Open navigation menu
Close suggestions
Search
Search
en
Change Language
Upload
Sign in
Sign in
Download free for days
0 ratings
0% found this document useful (0 votes)
1K views
50 pages
Manual - Oil Purifier
manual
Uploaded by
Jan Mark Wong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here
.
Available Formats
Download as PDF or read online on Scribd
Download now
Download
Save Manual - Oil Purifier For Later
Download
Save
Save Manual - Oil Purifier For Later
0%
0% found this document useful, undefined
0%
, undefined
Embed
Share
Print
Report
0 ratings
0% found this document useful (0 votes)
1K views
50 pages
Manual - Oil Purifier
manual
Uploaded by
Jan Mark Wong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here
.
Available Formats
Download as PDF or read online on Scribd
Download now
Download
Save Manual - Oil Purifier For Later
Carousel Previous
Carousel Next
Download
Save
Save Manual - Oil Purifier For Later
0%
0% found this document useful, undefined
0%
, undefined
Embed
Share
Print
Report
Download now
Download
You are on page 1
/ 50
Search
Fullscreen
Pall Corporation HNP0O21 Service Manual FLUID CONDITIONING PURIFIERS service manual Filtration. Separation. Solution.s#Copyright clause HNPO21 Service Manual FLUID CONDITIONING PURIFIERS Document Number: MAN021_EN Revision Level: M Original Information “oignator — checker Appar — approver [appre approvers | aoe ane [Abu ae SNOW 2006 Revision M_ Information Reyer Checker| Approvect [Apps AppioverS —[Appowr [Approve Kane [Mtewen Dae ZHU 2007 Copyright clause Reprints, even of extracts hereof, are permitted only if the source is quoted and permission has been granted by Pall. ‘The main components, devices, arrangements, as well as software, control and instrumentation equipment on all of our machines are protected both at home and abroad by patent applications, design registrations or copyright. © Copyright by Pall Europe Limited Europa House Havant Street Portsmouth. PO1 3PD MAN021_ENHNP021 Service Manual Contents| FLUID CONDITIONING PURIFIERS 1 Contents 41 Contents... 2 Foreword. 2.4 Temms of Guarantee 2.2 Trademarks & Intellectual Property. 3. Safety. 3.1 General Safety instructions. 3.2 Installation Site... 3.3. Safety of Personnel 4 Description of Operation 44 General 4.2 Principles of Operation .. 5 Technical Data 5.1 Mentification ... 5.2 General Data........ 5.3 Design Operating Conditions .. 5.4 Fluid System... 5.5 Vacuum System. 5.6 Electrical System and Motor & Drive System....... 5.7 Materials of Construction. 5.8 Options Available ..... 6 Components Details and Safety System 61 Fluid inlet System.. 62 Vacuum System 63 Fluid Outlet System 64 — AirDischarge System.. 65 Drive System.. 6.6 Base Assembly and Pipework 6.7 Main Manifold Block .. 68 — Electrical System. 68.1 Control Box....... 68.2 Alarms and Waming: 7 Installation and Operation... 7.1 Storage. 7.2 Pre-Instaliation Inspection 7.3. Connection of the Unit to Fluid Suppl 7.3.4 Inlet Line Design / Sizing.. 73.2 Outlet Line Reservoir Retum 7.3.3 Appreciation of Reservoir Internal Form. — MANO21_EN 3HNP021 Service Manual FLUID CONDITIONING PURIFIERS 7.3.4 Location of Suction Port on Reservoi 25 7.35 Location of Unit 26 7.4 — Installation... 26 7.5 Operation. 27 7.6 Diagnostic Functions. 28 7.6.1 Accessing Diagnostic Modes .. oo 28 7.6.2 Diagnostic Mode 1... 29 7.6.3 Diagnostic Mode 2. 29 30 30 31 8 Operating Procedures... 8.1 Pre-start Checks and Actions. 82 — Starting and Running 8.3 Shutting Down 34 8.3.1 Emergency Shut Down. 32 8.3.2 Resetting Unit After a Fault... 32 9 Maintenance 33 9.1 Maintenance Schedule. 34 9.2 Vacuum Pump Maintenance ... 9.3 Replacement / Cleaning of inlet Strainer (FLO1)... 9.4 — Replacement of Outlet Filter (FLO2 9.5 Replacement of Air Inlet Filter (FLO3) 9.6 Emptying Fluid Trap (FTO1) Bow. o 9.7 Replacement of Primary Oil Mist Seperator (FLO4) 9.8 Motor Maintenance... 9.9 Vacuum Pressure Adjustement (When Necessary) 9.10 Replacement of Fluid Pump Seals (if required). 9.11 Unit Disposal... 10 Troubleshooting 10.1 General... 10.2 Causes of Common Electrical Faults 411. Appendix Contents ... 42. INDEX... MANO21_EN —HNP021 Service Manual FLUID CONDITIONING PURIFIERS 2 Foreword Foreword This service manual Is provided to serve as the installation, operation and maintenance guide for the equipment supplied in accordance with the details given in the customer's purchase order. The contents should be read before attempting any phase of installation, operation and maintenance ‘The equipment and any optional items are packed individually for assembly by the customer. Unpack carefully and check all items received against the invoice. This equipment has been tested and quality controlled in accordance with ‘Pall’ standard procedures and also in accordance with the tests specified in the contract when required. However, the equipment as shipped may have been opened or disassembled for draining, cleaning, etc., after testing. The customer should satisfy himself that no nuts. bolts, flanges, pipes, closures or any other components have worked loose during shipment; these should be tightened wherever necessary. Anameplate has been permanently attached to the equipment. When requesting information, service or spare parts, please refer to the information given on this plate. Itis the user's responsibility to check actual operating conditions to ensure that the fitter elements, cartridges, vessel and sealing materials are compatible with the application and are within local safety codes. Pall reserve the right to modify the contents of this service manual without notification 2.4 Terms of Guarantee ‘The manufacturer is not liable for damage resulting from: improper use, failure to observe this manual, the employment of insufficiently qualified personnel, or unauthorised modifications to the unit and unit components supplied by Pall. hh these cases the manufacturer's warranty / guarantee is rendered void. CAUTION ~ IMPAIRMENT OF CORRECT UNIT OPERATION WHEN USING INCORRECT SPARE PARTS! ‘When using components that have not been approved, correct operation of the unit can no longer be guaranteed. Only use spare parts approved by Pall. MANO21_EN 5Foreword HNP021 Service Manual FLUID CONDITIONING PURIFIERS 2.2 Trademarks & Intellectual Property Pall, and ‘Deltadyne’ are all trade marks of Pall Corporation, Filtration. Separation, Solution. is a service mark of Pall Corporation. ‘The design of this equipment and all associated documentation is, copyright of Pall Corporation 1999, 6 MANO21_EN az”HNP021 Service Manual satety FLUID CONDITIONING PURIFIERS 3 Safety 3.1 General Safety Instructions Personnel in charge of installing, setting-up, operating, maintaining or repairing the unit and its components must have read and understood this manual and in particular the section on safety. Care must be taken in referring to this manual so as to ensure adherence with all wamings, cautions and important notes. These carry information related to the safety of personnel and the integrity and satisfactory operation of the equipment. IFnecessary, in-house instruction should be provided, taking into account the technical qualifications of the personnel concemed. The following symbols are used in this manual: WARNING: THESE ARE INSTRUCTIONS THAT DRAWATTENTION TO THE RISK OF INJURY OR DEATH! CAUTION: THESE ARE INSTRUCTIONS THAT DRAW ATTENTION TO THE RISK OF DAMAGE TO THE PRODUCT, THE PROCESS, THE EQUIPMENT OR THE SURROUNDINGS! IMPORTANT: THESE ARE INSTRUCTIONS THAT DRAW ATTENTION TO INFORMATION THAT WILL AID INSTALLATION, OPERATION OR, MAINTENANCE! THAT DRAW ATTENTION TO ANY POTENTIAL ELECTRICAL HAZARDS THAT COULD INJURE PERSONNEL, THE PROCESS OR j WARNING — ELECTRICAL HAZARD: THESE ARE INSTRUCTIONS THE EQUIPMENT! — MANO21_EN 7Safety 32 Installation Site HNP021 Service Manual FLUID CONDITIONING PURIFIERS When selecting an installation site for the equipment and relevant components, the specified escape routes must be kept clear. The unit must be positioned horizontally. This installation location must offer the system firm and level support. ‘The ambient temperature for operation should correspond to that stated on the Technical Data section. The ambient temperature for transport and storage: 10°C to 40°C / 14°F to 104°F. Ensure sufficient space for operating, maintaining and cleaning the unit. ZN CAUTION — DANGER OF DAMAGE! Do not place objects in front of or on top of the unit Observe relevant technical and building regulations. Hoses and electrical cables must be laid such that there is: + No danger of tipping, + Protection from damage. When selecting an installation site, the applicable safety regulations