Concepts.
Psychrometrics or psychrometry are terms used to describe the field of engineering concerned with the
determination of physical and thermodynamic properties of gas-vapor mixtures. The term derives from the
Greek psuchron meaning "cold" and metron meaning "means of measurement".
Thermodynamic properties of moist air are affected by atmospheric pressure. The standard temperature
is 59F and standard atmospheric pressure is 29.921 in-Hg (14.697 psi) at sea level.
Page 6 of 37
www.PDHcenter.com
www.PDHonline.org
The apparent molecular mass or weighted average molecular weight of all components, for dry air is
28.9645, based on the carbon-12 scale.
The gas constant for water vapor is 1545.32/18.01528 = 85.778 ft-lb/lbR. The temperature and
barometric pressure of atmospheric air vary with altitude as well as with local geographic and weather
conditions.
Gravity is also assumed constant at the standard value, 32.1740 ft/s2.
Psychrometric chart.
A psychrometric chart is a graphical presentation of the thermodynamic properties of moist air and
various air-conditioning processes and air-conditioning cycles.
The most common chart is the temperature - humidity ratio (w) chart. The Dry Bulb Temperature
(DB) appears horizontally as the abscissa and the humidity ratios (w) appear as the vertical axis.
Abridged sample of psychrometric chart is shown below:
Page 7 of 37
www.PDHcenter.com
www.PDHonline.org
Relative humidity (RH%): Curved lines that radiate from lower left to upper right are RH lines. Horizontal
line at the bottom represents 0% RH; the uppermost curved line is 100% RH line.
Humidity ratio: Humidity ratio or specific humidity w-lines are horizontal lines on the Y-axis, they range
from 0 to 0.28 lb/lb. Humidity ratio is dimensionless, sometimes expressed as grams of water per
kilogram of dry air or grains of water/lb of air.
Specific enthalpy (h): Enthalpy lines incline downward to the right-hand side (negative slope) at an
angle of 23.5 to the horizontal line and have a range of 12 to 54 Btu/lb expressed in Btu/lb of air.
Specific volume (v): Specific volume lines are represented by the diagonal lines close to 90. The moist
volume ranges from 12.5 - 15 ft/lb, also called Inverse Density, is the volume per unit mass of the air.
Example:
An air-conditioned room at sea level has an indoor design temperature of 75F and a relative humidity of
50%. Determine the humidity ratio, enthalpy, density, dew point, and thermodynamic wet bulb
temperature of the indoor air at design condition.
Solution:
Find the room temperature 75F on the horizontal temperature scale. Draw a line parallel to the 75F
temperature line and establish the point where it meets the relative humidity curve of 50% at point (r). This
point denotes the state point of room air.
Draw a horizontal line toward the humidity ratio scale from point (r). This line meets the ordinate and
thus determines the room air humidity ratio w = 0.0093 lb/lb.
Draw a line from point (r) parallel to the enthalpy line. This line determines the enthalpy of room air on
the enthalpy scale, h = 28.1 Btu/lb.
Draw a line through point (r) parallel to the moist volume line. The perpendicular scale of this line
indicates v = 13.67 ft/lb.
Draw a horizontal line to the left from point (r). This line meets the saturation curve and determines the
dew point temperature, Tdew = 55F.
Draw a line through point (r) parallel to the wet bulb line. The perpendicular scale to this line indicates
that the thermodynamic wet bulb temperature (WB) = 62.5F.
Basic Psychrometrics Calculation.
There are hundreds of psychometrics charts and calculation spreadsheets to be downloaded. For the
examples below try http://www.linric.com/webpsy.htm
Page 8 of 37
www.PDHcenter.com
www.PDHonline.org
Example 1. Calculate the air density, specific volume, and enthalpy in US units at the ambient conditions
of DB 87.8F, RH 80% and sea level.
Solution:
Air Density = 0.0714 lb/ft
Air Specific Volume = 14.32 ft/lb - dry air
Air Enthalpy = 46.35 Btu/lb - dry air
Example 2. Calculate the air density, specific volume, and enthalpy in US units at the ambient conditions
of DB 87.8F, RH 0% (Dry Air), and sea level.
