0% found this document useful (0 votes)
265 views

9120 Troubleshooting Guide

The document provides troubleshooting guidance for various alarms that could occur on a UPS system. For each alarm type, it describes possible causes and recommended steps to resolve the issue, which may include cleaning ventilation, reducing load, restarting the UPS, or initiating a replacement if the alarm persists.

Uploaded by

Andy Cole
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
265 views

9120 Troubleshooting Guide

The document provides troubleshooting guidance for various alarms that could occur on a UPS system. For each alarm type, it describes possible causes and recommended steps to resolve the issue, which may include cleaning ventilation, reducing load, restarting the UPS, or initiating a replacement if the alarm persists.

Uploaded by

Andy Cole
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

9120 TROUBLESHOOTING GUIDE

Please select the picture that matches what is shown on the front of your UPS
BATTERY FAILURE ALARM:
This is possibly because the batteries were not fully charged when the test was carried out
or the batteries have become weak. Use the
and
buttons as detailed in the user
manual carry out a manual battery test.
If the alarm doesnt clear please follow the standard RMA process and request a
replacement unit.

DC BUS FAULT ALARM:


This is possibly because there has been a high load demand on the output of the unit,
there has been a very sudden high surge on the mains supply, or there is a fault with the
unit. Shut the load down or place the load on external bypass and press and hold the
button to switch the unit off, wait 10 seconds, and turn it back on.
If the alarm is still present please follow the standard RMA process and request a
replacement unit.

OVERTEMPERATURE ALARM:
This is because the air temperature within the UPS is too high. Ensure that the ventilation
grills on the front and rear panels are not blocked, that the ambient temperature is not
above 40 degrees C, and that the unit is not in direct sunlight. Rectify any of these
problems if present.
If the alarm is still present 1 hour after rectifying the problem please follow the standard
RMA process and request a replacement unit.

LOW OUTPUT VOLTAGE ALARM:


This is possibly because there has been a high load demand on the output of the unit or
there is a fault with the unit. Shut the load down or place the load on external bypass and
press and hold the
button to switch the unit off, wait 10 seconds, and turn it back on.
If the alarm is still present please follow the standard RMA process and request a
replacement unit.

OUTPUT SHORT ALARM:


This is possibly because there has been a high load demand on the output of the unit,
there is a fault with a piece of equipment connected to the unit, or there is a fault with the
unit. Shut the load down or place the load on external bypass and press and hold the
button to switch the unit off, wait 10 seconds, and turn it back on.
If the alarm is still present please follow the standard RMA process and request a
replacement unit.

BYPASS NOT AVAILABLE in the display:


This is not a fault with the UPS, but a warning to you that the incoming mains is out of
tolerance and is therefore not available as a bypass path should it be needed by the UPS.
The default voltage for your unit is 230V but this can be set to 240V using the
and
buttons as detailed in the user manual.
This sometimes happens when there is a power surge. If this light remains on you should
check the quality of the supply into the UPS. The bypass voltage can be checked by using
the
button as detailed in the user manual.

You might also like