SEWA BRACKER AND CABLE SELECTION DETAILS
ELECTRICAL BREAKER CALCULATION =TOTAL CONNECTED LOAD x 1.739
ELECTRICAL BREAKER CALCULATION =TOTAL CONNECTED LOAD x 1.739 x 1.2 (FOR ISO)
SELECT CABLE SIZE IN THIS TABLE
Sl BREAKER/ TRANSFORMER MCCB/ACB SIZE OF CABLE SIZE OF CABLE REMARKS
NO. SIZE CU/XLPE/PVC+ CU/PVC/ECC
1 32A MCCB 2C x 10 MM2 / 1C x 10 MM2 / BELOW 5.9 KW
4C x 16 MM2 1C x 16 MM2 SP BREAKER
2 40A MCCB 4C x 16 MM2 1C x 16 MM2 BREAKER
3 63A MCCB 4C x 25 MM2 1C x 16 MM2 BREAKER
4 80A MCCB 4C x 25 MM2 1C x 16 MM2 BREAKER
5 100A MCCB 4C x 35 MM2 1C x 16 MM2 BREAKER
6 125A MCCB 4C x 50 MM2 1C x 25 MM2 BREAKER
7 160A MCCB 4C x 70 MM2 1C x 35 MM2 BREAKER
8 200A MCCB 4C x 95 MM2 1C x 50 MM2 BREAKER
9 225A MCCB 4C x 120 MM2 1C x 70 MM2 BREAKER
10 250A MCCB 4C x 150 MM2 1C x 70 MM2 BREAKER
11 300A MCCB 4C x 185 MM2 1C x 95 MM2 BREAKER
12 350A MCCB 4C x 240 MM2 1C x 120 MM2 BREAKER
13 400A MCCB 4C x 300 MM2 1C x 150 MM2 BREAKER
TRANSFORMER
(250 KVA)
14 800A MCCB 4 X 1C x 630 MM2 1C x 300 MM2 BREAKER
TRANSFORMER
(500 KVA)
15 1600A ACB 7 X 1C x 630 MM2 1C x 300 MM2 BREAKER
TRANSFORMER
(1000 KVA)
16 2500A ACB 11 X 1C x 630 MM2 1C x 300 MM2 BREAKER
TRANSFORMER
(1500 KVA)