Grundfosliterature 4359522 MAGNA3
Grundfosliterature 4359522 MAGNA3
MAGNA3
Installation and operating instructions
English (GB) Installation and operating instructions
English (GB)
2
1.2 Safety symbols on the pump 2.2.2 Plug-connected twin-head pump
English (GB)
Check the position of the clamp before you tighten
the clamp. Incorrect position of the clamp will cause
leakage from the pump and damage the hydraulic
parts in the pump head.
insulating shells
gaskets
quick guide
safety instructions
Fig. 1 Plug-connected single-head pump
box with terminal and cable glands.
The box contains the following items: 2.2.4 Terminal-connected twin-head pump
MAGNA3 pump
insulating shells
gaskets
quick guide
safety instructions
one ALPHA plug.
TM06 6791 2316
3
2.3 Lifting the pump 3. Installing the product
English (GB)
Always lift directly on the pump head or the cooling fins when
handling the pump. See fig. 5.
For large pumps, it may be necessary to use lifting equipment.
3.1 Location
Position the lifting straps as illustrated in fig. 5. The pump is designed for indoor installation.
3.2 Tools
1 0.6 x 3.5
2 1.2 x 8.0
3 TX10
4 TX20
TM05 5820 3216
5 5.0
6
Do not lift the pump head by the control box, i.e. the
red area of the pump. See fig. 6.
4
3.3 Mechanical installation 3.4 Positioning the pump
English (GB)
The pump range includes both flanged and threaded versions. Always install the pump with horizontal motor shaft.
These installation and operating instructions apply to both Pump installed correctly in a vertical pipe. See fig. 8, pos. A.
versions, but give a general description of flanged versions. If the
Pump installed correctly in a horizontal pipe. See fig. 8, pos. B.
versions differ, the threaded version will be described separately.
Do not install the pump with vertical motor shaft. See fig. 8,
Install the pump so that it is not stressed by the pipes. For
pos. C and D.
maximum permissible forces and moments for pipe connections
acting on the pump flanges or threaded connections, see page
59. A B
You can suspend the pump directly in the pipes, provided that the
pipes support the pump.
Twin-head pumps are prepared for installation on a mounting
bracket or base plate. The pump housing has a M12 thread.
To ensure adequate cooling of motor and electronics, observe the
following requirements:
Position the pump in such a way that sufficient cooling is C D
ensured.
The ambient temperature must not exceed 40 C.
3
in the pipes.
Flanged version:
Fit bolts and nuts. Use the
right size of bolts according
TM05 2865 3216 - TM05 8455 3216
to system pressure.
4 For further information about
torques, see page 59.
Threaded version:
Tighten the union nuts.
5
3.5 Control box positions 3.6 Pump head position
English (GB)
To ensure adequate cooling, make sure that the control box is in If you remove the pump head before installing the pump in the
horizontal position with the Grundfos logo in vertical position. See pipes, pay special attention when fitting the pump head to the
fig. 9. pump housing:
1. Visually check that the floating ring in the sealing system is
centred. See figures 11 and 12.
2. Gently lower the pump head with rotor shaft and impeller into
the pump housing.
3. Make sure that the contact face of the pump housing and that
of the pump head are in contact before you tighten the clamp.
See fig. 13.
6
3.7 Changing the control box position Step Action Illustration
English (GB)
The warning symbol on the clamp holding the pump
head and pump housing together indicates that there
is a risk of personal injury. See specific warnings
below.
CAUTION
Crushing of feet
Minor or moderate personal injury Single-head pump.
- Do not drop the pump head when loosening the Position the clamp so that the
clamp. 4a gap points towards the arrow.
It can be in position 3, 6, 9 or
CAUTION 12 o'clock.
Pressurised system
Minor or moderate personal injury
- Pay special attention to any escaping vapour
1
If you loosen the screw too
much, the pump head will be
completely disconnected
from the pump housing. Fit and tighten the screw that 5.0 8 Nm
holds the clamp to 8 Nm 1
Carefully turn the pump head
TM05 2868 3216
7
As an alternative to insulating shells, you can insulate the pump 3.8 Electrical installation
housing and pipes as illustrated in fig. 14.
English (GB)
WARNING
Electric shock
Death or serious personal injury
- Before starting any work on the product, make
sure that the power supply has been switched off.
Lock the main switch in position 0. Type and
requirements as specified in EN 60204-1, 5.3.2.
