DIGITAL
EARTH
LEAKAGE
RELAY
www.prokdvs.com
DIGITAL
EARTH LEAKAGE
RELAY
An ISO 9001 : 2008 Company
DIGITAL MICROCONTROLLER / MICROPROCESSOR BASED
EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE
CURRENT TRANSFORMER (CBCT / ZCT)MPEL SERIES IEEE
Device Code-64
Features
Digital Microprocessor / Microcontroller based compact design.
Continuous monitoring and display of set value and measured value of leakage current.
8 character 2 line LCD displays with back-lit.
Test & Reset facility.
CBCT / ZCT connection monitoring facility.
True RMS measurement of leakage current.
Trip Circuit Failure indication.
Immune to harmonics and transients.
Serial RS. 485 communication port with Modbus Protocol (optional).
Tropicalized and rugged design.
Transducer Output- (4 mA-20mA) (optional).
External Test, Reset, Fault & Healthy indication suitable for Mining application.
Applications
Frame leakage protection for LT control panels and switch boards.
Earth Leakage protection for Feeders / Motors / Generators / Transformers / Mobile
Operating Equipments.
Protection for hazardous sensitive environments like Oil Refineries/Cement Plant/Chemical
Plant/Steel Plant / Pulp Industries and General Electrical Distribution.
Protection for Mining and Control Engineering.
www.prokdvs.com
DIGITAL
EARTH LEAKAGE
RELAY
An ISO 9001 : 2008 Company
DIGITAL MICROCONTROLLER / MICROPROCESSOR BASED
EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE
CURRENT TRANSFORMER (CBCT / ZCT)MPEL SERIES IEEE
Device Code-64
Introduction
Earth Leakage Current give rise to generation of heat and result in progressive failure of
insulation, which leads to earth faults sparking flashovers, deterioration of earthing and finally
results into catastrophic fires which destroys costly equipments, gadgets and precious lives.
It is therefore essential to detect earth leakage current well before they cross the threshold
limits and isolate the circuit in the event of leakages.
Prok dv's make Digital microprocessor/microcontroller based Earth Leakage Relays (ELR) with
Core Balance Current Transformer (CBCT / ZCT) are used to detect leakage currents in
electrical power systems. ELR transmits a signal to activate the trip coil of the
MCCB/ACB/OCB/CONTACTOR in the event of earth leakage resulting in automatic isolation
of the load. ELR have been widely used and accepted because of field adaptability and
are economic.
Prok dv's make Earth Leakage Relay (ELR) MPEL series uses the state-of-the-art, Digital
microprocessor/micro controller based protection device to detect low level leakage due
to degradation of insulation of phase conductors or high impedance faults.The main feature
of Digital microprocessor/microcontroller Earth Leakage Relay (ELR) continuous display of
earth leakage currents of the power system. The unit has immunity to external disturbance
like harmonics and transients.
Principle of Operation
Digital microprocessor /microcontroller based Earth Leakage Relays ( ELR) with Core Balance
Current Transformer
(CBCT / ZCT) employs to sense the leakage current the (CBCT / ZCT) is mounted externally and
load current carrying cable are passed through the (CBCT / ZCT). Ideally in a leakage in a
leakage free system the incoming and outgoing currents are equal and opposite in
direction, which means that the vector sum of the three phase currents is zero and can be
expressed as
Ir + Iy + Ib = 0 for 3 phase 3 wire system
Ir + Iy + Ib+ In=0 for 3 phase 4 wire system.
For the above condition the CBCT / ZCT produces zero resultant magnetic flux keeping the
system healthy.
In case of earth leakage either due to insulation degradation / chemical corrosion etc. the
vector sum of currents is not zero and CBCT / ZCT generates voltage which is fed to the ELR.
This signal is compared with the set value of leakage current and trip command is initiated if
the leakage current is more than the set values of current and time. It is worthwhile to
emphasize that the unequal / unbalanced loading on phases does not effective the vector
sum and as such there is no difficulty in the use of Earth Leakage Relay ( ELR) on electrical
distribution system with unbalanced loading.
www.prokdvs.com
DIGITAL
EARTH LEAKAGE
RELAY
An ISO 9001 : 2008 Company
DIGITAL MICROCONTROLLER / MICROPROCESSOR BASED
EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE
CURRENT TRANSFORMER (CBCT / ZCT)MPEL SERIES IEEE
Device Code-64
Prok dv's recommends and suggests to use Digital Microprocessor/ Microcontroller based
Earth Leakage Relay (ELR) with core Balance Current transformer (CBCT / ZCT) for typical
areas like UPS/ Inverter application, Mining, Cement, Petroleum & Oil Refineries, Steel, Paper
and Pulping industries for greater Sensitivity, Selectivity and Reliability. The measurement of
Leakage Current is TRUE RMS reading and the device has an external ADC having 24 bit for
greater degree of Accuracy. The Earth Leakage Relay (ELR) has Back-Lit LCD Display 2 Line 8
Character for displaying the nature and magnitude of Fault. Earth Leakage Relay (ELR) can
detect if the CBCT/ZCT connection status ie detecting the CBCT /ZCT Open to ensure the
healthiness of the Relay. The ELR has Auto Re closure facility and also indicates the Trip Circuit
Failure if the Circuit Breaker fails to operate. The Earth Leakage Relay (ELR) has wide band
Auxiliary Input
Universal Power Supply of 85 Volts to 275 Volts AC / DC.