Solution:
Air Density: 0.0723 lb/ft
Air Specific Volume: 13.8224 ft/lb - dry air
Air Enthalpy: 21.1196 Btu/lb - dry air
Example 3. Calculate the air density, specific volume, and enthalpy in US units at the ambient conditions
of DB 87.8F, RH 80%, and 1,000 feet in altitude.
Solution:
Air Density: 0.0688 lb/ft
Air Specific Volume: 14.8824 ft/lb - dry air
Air Enthalpy: 47.3494 Btu/lb - dry air
Basic Air Conditioning Calculations.
The air conditioning loads are the Sensible Heat Loads + Latent Heat Loads as explained below:
Sensible heat loads - Sensible heat gain is directly added to the conditioned space by conduction,
convection, and/or radiation. Sensible heat load is a total of:
Latent Heat Loads - Latent heat gain occurs when moisture is added to the space from internal
sources or from outdoor air as a result of infiltration or ventilation to maintain proper indoor air
quality. Latent heat load is a total of:
Page 9 of 37
www.PDHcenter.com
www.PDHonline.org
Page 10 of 37
www.PDHcenter.com
www.PDHonline.org
Where:
CFM = Air circulation flow, CFM
Wo = Outside moisture content of air (lb/lb-dry air)
Wi = Inside moisture content of air (lb/lb-dry air).
3) Humidity:
In a humidifying process, water vapor is added to moist air and increases the humidity ratio entering the
humidifier if the moist air is not saturated. The humidifying capacity is given by:
Hm = CFM x x (Ho Hi) [lb/min]
Where:
CFM = Volume flow rate of supply air, (CFM)
= Density of supply air, (lb/ft)
Ho, Hi = Moisture content of air at final and initial states, (Lb/lb of dry air).
Total heat loads are:
Qtotal = 4.5 x CFM x (Ho Hi) [Btu/h]
Where:
CFM = Volume flow rate of supply air, (CFM)
Ho, Hi = Moisture content of air at final and initial states, (Lb/lb of dry air).
Design Volume Flow Rate:
The design volume flow rate - V (Kg/m) (CFM) is calculated on the basis of the capacity to remove the
space cooling load at summer design conditions to maintain a required space temperature Tr:
V=
QTotal
60 x air x (Ho- Hi)
QSensible
60 x air x (To - Ti)
Where:
V = Design volume flow rate, (m/h) (CFM)
Q Total, Q Sensible = Design cooling load, (kW) (Btu/h)
air = Air density - may vary with air systems (see tables), (Kg/m) (lb/ft)
To = Room temperature - normally 75F (24C) - for comfort applications)
Ti = Supply air temperature leaving the cooling unit, (F) (C)
Ho = Room enthalpy Kg/Kg) (Lb/lb of dry air)
Hi = Supply air enthalpy Kg/Kg) (Lb/lb of dry air).
Total Refrigeration Load:
Since the sensible heat Qsensible and the latent heat Qlatent are known, the total Refrigeration Load
can be determined by:
RL = CFH x air x (Ho Hi) [Btu/h]
2011 Jurandir Primo
Page 11 of 37
www.PDHcenter.com
www.PDHonline.org
Where:
CFH = Air flow in ft/h (CFM x 60)
air = Air density = 0.075 lb/ft
Hi = Enthalpy of the air - inside temperature
Ho = Enthalpy of the air outside temperature
OBS.:
CFM (Cubic feet per minute): amount of air that flows through a space in one minute. 1 CFM equals
approximately 2 liters/s (l/s). A typical system produces 400 CFM/ ton of air conditioning.
Constant of 4.5 = 1 CFM airflow, there are 60 units in an hour, then, 60 CFM = 4.5 lbs of air.
Constant of 1.08 = (Specific heat of air) 0.24 Btu/lb/F x 4.5 = 1.08 Btu/lb/F
Constant of 0.68 = 1060/7000 x 4.5 = 0.68 Btuh as, 1060 Btu/h is latent heat water vaporization.
Constant of 13.5 ft/lb dry air @ 70F, 50% RH = Specific volume of moist air
Heat Loss by Conduction
The different ways to calculate heat loss are: k values, C values, U values and "R" values.
1) k = Thermal Conductivity: Thermal conductivity means the rate of heat transfer through one inch
of a homogeneous material expressed in Btu-in/h.ft.F or Btu-ft/h. ft.F. Materials with lower
kvalues are better insulators.
