0% found this document useful (0 votes)
482 views2 pages

Datasheet Flatpack2 48V HE Rectifiers

The document discusses Flatpack2 48V HE rectifiers, including their key features such as being power dense, highly efficient, proven reliability, and global compliance. They are suited for applications in telecom, utilities, and datacenters.

Uploaded by

ajdCruise
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
482 views2 pages

Datasheet Flatpack2 48V HE Rectifiers

The document discusses Flatpack2 48V HE rectifiers, including their key features such as being power dense, highly efficient, proven reliability, and global compliance. They are suited for applications in telecom, utilities, and datacenters.

Uploaded by

ajdCruise
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

The original HE rectifier

Since setting the new standard for rectifier


efficiency, the Flatpack2 HE family is now
available in a variety of voltages and power
ratings, all with superior efficiency up to 96.5%.
With more than 4 billion in-field operating hours
and a proven cumulative field MTBF of more
than 1,9 million hours, Flatpack 2 HE is the only
HE (High Efficiency) rectifier with a proven track
record.
The line of systems available for the ENERGY
STAR qualified Flatpack2 HE 48V rectifiers
spans from 8kW 2U racks with complete
distribution to multi-cabinet systems up to
2.8MW.

FLATPACK2 48V HE RECTIFIERS


2000W HE & 3000W HE
Doc 24111x.105.DS3 v2.5

KEY FEATURES

APPLICATIONS

POWER DENSE, UP TO 33 W/INCH3

TELECOM MOBILE / WIRELESS

RADIO BASE STATIONS/ CELL SITES

LTE / 4G / WIMAX

MOBILE SWITCHING CENTER (MSC)

MICROWAVE

BROADBAND

HIGH EFFICIENCY
PROVEN RELIABILITY
APPLICATION FLEXIBILITY 2KW-3MW
GLOBAL COMPLIANCE
PATENTED HE TECHNOLOGY

TELECOM FIXED
CENTRAL OFFICE

TELEPHONY SERVERS / SWITCHES

FIBER OPTICS

MICROWAVE

CABLE

BROADBAND

BROADCAST

DATACENTERS

6U 300A SYSTEM

POWER UTILITIES
SCADA

108KW SYSTEM

FLATPACK2 SYSTEM IN TYPE 3 OUTDOOR CABINET

Eltek Grterudveien 8, PB 2340 Strms, 3003 Drammen, Norway

Phone: +47 32 20 32 00

Eltek 2016 www.eltek.com

FLATPACK 2 48V HE RECTIFIERS


2000W HE & 3000W HE
Model

48V / 2000W HE

48V / 3000W HE

241115.105

241119.105

Voltage (nominal)

185 - 275 VAC / 185 - 275 VDC

176 - 277 VAC

Voltage (range)

85 - 300 VAC / 140 - 275 VDC

85 - 305 VAC

45 - 66 Hz / 0 Hz

45 - 66 Hz

Part number

INPUT DATA

Frequency
Current (maximum) @ nominal input, full load
Protection

11.6 ARMS
Fuse in both lines
Varistor for transient protection
Disconnect above 300 VAC/DC

19.2 ARMS
Fuse in both lines
Varistor for transient protection
Disconnect above 305 VAC

OUTPUT DATA
Voltage (default)

53.5 VDC

Voltage (adjustable range)

43.5 - 57.6 VDC

Power (maximum)

2000 W

3000 W

Power @ 85 VAC

850 W

1380 W

Current (maximum) @ nominal input, full load

41.7 A

62.5 A

< 100 mVpp

< 150 mVpp

< 2 mVRMS

< 2 mVRMS

Ripple, 30MHz bandwidth


Psophometric noise
Static Voltage regulation

0.5% for 10 - 100% load

Dynamic Voltage regulation


Protection

5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
Fuse
Short circuit proof
High temperature protection
Hot plug-in inrush current limiting

OTHER SPECIFICATIONS
Efficiency @ nominal input
Isolation

Up to 96.5 %
3.0 kVAC - input to output
1.5 kVAC - input to earth
500 VDC - output to earth

Up to 96.2 %

Alarms: Red LED 'on'

Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage
shutdown on output, Fan failure, Low voltage alarm, CAN bus failure

Warnings: Yellow LED 'on'

Rectifier in power de-rate mode, Remote battery current limit activated, Input voltage out of
range, flashing at overvoltage

Normal (module running): Green LED 'on'


Acoustic noise, full load @ Tambient = 25C
full load @ Tambient = 40C

< 20 dBA
< 56 dBA

< 40 dBA
< 58 dBA

MTBF (Telcordia SR-332 Issue I method III (a))

>350 000 (@ Tambient : 25 C)

>300 000 (@ Tambient : 25 C)

Operating temperature

-40 to +75C (-40 to +167F), humidity 5 - 95% RH non-condensing

Temperature de-rating above 45C (110F)

2000W to 1200W @ 75C (167F)

Storage temperature

-40 to +85C (-40 to +185F), humidity 0 - 99% RH non-condensing

Dimensions[WxHxD] / Weight

109 x 41.5 x 327mm (4.25 x 1.69 x 13) / 1.95 kg (4.3 lbs)

3000W to 2100W @ 75C (167F)

DESIGN STANDARDS
Electrical safety
EMC

UL 60950-1, EN 60950-1, CSA 22.2


EN 61000-6-1 / -2 / -3 / -4, EN 61000-3-2
ETSI EN 300 386 V.1.4.1, Telcordia NEBS GR1089 CORE

Environment

ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)
ETSI EN 300 132-2
Telcordia NEBS GR63 CORE Zone 4
ROHS compliant

Doc 24111x.105.DS3 rev2.5


Eltek Grterudveien 8, PB 2340 Strms, 3003 Drammen, Norway

Specifications are subject to change without notice


Phone: +47 32 20 32 00

Eltek 2016 www.eltek.com