and manufacturer's instructions concerning substances used for or located near the machine must be observed. J\ CAUTION — INSTALLATION REGULATIONS! Itis the customers responsibility to ensure that all installations, including the disposal and treatment of materials, meet the requirements of local regulations. Pease refer to the Installation and Operation section for more information MANO21_EN =HNP021 Service Manual satety FLUID CONDITIONING PURIFIERS 3.3 Safety of Personnel Avoid any working practice which: *Endangers the health and safety of the user or third partes. «1 detrimental to the unit or others. + Impairs the safety and operation of the unit. + Does not comply with safety instructions. Servicing and maintenance should only be completed by suitably qualified persons, who are familiar with the unit and who have been informed of all potential hazards. Z\ WARNING ~ DANGER TO PERSONNEL! There is an increased risk of injury if the safety devices are put out of operation. * Never dismantle any safety device or put out of operation. * Check the safety devices regularly for correct operation. Malfunctions and defects conceming the safety devices must be reported immediately to the after-sales service of Pall. + Repairs to pipe work and tanks must be carried out only when the system is depressurised and the unit has been switched off, + Observe the applicable safety data sheets and corresponding disposal information from suppliers, as well as any relevant local safety regulations when handling chemicals. Z\ WARNING — ELECTRICAL HAZARD! Ensure that the power supply is switched off before carrying out maintenance work on the electrical system. Any safety devices removed for set up, maintenance or repair purposes must be refitted and checked immediately upon completion of maintenance and repair work. In the above case, particular attention should be peid to accident, prevention and safety regulations. — MANO21_EN 9Description of Operation 0 HNP021 Service Manual FLUID CONDITIONING PURIFIERS 4 Description of Operation 44 General ‘The HNP purifier conditions high and low viscosity hydraulic and lubrication fluids by removing water, particulate contamination and gases itis designed for e power supply given on the identification plate, which is used at full voltage for the pump motors, but transformed to 230V AC for solenoid and ball vaive control and thereafter to 24V DC for the remainder of the control circuit. WARNING: ALL SAFETY PROCEDURES ASSOCIATED WITH THE OPERATION OF EQUIPMENT AT HIGH VOLTAGE MUST BE OBSERVED! ‘The HNP series Purifier is a fluid purification system designed to remove the following: + Water— 100% of free water and as much as 90% of dissolved water, depending upon running vacuum setting, + Gases - 100% of free and entrained gases and in excess of 80% of dissolved gases, depending upon running vacuum setting + Dirt—including silt and other solids or particulate contaminants. Reference should be made to the P&iD included with the Product Claims and Specifications (PCS) drawing included in the appendices. MANO21_EN —— HNP021 Service Manual Description of Operation FLUID CONDITIONING PURIFIERS iples of Operation ‘The contaminated oil is passed through the purifier vessel via the nozzles. Fluid sprays outward from the nozzles and falls under gravity to the bottom of the vessel, air and water being removed through the top of the vessel by the airflow. Airis drawn out of the top of the vessel by the vacuum pump. fn flowing through the vessel, the contaminated oil presents a large and constantly changing surface area to the dry airflow. The dry air passes over the wet oil and moisture is transferred from the oil into the airflow. ‘The dry air is obtained by producing a vacuum inside the purifier vessel. ‘When ambient airis drawn into the side of the vessel through the vacuum adjustment valve, it expands to approximately three times its former volume (based upon factory vacuum setting of -0.7 bar g / 20.7 in Hg). The amount of water in grams in the air does not change. With the volume having been increased by 3 times, it now has a much lower percentage of water, the air has effectively been dried. The vessel vacuum also expands any dissolved gas within the oil. The gases and water vapour are then discharged to atmosphere via the vacuum pump. — MANO21_EN uTechnical Data HNP021 Service von FLUID CONDITIONING PURIFIERS 5 Technical Data 5.1 Identification Model type ‘See nameplate 5.2 General Data Dimensions Refer to the PCS drawing included in the appendices Dry mass 180 Kg (397 lbs) Fluid connections Refer to the PCS drawing included in the appendices Vacuum pump exhaust Refer to the PCS drawing included in the appendices NB: Do not restrict vacuum pump exhaust by fitting small bore pipework! 53 Design Operating Conditions Fluid To be compatible with seal material Operating pressures Inlet (-0.4 barg (11.8 “Hg) min +0.4 barg (+5.8 psig) max ‘System back pressure +4.6 barg (+66.7 psig) max Operating vacuum -0.6 barg (18 "H) min (adjustable) -0.9 barg (27 "Hig) max Vacuum pump exhaust +3 mbarg (+0.04 psig) max back pressure Fluid viscosity 12 cSt (68 SUS) min Refer to the PCS drawing included in the appendices for max* Fluid temperature +10 °C (+50 °F) min (+70 °C (+158 °F) max Ambient service 45°C (441 °F) min" temperature #40 °C (+104 °F) max Ambient humidity 85% RH max * Maximum service viscosity stated is under normal running conditions. Short term cold start conditions with higher viscosity may be accommodated using the unit, although such usage should be approved by Pall and or its agent prior to installation. * Minimum service temperature is limited by the vacuum pump lube oil viscosity. 2 MANO21_EN —HNP021 Service Manual FLUID CONDITIONING PURIFIERS 5.4 Fluid System Mean circulating rate 5.5 Vacuum System Flow rate 5.6 Electrical System and Motor & Drive System Power supply Supply voltage tolerance Supply frequency tolerance Control voltage Total motor power Technical Data 21 Imin (5.5 USgpm) @ 50 Hz 25 Iimin (6.6 USgpm) @ 60 Hz 18 m*/hr (635.7 ft'/hr) @ 50 Hz 21 m°yhr (741.6 ft'/hr) @ 60 HZ See unit nameplate 10% of nominal voltage 2% short term 1% extended 230Vac & 24V de 2.15 kW (2.82 Hp) @ 50Hz, 19 2.22 KW (2.98 Hp) @ 60Hz, 18 2.05 kW (2.75 Hp) @ 50Hz, 3 2.16 kW (2.90 Hp) @ 60Hz, 30 (For individual motor powers refer to the PCS drawing included in the Power supply fuse rating Motor circuit breaker settings Control circuit breaker setting Ingression rating to EN60529 MANO21_EN appendices) To suit full load current shown on unit nameplate To suit full load current shown on motor nameplates 2A P54Technical Data HNP021 Service von FLUID CONDITIONING PURIFIERS 5.7 Materials of Construction Frame, vessel Stainless steel Electrical control box Stainless stee! Fitings Carbon steel, zinc plated Hoses, seals Refer to the PCS drawing included in the appendices Solenoid valve Brass body with optional diaphragm as per seal material inlet strainer Stainless steel Outet filter Carbon steel, painted Fluid pump, Cast iron, painted Vacuum pump. Aluminium, painted For a full list of materials of construction contact Pall and/or their agent. 5.8 Options Available The following options are available for the Pall HNPO21 series fluid conditioning purifiers: + Panels + Electrical Cable and Plug + High Dirt Capacity Filtration + levOutlet Hoses + Non-Resettable Mechanical Hour Run Meter + Remote Functionality + Water Sensor + Larger Castors any of the above options are fitted, refer to the PCS drawing included in the appendices and Pall service manual MANO21-KITS for more information 4 MANO21_EN —HNP021 Service Manual Components Details and Safety FLUID CONDITIONING PURIFIERS ‘Systems 6 Components Details and Safety Systems ‘Throughout the description of the unit, those items which are contained within the main manifold block are shown by asterisks (*). See later text for description of main manifold block. 6.1 Fluid Inlet System The nozzles are protected from the ingression of large particulate debris by an inlet filter (225m) (FLO1"). As the filter becomes blocked or if the inlet line becomes restricted, pressure will fallin the line between the strainer and the inlet pump. The pressure can be read on the pressure ‘gauge mounted on the front of the unit. An inlet pressure of below -0.8 bar g /24"Hg will cause an amber waming lamp to illuminate. The unit will shut down to avoid cavitation, which can cause severe wear to the inlet pump. hlet pressure switch (PS02*) controls all inlet pressure alarms. The oil from inlet pump (P01) passes through check valve (CVO1), the function of which is to prevent flooding when the unit is notin use. The fluid then passes into the vacuum vessel via the nozzles. The fi switch assembly (LS01, LS02 and LS03) is provided to control the fluid running level and to switch off the unit should the fluid level in the vacuum vessel rise or fall beyond the intended limits. No pressure indication is provided on the delivery side of the inlet pump (P01), but the pump is protected from over pressure by a relief valve (RV01*). 