The original HE rectifier
Since setting the new standard for rectifier
efficiency, the Flatpack2 HE family is now
available in a variety of voltages and power
ratings, all with superior efficiency up to 96.5%.
With more than 4 billion in-field operating hours
and a proven cumulative field MTBF of more
than 1,9 million hours, Flatpack 2 HE is the only
HE (High Efficiency) rectifier with a proven track
record.
The line of systems available for the ENERGY
STAR qualified Flatpack2 HE 48V rectifiers
spans from 8kW 2U racks with complete
distribution to multi-cabinet systems up to
2.8MW.
FLATPACK2 48V HE RECTIFIERS
2000W HE & 3000W HE
Doc 24111x.105.DS3 v2.5
KEY FEATURES
APPLICATIONS
POWER DENSE, UP TO 33 W/INCH3
TELECOM MOBILE / WIRELESS
RADIO BASE STATIONS/ CELL SITES
LTE / 4G / WIMAX
MOBILE SWITCHING CENTER (MSC)
MICROWAVE
BROADBAND
HIGH EFFICIENCY
PROVEN RELIABILITY
APPLICATION FLEXIBILITY 2KW-3MW
GLOBAL COMPLIANCE
PATENTED HE TECHNOLOGY
TELECOM FIXED
CENTRAL OFFICE
TELEPHONY SERVERS / SWITCHES
FIBER OPTICS
MICROWAVE
CABLE
BROADBAND
BROADCAST
DATACENTERS
6U 300A SYSTEM
POWER UTILITIES
SCADA
108KW SYSTEM
FLATPACK2 SYSTEM IN TYPE 3 OUTDOOR CABINET
Eltek Grterudveien 8, PB 2340 Strms, 3003 Drammen, Norway
Phone: +47 32 20 32 00
Eltek 2016 www.eltek.com
FLATPACK 2 48V HE RECTIFIERS
2000W HE & 3000W HE
Model
48V / 2000W HE
48V / 3000W HE
241115.105
241119.105
Voltage (nominal)
185 - 275 VAC / 185 - 275 VDC
176 - 277 VAC
Voltage (range)
85 - 300 VAC / 140 - 275 VDC
85 - 305 VAC
45 - 66 Hz / 0 Hz
45 - 66 Hz
Part number
INPUT DATA
Frequency
Current (maximum) @ nominal input, full load
Protection
11.6 ARMS
Fuse in both lines
Varistor for transient protection
Disconnect above 300 VAC/DC
19.2 ARMS
Fuse in both lines
Varistor for transient protection
Disconnect above 305 VAC
OUTPUT DATA
Voltage (default)
53.5 VDC
Voltage (adjustable range)
43.5 - 57.6 VDC
Power (maximum)
2000 W
3000 W
Power @ 85 VAC
850 W
1380 W
Current (maximum) @ nominal input, full load
41.7 A
62.5 A
< 100 mVpp
< 150 mVpp
< 2 mVRMS
< 2 mVRMS
Ripple, 30MHz bandwidth
Psophometric noise
Static Voltage regulation
0.5% for 10 - 100% load
Dynamic Voltage regulation
Protection
5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
Fuse
Short circuit proof
High temperature protection
Hot plug-in inrush current limiting
OTHER SPECIFICATIONS
Efficiency @ nominal input
Isolation
Up to 96.5 %
3.0 kVAC - input to output
1.5 kVAC - input to earth
500 VDC - output to earth
Up to 96.2 %
Alarms: Red LED 'on'
Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage
shutdown on output, Fan failure, Low voltage alarm, CAN bus failure
Warnings: Yellow LED 'on'
Rectifier in power de-rate mode, Remote battery current limit activated, Input voltage out of
range, flashing at overvoltage
Normal (module running): Green LED 'on'
Acoustic noise, full load @ Tambient = 25C
full load @ Tambient = 40C
< 20 dBA
< 56 dBA
< 40 dBA
< 58 dBA
MTBF (Telcordia SR-332 Issue I method III (a))
>350 000 (@ Tambient : 25 C)
>300 000 (@ Tambient : 25 C)
Operating temperature
-40 to +75C (-40 to +167F), humidity 5 - 95% RH non-condensing
Temperature de-rating above 45C (110F)
2000W to 1200W @ 75C (167F)
Storage temperature
-40 to +85C (-40 to +185F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight
109 x 41.5 x 327mm (4.25 x 1.69 x 13) / 1.95 kg (4.3 lbs)
3000W to 2100W @ 75C (167F)
DESIGN STANDARDS
Electrical safety
EMC
UL 60950-1, EN 60950-1, CSA 22.2
EN 61000-6-1 / -2 / -3 / -4, EN 61000-3-2
ETSI EN 300 386 V.1.4.1, Telcordia NEBS GR1089 CORE
Environment
ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)
ETSI EN 300 132-2
Telcordia NEBS GR63 CORE Zone 4
ROHS compliant
Doc 24111x.105.DS3 rev2.5
Eltek Grterudveien 8, PB 2340 Strms, 3003 Drammen, Norway
Specifications are subject to change without notice
Phone: +47 32 20 32 00