8
3.9 Connecting the power supply
Step Action Illustration
English (GB)
Terminal-connected versions
7 mm
20 mm
Min. 7 mm
Max. 14 mm
9
Plug-connected versions
Step Action Illustration
English (GB)
10
3.9.1 Connection diagram
English (GB)
External switch
Fuse
RCD/RCCB
External switch
Fuse
RCD/RCCB
11
4. Starting up the product
English (GB)
Do not start the pump until the system has been filled with liquid
and vented. Furthermore, the required minimum inlet pressure
must be available at the pump inlet. See section 12. Technical
data.
The pump is self-venting through the system, and the system
must be vented at the highest point.
1/On
Switch on the power supply to the pump.
1 The pump starts in "AUTOADAPT" mode after
approximately 5 seconds.
12
4.2 Twin-head pump 6. Product introduction
English (GB)
TM05 8894 2813
MAGNA3 is a complete range of circulator pumps with integrated
controller enabling adjustment of pump performance to the actual
system requirements. In many systems, this reduces the power
consumption considerably, reduces noise from thermostatic
Fig. 17 MAGNA3 D
radiator valves and similar fittings and improves the control of the
system.
You can set the desired head on the control panel.
Check that the second pump head is connected to
the power supply. 6.1 Applications
The pump is designed for circulating liquids in the following
If you have not connected the second pump head to the power systems:
supply, warning 77 appears in the display. See fig. 18.
heating systems
Connect the second pump head, and restart the pump.
domestic hot-water systems
air-conditioning and cooling systems.
You can also use the pump in the following systems:
ground-source heat-pump systems
solar-heating systems.
5. Storing and handling the product Observe local legislation regarding pump housing
material.
5.1 Frost protection
We strongly recommend that you use stainless-steel pumps in
domestic hot-water applications to avoid corrosion.
If the pump is not used during periods of frost, take In domestic hot-water systems, we recommend that you use the
the necessary steps to prevent frost bursts. pump only for water with a degree of hardness lower than
approximately 14 dH.
In domestic hot-water systems, we recommend that you keep the
liquid temperature below 65 C to eliminate the risk of lime
precipitation.
13
6.2.1 Glycol 6.3 Identification
English (GB)
You can use the pump for pumping water-ethylene-glycol 6.3.1 Nameplate
mixtures up to 50 %.
Example of a water-ethylene-glycol mixture:
Maximum viscosity: 50 cSt ~ 50 % water / 50 % ethylene-glycol
mixture at -10 C.
The pump has a power-limiting function that protects it against
overload.
17 QR code
18 CE mark and approvals
19 Manufacturer's name and address
14
6.4 Model type 6.6 Insulating shells
English (GB)
These installation and operating instructions cover all models. Insulating shells are available for single-head pumps only.
The model version is stated on the nameplate. See fig. 22.
Reduce the heat loss by insulating the pump housing and the
pipes. See figures 23 and 14.
Insulating shells for pumps in heating systems are supplied
with the pump.
Insulating shells for pumps in air-conditioning and cooling
systems, down to -10 C, must be ordered separately. See
section 11.7 Insulating kits for air-conditioning and cooling
systems.
The fitting of insulating shells increases the pump dimensions.
You can see the different model versions in the MAGNA3 data
booklet.
15
7. Control functions
English (GB)
16
7.2 External connections
English (GB)
Pos. 3
Max. Max.
24 V DC 250 V AC
24V IN
22 mA 2 A AC1
Vcc Signal
0 - 10 V DC Min.
5 V DC
20 mA
Vcc Signal
4 - 20 mA
I
Pos. 2
M M
A I S/S NC N0 C
Pos. 1
17
The connection terminals of plug-connected versions differ from 7.4 Priority of settings
those of terminal-connected versions, but they have the same
English (GB)
18
7.4.2 Digital inputs
Relay 1 Relay 2
English (GB)
See fig. 25, pos. 2.
NC NO C NC NO C You can use the digital input for external control of start-stop or
forced maximum or minimum curve.
If no external on-off switch is connected, the jumper between
terminals start-stop (S/S) and frame ( ) must be maintained. This
connection is the factory setting.
M M
A I S/S
Operation
The functions of the signal relays appear from the table below:
Activated:
1 2 3 The pump has registered a fault.