Q=kxAxT/t
Where:
k = is thermal conductivity - see tables - (Btu-in/h ft F) or (Btu-ft/h ft F).
A = is the concerning rea, ft
T = average temperature difference across the material, (F)
t = thickness of a wall or some material (in)
Example:
Calculate the heat loss through a 3 thick insulation board that has an area of 2 ft and has a k-value of
0.25. Assume the average temperature difference across the material is 70F.
Q = k-value x A x T / t
Q = 0.25 (k) x 2 (ft) x 70F ( T)
3 (in)
Q = 35 / 3 = 11.66 Btu/h
Most good insulating materials have a kvalue of approximately 0.25 or less, and rigid foam insulations have
been developed with k factors as low as 0.12 to 0.15.
2) Specific Heat: is defined as the amount of heat energy needed to raise 1 gram of a substance
1C in temperature, or, the amount of energy needed to raise one pound of a substance 1F in
temperature.
Q = m x Cp. (To Ti)
2011 Jurandir Primo
Page 12 of 37
www.PDHcenter.com
www.PDHonline.org
Where:
Q = Heat energy needed (Joules) (Btu),
m = Mass of a substance (Kg) (lb),
Cp = Specific heat of air (see tables), 0.24 Btu/lbF (1.01 Kcal/KgC)
(To Ti ) = Dry Bulb temperature of air change (C) (F)
Substances with higher specific heats require more heat energy to lower temperature than do
substances with a low specific heat.
Example:
Using metric units and imperial units, how much energy is required to heat 350 grams (0.77 pounds) of
gold from 10C (50F) to 50C (122F)?
Mass = 350g = 0.35 Kg = 0.77 lb
Specific heat of gold (see tables) = 0.129 J/(g.C) = 129 J/(Kg.C) x 0.000239 = 0.0308 Btu/(lb.F).
Q = m x Cp. (To Ti)
Metric Units:
Q = (0.35 Kg) (129 J/(Kg.C) (50C - 10C)
Q = 1806 J (1.71 Btu)
Q = m x Cp. (To Ti)
Imperial Units:
Q = (0.77 lb) (0.0308 Btu/(lb.F) (122F - 50F) =
Q = 1.71 Btu
OBS:
A greater means a smaller airflow rate (Kg/m) (CFM) for a given supply mass flow rate.
Greater the cooling load or sensible heat, Q Sensible, higher will be the airflow rate (Kg/m) (CFM).
3) C = Thermal Conductance: Thermal conductance is a specific factor is a heat transfer factor per
inch of thickness. The lower the C value, the better the insulator and the lower is the heat
loss.
The overall C value must not be additive because two insulating materials with a C-value of 0.5
each, the result will be 1.0.
4) U = Overall Coefficient of Heat Transmission: The U value is the rate of heat flow passing
through a square foot of a material per hour of each degree Fahrenheit difference in
temperature expressed in Btu/h. ft.F.
The U value is the inverse of the R value, (U = 1/R) since the lower the U factor, the
lower is the heat loss.
2011 Jurandir Primo
Page 13 of 37
www.PDHcenter.com
www.PDHonline.org
5) R = Thermal Resistance: The thermal resistance R value is a measure to retard heat flow. By
definition, thermal resistance is the reciprocal of a heat transfer coefficient.
In other words, the R value is the inverse of the k value (R = 1/k), the C value (R = 1/C) and
the U value (U = 1/R).
Example:
Calculate the heat loss through a 100 ft wall with an inside temperature of 65F and an outside
temperature of 35F. The wall is composed of 2" thickness bricks having a k factor of 0.80. The
insulation is also 2" thickness having a C factor of 0.16.
