Standard PDI G102
Standard PDI G102
1
FORWARD
The Plumbing & Drainage Institute is comprised of a group of member companies, each
of which is engaged in the manufacture of products for the plumbing industry. The basic
aim of PDI is to contribute its combined talents and resources to the further advancement
of plumbing engineering and the plumbing industry. This standard is dedicated to those
goals.
For nearly 50 years, grease interceptors conforming to the Plumbing & Drainage
Institutes standard PDI-G101 have been used in plumbing waste water systems to permit
free flow of drainage from sinks and similar equipment by preventing grease
accumulations from clogging connecting piping and sewer lines. Since its publication,
Standard PDI-G101 has been widely recognized; it is referenced in most plumbing codes
and it is included as the basic testing and rating requirement of Military Specification
MIL-T-18361.
This standard PDI-G102 allows for the evaluation and verification of this new generation
of FOG sensing/ alarm devices in combination with PDI-G101 Hydro Mechanical Grease
Interceptors.
The Plumbing and Drainage Institute currently maintains a grease interceptor testing,
rating and certification facility and manufacturers interested in having interceptors tested,
rated, and certified in conformance with Standard PDI-G101 and G102 may obtain the
details by contacting the Plumbing & Drainage Institute.
This Standard is not intended to be limiting in any way, but rather is intended to provide a
uniform measure of performance by Grease Interceptor Sensing and Alarm devices. The
use of this Standard is voluntary and the issuance or existence of this Standard does not in
any respect prevent or restrict any member or non-member of The Plumbing and
Drainage Institute from manufacturing or supplying products that do not meet the
performance criteria contained in the Standard. The data in this publication are based on
information believed to be reliable and are offered in good faith but without guarantee.
The Plumbing and Drainage Institute and its member companies assume no responsibility
or liability for the use of this Standard. No warranty, express or implied, is made of the
information contained in this Standard by The Plumbing and Drainage Institute or by any
of its member companies.
Table of Contents
Scope... 3
Purpose....... 3
Test Method 5
Concurrent testing with G-101............. 5
Non Concurrent Testing....... 5
Installation.. 6
Certificate of Approval...... 6
Marking.. 6
-2-
SCOPE
1.0 To provide requirements for FOG sensing and alarm devices used in grease
interceptors that meet the requirements of PDI-G101
FOG sensing and alarm devices are meant to notify personnel at the installation
site that the grease level within the grease interceptor is approaching its rated
capacity.
PURPOSE
2.0 The Plumbing and Drainage Institute (PDI) has long recognized and emphasized
the need for regular maintenance of interceptors that meet the PDI-G101 standard.
Without regular maintenance, it is possible for these interceptors to reach their
maximum rated capacity and allow FOG (fats, oils, and greases) to flow through,
thus not properly maintaining the efficiency levels as indicated in PDI G101.
Grease interceptors that meet the requirements of PDI-G101 are effective up to
their rated capacity. PDI-G102 sets requirements for how sensing and alarm
devices perform to signal that the interceptor is approaching said rated capacity.
This allows the installation site personnel the opportunity to properly
maintain/clean the grease interceptor before reaching its said rated capacity.
-3-
Sensing and Alarm Devices
3.0 Requirements
Referencing the PDI-G101 grease interceptor test requirements, PDI- G102 requires
an audible as well as a visible alarm be activated automatically when the monitored
(sensing and alarm equipped) grease interceptor reaches 60% - 100% of either its
rated capacity or actual capacity.
3.1 The alarm must be activated automatically with input from the sensor. The
alarms shall activate by sensing the grease level in the interceptor at some
time after the 6th test increment (drop) and no later than 3 hours after the 10th
test increment (drop) in a standard PDI-G101 test or grease retained is
between 60% to 100% of the breakdown point (actual capacity) when tested
per PDI-G101 section7.7.
3.3 Once the visible alarm is activated it may only be deactivated automatically
if within 3 hours grease from the unit is removed to a level less than that of
the alarm activation level. After 3 hours a manual re-set is required.
3.4 The audible alarm must be rated between 60 and 80 decibels, measured with
a hand held meter conforming to ANSI 1.4 / IEC 651 Type 2 at a distance of
15 feet from the alarm.
3.5 When initially activated, the audible alarm shall sound at a rate no less
frequent than once every 5 seconds or shall be constant.
3.7 The sensing device installed in an interceptor, qualifying under section 4.2,
shall have no greater than a 1% effect on that interceptors static water level
volume.
3.8 Any battery powering the sensing and alarm device shall have a minimum
operating battery life of 1 year.
-4-
3.9 All electrical components shall conform to the appropriate section of UL
Standards 499,917,1004 and 15
Test Method
4.0 Performance testing of a FOG sensing and alarm device per this Standard shall be
executed concurrently during an interceptors PDI-G101 testing or conducted
subsequently, as an additional test, on interceptors previously certified to PDI-
G101
4.1.1 The sensing and alarm device shall be installed and operational before
concurrent performance testing begins.
4.1.2 The test increment (drop) in the PDI-G101 test protocol at which the
audible and visual alarms are activated shall be recorded
4.1.3 If the alarms have not activated before the 10th test increment (drop of
grease) in the PDI-G101 protocol, the allotted 3 hours (reference Section
3.1) after the 10th drop shall be allowed for the alarms to activate.
4.1.4 The laboratory test report shall state at what percentage of the interceptors
rated capacity the alarms were activated and if it meets the requirement in
Section 3 of this standard, activating automatically after test increment 6,
7, 8, 9 or 10.
-5-
INSTALLATION
5.1 Grease interceptors shipped with a sensing and alarm device shall have
the sensor located in the correct operational position. Complete operating
instruction shall also be included.
6.0 A certificate shall be issued from the authorized testing laboratory to The
Plumbing and Drainage Institute (PDI) upon the successful completion of the
testing requirements of this standard. The certificate shall specify the Model
number of the Sensing and alarm device and the interceptor Model that was tested
or a single Model number for the complete Interceptor and sensing and alarm
assembly. The laboratory shall complete PDI G102 Grease Interceptor Sensing &
Alarm Device Test Form #1
-6-
6.0.1 Test Form # 1
Section 3.2
Section 3.3
Section 3.4
Section 3.5
Section 3.6
Section 3.7
Section 3.8
Section 3.9
6.1 A PDI Seal with PDI-G102 can only be affixed to an interceptor with sensing and
alarm assembly where that specific combination of interceptor and sensing and
alarm device has been certified to this standard.
-7-