NC NO C
Not activated:
The pump has registered a fault and is Contact symbol Function
1 2 3
NC NO C
1 2 3 unable to run. M Maximum curve
NC NO C
The power supply has been switched off. A 100 % speed
Activated: M
Minimum curve
The pump has been set to stop, but is ready I
1 2 3 to run. S/S Start-stop
NC NO C
The pump is running.
Frame connection
Signal relay Operating signal
External start-stop
Not activated: You can start and stop the pump via the digital input.
1 2
1NC NO
2 C3
3
The power supply has been switched off.
NC NO C
Start-stop
Activated: S/S H Normal duty
1 2 3 The pump is running.
NC NO C Factory setting with jumper
between start-stop and .
Factory settings of relays: Q
19
Externally forced maximum or minimum curve In order to optimise the pump performance, you can use external
sensors in the following cases:
English (GB)
Q
1
M H
A
Maximum curve
24V IN
Q Vcc Signal
Minimum curve
M H 2
I
Normal duty
M H
I
Minimum curve
Q
Fig. 31 Examples of external sensors
Select the function of the digital input on the pump control panel
or with Grundfos GO.
Pos. Sensor type
7.4.3 Analog input
Combined temperature and pressure sensor,
See fig. 25, pos. 3. 1 Grundfos type RPI T2.
You can use the analog input for the connection of an external 1/2" connection and 4-20 mA signal.
sensor for measuring temperature or pressure. See fig. 31. Pressure sensor, Grundfos type RPI.
You can use sensor types with 0-10 V or 4-20 mA signal. 2
1/2" connection and 4-20 mA signal.
You can also use the analog input for an external signal for the
For further details, see section 11.4 External sensors.
control from a building management system or similar control
system. See fig. 32.
When the input is used for the heat energy monitor, install a
temperature sensor in the return pipe. BMS
If the pump is installed in the return pipe of the system, install PLC
the sensor in the flow pipe.
If the constant-temperature control mode has been enabled 24V
and the pump is installed in the flow pipe of the system, install
the sensor in the return pipe.
If the pump is installed in the return pipe of the system, you
Vcc
Vcc signal
signal
sensor
sensor
24V IN
TM05 2948 0612
Vcc signal
sensor
20
8. Setting the product
English (GB)
Select this control
System application
mode
Recommended for most heating systems, especially in systems with relatively large pressure losses in the AUTOADAPT
distribution pipes. See the description under proportional pressure.
H
In replacement situations where the proportional-pressure duty point is unknown.
The duty point has to be within the AUTOADAPT operating range. During operation, the pump automatically
adjusts to the actual system characteristic.
This setting ensures minimum energy consumption and noise level from valves, which reduces operating costs Q
and increases comfort.
The FLOWADAPT control mode is a combination of AUTOADAPT and FLOWLIMIT.
This control mode is suitable for systems where you want a maximum flow limit, FLOWLIMIT. The pump
continuously monitors and adjusts the flow, thus ensuring that the selected FLOWLIMIT is not exceeded.
Recommended for main pumps in boiler applications where a steady flow through the boiler is required. No extra
FLOWADAPT
energy is used for pumping too much liquid into the system.
H
In systems with mixing loops, you can use the control mode to control the flow in each loop.
Benefits:
Enough water for all loops at peak load conditions if you have set each loop to the right maximum flow.
The dimensioned flow for each zone, required heat energy, is determined by the flow from the pump. You can Q
set this value in the FLOWADAPT control mode without the use of throttling valves.
When the flow is set lower than the balancing valve setting, the pump ramps down instead of losing energy by
pumping against a balancing valve.
Cooling surfaces in air-conditioning systems can operate at high pressure and low flow.
Recommended in systems with relatively large pressure losses in the distribution pipes and in air-conditioning
and cooling systems.
Two-pipe heating systems with thermostatic valves and the following:
very long distribution pipes Proportional
strongly throttled balancing valves pressure
differential-pressure regulators H
large pressure losses in those parts of the system through which the total quantity of water flows, for
example boiler, heat exchanger and distribution pipe up to the first branching. Hset
Primary circuit pumps in systems with large pressure losses in the primary circuit. Hset
2
Select this control mode if the pump performance is to be controlled according to a differential temperature in the Differential
system where the pump is installed. temperature
This control mode requires an external temperature sensor in addition to the internal one. H
t
21
Select this control
English (GB)
System application
mode
If an external controller is installed, the pump is able to change from one constant curve to another, depending Constant curve
on the value of the external signal.