Solution:
The U value is found as follows:
R total = 1/k + 1/C =
R total = 2/0.80 + 1/0.16 =
R total = 8.75, Then:
U = 1/8.75 = 0.114 Btu/h ft F
Once the U factor is known, the heat loss can be calculated by the basic heat transfer equation:
Q = A x U x (Ti To)
Q = 0.114 (Btu/h ft F) x 100 (ft) x [65 (F) - 35 (F)]
Q = 0.114 x 100 x 30
Q = 342 Btu/h
Basic Calculations of Overall Coefficient of Heat Transmission - U
The basic equation to calculate the Overall Coefficient of Heat Transmission (U) is:
U = 1/R Total
Or
U=
1
Ri + R1 + R2 + . . .Ro
Where:
2011 Jurandir Primo
Page 14 of 37
www.PDHcenter.com
www.PDHonline.org
1
Ri + R1 + R2 + R3 + Ro
U=
1
0.68 + 0.94 + 8.0 + 0.18 + 0.17
U=
1
9.97
U=
0.10 Btu/h ft F
The heat loss Q for a 100 ft of wall with a 70 F temperature difference will be:
Q=AxUxT=
Q = 100 x 0.10 x 70 =
Q = 700 Btu/h
HVAC Heating Loss Calculations
The heat loss is divided into two groups:
1) The conductive heat losses through the building walls, floor, ceiling, glass, or other surfaces;
2) The convective infiltration losses through cracks and openings, or heat required to warm outdoor
air used for ventilation.
The heat loss is determined by the basic equation:
Q = A x U x (To Ti) = A x U x T
Where:
2011 Jurandir Primo
Page 15 of 37
www.PDHcenter.com
www.PDHonline.org
Q = Total hourly rate of heat loss through walls, roof, glass, etc (Btu/h);
U = Overall heat-transfer coefficient of walls, roof, ceiling, floor, or glass (Btu/h.ft.F);
A = Net area of walls, roof, ceiling, floor, or glass (ft);
Ti = Inside design temperature (F);
To = Outside design temperature (F).
T = To Ti (F)
Net Area (A):
The net area of each building section is determined from drawings or measurements considering the areas
of the four walls, floor, and ceiling, doors and windows. We will also need to determine the volume of the
building to estimate the rate of infiltration into the building measured in air changes per hour (ACH).
Overall Coefficient of Heat Transfer (U):
The U-value measures how well a building component (wall, roof or a window), keeps heat inside a
building. It is an indicator of how easy it is to keep the inside of the building cold. A house built with low Uvalue building components will use less energy and thus using less energy is good for the environment.
The inside design temperature is traditionally taken as 65F. The temperature difference between the
inside and outside of the building is the primary cause of heat loss in the winter months.
Outside Design Temperature (To):
The winter month heating load conditions are based on annual percentiles of 99.6 and 99%, which
suggests that the outdoor temperature is equal to or lower than design data 0.4% and 1% of the time
respectively. Then, commonly the outside design temperature (To) is 4F.
Example:
What is the value of the heat loss for a 10 ft building with a single glass [U-value of 1.13] with an inside
temperature of 70F and an outside temperature of 0:
Q = A (10) x U (1.13) x T (70 - 0) = 791 Btu/hr
Calculate the heat loss through each of the components separately and then add their heat losses together
to get the total amount.
Q (wall) =Q (framed area) +Q (windows) +Q (door)
Heat Conduction and Thermal Resistance:
The heat conducted through a plane wall is:
Qw =
k x A (t1 - t2)
L
[Btu/h]
Where:
k = Thermal conductivity of the wall material, Btu-in/h ft F
A = Area of the wall, ft
t1, t2 = Temperature difference of the wall, F
L = Wall thickness, inches
2011 Jurandir Primo
Page 16 of 37
www.PDHcenter.com
www.PDHonline.org
A (To - Ti)
R
Page 17 of 37
www.PDHcenter.com
www.PDHonline.org
Practical Example:
A building, 35.0 ft wide, 73.0 ft long and 8.0 ft high, is constructed with concrete 4 inches thick and
polystyrene insulation 2 inches thick on each side. The building has a total of 4 windows east, 16
windows north measuring 2.5 ft by 4 ft. Roof and ceiling are frame construction. The conditions are:
Inside: (Ti)
Dry bulb temperature = 80 F
Relative Humidity = 50%
Outside: (To)
Dry bulb temperature = 95 F
Dew Point = 75 F DP (dew point)
Ventilation:
Supply air = 65 F - Dry bulb temperature.
Air Handling Unit (AHU) = Assume 4,000 CFM per AHU
Others:
Average electrical usage = 1.0 watts/ft
Human activity per person = 180 Btu/h
Infiltration rate, assume = 20 CFM
Air density (air) = 0.075 lb/ft, at 80F, sea level.
