I/O Extension Module - RAD-DAIO6-IFS - 2901533: Key Commercial Data
I/O Extension Module - RAD-DAIO6-IFS - 2901533: Key Commercial Data
com/sg/products/2901533
Analog/digital I/O extension module with 2 digital inputs/outputs (0...250 V AC/DC) and 1 analog input
(0/4...20 mA) and output (0/4 ... 20 mA, 0...10 V), with screw connection, incl. DIN rail connector
GTIN
GTIN 4046356610216
Weight per Piece (excluding packing) 200.000 g
Custom tariff number 85389091
Country of origin Germany
Technical data
Note
EMC: class A product, see manufacturer's declaration in the download
Utilization restriction
area
Dimensions
Width 17.5 mm
Height 99 mm
Depth 114.5 mm
03/13/2017Page1/8
https://www.phoenixcontact.com/sg/products/2901533
General
Overvoltage category II
Mounting position any
Assembly instructions on standard DIN rail NS 35 in accordance with EN 60715
Degree of pollution 2
Housing material PA 6.6-FR
Flammability rating according to UL 94 V0
889 Years (Telcordia standard, 25C temperature, 21% operating cycle
MTTF
(5 days a week, 8 hours a day))
391 Years (Telcordia standard, 40C temperature, 34.25% operating
cycle (5 days a week, 12 hours a day))
151 Years (Telcordia standard, temperature 40 C, operating cycle 100
% (7 days a week, 24 hours a day))
Supply
Supply voltage range 19.2 V DC ... 30.5 V DC (DIN rail connector)
Max. current consumption 95 mA (At 24 V DC, at 25C)
Transient surge protection Yes
Analog inputs
Number of inputs 1
Current input signal 0 mA ... 20 mA (can be set via DIP switches)
4 mA ... 20 mA (can be set via DIP switches)
Max. current input signal 22 mA
Input resistance current input < 70
Precision 0.02 % (at 25 C)
Temperature coefficient, typical typ. 0.0025 %/K (at -40 C ... +70 C)
Supply voltage 12 V DC (For passive sensors (via terminal PWR1, +I1))
Resolution 16 bit
Protective circuit Short-circuit and overload protection
Digital inputs
Description of the input Digital input
03/13/2017Page2/8
https://www.phoenixcontact.com/sg/products/2901533
Analog outputs
Number of outputs 1
Voltage output signal 0 V ... 10 V
Max. voltage output signal approx. 10.83 V
Load 10 k
Precision typ. 0.5 % (Voltage output)
Current output signal 0 mA ... 20 mA
4 mA ... 20 mA
Max. current output signal approx. 21.67 mA
Load 500
Precision 0.02 % (at 25 C)
Resolution 16 bit
Temperature coefficient, typical typ. 0.0025 %/K (at -40 C ... +70 C)
Behavior of the outputs (adjustable via DIP switch) Hold / Reset
Protective circuit Transient protection of outputs
Digital outputs
Number of outputs 2
Contact type PDT
Contact material AgSnO2
Maximum switching voltage 250 V AC
24 V DC
Min. switching current 10 mA
Max. switching current 2A
Mechanical service life 7
1 x 10 cycles
Electrical service life 5
2 x 10 cycles (At 2 A, 250 VAC, cos 0.4)
5
2 x 10 cycles (At 1 A, 24 V DC, L/R = 48 ms)
Maximum switching frequency 2 Hz
Switching capacity 48 W (24 V DC)
60 W (30 V DC)
20 W (48 VDC)
18 W (60 V DC)
22 W (110 V DC)
40 W (220 VDC)
03/13/2017Page3/8
https://www.phoenixcontact.com/sg/products/2901533
Electrical isolation
300 V (Rated insulation voltage (in each case between the digital
Digital I/O inputs // digital outputs //TBUS supply, reinforced insulation according to
EN61010))
50 V (Rated insulation voltage (in each case between the TBUS analog
Analog I/O inputs / analog outputs /supply, reinforced insulation according to
EN61010))
300 V (Rated insulation voltage (in each case between the digital inputs
Digital/analog I/O and outputs // analog inputs and outputs, reinforced insulation according
to EN61010))
Test voltage
Digital I/O 2.5 kV AC (50 Hz, 1 min.)
Analog I/O 1.5 kV AC (50 Hz, 1 min.)
Connection data
Connection method Screw connection
Conductor cross section solid min. 0.2 mm
Conductor cross section solid max. 2.5 mm
Conductor cross section flexible min. 0.2 mm
Conductor cross section flexible max. 2.5 mm
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 7 mm
Tightening torque 0.6 Nm
Screw thread M3
Status indicator
Status display Green LED (supply voltage, PWR)
Green LED (bus communication, DAT)
Red LED (periphery error, ERR)
Yellow LED (digital input, DI1)
Yellow LED (digital input, DI2)
Yellow LED (digital output, DO1)
Yellow LED (digital output, DO2)
Approvals
Approvals
Approvals
Ex Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 238705
03/13/2017Page5/8
https://www.phoenixcontact.com/sg/products/2901533
EAC
EAC-Zulassung
cULus Listed
Accessories
Accessories
Communication module
Communication module-RAD-RS485-IFS-2702184
Multipoint multiplexer for RS-485 bus system, can be extended with I/O extension modules. Can be used as Modbus
RTU bus coupler or combined with Radioline wireless system, screw connection. Up to 99 stations, including DIN rail
connector
DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-plated contacts, 5-pos.
Extension module
Analog/digital I/O extension module with 2 digital inputs/outputs (0...250 V AC/DC) and 1 analog input (0/4...20 mA)
and output (0/4 ... 20 mA, 0...10 V), with screw connection, incl. DIN rail connector
03/13/2017Page6/8
https://www.phoenixcontact.com/sg/products/2901533
Wireless module-RAD-2400-IFS-2901541
2400 MHz wireless transceiver with RS-232, RS-485 2-wire interface, expandable with I/O extension modules, with
screw connection, antenna connection:RSMA (female), including DIN rail connector, without antenna
Wireless module-RAD-868-IFS-2904909
868 MHz wireless transceiver with RS-232, RS-485 2-wire interface, expandable with I/O extension modules, with
screw connection, antenna connection:RSMA (female), including DIN rail connector, without antenna.
Wireless module-RAD-900-IFS-2901540
Bidirectional, Radioline 900 MHz transceiver for wireless transmission of serial and I/O data
Wireless module-RAD-2400-IFS-2901541
2400 MHz wireless transceiver with RS-232, RS-485 2-wire interface, expandable with I/O extension modules, with
screw connection, antenna connection:RSMA (female), including DIN rail connector, without antenna
Wireless module-RAD-900-IFS-2901540
Bidirectional, Radioline 900 MHz transceiver for wireless transmission of serial and I/O data
03/13/2017Page7/8
https://www.phoenixcontact.com/sg/products/2901533
Wireless module-RAD-868-IFS-2904909
868 MHz wireless transceiver with RS-232, RS-485 2-wire interface, expandable with I/O extension modules, with
screw connection, antenna connection:RSMA (female), including DIN rail connector, without antenna.
Communication module-RAD-RS485-IFS-2702184
Multipoint multiplexer for RS-485 bus system, can be extended with I/O extension modules. Can be used as Modbus
RTU bus coupler or combined with Radioline wireless system, screw connection. Up to 99 stations, including DIN rail
connector
Additional products
Analog/digital I/O extension module with 2 digital inputs/outputs (0...250 V AC/DC) and 1 analog input (0/4...20 mA)
and output (0/4 ... 20 mA, 0...10 V), with screw connection, incl. DIN rail connector
03/13/2017Page8/8