62 Vacuum System Vessel vacuum is maintained by the vacuum pump (P03). Vessel vacuum is controlled by the vacuum adjustment valve, whichis used to set the vacuum level on the unit. The factory setting is -0.7 berg / 21"Hg, as indicated on the vacuum gauge mounted on the front of the unit, — MANO21_EN sSystems Components Details and Safety HNP021 Service Manual FLUID CONDITIONING PURIFIERS 16 6.3 Fluid Outlet System Fluid is pumped from the base of the vacuum vessel by outlet pump (P02), via outlet filter (FLO2), a 0.34 barg (4.93 psig) check valve (cvo2"), The float switch assembly high and low-level floats, LS02 and LSO1 Tespectively, control the operating level of the fluid in the vessel. By returning part of the outlet pump flow back to the vessel via the solenoid valve (AVO1) when the fluid level actuates the lower switch and using the flow advantage of the outlet pump to empty the vessel when the level reaches the higher switch. ‘The PLC controls the actuation of the recirculation solenoid valve, applying a signal to open the valve when the fluid reaches high-level control switch (LS02) and removing the signal to close the valve when the fluid reaches low-level control switch (LSO1). If the fluid level falls below low-level control switch (LS01) for longer than its alarm set point, ‘the unit will shut down, showing a low level fault. Actuation of high-level switch (LS03) will shut the unit down, showing a high level fault. When the outlet filter becomes blocked and the differential pressure reaches 2.4 bar (35 psi), the unit will give waming that the outlet fiter element will need to be changed. if the units allowed to run for more than 2 hours after the waming is actuated the unit will shut down. In most applications, ths warning phase will offer adequate time to source a replacement element from stores. ‘The outlet system is protected from the effect of a blocked outlet or accidental closing of the outlet isolating valve while running by outlet relief valve (RVO2). This valve is integral to the outlet stage of the fluid pump. The purifier outlet pressure may also be referenced on the pressure gauge mounted on the front of the unit. The purifier is protected from back flow and consequent flooding by check valve CVO2* When necessary, residual fluid may be drained from the vessel by fully closing the recirculation ball valve MVO2 during nommal running operation. This prevents any fluid retuming to the vacuum vessel and the flow advantage of the outlet pump will empty the vessel. MANO21_EN —HNP021 Service Manual Components Details and Safety FLUID CONDITIONING PURIFIERS ‘Systems 64 Air Discharge System 65 Drive System (On units were the fluid to be processed is very aerated, it could be possible for an excessive number of fluid droplets to be carried through the air line form the vacuum vessel. This purifier is fitted with a fluid trap (FT01) installed between the vacuum vessel end vacuum pump. ‘The fluid trap will catch any large amounts of oil that are carried over. ‘The float inside the housing will block the outlet port, should a large amount of fluid be allowed to fill the housing. This will result in a shut down of the unit, thus preventing the vacuum pump from spilling oil onto the floor. Any oil can be drained, by loosening the drain plug in the base of the fluid trap. The fluid trap should be checked regularly and drained when required. On passing the fluid trap, the air passes through the vacuum pump and its integral coalescing filters before discharging to atmosphere. The fluid pump and vacuum pump are directly driven by electric motors. No adjustments are necessary. 66 Base Assembly and Pipework The base assembly is manufactured entirely from stainless steel. A non- removable drip tray with a high level waming mechanism (LS04) is, included, which shuts down and isolates the unit in case of fluid spillage. Most of the pipe work is stainless or corrosion protected carbon steel, with flexible hoses connecting items bolted to the base plate to reduce noise and vibration during operation. Any fabricated pipe work is manufactured entirely from stainless steel. MANO21_EN 17Components Details and Safety HNP021 Service Manual Systems FLUID CONDITIONING PURIFIERS 6.7 Main Manifold Block ‘The main manifold block houses much of the operating equipment of the purifier. The block is mounted at the front right hand comer, as viewed from the control box end of the unit. All equipment mounted within the manifold block is readily accessible for servicing The items which are mounted within the manifold block are as follows. het strainer (FLO1) hhlet ball valve (MV01) Recirculation ball valve (MV02) Nozzle relief valve (RVO1) let depression switch (PS02) Outlet filter (FLO2) Outlet filter differential pressure switch (OP01) het pressure gauge tapping (PGO1) Outlet pressure gauge tapping (G03) Fluid temperature gauge bulb (TGO1) 8 MANO21_EN —HNP021 Service Manual Components Details and Safety FLUID CONDITIONING PURIFIERS ‘Systems 68 Electrical System Refer to the schematic wiring diagram included with this manual. Intemal short circuit and overload protection is provided by means of the following. Single-phase options: Motor protection circuit breakers with adjustable thermal trips and a miniature circuit breaker. Breakers MBO1 and MBO2 provide protection to the pump motors, whilst CBO1 protects voltage relay VRO1 and power supply PUO1 from the effects of over-current. Three-phase options: Motor protection circuit breakers with adjustable thermal tips. Breakers MB01 and MBO2 provide protection to the pump motors, whilst MBO3 protects transformer TXO1 and phase failure relay PRO1 from the effects of over-current. WARNING: AN EARTHED POWER SUPPLY MUST BE USED FOR CONNECTION TO THIS EQUIPMENT. THE SUPPLY MUST BE FITTED WITH A FUSE OR CIRCUIT BREAKER SUITABLE FOR THE LOAD OF THE UNIT, AS DEFINED IN “TECHNICAL DATA’! For both single-phase and three-phase options the incoming power supply is used at supplied voltage to drive both pump motors, via contactors (CTO1 and CTO2), which are switched by the PLC in order to control their operation. For single-phase options the voltage relay (VRO1) is employed as protection against the effects of undervoltage or loss of supply phase. For three-phase options the phase failure and undervoltage relay (PRO1) is employed as protection against the effects of undervoltage, loss of supply phase or incorrect phase rotation. ‘The undervoitage setting, as indicated by the dial on the front of VRO1 or PRO1, is 10% below the normal supply voltage. This setting must not be ‘changed and must be maintained on replacement parts. hh cases where a fault is detected by VRO1 or PRO1, the unit will shut down and will require operator intervention For single-phase options the power supply is also used at full voltage for the solenoid valve (AVO1) and lamps (LPO1-LP08). This is then converted by PU01 to 24V de and is used to supply the programmable logic controller (PCO1) and contactors (CTO1 and CTO2). For three-phase options the power supply is stepped down transformer (X01) to a single phase supply of 230Vac. This is used to supply the solenoid valve (AVO1) and lamps (LP01-LP08). This is then converted by PUO1 to 24V de and is used to supply the programmable logic controller (C01) and contactors (CTO1 and CT02). The programmable logic controller controls the functionality and safety of the unit. — MANO21_EN 0Components Details and Safety Systems 20 681 Control Box HNP021 Service Manual FLUID CONDITIONING PURIFIERS Except for the motors, solenoid valves and all sensing units, the electrical equipment is housed inside the control box. This is equipped with @ door-interlocked isolator, in order to prevent access to the equipment when itis live. ‘The following controls and indications are included on the control panel: + Control selector switch - Start/Stop (CS01) + Alarm reset pushbutton (ARO1) + Lamp test pushbutton (LT01) + Power on information lamp (LP01) © Pumps running information lamp (LP02) * Vessel vacuum low information lamp (LP03) ‘+ Fluid level lowinformation lamp (LP04) ‘+ Fluid level high information lamp (LP05) + Inlet cavitation information lamp (LPO6) * Outlet filter blocked