The Thermal Conductivities k, the Thermal Resistances R, and the Overall Heat Transfer
Coefficient U are shown in table below.
Material
k (Btu-in/ h ft F)
Siding
Polystyrene wall side 1 (2.0 in)
Polystyrene wall side 2 (2.0 in)
Concrete (4.0 in)
Drywall
Pine 2 x 4
Insulation
Sheathing (0.5 in)
Glass
Framed roof and ceiling
R (Btu/h ft F)
U (Btu/h ft F)
1.0
0.17
0.17
10.0
0.45
0.8
0.28
0.8
1.13
0.23
1.0
6.0
1
+ 2.0 + 4.0 + 0.45 +
0.17
0.17
10
1
1.63
R = 26.0 Btu/h ft F
2011 Jurandir Primo
Page 18 of 37
www.PDHcenter.com
www.PDHonline.org
1) Sensible Loads:
The heat conducted through the wall area minus the windows area is:
Qwindows = A(To Ti) = [(Abuilding Awindows) x (To Ti)] =
R
R
East wall - Qw = [(8.0 x 35.0) - 4(2.5x4.0)] x (95 - 80) / 26 = 138 Btu/h
North wall - Qw = [(8.0 x 73.0) - 16(2.5x4.0)] x (95 - 80) / 26 = 245 Btu/h
Qwindows = 383 Btu/h
There are 20 windows, 10 ft each, the total glass area is 200 ft, considering that glass U = 1.13, the
heat conducted through the glass is given by equation:
Qwindows = A x U x (To Ti)
Qwindows = 200 x 1.13 (95 - 80) = 3390 Btu/h
The infiltration of outside air through cracks around windows and doors, a leakage rate of 20 CFM
assumed. The resulting sensible or infiltration heat gain inside is:
Qinfiltration = 1.08 x CFM (To Ti)
Qinfiltration = 1.08 (20) (95 - 80) = 330 Btu/h
For the medium size building considered here, the reference for average electrical usage is 1.0 watts/ft.
The heat gain from electrical appliances and lights is:
Remember:
1 Watt = 1 Watt-Hour = 0.000948 (Btu/s) x 60 x 60 = 3.412 Btu/h
Qlight = 3.412 x A
Qlight = 3.412 x (35.0 ft x 73.0 ft) = 8717 Btu/h
The sensible heat according to estimated for light activity is 200 Btu/h per person. For twenty people in
the building, this gives a heat gain of:
Qoccupancy = 20 (200) = 4000 Btu/h
The heat conducted through the frame ceiling is:
Qceiling = A x U x (To Ti) =
Qceiling = (35.0 x 73) x 0.23 x (95 80) = 8815 Btu/h
Adding all the heat gains the total Qsensible load is:
Qsensible = 383 + 3390 + 8717 + 330 + 4000 + 8815 =
Qsensible = 25635 Btu/h
2) Latent Loads:
For light activity, people produce a latent gain of about 180 Btu/h per person, so for twenty persons:
Qlatent light = 20 (180) = 3600 Btu/h
Kitchen appliances add latent heat to the building as estimated below:
2011 Jurandir Primo
Page 19 of 37
www.PDHcenter.com
www.PDHonline.org
Page 20 of 37
www.PDHcenter.com
www.PDHonline.org
Page 21 of 37
www.PDHcenter.com
www.PDHonline.org
Page 22 of 37
www.PDHcenter.com
www.PDHonline.org
Corrected
ASHRAE Method:
The ASHRAE tables provide hourly CLTD values for one typical set of conditions. Outdoor maximum
temperature of 95F with mean temperature of 85C and daily range of 21F, the equation is adjusted to
correction factors, then:
Q = U x A x CLTD
Corrected
Page 23 of 37