H
You can also set the pump to operate according to the maximum or minimum curve, like an uncontrolled pump:
Use the maximum-curve mode in periods in which a maximum flow is required. This operating mode is for
instance suitable for hot-water priority.
Use the minimum-curve mode in periods in which a minimum flow is required. This operating mode is for
Q
instance suitable for manual night setback if you do not want automatic night setback.
22
8.1 Operating the product 8.2 "Home" menu
English (GB)
CAUTION
Hot surface
Minor or moderate personal injury
- At high liquid temperatures, the pump housing may
be so hot that only the control panel should be
touched to avoid burns.
Undef-010
Navigation
"Home"
Press to go to the "Home" menu.
"Home" menu, factory setting
Shortcut to control mode settings
Shortcut to setpoint settings
"Estimated flow rate"
"Head".
Navigate in the display with or and change between the two
shortcuts with or .
TM05 3820 1612
You can define the Home display. See section "Define Home
display".
8.2.1 "Home" display icons
"Settings "
This menu gives access to all setting parameters. You can make
a detailed setting of the pump in this menu. See section
8.6 "Settings" menu.
"Assist"
This menu enables assisted pump setup, provides a short
description of the control modes and offers fault advice. See
section 8.8 "Assist" menu.
23
8.3 Menu overview
English (GB)
24
"Flow rate"
English (GB)
"Volume"
"Temperature"
"Differential temp."
"Electrical power"
"Electrical energy"
"Heat power"
"Heat energy"
"Enable/disable settings"
"Alarm and warning settings"
"Dry running (57)"
"Internal sensor fault (88)"
"Internal fault (157)"
"Delete history"
"Delete operating log"
"Delete heat energy data"
"Delete energy consumption"
"Define Home display"
"Select Home display type"
"List of data"
"Graphical illustration"
"Define Home display contents"
"List of data"
"Graphical illustration"
"Display brightness"
"Brightness"
"Return to factory settings"
"Run start-up guide"
25
8.4 Status menu 8.6 "Settings" menu
English (GB)
3.1.0.0.0.0 Settings
2.1.0.0.0.0 Status
Navigation Navigation
"Home" > Status "Home" > "Settings"
Press and go to the Status menu with . Press and go to the "Settings" menu with .
Status menu "Settings" menu
This menu offers the following status information: This menu offers the following setting options:
"Operating status" "Setpoint"
"Pump performance" "Operating mode"
"Power and energy consumption" "Control mode"
"Warning and alarm" "Controller settings", not model A
"Heat energy monitor" "FLOWLIMIT"
"Operating log" "Automatic Night Setback"
"Fitted modules" "Analog Input"
"Date and time" "Relay outputs"
"Pump identification" "Setpoint influence"
"Multi-pump system". "Bus communication"
Navigate between the submenus with or . "General settings".
Navigate between the submenus with or .
8.5 "Operating status"
8.6.1 "Setpoint"
2.1.1.0.0.0 Operating mode
3.1.1.0.0.0 Setpoint
Navigation
"Home" > Status > "Operating status" Navigation
"Operating status" "Home" > "Settings" > "Setpoint"
"Operating mode, from" "Setpoint"
"Control mode". Set the setpoint so that it matches the system.
This example shows that the pump runs in normal operation in a Setting:
multipump system. 1. Press [OK].
The status in the submenus gives information about the pump 2. Select digit with and and adjust with or .
settings and other operational parameters. 3. Press [OK] to save.
Navigate between the submenus with or . A too high setting may result in noise in the system whereas a too
low setting may result in insufficient heating or cooling in the
system.
26
8.6.2 "Operating mode" 8.6.3 "Control mode"
English (GB)
3.1.2.0.0.0 Operating mode
Min.
Q
Fig. 34 Maximum and minimum curves
27
"AUTOADAPT" "Prop. press."
English (GB)
The AUTOADAPT control mode continuously adapts the pump The head is reduced at decreasing flow demand and increased at
performance according to the actual system characteristic. rising flow demand. See fig. 37.
Manual setting of the setpoint is not possible. You can set the setpoint with an accuracy of 0.1 metre. The head
against a closed valve is the setpoint.
H
H
Hfac Hset1
A1
Hset
H 25 % Q max 90 % Q max
Setting range
Hfac
Hauto_min
TM05 3334 1212
Q
Q fac
Fig. 36 FLOWADAPT
28
"Const. temp."