information lamp (LPO7) * Drip tray full information lamp (LP08) * Power isolator - Red/Yellow, used as emergency stop facility and enclosure interlock (IS01) MANO21_EN —HNP021 Service Manual FLUID CONDITIONING PURIFIERS 6.8.2 Alarms and Warnings Components Details and Safety ‘Systems The equipments also provided with a number of interlocks and switches to ensure that it operates correctly and safely. The following tables list all alarm conditions for the equipment. The active mode refers to the times at which the alarm may be invoked. The action shows the result of each alam. ‘THERE IS A RUNNING PERIOD OF 3 MINUTES, DURING WHICH NON-ESSENTIAL ALARMS ARE DEACTIVATED. THIS ALLOWS THE @ VACUUM AND FLUID LEVEL TO RISE TO THE PRE-DETERMINED SET LEVELS. DURING THIS PERIOD, THE ‘FLUID LEVEL HIGH” AND ‘INLET VACUUM HIGH’ ALARMS REMAIN ACTIVE. Ras rT Tol INDICATION ts a oo PSO1 <-0.45 barg LPO3 ILLUMINATED Shutdown | Running | Prevention of (13 "Hg) ineffective running whilst unattended. PSO1 > -0.45 barg LPO3 FLASHING Warming | Shutdown |Prevention of (13 "Hg) damage to unit MBO1 = open > 30 seconds components LS01 = open > 20 LP04 ILLUMINATED Shutdown | Running |Prevention of seconds air ingression into customer system. LS01 = closed LPO4 FLASHING Shutdown | Running | Prevention of - . fluid loss Feo “closed = | through air lines. LS03 = Open > 10 LPOS ILLUMINATED Shutdown | Running |Prevention of seconds fluid loss through air lines. LPOS ILLUMINATED Shutdown | Running | Prevention of fuid loss through air seconds linse LS03 = failure to LPOS FLASHING Shutdown | Running | Prevention of close fluid loss through air lines. PS02 <-0.8 barg LPO6 ILLUMINATED Shutdown | Running | Protection of (24"Hg) inlet pump from under- pressure. DPOt = open LPOT FLASHING Waring | Running [Elimination of - . unnecessary MBO1 = closed <2 ciitdoone hours, MANO21_ENComponents Details and Safety HNP021 Service Manual FLUID CONDITIONING PURIFIERS Systems rT eee eT re aon LPO7 ILLUMINATED Shutdown | Running] Prevention of inefective running whilst unattended and prevention of element collapse. S04 = Open LPO8 ILLUMINATED Shutdown | Running | Prevention of fuid spillage. \VROt = open LPOS/LPO4/LPOS/LPOBLPOTILPO8 | Shutdown | Running | Prevention eee FLASHING TOGETHER undervottage: options only) PRO1 = open LPOS/LPOA/LPOS/LPOBLPOTILPOB | Shutdown | Running [Prevention of to FLASHING TOGETHER rere peration of ‘options only) motors or undervoltage: MBOt = Open LPOS/LPOA/LPOS/LPOGILPOT/LPO8 | Shutdown | Running | Protection FLASHING SEQUENTIALLY LEFT TO from RIGHT overcurrent. MB02 = Open LPOSLPOA/LPOS/LPOBLPO7ILPO8 | Shutdown | Running | Protection FLASHING SEQUENTIALLY RIGHT TO from LEFT overcurrent. MANO21_EN— HNP021 Service Manual Installation and Operation FLUID CONDITIONING PURIFIERS 7 Installation and Operation WARNING: IF THERE IS ANY POSSIBILITY THAT THE FLUID TO BE TREATED HAS BEEN CONTAMINATED WITH A TOXIC FLUID, THE VAPOURS OF WHICH COULD CAUSE A HAZARD, THIS PALL EQUIPMENT SHOULD NOT BE USED UNLESS ADEQUATE PRECAUTIONS ARE TAKEN TO VENT THE VAPOURS IN ACCORDANCE WITH SAFETY STANDARDS AND LOCAL CODES. ‘THIS WARNING IS NECESSARY TO PREVENT THE POSSIBILITY OF TOXIC INJURY TO PERSONNEL! WARNING: THE EQUIPMENT CANNOT BE USED WITH A FLUID WITH A FLASH POINT BELOW 93°C, OR WITH FLUIDSINATED WITH OTHER FLAMMABLE on COMBUSTIBLE FLUIDS. THs WARNINGS NECESSARY TO PREVENT THE POSSIBILITY OF FIRE OR EXPLOSION! 74 Storage if the equipment is not to be installed immediately: + Store the equipment in clean, dry and cool conditions and wherever practical in the packaging supplied. * DO NOT remove packaging until ready to install. * To prevent accidental intemal contamination, retain the port blanking plugs in position until ready to connect to the sysiem 7.2 Pre-Installation Inspection Prior to installation check that the equipment is suitable for use on the intended system. Such factors as pressures, flow rate and seal materials should be considered. Remove all protective shipping framework, covers and shipping packaging To prevent the ingress of local contaminants, it is recommended that all of the blanking plugs are left in place, until connection is made to the system pipe work. Inspect the unit upon arrival for possible damage incurred during shipment. in the event that damage has occurred, immediately enter a claim with the carrier. Ifnecessary Pall or its representative may be consulted. — MANO21_EN 2Installation and Operation HNPO21 Service von FLUID CONDITIONING PURIFIERS 7.3 Connection of the Unit to Fluid Supply 7.34 InletLine Design / Sizing ‘The unit inlet line must be sized and designed so as to avoid excessive pressure drops in the inlet line. Itis recommended that inlet pressures are not allowed to fall below 0 bar g /0 psi g. Low pressures in the inlet line can cause problems associated with the following: * Increased likelihood of leakage. It should be noted that, ‘where a suction exists in the inlet line, air will be drawn in through a leak, rather than fluid being lost. * Expansion of air out of solution, forming air bubbles. ‘These conditions will lead to a loss of treatment efficacy. Where hoses are used, they should be rated for duty; for the inlet ine, where suction is envisaged, the hose should be rated to SAE100R4. The hose should be retained and sealed to the fittings using swage ferrules or high load bolt clamps — not jubilee clips, as these often donot seal against the ingression of air. 7.3.2 Outlet Line Reservoir Return ltis counter-productive if, once the purifier has removed substantial amounts of gas from the fluid, itis allowed to cascade from a height into the fluid reservoir. This line should be terminated below the fluid level. 7.3.3. Appreciation of Reservoir Internal Form The unit should be supplied from an area of the reservoir where it has a supply of de-aerated fluid. If air bubbles are present at atmospheric Pressure, then a loss of pump efficiency will be encountered. ‘The unit should always be located on the process feed side of the reservoir. 2 MANO21_EN —— HNP021 Service Manual Installation and Operation FLUID CONDITIONING PURIFIERS 7.3.4 Location of Suction Port on Reservoir IMPORTANT: THE LOCATION OF THE SUCTION PORT AT THE BOTTOM OF THE FLUID RESERVOIR SHOULD BE AVOIDED WHENEVER POSSIBLE! Typically there may be dirt and silt deposits and free water present at the bottom of the reservoir. If this is likely, then the following protective measures should be taken: + Adrain valve should be provided at the bottom of the reservoir, allowing regular and frequent drainage of free water from the bottom of the reservoir. + Ifshort element life is encountered, then a coarse grade of element should be fitted. MAY RESULTIN THE INTRODUCTION OF PARTICULATE, CONTAMINATION INTO THE PROCESS SYSTEM IN THE EVENT OF A i CAUTION: REMOVAL OF THE PURIFIER OUTLET FILTER ELEMENT ‘COMPONENT FAILURE WITHIN THE PURIFIER! Select a point of maximum turbulence, where possible. — MANO21_EN 2sInstallation and Operation 26 735 74 HNP021 Service Manual FLUID CONDITIONING PURIFIERS Location of Unit Installation Placement of the unit above the reservoir should be avoided if possible. ‘Where it cannot, allowance for the subsequent pressure drop to the inlet should be made at the rate of 0.1 barg / 1.5 psi for every 1 metre / 3.4” through which the fluid is raised Further conditions which should be considered when locating the unit are as follows: * Vibration: High levels of vibration can cause malfunction of electrical equipment and switches. + Temperature: Ambient temperature levels should be less than 40°C / 104°F. * Contamination: h order to avoid excessive air inlet filter usage and contamination during maintenance, sites of high levels or airbome contamination should be avoided. * Accessibility: Consideration should be given to the need for access to the unit for maintenance. * Mounting Stability: The unit should be mounted on level ground, with the castors locked in the case of mobile units. * Avoid areas of high humidity - e.g., near a pipe witha steam leakage. This will severely impair the function of the unit. CAUTION: APPROPRIATE LOAD RATED LIFTING EQUIPMENT MUST BE USED AND SAFE LIFTING PROCEDURES OBSERVED DURING ALL MOVEMENTS OF THE UNIT! Units with H option seals are tested with mineral cil, those with Z option seals with industrial phosphate ester fluid and those with J option seals with Skydrol 500B. Some fluid will be present in the unit upon delivery. IFitis desirable to remove this fluid, it will be necessary to flush the unit, with system oil. Remove all blanking plugs before connecting the unit to the system pipe work. Ensure that