www.PDHcenter.com
www.PDHonline.org
Corrected
Where:
Page 24 of 37
www.PDHcenter.com
Time of
Day
9.00
10.00
11.00
12.00
13.00
14.00
15.00
16.00
17.00
CLTD*
CLTDc = (CLTD 5)
Q = U * A * CLTDc
9
9
9
10
10
11
12
14
15
4
4
4
5
5
6
7
9
10
154
154
154
192
192
230
269
346
384
www.PDHonline.org
U = 0.2 Btu/h.ft .F
A = 192 ft
SCL
SC
Q = A x SC x SCL
27
30
33
34
35
34
32
29
29
0.72
0.72
0.72
0.72
0.72
0.72
0.72
0.72
0.72
933
1037
1140
1175
1210
1175
1106
1002
1002
Page 25 of 37
www.PDHcenter.com
www.PDHonline.org
Practical Review:
Example:
Calculate the U-values and the Heat Loss through the various components with the following data:
Given:
4" common face brick, density: 130 lb/ft 3 Rw1 = 0.56 Btu/h.ft.F
0.5" air space, 50F mean and 10F temperature difference Rw2 = 2.54 Btu/h.ft.F
0.5" nail-base sheathing with bright aluminum foil to air space - Rw3 = 1.06 Btu/h.ft.F
3.5glass fiber batt insulation(3.5) Rw4 = 12.98 Btu/h.ft.F
0.5" gypsum board Rw5 = 0.45 Btu/h.ft.F
And,
Outside air film (15 mph) Ri = 0.17
Inside air film (vertical surface) - Ro = 0.68
Also,
Windows clear glass, double pane with 0.5" air space, area 210 ft, U-value = 0.64 Btu/h.ft.F;
Door, 1 3/4" solid core with metal, area 24 ft, U-value = 0.26 Btu/h.ft.F.
Assume infiltration - Air change = 0.6 for building volume = 12000 ft.
Assume ten people in the building, 20 CFM per person.
Using the webpsy/linric for dry-bulb temperature 70F and relative humidity 40% is found:
Wb = 55.76 F wb
Hi = 23.60 Btu/lb
Dp = 44.60 F dp
Wi = 43.66 gr/lb / 7000 = 0.0062 lb/lb dry air
Using the webpsy/linric for dry-bulb temperature 70F and dew point 50F for cooled air is found:
Page 26 of 37
www.PDHcenter.com
www.PDHonline.org
Wb = 58,18 F wb
RH = 49,02 % RH
Ho = 25,15 Btu/lb
Wo = 53.62 gr/lb / 7000 = 0.0076 lb/lb dry air
Page 27 of 37
www.PDHcenter.com
www.PDHonline.org
5) Determination of Heat Loss - windows clear glass, double pane, 0.5" air space:
Solution:
Window area = 210 ft, U-value = 0.64 Btu/h.ft.F, Ti = 70F To = 22F
Qwindow = U x A x (Ti - To) =
Qwindow = 0.64 x 210 x (48) = 6451.20 Btu/h
6) Determination of Heat Loss - door, 1 3/4" solid core with metal:
Solution:
Door Area = 24 ft, U-value = 0.26 Btu/h.ft.F, Ti = 70F To = 22F
Qdoor = U x A x (Ti - To) =
Qdoor = 0.26 * 24 * (48) = 299.52 Btu/h
7) Determination of heat loss by infiltration - Air change = 0.6, Building Volume: 12000 ft:
a) Sensible Heat Loss:
Qs = 1.08 x VCFM x (Ti - To) =
VCFM = (0.6*12000) / 60 = 120 CFM
Qsensible-inf. = 1.08 * 120 * 48 = 6220.80 Btu/h
b) Latent Heat Loss:
Qlatent-inf. = 4840 x VCFM x (Wo - Wi) =
Qlatent = 4840 x 120 x (0.0076 0.0062) = 813.12 Btu/h
8) Determination of Heat Loss by Ventilation - ten people, 20 CFM per person:
VCFM = 10 persons x 20 CFM = 200 CFM
Qsensible-vent. = 1.08 * VCFM * (Ti - To) =
Qsensible-vent = 1.08 * 200 * 48 = 10368 Btu/h.