English (GB)
This control mode ensures a constant temperature. Constant
temperature is a comfort control mode that you can use in
domestic hot-water systems to control the flow to maintain a fixed
temperature in the system. See fig. 39. When you use this control
mode, do not install any balancing valves in the system.
If the pump is installed in the flow pipe, install a temperature
H
H
Q
Q
Fig. 42 Constant curve
Fig. 39 Constant temperature
If you have set the pump speed in the range between minimum
"Differential temp." and maximum, the power and pressure are limited when the
This control mode ensures a constant differential-temperature pump is running on the maximum curve. This means that the
drop across heating and cooling systems. maximum performance can be achieved at a speed lower than
The differential-temperature control mode is available from model 100 %. See fig. 43.
B. The model version is stated on the nameplate. See fig. 22.
In this control mode, the pump maintains a constant differential H
Limited maximum curve
temperature between the pump and the external sensor. See
figures 40 and 41.
H
t
70
%
50
%
30
%
Mi
n.
90%
Q
Speed setting from min. to 100 %
Q
Fig. 43 Power and pressure limitations influencing the
Fig. 40 Differential temperature maximum curve
29
8.6.4 "Controller settings" Guidelines for setting of PI controller
English (GB)
A change of the gain and integral-time values affects all control For most applications, the factory setting of the controller
modes. If you change the control mode to another control mode, constants, gain and integral time, ensures optimum pump
change the gain and integral-time values to the factory settings. operation. However, in some applications an adjustment of the
Factory settings for all other control modes: controller may be required.
The gain, Kp, is equal to 1. You find the setpoint displayed in figures 44 and 45. For further
The integral time, Ti, is equal to 8. information about setup, see the "Assist" menu in section
8.8.1 "Assisted pump setup".
The table below shows the suggested controller settings:
If you use a built-in temperature sensor as one of the sensors,
you must install the pump as close as possible to the consumer.
Kp
System/application Heating Cooling Ti
system 1) system 2)
undef-079
10 + 5
0.5 - 0.5
t (L1 + L2)
L2 [m] Fig. 44 "Controller gain Kp"
3)
10 + 5
t - 0.5 (L1 + L2)
L2 [m]
L2 [m]
undef-080
1)
In heating systems, an increase in pump performance results
in a rise in temperature at the sensor. Fig. 45 "Control. integr. action time Ti"
2)
In cooling systems, an increase in pump performance results Proceed as follows:
in a drop in temperature at the sensor.
1. Increase the gain until the motor becomes unstable. Instability
3)
Built-in temperature sensor. can be seen by observing if the measured value starts to
L1: Distance in metres between pump and consumer. fluctuate. Furthermore, instability is audible as the motor
starts hunting up and down.
L2: Distance in metres between consumer and sensor. Some systems, such as temperature controls, are
slow-reacting, meaning that it may be several minutes before
the motor becomes unstable.
2. Set the gain to half the value of the value which made the
motor unstable.
3. Reduce the integral time until the motor becomes unstable.
4. Set the integral time to twice the value which made the motor
unstable.
Rules of thumb
If the controller is too slow-reacting, increase the gain.
If the controller is hunting or unstable, dampen the system by
reducing the gain or increasing the integral time.
Model A:
Use Grundfos GO to change the controller constants, gain and
integral time. You can only set positive values.
Model B and C:
Change the control settings by means of the display or Grundfos
GO. You can set both positive and negative values.
30
8.6.5 "FLOWLIMIT" 8.6.6 "Automatic Night Setback"
English (GB)
3.1.6.0.0.0 Automatic Night Setback
3.1.5.0.0.0 FLOWLIMIT
Navigation Navigation
"Home" > "Settings" > "FLOWLIMIT" "Home" > "Settings" > "Automatic Night Setback"
"FLOWLIMIT" "Automatic Night Setback"
"Enable FLOWLIMIT function" To enable the function, select "Active" with or and press
"Set FLOWLIMIT". [OK].
Setting: Once you have enabled automatic night setback, the pump
automatically changes between normal duty and night setback,
1. To enable the function, select "Active" with or and press
i.e. duty at low demand. The changeover depends on the
[OK].
flow-pipe temperature.
2. To set the FLOWLIMIT, press [OK].
The pump automatically changes over to night setback when the
3. Select digit with and and adjust with or . built-in sensor registers a flow-pipe temperature drop of more
4. Press [OK] to save. than 10 to 15 C within approximately two hours. The temperature
drop must be at least 0.1 C/min.