the isolator switchis set to‘0'. Also, ensure that mains power is isolated from the power lead upon which any work is carried out. Connect an electrical supply in accordance with the specification given on the identification plate attached to the unit. CAUTION: THIS UNIT DOES NOT HAVE AN OUTLET FILTER ELEMENT FITTED WHEN SUPPLIED. ENSURE AN OUTLET ELEMENT OF SUITABLE FILTRATION RATING IS INSTALLED PRIOR TO RUNNING UNIT. MANO21_EN =— HNP021 Service Manual Installation and Operation FLUID CONDITIONING PURIFIERS 7.5 Operation In order to energize the unit, the isolator should be tumed to the 'l (On) Position. The unit now has power supplied to the main and control circuits. Three phase units only: if, when power is first applied to the purifier, the phase rotation does not correspond to the required pump direction, the Phase Failure Relay will inhibit operation and all fault lamps will fash simultaneously on the main panel. The Phase Failure Relays themselves will indicate this fault as follows: a) Forunits running on 480V AC or below, failure to illuminate the red light on the phase failure relay mounted within the control box; i.e. only @ green light will be illuminated. b) For units running on 500V AC or above, the illumination of the red light on the phase failure relay mounted within the control box; i.e. both red and green lights will be illuminated Reversing any two of the three wires on the incoming supply can rectify this problem. ‘The phase failure or voltage relay will also inhibit operation if the supply voltage is 10% or more below the nominal operating voltage with the ‘same indication as listed above To start the unit, the control selector switch should be tumed clockwise to the spring retum position. The operator may release the switch immediately. In circumstances where it is necessary to override an alarm condition to start the unit (e.g., where high fluid level shutdown has occurred), then holding the control selector switch in the ‘Start’ position will allow running whilst an alarm is active. CAUTION: ALARMS SHOULD ONLY BE OVERRIDDEN WHEN THE OPERATOR IS SURE THAT THE PROBLEM WHICH CAUSED THE ALARM HAS BEEN REMEDIED Immediately following starting of the unit, the vacuum pump is energised by contactor CTO1. The vacuum builds up, as may be observed on the vacuum gauge. Once the vacuum reaches -0.45 barg (13" Hg), contactor CTO2 is energised, hence starting the fluid pump. The "Running’ lamp should now be illuminated. If, during the initial 3 minutes, the vacuum does not reach -0.45 barg (13” Hg), the unit will shut down; the ‘Vessel Vacuum Low’ lamp being illuminated. Following the starting of the unit, there is a running period of 3 minutes, during which non-essential alarms are deactivated. This allows the vacuum and fluid level to rise to the pre-determined set levels. During this period, the ‘Fluid Level High’ and ‘inlet Vacuum High alarms remain active. With the fluid pump running, fluid is supplied to the vessel. This should result in the accumulation of @ running level of fluid in the vacuum vessel. if the fluid level does not reach the upper control float switch during the initial 3 minute period, then the unit will shut down; the ‘Fluid Level Low’ lamp being illuminated. If both vacuum and level requirements are Satisfied within the initial 3 minute period, then the unit alarms are all re-energised, allowing the unit to be left unattended whilst running. MANO21_EN 2728 HNP021 Service Manual FLUID CONDITIONING PURIFIERS ‘Two diagnostic modes are provided on the unit in order to aid fault finding and general service activity. These are detailed below. 7.6 Diagnostic Functions 7.6.4 Accessing Diagnostic Modes ain Ceres 1 Press Lamp test button and Reset button. —_] Use reset button to scroll through diagnostic modes. Mode 1: 1st amber lamp will illuminate. Mode 2: 2nd amber lamp will illuminate, a fault occurs during any of the diagnostics modes, then the unit will return to normal operation and display the fault alarm. MANO21_EN =HNP021 Service Manual FLUID CONDITIONING PURIFIERS 7.6.2 Diagnostic Mode 1 This displays the state of the switches on the unit using the 6 amber fault lamps. This is intended for use in determining a fault where the actuation ofa switch is suspected to be faulty or transient. Sea Sr COMMENTS 1 Press Lamp test button and Reset button | ist amber lamp illuminates, indicating once. that diagnostic mode 1 is activated. 2 |Release pust-buttons. Lamps are now displaying switch status (if lamp is illuminated this indicates a closed switch; if the lamp is not illuminated then the switch state is open) For normal switch states see table below. The table below illustrates the lamps used in conveying PLC input states. Re Peas eee sae LPO3 | Vessel Vacuum Switch On start up switch should be open, when vacuum “Vessel reaches -0.45 barg (13.5"Ha) the switch state Vacuum should become closed Low” LP04 | Low Fluid Level Control Switch | Normally open (closed when fluid is above the “Low Fluid switch). This should momentarily extinguish at the Level” bottom of each level control cycie. LP0S | High Fluid Level Control Switch | Normally closed (open when fluid is above the “High Fluid switch). This should momentaiily extinguish at the Level” top of each Muid level control cycle. LPO6 inlet Cavitation Switch Normally closed. When inlet pressure is less than - “Inlet 0.8 barg (24’Hg), this lamp should extinguish. Cavitation” LPO7 Outlet Filter Blocked Switch | Normally closed. When fitter differential pressure “Outlet exceeds 2.4 bar (35 psi), this lamp should Filter extinguish. Blocked" LP08 | Drip Tray Float Switch Normally Closed. When the float is lifted to the “Drip Tray extent ofits travel, the lamp should extinguish Full” 7.6.3 Diagnostic Mode 2 This displays the last ten shutdown faults using the 6 amber fault lamps. Baa Siren Cer 1 Hold Lamp test button down and press ‘2nd amber lamp illuminates. Reset button twice. 2 Release all push-buttons. Last unit shutdown is displayed. 3 Press lamp test button as required. Use lamp test button to scroll through tthe last ten unit shutdowns. — MANO21_ENOperating Procedures 30 8 Operating Procedures 8.1. Pre-start Checks and Actions HNPO21 Service Manual "i FLUID CONDITIONING PURIFIERS uaa Sie COMMENTS 4 Remove all blanking plugs. install the unit | Blanking plugs are fitted to liquid and inlet and outlet connections and ensure that | air ports. they are tightly secured. 2 [Ensure an outlet fter element of suitable __| For element part number options see rating is installed prior to running unit. spares lists on PCS drawing included with this manual (appendix), 3 | Check the vacuum pump lubricator reservoir | See separate instructions for oil type and drain or fill (via the filer cap) as and volume. Pump is filed with oil necessary. before leaving factory. 4 |Connect the electricity supply and ensure | Check ‘Power On’ lamp is illuminated. that: a) The supply fuse rating is correct b) Ioperating on 110 V, the power supply/transformer rating is adequate (KVA) c) The voltage monitor is set 10% below supply voltage 5 | Three-phase options only: Tum contro! __| Vacuum pump motor rotation should selector switch anticlockwise until vacuum —_| be as indicated on pump body. pump starts turning. Turn to ‘Stop’ once vacuum pump starts. Check rotation of vacuum pump. 6 | Three-phase options only: ff rotation ‘Ail rotations were correct when unit direction is wrong, disconnect the supply and | left factory. This procedure should reconnect the leads to the motor as only be necessary if motors have appropriate. Motor rotation should now be —_| been disconnected from control box. correct when started. 7 | Three-phase options only: Allow vacuum | Correct direction of rotation is to build until fluid pump starts. Observe indicated on the pump body. direction of rotation from fan end and immediately tum control selector to ‘Stop’. 8 | Three-phase options only: Correct the direction of rotation, if necessary as in 5. MANO21_ENHNP021 Service Manual FLUID CONDITIONING PURIFIERS 82 Starting and Runt Operating Procedures Sag Si COMMENTS 1 |Open the inlet isolating ball valve MVO1, [ 2 Open the recirculation ball valve MVO2. [3 Ensure that all system valves are opened. 4 |Tum on the electricity supply to the unit. | Check that this corresponds with the voltage shown on the nameplate. 5 | Tum the purifier isolator switch to "T (on) 6 _ |Use the lamp test button to check function of [Replace defective lamps as all lamps. necessary. 