Digital Microcontroller / Microprocessor based Earth Leakage Relay ( ELR ) has RS 485
Communication Port with Modbus Protocol at a Baud Rate of 9.6 KBPS for Remote Access
and Control as an Optional Feature. A Transducer Output of 4 mili Amps to 20 mili Amps is
possible as an Optional Feature.
www.prokdvs.com
DIGITAL
EARTH LEAKAGE
RELAY
An ISO 9001 : 2008 Company
DIGITAL MICROCONTROLLER / MICROPROCESSOR BASED
EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE
CURRENT TRANSFORMER (CBCT / ZCT)MPEL SERIES IEEE
Device Code-64
Specifications
PARAMETERS
(Microcontroller/Microprocessor based)
CURRENT SETTING RANGE
TRIPPING TIME
300mA-12A -( MPEL-01 )
30mA-3.0 A - ( MPEL-02)
(18- steps .)
0.0 Sec-5 Sec
Step size- 0.05Sec.
AUXILIARY VOLTAGE
85-275V AC/DC
415V & 550V. AC
COMMUNICATION WITH
MODBUS PROTOCOL RS-485
Device ID: 1-31
Baud Rate:9600
Protocol: Modbus
CORE BALANCE CURRENT
TRANSFORMER TYPE
Moulded Case
or Resin Cast
CBCT / ZCT STANDARD SIZE
Internal Diameter
CONTACT RATING
MOUNTING
DIMENSION
CIRCULAR:
40mm,65mm, 100mm, 150mm
200mm,250mm & 300mm
RECTANGULAR:
User specified.
8A 250V AC/ 8A 30V DC
2C/O
Flush / Din
Flush: 96 x 96 x 70mm
Din:80 x 94 x 76mm
(WxHxD)
PANEL CUT OUT(FLUSH)
90 x 90 + .1mm
OPERATING TEMPERATURE
-5 C to + 55 C
REFERENCE STANDARDS
Note:
ELR / DEL-02 / MPEL-02 / DMPEL-02 / EL-05
/ DEL-05 is Calibrated for the maximum
CBCT / ZCT of size
40mm, 65mm, 100mm & 150 mm only
www.prokdvs.com
MPEL/DMPEL Series
IEC 60255 / IEC 755
a) IEC-755 clause 8.3
Verification of operating
characteristics ( PerformanceTest )
b) Insulation test IEC-60255
Insulation resistance test
- As per IEC-60255-Cl-5&7
Di-electric test- As per
IEC-60255-Cl-5&6
Impulse Voltage test
- As per IEC-60255-Cl-5&8
DIGITAL
EARTH LEAKAGE
RELAY
An ISO 9001 : 2008 Company
DIGITAL MICROCONTROLLER / MICROPROCESSOR BASED
EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE
CURRENT TRANSFORMER (CBCT / ZCT)MPEL SERIES IEEE
Device Code-64
WIRING DIAGRAM FOR DIGITAL MICROCONTROLLER /
MICROPROCESSOR BASED EARTH LEAKAGE RELAY(ELR)
WITH CORE BALANCE CURRENT TRANSFORMER (CBCT /
ZCT)(MPEL SERIES) - FLUSH MOUNTING TYPE WITH RS-485
DIGITAL MICROCONTROLLER / MICROPROCESSOR BASED
EARTH LEAKAGE RELAY(ELR) HIERARCHY (Time & Current
sensitivity)
www.prokdvs.com
DIGITAL
EARTH LEAKAGE
RELAY
An ISO 9001 : 2008 Company
DIGITAL MICROCONTROLLER / MICROPROCESSOR BASED
EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE
CURRENT TRANSFORMER (CBCT / ZCT)MPEL SERIES IEEE
Device Code-64
WIRING DIAGRAM FOR DIGITAL MICROCONTROLLER /
MICROPROCESSOR BASED EARTH LEAKAGE RELAY(ELR)
WITH CORE BALANCE CURRENT TRANSFORMER (CBCT /
ZCT)(DMPEL SERIES) - DIN MOUNTING FOR MINING
APPLICATION
WIRING DIAGRAM FOR DIGITAL MICROCONTROLLER /
MICROPROCESSOR BASED EARTH LEAKAGE RELAY(ELR)
WITH CORE BALANCE CURRENT TRANSFORMER (CBCT /
ZCT)(DMPEL SERIES) - DIN MOUNTING-RS 485 MODEL
www.prokdvs.com
DIGITAL
EARTH LEAKAGE
RELAY
An ISO 9001 : 2008 Company
DIGITAL MICROCONTROLLER / MICROPROCESSOR BASED
EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE
CURRENT TRANSFORMER (CBCT / ZCT)MPEL SERIES IEEE
Device Code-64
DIGITAL MICROCONTROLLER / MICROPROCESSOR BASED
DIN MOUNTING EARTH LEAKAGE RELAY(ELR) (MPEL) WITH
CORE BALANCE CURRENT TRANSFORMER (CBCT / ZCT )
DIGITAL MICROCONTROLLER / MICROPROCESSOR BASED
FLUSH MOUNTING EARTH LEAKAGE RELAY(ELR) WITH CORE
BALANCE CURRENT TRANSFORMER (CBCT / ZCT )
www.prokdvs.com
DIGITAL
EARTH LEAKAGE
RELAY
An ISO 9001 : 2008 Company
DIGITAL MICROCONTROLLER / MICROPROCESSOR BASED
EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE
CURRENT TRANSFORMER (CBCT / ZCT)MPEL SERIES IEEE
Device Code-64
ISO 9001-2008
Prok Devices Private Limited
SIMHADRI ,
No.2930, 14 th Cross,
Banashankari II nd Stage,
Off K.R. Road,
Bengaluru-560070
Karnataka
India
Tel:+91 80
43487777/26760718/26761719
Fax:+91 80 26761720
Email:
[email protected]www.prokdvs.com