Description of Option H6 (Serial Communication - Cummins GCS)
Description of Option H6 (Serial Communication - Cummins GCS)
Option H6
Serial communication Cummins GSC
Multi-line 2 version 2
4189340360C
SW version 2.4X.X
Description of option
Functional description
DEIF A/S
Parameter list
Modbus communication
DEIF A/S, Frisenborgvej 33 Tel.: +45 9614 9614, Fax: +45 9614 9615
DK-7800 Skive, Denmark E-mail: [email protected], URL: www.deif.com
GPU, GPC, PPU Option H6, Serial communication Cummins GSC
Table of contents
This manual is valid for standard multi-line 2 GPU/GPC/PPU units with firmware version
2.40.0 or later.
The units are not to be opened by unauthorised personnel. If opened anyway, the
warranty will be lost.
Safety issues
Installing the unit implies work with dangerous currents and voltages. Therefore, the installation
should only be carried out by authorised personnel who understand the risks involved in working
with live electrical equipment.
Be aware of the hazardous live currents and voltages. Do not touch any AC
measurement inputs as this could lead to injury or death.
Definitions
Throughout this document a number of notes and warnings will be presented. To ensure that these
are noticed, they will be highlighted in order to separate them from the general text.
Notes
The notes provide general information which will be helpful for the reader to
bear in mind.
Warning
2. Description of option
H6 option
Option H6 is a hardware option, and therefore a separate PCB is installed in slot #8 in addition to
the standard-installed hardware.
Terminal description
Engine side modbus connections
The PCB for the ECM communication module is placed in slot #8.
Only modbus can be used to transmit the data to the PLC. Profibus cannot be
used.
Wirings
Principle diagram
Display
QSxxx Modbus
Cummins gen-set
Connection diagram
3. Functional description
This communication extracts information from the Electronic Control Module (ECM) of a
Cummins engine equipped with the ECM module. The values can be used as display values,
alarms/shutdown alarms and values to be transmitted through modbus.
Engine type
The Cummins Engine Interface Communication (EIC) supports two protocols depending on the
Generator drive Control System (GCS).
It is possible to read data from the engine types QSX15, QSX45 and QSX60. The specific
engine type can be set up via the display or via the PC utility software.
Communication system
The Cummins protocol is based on a modbus system where the controller unit is the master
unit. The Baud rate is fixed by Cummins at 9600 Baud. The Cummins GCS (Generator drive
Control System) has a fixed slave address (i.e. ID) at 01. The Baud rate and ID cannot be
changed in the controller.
Please refer to the Cummins user manuals for more information about the
Cummins protocols technical description and details.
Alarm
A number of alarms can be configured. Please refer to the Designers Reference Handbook for
information about this configuration.
If the alarm must activate a relay output, please notice that the number of
configurable relay outputs is option dependent.
Displayed values
The table shows which values can be displayed in the view menu. That is in V1, V2 and V3.
For information about the menu structure of the ML-2, please see the Designers
Reference Handbook.
The display values corresponding to the engine communication have a description beginning
with EIC.
Error messages
The following error messages can occur:
Message Description
Engine I. value N.A. The value is not available for the present engine type
Value selected error The value cannot be read due to sensor error, sub-system or
module error
N.A. The available value changes to N.A. due to communication
error
Object selection
The view lines can be configured with the available values:
Menu 4780 (EIC unit) affects the display value. This menu does not affect the
data readable by the modbus communication (option H2).
Modbus communication
If the modbus option (H2) is installed, then the data can be transmitted to a PLC or a computer.
4. Parameter list
For information about the structure of the parameter descriptions, please see
the Designers Reference Handbook.
5. Modbus communication
This chapter is to be considered as additional information for option H2. Please refer to the ECM
(Engine Communication Module) user manuals for more information about the ECM protocol
technical description and the details of each communication value.