7 [Tum the selector switch to start the unit. & _ |When unit has attained correct vacuum for ‘operation, the fluid pumps will start. When the vessel fluid level is sufficient for operation, all alarm functions are operative. F the vacuum does not exceed -0.45 bar g (13° Hg) within 3 minutes of start-up then the unit will stop for remedial action. 9 [Once the unitis running, adjust the Use the appropriate lamps in the recirculation valve to actieve a filing time of | diagnostic mode to trim the approximately one minute. filing/emptying time of the vessel between LSO1 and LS02. This adjustment will depend on the viscosity of the fluid and the back pressure on the purifier outlet. 8.3 Shutting Down Buea Si com 1__|Tum the control switch to ‘Stop’ position. [2 ‘Switch the isolator to‘0' 3 |Close the inlet isolating valve. The inlet Outlet is isolated by check vaive check valve will prevent flooding of the unit for long periods, but the unit should be isolated using the inlet valve. MANO21_ENOperating Procedures HNPO21 Service von FLUID CONDITIONING PURIFIERS 8.3.1 Emergency Shut Down AN EMERGENCY STOP SHOULD BE PERFORMED BY THE SAFEST MEANS. Baa Sr Cees) 1 Tum the isolator to "0! Safety devices fitted to unit make serious emergencies unlikel 2 Funit cannot be approached, switch off electricity supply at remote position. 3 [Close inletisolating valve as soon as possible. The inlet check vaive will prevent ficoding of the unit for long periods, but the unit should be isolated using the inlet valve. 8.3.2 Resetting Unit After a Fault Bsa Coren CEs) a ‘Once the fault has been cleared, press the | Fault conditions must be corrected “Alarm Reset’ pushbutton. before attempting to restart the unit. CAUTION: ALARMS SHOULD ONLY BE RESET WHEN THE OPERATOR IS SURE THAT THE PROBLEM WHICH CAUSED THE ALARM HAS BEEN REMEDIED 32 MANO21_EN aaHNP021 Service Manual Maintenance FLUID CONDITIONING PURIFIERS 9 Maintenance WARNING: NO MAINTENANCE PROCEDURE SHOULD BE ATTEMPTED WHILE THE UNIT IS OPERATING, WITH THE EXCEPTION OF ADJUSTING THE VESSEL VACUUM REGULATING VALVE. BEFORE ANY OTHER MAINTENANCE OPERATION, ENSURE THAT THE SYSTEM IS ELECTRICALLY SAFE, ISOLATING ‘THE SUPPLY AND CLOSING THE INLET VALVE! For consistent performance and long system life, routine maintenance is essential The following work should be completed at the intervals stated in the Maintenance Schedule. MANO21_EN 33Maintenance 91 Maintenance Schedule HNPO21 Service Manual "i FLUID CONDITIONING PURIFIERS ia iene Check vacuum pump oil level. Daily. Empty fluid trap bowl. Daily. Replace vacuum pump oil Every 1000 Hours operation. Replace vacuum pump oil separator element. Every 2000 Hours operation or when Change air breather element (FLO3). blocked. Test lamps. Monthly. Primary oll mist separator element Every 3 months or when blocked Clean unit, paying particular attention to areas around —_| Every 3 Months. intakes, pipe joints, air flow paths, etc. Measure motor currents and main unit current, noting | Every 3 Months. increases against historical values. Check conditions of all hoses / seals. Every 6 Months. Check cable conduits for signs of deterioration. Every 6 Months. Every 6 Months or when blocked. Replace outlet filter element. Every 6 Months or on indication. Check linkage couplings of fluid and vacuum pumps. Clean inlet strainer. Every 6 Months, Every 3 Months, Clean diaphragm solenoid vaive intemals, inspect for wear and replace parts as required. ‘Annually or upon sluggish operation or failure to close instructions (appendix). Check accuracy of vacuum switches and all gauges. Annually. Check operation of all safety interlocks. Vacuum pump minor service. See manufacturer's Annually. Instructions (appendix). Electrical safety tests to EN60204 or local equivalent. Annually. Touch up paintwork. Replace corroded parts. Annually. Fluid pump set and motor. See manufacturer's 2 Years. instructions (appendix). ‘Vacuum pump major service. See manufacturer's 3 Years. MANO21_ENHNP021 Service Manual Maintenance FLUID CONDITIONING PURIFIERS 9.2 Vacuum Pump Maintenance All vacuum pump maintenance should be carried out in accordance with the manufacturers service instructions, included in the appendices. Vacuum Pump Lubricating Oil Type - Corena VNE non-emulsifying oil. 93. Replacement / Cleaning of Inlet Strainer (FLO1) Bea Sr com 1 ‘Switch off the unit and allow pressure to dissipate before starting work. 2 Close inlet isolating valve MVO1. 3 Unscrew inlet port fitting. This is identified | The inlet strainer is mounted within with the strainer part number and the text | the main manifold block. ‘inlet Strainer - Remove to Service’. ENTS 4 | Clean the element in accordance with the |For strainer part number options see ‘operator's own procedures or contact Pall for | spares lists on PCS drawing included details of the cleaning service offered to _| with this manual (appendix) customers. if element is to be discarded it must be in accordance with local Health and Safety Procedures. 5 | Clean threads and sealing surfaces. Check condition of o-ring seal. Replace if necessary. 6 Lubricate the threads with system fluid and re-install the filter element and bowl. — MANO21_EN 35Maintenance FLUID 94 Replacement of Outlet Filter (FL02) Sea 4 Eoin ‘Stop the unit and allow pressure to dissipate before starting work. HNPO21 Service Manual "i com Es) Close inlet isolating valves MVO1 ‘Open the filter drain plug in the bottom of the outlet filter bow! and drain the fluid. Close drain plug on completion. Unscrew the filter bow! using a suitably sized ‘spanner on the hex at the base of the bowl. Remove and discard the element in accordance with local Health and Safety Procedures. Install a new element. Clean, and inspect all threads and sealing surfaces for condition. Check the O-ring seal for damage and replace if necessary. For element part number options see spares lists on PCS drawing included with this manual (appendix). Lubricate the threads with system fluid and re-install the filter element and bowl. Re-fit bowl. Torque tighten to 40 Nm. MANO21_ENHNP021 Service Manual FLUID CONDITIONING PURIFIERS 9.5 Replacement of Air Inlet Filter (FLO3) Bea Maintenance When the vacuum becomes very high, and the adjusting valve has little effect, the breather element requires replacement. The element cannot be cleaned! Eoin ‘Stop the unit and allow vacuum to dissipate from the system. eens) Remove air inlet filter by unscrewing anti- clockwise. ‘The vacuum indicator should be retained and fitted to the new filter. Replace every six months or as indicated by operating conditions. Fit the element onto mounting. Hand-tighten only. 9.6 Em; Bea 1 ptying Fluid Trap (FT01) Bow! ACTION ‘Stop the unit and allow vacuum to dissipate from the system. Unfasten the bow! from the head by tuming anti-clockwise as viewed from underneath. COMMENTS Discard the fluid from the bowl, taking care to retain the spherical float. Ifthe unit has shutdown due to low vacuum, it may be necessary to release the float from the head by easing away using a finger. Clean, and inspect all threads and sealing surfaces for condition. Check the O-ring seal for damage and replace if necessary. Lubricate the threads with system fluid and re-fit bowl. Aiea z 97 Replacement of Primary Oil Mist Seperator (FLO4) Rare ‘Stop the unit and allow vacuum to dissipate from the system. eens) Remove the airline from the plate on top of, the vacuum vessel. Unfasten the dome nuts around the filter mounting plate. Withdraw the filter. Replace the element. Re-assemble the filter and air line. For element part number options see spares lists on PCS drawing included with this manual (appendix) Check the oil level in the fluid trap and drain ifnecessary. MANO21_ENMaintenance HNP021 Service Manual FLUID CONDITIONING PURIFIERS 9.8 Motor Maintenance Ss Cate cy 1 |Stop the unit and allow vacuum to dissipate WARNING - ELECTRICAL from the system. HAZARD: Do NOT ATTEMPT bolate the power supply. Le SeRN CE MOTORS) WITHOUT ISOLATING POWER SUPPLY. 2 |Clean the outside of the motors, ensuring that the cow! intake vents are not choked. 3 | Check the security of the electrical connections and the retaining bolts. 4 |Lubrication. Bearings are packed with Refer to manufacturer's service grease on assembly and there should be sufficient lubrication for at least two years continuous operation without attention under normal conditions. instructions. 9.9 Vacuum Pressure Adjustement (When Necessary) Saw Sry COMMENTS 1 Run the unit. 2 | Tum the vacuum trim valve MVO4 until IMPORTANT: THE VACUUM desired vacuum setting is achieved. IS FACTORY SET TO -0.7 @ — |BARG/20.7 INH. HiGHER AND LOWER SETTINGS MAY ALSO BE USED! 3 __| Check the running vacuum after adjustment. 