Qlatent-vent. = 4840 * VCFM * (Wi - Wo) =
Qlatent-vent = 4840 x 200 x (0.0076 0.0062) = 1355.20 Btu/h
9) Total Heat Loss through the Building:
Qroof = 2926.08 Btu/h
Qwall = 2592 Btu/h
Qwindow = 6451.20 Btu/h
Qdoor = 299.52 Btu/h
Qsensible-inf. = 6220.80 Btu/h
Qlatent-inf = 813.12 Btu/h
Qsensible-vent = 10368 Btu/h
Qlatent-vent = 1355.20 Btu/h
2011 Jurandir Primo
Page 28 of 37
www.PDHcenter.com
www.PDHonline.org
Page 29 of 37
www.PDHcenter.com
www.PDHonline.org
SI units:
vm = qm / Am = 4 qm / ( dm2) = qm / (am bm) =
Where:
vm = Air velocity (m/s)
qm = Air flow (m3/s)
Am = Area of duct (m2)
dm = Diameter of duct (m)
am = Width of duct (m)
bm = Width of duct (m)
Pressure loss in ducts can be expressed as:
Dpt = dpf + dps + dpc =
Where:
Dpt = Total pressure loss in system psi (Pa, N/m2)
dpf = Major pressure loss in ducts due to friction psi (Pa, N/m2)
dps = Minor pressure loss in fittings, bends etc. psi (Pa, N/m2)
dpc = Minor pressure loss in components as filters, heaters etc. psi (Pa, N/m2)
Pressure loss in ducts due to friction can be expressed as:
Dpf = R l
Where:
R = Duct friction resistance per unit length - psi/ duct ft (Pa, N/m2 per m duct)
l = Length of duct inches (m)
Duct friction resistance per unit length can be expressed as:
R = / Dh ( v2 / 2) =
Where:
R = Pressure loss psi (Pa, N/m2)
= Friction coefficient
Dh = Hydraulic diameter inches (m)
A proper velocity will depend on the application and the environment. The table below indicate commonly
used velocity limits:
Type of Duct
Main ducts
Main branch
ducts
Branch ducts
Comfort Systems
m/s
FPM
4-7
780 - 1380
Industrial Systems
m/s
FPM
8 - 12
1575 - 2360
3-5
590 - 985
5-8
985 - 1575
6 - 12
1180 - 2360
1-3
200 - 590
3-5
590 - 985
5-8
985 - 1575
Page 30 of 37
www.PDHcenter.com
www.PDHonline.org
Obs.:
Be aware that high velocities close to outlets and inlets may generate unacceptable noise. Maximum air
velocity in the ducts should be kept below certain limits to avoid unacceptable generation of noise.
The values from the table below can be used to rough sizing of ducts in comfort, industrial and high speed
ventilation systems. Commonly, the accepted duct velocities can be found in the table below:
Velocity - v
Service
Air intake from outside
Heater connection to fan
Main supply ducts
Branch supply ducts
Supply registers and grilles
Low level supply registers
Main extract ducts
Branch extract ducts
Public buildings
(m/s)
2.5 - 4.5
3.5 - 4.5
5.0 - 8.0
2.5 - 3.0
1.2 - 2.3
0.8 - 1.2
4.5 - 8.0
2.5 - 3.0
FPM
500 - 900
700 - 900
1000 - 1500
500 - 600
250 - 450
150 - 250
900 - 1500
500 - 600
Industrial plant
(m/s)
5-6
5-7
6 - 12
4.5 - 9
1.5 - 2.5
FPM
1000 - 1200
1000 - 1400
1200 - 2400
900 - 1800
350 - 500
6 - 12
4.5 - 9
1200 - 2400
900 - 1800
Page 31 of 37
www.PDHcenter.com
www.PDHonline.org
Page 32 of 37
www.PDHcenter.com
www.PDHonline.org
The friction loss in a 20 inches duct with air flow 4000 CFM can be estimated to approximately 0.23
inches water per 100 feet duct as shown in the diagram below. The air velocity can be estimated to
approximately 1850 FPM.
The diagram is based on standard air 0.075 lb/ft in clean round galvanized metal ducts.
Obs.:
1 inch water = 248.8 N/m (Pa) = 0.0361 lb/in (psi) = 25.4 kg/m = 0.0739 in mercury
1 ft/min (CFM) = 1.7 m/h = 0.47 l/s
1 ft/min (FPM) = 0.00508 m/s
Chillers and Air Handling Unit (AHU):
Chillers provide cooling of the chilled water which is then used in the air cooling coils for air conditioning,
while AH Units provide cooling by direct expansion of the refrigerant in the air cooling coils.
