Water Contamination and Water Removal
in Industrial Ammonia Refrigeration Systems
By Ray Ficker, PE
Effects of Water Contamination
Water contamination in an industrial ammonia refrigeration system can lower system
efciency, and increase the electrical costs required to run the systems refrigeration
compressors.
For a given pressure, the addition of water to the ammonia will raise its temperature.
At typical suction pressures, the addition of 10% water by weight will increase the
evaporator temperature by about 4F (2C).
Stated another way, for a given required evaporator temperature, the addition of
water to the ammonia will require a lower suction pressure. For example, pure
ammonia at -4F (-20C) has a saturation pressure of 12.9 psig (0.90 barg). An
ammonia-water solution of 10% water and 90% ammonia by weight, at the same
-4F (-20C) has a saturation pressure of 10.2 psig (0.72 barg). Therefore to
maintain an evaporator temperature of -4F (-20C) in a system with 10% water
contamination, the suction pressure would have to be run at 12.9 10.2 = 2.7 psi
(0.18 bar) lower than if the water were not present.
Hansen Technologies Corporation Tel 630.325.1565 Fax 630.325.1572 Email [email protected] www.hantech.com
Ammonia / Water Solutions
Suction Pressure Penalty of Water
30
+14 F
25
Evapo
rator
4.1 psid
= 4.4 F
9.0 psid
= 10.4 F
Suction Pressure, psig
20
15
-4 F Eva
2.7 psid
= 4.2 F
porator
5.9 psid
= 9.7 F
10
-22 F Evapor
ator
1.7 psid = 3.8 F
3.8 psid
= 9.0 F
1.0 psid = 3.4 F
10" Hg
2.3 psid
= 8.3 F
-40 F Evaporator
20" Hg
0%
5%
10%
Water Concentraion by Weight
15%
20%
The requirement to maintain a lower suction pressure than would be necessary
if the water could be removed is a waste of electrical energy. As an example,
consider a booster compressor operating with -40F (-40C) evaporating and +20F
(-7C) condensing. At -40F (-40C), sizing software from a major compressor
Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems
2
manufacturer calculates that the power required is 1.44 hp/ton (COP=3.266). At
-44F (-42C), it calculates that the power required is 1.55 hp/ton (COP=3.043). The
4F (2C) difference represents a water concentration of slightly more than 10%.
Therefore, the extra energy required due to the 10% water concentration is
(1.55-1.44)/1.44 = 7.6%.
Energy Savings - Water Removal
(-40F evaporating, +20F condensing)
25%
Energy Penalty
Due to Excess Water
20%
15%
10%
5%
0%
0%
5%
10%
15%
20%
Water Concentration by Weight
To calculate the energy savings that could be achieved if the water were removed,
consider a total system operating at 1500 tons (3500 kW), a compressor run time
of 6500 hours per year, and an electricity rate of $.06/kW-hr. Then the excess
energy to run the compressors at the lower suction pressure due to 10% water for
Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems
3
this example is: (.076)(1500tons)(1.44hp/ton)(.746kW/hp)(6500hr/yr)($.06/kW-hr) =
$48,000 per year potential energy savings if the water is removed.
The effect of air contamination in industrial refrigeration systems has been well
documented over many years. Like water contamination, air contamination lowers
system efciency and increases electrical costs due to the higher compressor
discharge pressure caused by the presence of the air. When the air is removed with
a non-condensible gas purger (for example, a Hansen Auto-Purger) the discharge
pressure is reduced, system efciency is restored, and electrical costs are reduced.
The energy savings quickly pay for the cost of installing the non-condensible gas
purger. Typically, there is a 6% savings in energy cost for every 10 psi (0.7 bar) of
excess pressure due to non-condensible air that is removed from the refrigeration
system.
Compressor Power
kW per ton
4.00
p
em
t
n
3.00
e
tur
a
r
e
tio
uc
s
ture
a
F
r
e
0
emp
t
-4
n
tio
suc
F
re
- 20
ratu
e
p
n tem
o
i
t
c
u
0F s
6% decrease in kW per ton
for each 10 psi decrease in
condensing pressure
2.00
1.00
60
100
140
180
220
Condensing Pressure (psig) NH3
Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems
4
Other Benets of Proper Maintenance of Refrigerant Quality
Removing air and water from ammonia refrigeration systems certainly saves energy,
but there are other benets that improve system operation. On the high side of the
system, operating at the lowest condensing pressure permissible means less wear
and tear on compressor bearings and other mechanical parts. The lower discharge
temperatures also reduce oil and refrigerant breakdown, and extend gasket life. Air
removal means there is less oxygen in the system, which is sometimes associated
with corrosion of piping and vessels. In the same way, removing water from the
refrigeration system may reduce corrosion.
Means of Water Entry into a System
The most common way that water enters a system is with the air that enters the
system. The air that enters the system has a certain relative humidity. Therefore, as
air enters a system, a certain amount of moisture also enters the system.
The moist air enters the system in two common ways. 1.) For systems that operate
in a vacuum, system leaks will pull moist air into the system through the leak path.
2.) For all systems, regardless of whether they operate in a vacuum, if maintenance
is performed on a portion of the system, and if this portion is not pulled into a strong
vacuum before restoring it to service, that moist air remains in the system.
Non-condensible gas purgers are very effective at removing the air from the system.
They are however, less effective at removing the moisture from the system.
Another means of water entry into a system is when a water chiller develops a tube
leak, and water from the tube side mixes with the ammonia on the shell side, or vice
versa. This can introduce large amounts of water to a system, and drastic measures
may be required, including replacement of the entire refrigerant charge.
Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems
5
Location Where Water Typically Collects
The ammonia, air, water, and oil circulate through the refrigeration system.
Water will tend to collect on the low side of the system. Only gas can leave the low
side of the system. Therefore water, for the most part, can not leave the low side
and will collect here. (Some water can leave as water vapor, but most will stay in
the low side.) In two or more stage systems, the water will eventually collect in the
lowest stage vessel.
The oil, also not being a gas, collects in the low side of the system, and must be
routinely drained.
Alternatively, only liquid can exit the high side of the system, so air collects in the
high side. This is typically near the outlet of evaporative condensers or in the
coolest, low velocity section of receivers and water cooled condensers.
Removal of Water and Air from the Refrigeration System
Hansen Technologies pioneered the automatic, non-condensible gas purger over
two decades ago. Hansen Auto-Purgers efciently remove air from the high side of
the system where air collects.
Now Hansen Technologies has improved on the Auto-Purger to add water removal
capability. Auto-Purger models that have both water and air removal capabilities are
model Auto-Purger Plus.
Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems
6
" FOUL
GAS LINE
" LIQUID
RETURN LINE
" LOW-PRESSURE
PUMPED LIQUID LINE
VAPOR
TRAP
FLOAT
SWITCH
STRAINER/
ORIFICE
LIQUID
DRAINER
EVAPORATOR CHAMBER
" SUCTION LINE
LIQUID LEVEL
CONTROL SENSOR
AIR SEPARATOR
CHAMBER
EVAPORATOR SHELL
THERMOCOUPLE
WATER CONCENTRATION
SENSOR
Figure 1, Collecting Non-Condensible Gases
The Auto-Purger Plus removes air the same as the familiar Auto-Purger model. An
ammonia gas and air mixture (foul gas) is taken from various locations in the high
side. This gas is brought into the tube side of a shell and tube heat exchanger with
cold ammonia liquid on the shell side. The ammonia gas in the tube condenses to
liquid. The air being non-condensible remains a gas. When enough air is collected,
it is released. See gure 1.
Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems
7
Liquid Ammonia
and Water in
" FOUL
GAS LINE
" LIQUID
RETURN LINE
" LOW-PRESSURE
PUMPED LIQUID LINE
" SUCTION LINE
Only Ammonia
Gas Out
VAPOR
TRAP
FLOAT
SWITCH
STRAINER/
ORIFICE
LIQUID
DRAINER
EVAPORATOR CHAMBER
LIQUID LEVEL
CONTROL SENSOR
AIR SEPARATOR
CHAMBER
Water Concentration
Gradually Increases
EVAPORATOR SHELL
THERMOCOUPLE
WATER CONCENTRATION
SENSOR
Figure 2, Collecting Water
In the familiar Auto-Purger models, the liquid comes from the high side receiver and
from condensed foul gas and is expanded into the shell side of the heat exchanger
which is maintained at suction pressure. In the new Auto-Purger Plus model, the
liquid is taken from the pump discharge of the lowest pressure recirculator. This is
where we expect the water to collect. Only ammonia gas can exit the shell side of
the heat exchanger. The concentration of water gradually increases over time as
liquid ammonia and water are brought in, and only ammonia gas leaves.
See gure 2.
Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems
8
" FOUL
GAS LINE
" LIQUID
RETURN LINE
" LOW-PRESSURE
PUMPED LIQUID LINE
" SUCTION LINE
VAPOR
TRAP
LIQUID
DRAINER
LIQUID LEVEL
CONTROL SENSOR
Highly Concentrated
Water
AIR SEPARATOR
CHAMBER
EVAPORATOR CHAMBER
LOW LEVEL
SAFETY CUTOUT
EVAPORATOR SHELL
THERMOCOUPLE
WATER CONCENTRATION
SENSOR
PLATE THERMOCOUPLE
LIQUID THERMOCOUPLE
ELECTRIC HEATERS
Figure 3, Concentrating Water
Using foul gas as a heat source for concentrating the water can only bring the
concentration to about 50% water and 50% ammonia depending on the evaporating
pressure and the condensing temperature. In order to concentrate the water
much more, a water concentration sensor (pressure/temperature transducer) in
the shell side of the heat exchanger monitors the mixture. When the concentration
of water in the shell side of the heat exchanger gets to about 20%, the AP Plus
stops collecting air, isolates the mixture of ammonia and water, and energizes two
electric heaters to heat the ammonia water solution even hotter, and to much more
Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems
9
effectively concentrate the water. The heaters remain energized until the ammonia
water solution is heated to 185F (85C). This corresponds to a concentration of
about 80% to 90% water and 10% to 20% ammonia, depending on the suction
pressure. This concentrated water is then drained to a customer supplied container.
See gure 3.
After the water is drained, the Auto-Purger Plus goes back to normal operation
collecting air and water. If no air or water is present, there are no releases to
atmosphere.
Specications
For non-condensible gas (air) removal, the AUTO-PURGER PLUS is suitable for
systems up to 1500 tons (5300 kW) nominal system capacity when the system
operates above a vacuum. It is suitable for systems up to 750 tons (2600 kW)
nominal system capacity when the system operates in a vacuum.
For water removal, the AUTO-PURGER PLUS has the following capacities:
5% system water concentration 3 gallons per day,
10% system water concentration 5 gallons per day,
20% or more system water concentration 7 gallons per day.
Conclusion
Many industrial ammonia refrigeration systems contain signicant amounts of water
which reduces their efciency. The removal of this water has not received sufcient
attention in our industry. Removing the water with a Hansen model Auto-Purger
Plus can restore system efciency, reduce electrical costs, and save money.
Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems
10