9.10 Replacement of Fluid Pump Seals (if required) Bia Sie COMMENTS 1 Remove fluid pipe work and mounting bolts and lft out the pump P01. Drain the residual fuid. 2 [Consult the manufacturer's leaflet IMPORTANT: ENSURE THAT (appendix). ‘THE COUPLINGS ARE @ | SECURE ON THE PUMP / MOTOR SHAFTS! 3 | Refit the pump and replace the fluid pipe work, ensuring that flange seals are central MANO21_ENHNP021 Service Manual Maintenance FLUID CONDITIONING PURIFIERS 9.11 Unit Disposal Atthe end ofits operational life, the equipment should be dismantled and disposed of in accordance with all applicable local, national and intemational waste disposal laws and bylaws. Where facilities exist, component parts of the unit may be recycled. Details of the materials of construction are given in the ‘Technical Date’ section of this manual Some or all of the components parts of the equipment may be contaminated with the service fluid. The Manufacturer's Safety Data ‘Sheet (MSDS) for the fluid should be read to ensure that contaminated components parts are disposed of safely. MANO21_EN 39Troubleshooting HNP021 Service von FLUID CONDITIONING PURIFIERS 10 Troubleshooting 10.1 General CAUTION: ALARMS SHOULD ONLY BE RESET WHEN THE OPERATOR IS SURE THAT THE PROBLEM WHICH CAUSED THE ALARM HAS BEEN REMEDIED FAULT EE Ei Low hilet Pressure | inlet valve is closed. Open inlet valve. Obstruction in the customer Remove obstruction. pipeline. Unit is located above fluid supply or | Relocate unit. ata distance, which can cause significant loss of pressure at the inlet. The hose to the purifier inlet has |« Hoses on the inlet of the collapsed. purifiers must be rated for suction service (e.g. SAE 100R4). itis not necessarily apparent when a hose has collapsed, as it may be the inner and not the outer layer. The likelihood of collapse is increased if the hose material is incompatible with the system fluid. © Check and replace hoses if necessary. Fluid not within the service Raise fluid temperature. viscosity range of the purifier. Purifier inlet filter is blocked. Clean filter element and refit Faulty pressure switch (PS02)or |* Check gauge reading. Pressure gauge (PGO1). + Replace switch or gauge as required. Inlet pipe work in purifier blocked. | Remove blockage and ensure strainer if fitted. If the fault cannot be rectified by completing the above, contact Pall for advice. 40 MANO21_EN =HNP021 Service Manual FLUID CONDITIONING PURIFIERS ea Vessel Vacuum Low EXE Vacuum adjustment valve set incorrectly. Troubleshooting Ee Set vacuum to desired level using adjustment valve. Fluid is very aerated. ‘© Fully close adjustment valve. Can @ vacuum in excess of -0.7bar g / 21"Hg be attained? * Ifless aerated fluid can be drawn from another point in the circuit, relocate the purifier connections. Fluid trap bow! is full Empty fluid trap. Primary oil mist separator blocked. Clean or replace separator and refit. The fluid has @ very high water content (i. >5%). There is a large amount of water vapour visible at the vacuum pump exhaust. © Drain free water from the reservoir drain. © The vacuum will increase as the water content is reduced Oil level in the vacuum pump is outside normal limits. Fill / drain vacuum pump to restore normal oil level. Intemal vacuum pump oil separator element blocked. Replace intemal vacuum pump oil separator element. ‘Vacuum pump exhaust restriction. Remove obstruction. Air leaks in the system. Locate and repair leaks. ‘Vacuum pump gas ballast is open. Fully close gas ballast. If the fault cannot be rectified by completing the above, contact Pall for advice. MANO21_EN 4lTroubleshooting ea High Vessel Fluid Level HNP021 Service Manual FLUID CONDITIONING PURIFIERS EXE Ee Retum line to the tank restricted. | Remove obstruction. Defective outlet check valve Replace faulty check valve. Vacuum is not set within acceptable limits. Adjust vacuum to acceptable value. Unit is not standing on level ground (<10° slope). Relocate unit. Recirculation solenoid valve is faulty. Possible failure of high level control fioat switch or wiring. ‘+ Check function of low-level control switch by actuating manually and monitoring signal at local switch connections. + Replace faulty float switch ‘The fluid supply / reservoir is excessively aerated / foamy. ‘© Check continuity of wiring relays, Aux contacts, etc. ¢ Rewire or replace components as required. ‘* Possible defective actuator on recirculation valve or jammed valve. * Trymunning the vessel vacuum at-0.5 bar g/15"Hg. Ifthis cures the problem set the vacuum as high as possible and monitor at the new vacuum «Run unit from a clean barrel of il. If the problem persists, there is possibly an application problem, consider relocating the unit. Assess modes of fluid contamination. Leakage across outlet pump relief valve causing diminished outlet flow. Indicated by noise from pump relief valve segment Reset or replace intemal parts. Check the line from the vessel to the outlet pump for air leaks. Reetify leaks. The nozzle gaps are blocked or set incorrectly. «Reset and / or remove and clean * Check inlet filter FLO1 If the fault cannot be rectified by completing the above, contact Palll for advice. MANO21_ENHNP021 Service Manual Troubleshooting FLUID CONDITIONING PURIFIERS FAULT Er Emi Low Vessel Fluid Level | Interruption to fluid supply or ‘© Check fluid supply. defective inlet check valve. + Replace faulty check valve. Closed recirculation ball valve. Open vaive. Unit is not standing on level ground | Relocate unit. («10° slope). Inlet flow is interrupted bylarge | Connect purifier where toa part amounts of air. on the system where continuous flow will be achieved. «Repair air leaks within or to purifier. Recirculation solenoid valve is |» Check function of low-level failing to open. Possible failure of | control switch by actuating low level control float switch, relay | manually and monitoring signal or valve malfunction. at local switch connections. Replace faulty float switch ‘© Check continuity of wiring relays, Aux contacts, etc. ‘* Rewire or replace components as required. * Possible defective actuator on recirculation valve or jammed valve. Insufficient inlet flow. Inlet ‘Fluid is not within service pressure reading is fluctuating Viscosity range of the purifier. slightly and a “ringing” sound is Raise fuid temperature or evident from the main manifold change purifier. block, «Service nozzles, if blocked by dirt, check that inlet strainer is fitted. If the fault cannot be rectified by completing the above, contact Pall for advice. — MANO21_EN 43Troubleshooting HNP021 Service von FLUID CONDITIONING PURIFIERS ra EXE Ee Outlet Pressure High. | Defective outet check valve Replace faulty check valve. System backpressure is too high. _| Relocate purifier if outlet pressure is greater than 4 barg. Possible failure of outlet pressure | Check outlet pressure reading is gauge (P03). correct Replace gauge. Outlet filter is blocked, ‘© Check function of DPO2 and circuit. Change element. Outlet line is obstructed ‘* Check and remove obstruction. «Possible undersized outlet line. Hf the fault cannot be rectified by completing the above, contact Palll for advice. FAULT CAUSE Em Excessive Vacuum | Insufficient vacuum pump, Top up pump reservoir via filer Pump Noise lubrication. cap. Blocked coalescer element. Replace element. Pump casing fouled. Consult manufacturer's service instructions. Broken pump vane. Consult manufacturer's service instructions. Excessive back pressure on Check for obstructions on mesh in vacuum pump the exhaust of the vacuum pump. If pipe work has been fitted to the exhaust, it should be not smaller than 3/4” diameter. If the fault cannot be rectified by completing the above, contact Pall for advice. 4 MANO21_EN =HNP021 Service Manual Troubleshooting FLUID CONDITIONING PURIFIERS SOLUTION Outet Filter Element | Excessive dirt loading. + hnstall a settling tank in the requires frequent supply system and ensure replacement ‘suction outlet is above tank bottom, minimum of 150mm off the bottom of the tank. _hstall a pre-filter unit. Purifier filtration is much finer than | Consider using a coarser grade of main system fitration. elements in the purifier. Aitematively, fit fner system filtration. If the fault cannot be rectified by completing the above, contact Pall for advice. — MANO21_EN 45
You might also like
CAT 3408-3412 Manual
PDF
95% (57)
CAT 3408-3412 Manual
91 pages
Repair Manual D2862 LE Series
PDF
96% (24)
Repair Manual D2862 LE Series
574 pages
Detroit Diesel Engine Series 92 Manual
PDF
100% (48)
Detroit Diesel Engine Series 92 Manual
2,183 pages
Tanl Level and Draft - Air Purge
PDF
No ratings yet
Tanl Level and Draft - Air Purge
38 pages
Cat - 3512C Parts PDF