In general AH Units are used for relatively small capacity systems and chillers are used for relatively
large capacity systems. Typically an AHU system is not used for systems larger than 100 ton capacity.
2011 Jurandir Primo
Page 33 of 37
www.PDHcenter.com
www.PDHonline.org
Page 34 of 37
www.PDHcenter.com
www.PDHonline.org
Obs.:
The air cooling coil in AH Units and the chilled water heat exchanger in chillers are also called an
"Evaporator" since evaporations of the liquid refrigerant occurs in these components.
Centrifugal compressor chillers (used for medium to large capacity applications);
Screw compressor chillers (used for medium capacity applications);
Reciprocating compressor chillers (used for small to medium capacity applications);
Scroll compressor chillers (used for small to medium capacity applications);
Refrigerants:
In general the most common refrigerants used in the industry belong to the following three categories:
CFC - These are the Chloro Fluoro Carbon refrigerants, such as R11, R12, R113, R114, identified
as the most harmful to Ozone layer by the Montreal Protocol, and were phased out in 2000.
The R12 is used commonly in the older cars for air conditioning.
HCFC - These are the Hydro Chloro Fluoro Carbon refrigerants, such as R22, R123, etc, identified
as slightly harmful to the Ozone layer by Montreal Protocol, and will be phased out by 2030.
The R22 refrigerant is commonly used in most reciprocating type of compressors, while R123 is
used in centrifugal chillers as a temporary replacement for R11.
HFC - These are the Hydro Fluoro Carbon refrigerants, such as R134a, that do not harm the
Ozone layer, and are being used in the newer machines to replace the CFC and HCFC.
The R134a is now commonly used to replace either R12 and R500, and in all new cars air
conditioning systems.
Refrigerant Analysis:
A periodic refrigerant analysis is important to detect and control contaminants in the refrigerant, which can
result in degradation / failure of the various components, and cause inefficient operation of the unit.
Refrigerants should be tested for the following contaminants:
Moisture, Acid; Particulate/solids, Organic matter sludge, wax, tars, Non-condensable gases.
Moisture
Moisture is one of the primary causes of contamination-related problems in a refrigeration system which
may cause damages to the chiller or AH Unit.
The acceptable levels of moisture in new or reclaimed refrigerants are given in ARI 700. These levels are
generally more demanding than what is typically feasible and acceptable in an operating system.
Page 35 of 37
www.PDHcenter.com
Refrigerant
R11
R12
R22
R113
R114
R134a
R500
Allowable
Moisture Level
per ARI 700
(ppm by wt)
20
10
10
20
10
10
10
www.PDHonline.org
Viscosity
Units
Water
Air
KJ/kg C
4.2
1.0
Btu/lb F
1.0
0.239
kg/m3
1000
lb/ft3
62.29
KJ/kg
1200 - 2100
Btu/lb
516 - 903
W/m C
0.55 - 0.70
0.025 - 0.05
Btu/h ft F
0.32 - 0.40
0.014 - 0.029
1.8 @ 0 C
0.02 - 0.05
cP
0.57 @ 50 C
0.28 @ 100 C
0.14 @ 200 C
Prandtl Number
1 - 15
0.7
REFERENCES:
ASHRAE: The American Society of Heating Air Conditioning and Refrigeration
2001 ASHRAE Handbook of Fundamentals
1997 ASHRAE Handbook of Fundamentals
ASHRAE Cooling and Heating Load Calculation Manual
NIST Standard Reference Database 69: NIST Chemistry WebBook.
University of Arkansas School of Architecture
Cooling Load Calculations and Principles, A. Bhatia, CEDengineering.com
Refrigerants Temperature/Pressure Table for common refrigerants
Page 36 of 37
www.PDHcenter.com
www.PDHonline.org
Links:
http://www.engineeringtoolbox.com/sizing-ducts-d_207.html
www.engineeringtoolbox.com/air-psychrometrics-properties-t_8.html
www.linric.com/webpsy.htm
http://www.flycarpet.net/en/download.asp
http://www.trane.com
http://www.refron.com/InfoCenter/Home.asp
http://www.chemicalogic.com/moistairtab/default.htm
http://www.epa.gov/ozone/title6/index.html
http://www.smacna.org/
Page 37 of 37