PDF
85% (27)
Cat - 3512C Parts PDF
467 pages
Reintjes Marine Reduction Gear Operating Manual
PDF
96% (25)
Reintjes Marine Reduction Gear Operating Manual
72 pages
Mitsubishi Selfjector (Manual-2)
PDF
80% (10)
Mitsubishi Selfjector (Manual-2)
131 pages
Project Guide - MaK M 25 C Propulsion PDF
PDF
100% (8)
Project Guide - MaK M 25 C Propulsion PDF
107 pages
Woodward Ug-8 PDF
PDF
86% (14)
Woodward Ug-8 PDF
40 pages
Westfalia Separator O&M Manual, Model: OSO 80-01-007
PDF
87% (15)
Westfalia Separator O&M Manual, Model: OSO 80-01-007
230 pages
s6r Series PDF
PDF
100% (11)
s6r Series PDF
318 pages
6,8dk-28 Instruction Manual (Operation)
PDF
100% (1)
6,8dk-28 Instruction Manual (Operation)
109 pages
CAT 3516B Parts Catalogue
PDF
100% (19)
CAT 3516B Parts Catalogue
209 pages
MAN-BW L16-24 (ЧН 16 - 24) (Инстр. по экспл.) + PDF
PDF
100% (10)
MAN-BW L16-24 (ЧН 16 - 24) (Инстр. по экспл.) + PDF
544 pages
S35MC 01
PDF
50% (2)
S35MC 01
782 pages
6N18L Operation Manual Part 1
PDF
88% (8)
6N18L Operation Manual Part 1
240 pages
Niigata
PDF
100% (8)
Niigata
225 pages
Ynmar Manual - 6EY18 (A) L
PDF
100% (8)
Ynmar Manual - 6EY18 (A) L
650 pages
Allweiler Pumps Manual
PDF
60% (5)
Allweiler Pumps Manual
428 pages
Mitsui-Man B&W Me-B Engines Instruction
PDF
100% (5)
Mitsui-Man B&W Me-B Engines Instruction
520 pages
Manual Waartsila PDF
PDF
80% (20)
Manual Waartsila PDF
374 pages
Oily Water
PDF
No ratings yet
Oily Water
8 pages
Aquamaster Service Manual - Part 1
PDF
100% (2)
Aquamaster Service Manual - Part 1
76 pages
Alpha Lubricator Manual 140809
PDF
100% (3)
Alpha Lubricator Manual 140809
270 pages
DPS992
PDF
No ratings yet
DPS992
60 pages
ZRM Zirconia Oxygen Analyzer Converter
PDF
No ratings yet
ZRM Zirconia Oxygen Analyzer Converter
58 pages
Marelligenerators - Marine
PDF
No ratings yet
Marelligenerators - Marine
81 pages
Alfa Laval Fuel Conditioning Module 1.5
PDF
No ratings yet
Alfa Laval Fuel Conditioning Module 1.5
2 pages
AF120 (-S) US, AF230 (-S) US: On-Off, Spring Return Fail-Safe, 120 or 230 VAC
PDF
No ratings yet
AF120 (-S) US, AF230 (-S) US: On-Off, Spring Return Fail-Safe, 120 or 230 VAC
11 pages
Valiadis Catalogue
PDF
No ratings yet
Valiadis Catalogue
220 pages
Yanmar Diesel Engine
PDF
87% (23)
Yanmar Diesel Engine
240 pages
Rotary Screw AIREND Manual 2003
PDF
100% (5)
Rotary Screw AIREND Manual 2003
41 pages
Boll Filter Protection System Program
PDF
No ratings yet
Boll Filter Protection System Program
38 pages
Catalog HYUNDAI HGMP (E)
PDF
No ratings yet
Catalog HYUNDAI HGMP (E)
33 pages
Catalogue Thiet Bi Dien ABB Relay Nhiet Abb
PDF
No ratings yet
Catalogue Thiet Bi Dien ABB Relay Nhiet Abb
40 pages
Manual For Trouble Shooting and Calibration of Load Cell
PDF
100% (1)
Manual For Trouble Shooting and Calibration of Load Cell
4 pages
Ma Abb VSC (En)
PDF
No ratings yet
Ma Abb VSC (En)
28 pages
Main Air Compressor PDF
PDF
No ratings yet
Main Air Compressor PDF
86 pages
Abb Ref615 Relay Ansi Broch 1mac105890-Db Enf
PDF
100% (1)
Abb Ref615 Relay Ansi Broch 1mac105890-Db Enf
4 pages
M19 Level Gauge
PDF
100% (1)
M19 Level Gauge
34 pages
723PLUS Digital DSLC/MSLC Gateway: Product Manual 02831 (Revision C)
PDF
No ratings yet
723PLUS Digital DSLC/MSLC Gateway: Product Manual 02831 (Revision C)
112 pages
RCEL
PDF
No ratings yet
RCEL
12 pages
Self-Regulating and Power Limiting Heating Cable Systems: Installation and Maintenance Manual
PDF
No ratings yet
Self-Regulating and Power Limiting Heating Cable Systems: Installation and Maintenance Manual
40 pages
Manual VN87Plus-EX V1.3
PDF
100% (1)
Manual VN87Plus-EX V1.3
62 pages
Alfa Laval - Emd00308en - Eh
PDF
No ratings yet
Alfa Laval - Emd00308en - Eh
4 pages
LS VCB Mec PDF
PDF
100% (2)
LS VCB Mec PDF
100 pages
Stober 03
PDF
No ratings yet
Stober 03
140 pages
(Ess 5 e 12) - Catalog
PDF
No ratings yet
(Ess 5 e 12) - Catalog
1 page
High-Voltage Vacuum Contactors
PDF
No ratings yet
High-Voltage Vacuum Contactors
9 pages
TOYO KEIKI English-GP-MP-HP-Transducer PDF
PDF
No ratings yet
TOYO KEIKI English-GP-MP-HP-Transducer PDF
48 pages
M-53 Bilge Pump Instruction Manual (Piston Pumps PD LD)
PDF
No ratings yet
M-53 Bilge Pump Instruction Manual (Piston Pumps PD LD)
13 pages
3.5 Dump Valve PDF
PDF
No ratings yet
3.5 Dump Valve PDF
5 pages
Samson Manual
PDF
No ratings yet
Samson Manual
144 pages
Lsa 50.2
PDF
No ratings yet
Lsa 50.2
12 pages
6.3 Main Air Compressor - Test Record
PDF
No ratings yet
6.3 Main Air Compressor - Test Record
4 pages
Instruction Manual: Nash Type Vacuum Pumps
PDF
No ratings yet
Instruction Manual: Nash Type Vacuum Pumps
16 pages
VACON NX Inverters FI4 FI8 Operating Guide DPD00908D EN PDF
PDF
No ratings yet
VACON NX Inverters FI4 FI8 Operating Guide DPD00908D EN PDF
166 pages
MSB Finished Drawing
PDF
No ratings yet
MSB Finished Drawing
356 pages
Technical Data: Connection Diagrams Series High Wye
PDF
No ratings yet
Technical Data: Connection Diagrams Series High Wye
3 pages
FRS Electrical Panel Spec EOI
PDF
No ratings yet
FRS Electrical Panel Spec EOI
20 pages
Hybrid Universal Analog Digital Voltage Regulator Operation Manual
PDF
No ratings yet
Hybrid Universal Analog Digital Voltage Regulator Operation Manual
6 pages
Power Pack 45802 SPU
PDF
100% (1)
Power Pack 45802 SPU
8 pages
Instruction Manual
PDF
No ratings yet
Instruction Manual
15 pages
Siemens SipartPS2 ManA5E00074631-08
PDF
No ratings yet
Siemens SipartPS2 ManA5E00074631-08
248 pages
Fans - Taiyo
PDF
No ratings yet
Fans - Taiyo
48 pages
Rlex Mechanical
PDF
No ratings yet
Rlex Mechanical
75 pages
Wiring Manual - 2011
PDF
100% (1)
Wiring Manual - 2011
659 pages
MD-7-0005 Emergency Diesel Generator
PDF
No ratings yet
MD-7-0005 Emergency Diesel Generator
152 pages
Main Generator
PDF
No ratings yet
Main Generator
24 pages
Ef-61 Group Starter Panel
PDF
No ratings yet
Ef-61 Group Starter Panel
288 pages
VAMP 255 / 245 / 230 Technical Data Sheet
PDF
No ratings yet
VAMP 255 / 245 / 230 Technical Data Sheet
38 pages
OPX300K2
PDF
No ratings yet
OPX300K2
28 pages
Insulation Class of Motor
PDF
No ratings yet
Insulation Class of Motor
1 page
III-8.1-3GC-three-screw-pump-catalogueSILI-PUMP (Standby Pump)
PDF
No ratings yet
III-8.1-3GC-three-screw-pump-catalogueSILI-PUMP (Standby Pump)
13 pages
1LA7083-4AA10-Z A11 Datasheet en PDF
PDF
No ratings yet
1LA7083-4AA10-Z A11 Datasheet en PDF
1 page
Fuel Oil Meter Manual
PDF
No ratings yet
Fuel Oil Meter Manual
89 pages
OC Trip, UV Trip and PF Trip Test
PDF
No ratings yet
OC Trip, UV Trip and PF Trip Test
2 pages
Installation, Operation, Maintenance, Drwgs & SP
PDF
100% (2)
Installation, Operation, Maintenance, Drwgs & SP
86 pages
Drawing PDF
PDF
No ratings yet
Drawing PDF
18 pages
Hydraulic Single-Acting Balanced Rotary Actuator 90° (Quarter-Turn) Fail-Safe
PDF
No ratings yet
Hydraulic Single-Acting Balanced Rotary Actuator 90° (Quarter-Turn) Fail-Safe
3 pages
Actuator Instruction Manual - RCEL015-250
PDF
No ratings yet
Actuator Instruction Manual - RCEL015-250
2 pages
Oil Purifier Ifpm31 - Man - GB
PDF
No ratings yet
Oil Purifier Ifpm31 - Man - GB
53 pages
PALL - Oil Purifier
PDF
No ratings yet
PALL - Oil Purifier
4 pages
Ace3 Maintenance Service Instruction
PDF
No ratings yet
Ace3 Maintenance Service Instruction
12 pages
Imo Pump Ace
PDF
50% (2)
Imo Pump Ace
4 pages
Ug8 L000386
PDF
100% (2)
Ug8 L000386
56 pages
Donghwa-Tanabe Air Compressor: Instruction Manual
PDF
83% (6)
Donghwa-Tanabe Air Compressor: Instruction Manual
95 pages
Imo ACE3 Series Screw Pump Range Instruction Manual and Parts List
PDF
No ratings yet
Imo ACE3 Series Screw Pump Range Instruction Manual and Parts List
24 pages
1982 - Woodward 3161 - Instructions Manual
PDF
100% (2)
1982 - Woodward 3161 - Instructions Manual
46 pages
Custom Search: Today Is Friday, June 23, 2017
PDF
No ratings yet
Custom Search: Today Is Friday, June 23, 2017
11 pages
Be It Enacted by The Senate and House of Representatives of The Philippines in Congress Assembled
PDF
0% (1)
Be It Enacted by The Senate and House of Representatives of The Philippines in Congress Assembled
14 pages
Business Plan Operations
PDF
0% (1)
Business Plan Operations
9 pages
G.R. No L-36402
PDF
No ratings yet
G.R. No L-36402
4 pages
G.R. No 108946
PDF
No ratings yet
G.R. No 108946
7 pages
New Text Document
PDF
No ratings yet
New Text Document
1 page
USJR ETEEAP Qualifications & Requirements
PDF
100% (3)
USJR ETEEAP Qualifications & Requirements
1 page
Lisega Spring Support Type 29
PDF
No ratings yet
Lisega Spring Support Type 29
1 page
Refining Vs NG Sam
PDF
No ratings yet
Refining Vs NG Sam
4 pages
GR 115758 Digest
PDF
No ratings yet
GR 115758 Digest
1 page
Rules of Court - Evidence (128 - 134)
PDF
No ratings yet
Rules of Court - Evidence (128 - 134)
14 pages