H 25 % Q max 90 % Q max Changeover to normal duty takes place without a time lag when
the temperature has increased by approximately 10 C.
You cannot enable automatic night setback when the pump is in
Setting range
constant-curve mode.
TM05 2445 1212
Q
Q limit
Fig. 46 FLOWLIMIT
31
8.6.7 "Analog Input" 8.6.8 "Relay outputs"
English (GB)
"Ready"
The signal relay is active when the pump is running or has
been set to stop, but is ready to run.
"Alarm"
The signal relay is activated together with the red indicator
light on the pump.
"Operation"
The signal relay is activated together with the green indicator
Navigation light on the pump.
"Home" > "Settings" > "Analog Input" > "Function of analog input"
"Not active"
"Differential-pressure control"
"Constant-temperature control"
"Differential-pressure control"
"Heat energy monitor"
"External setpoint influence"
Setting:
1. Select function mode with or .
2. Press [OK] to enable the function mode.
When you have selected the function of the input, specify the
sensor parameters by filling in the right values in unit, sensor
range, etc.
You can also set the analog input via the "Assist" menu where a
wizard guides you through each step of the configuration. See
8.8.5 "Setup, analog input".
32
8.7 Setting values for control modes
English (GB)
The setting values for FLOWADAPT and FLOWLIMIT are indicated
as percent of maximum flow, but you must enter the value in m3/h
in the "Settings" menu.
The maximum flow is a theoretical value corresponding to H is
equal to 0. The actual maximum flow is dependent on the system
characteristics.
33
8.7.1 "Setpoint influence" "Temperature influence"
English (GB)
H H
Navigation 100 %
"Home" > "Settings" > "Setpoint influence" Hactual
"Setpoint influence"
"External setpoint function" 30 %
Min.
Selection of maximum temperature
In systems with a dimensioned flow-pipe temperature:
V Up to and including 55 C, select a maximum temperature
0 2 10
equal to 50 C.
Fig. 47 "External setpoint function", 0-10 V
Above 55 C, select a maximum temperature equal to 80 C.
The range of control depends on the minimum speed, power and You cannot use the temperature influence function in
pressure limits of the pump. air-conditioning and cooling systems.
You can configure the analog input to an external setpoint
function in "Settings" or in the "Assist" menu. See section
7.4.3 Analog input.
3.1.15.10.0 External setpoint function
34
8.7.2 "Bus communication" 8.7.3 "General settings"
English (GB)
"Language"
3.1.19.1.0.0 Language
Navigation
"Home" > "Settings" > "Bus communication" Navigation
"Bus communication" "Home" > "Settings" > "General settings" > "Language"
"Pump number" "Language"
"Forced local mode" The display can be shown in any of the following languages:
"Pump number" Bulgarian
Croatian
Czech
Danish
Dutch
English
3.1.18.1.0.0 Pump number
Estonian
Finnish
French
German
Greek
Hungarian
Navigation Italian
"Home" > "Settings" > "Bus communication" > "Pump number" Japanese
"Pump number" Korean
You can allocate a unique number to the pump. This makes it Latvian
possible to distinguish between pumps in connection with bus Lithuanian
communication.
Polish
"Forced local mode" Portuguese
You can temporarily override remote commands from a building Romanian
management systems to make local settings. Once you have
Russian
disabled "Forced local mode", the pump reconnects to the
network when it receives a remote command from the building Serbian
management system. Simplified Chinese
Slovak
Slovenian
Spanish
Swedish
3.1.18.2.0.0 Forced local mode
Turkish
Ukrainian.
Measuring units are automatically changed according to the
selected language.
Setting:
1. Select language with and .
2. Press [OK] to enable the language.
Navigation
"Home" > "Settings" > "Bus communication" > "Forced local
mode"
"Forced local mode"
"Enable"
"Disable".
35
"Set date and time" In this menu you can select between SI and US units. The setting
can be made generally for all parameters or customised for each
English (GB)
individual parameter.
"Pressure"
"Differential pressure"
Navigation
"Home" > "Settings" > "General settings" > "Units"
"Units"
"SI or US units"
"Customised units".
36
"Alarm and warning settings" "Delete history"
English (GB)
"Delete operating log"
"Disable" In this menu, you can set the Home display to show up to four
user-set parameters or a graphical illustration of a performance
In case of a sensor problem related to the quality of the liquid, the
curve.
pump is able to continue operation with satisfactory performance
in most situations. In such situations, you can disable "Internal "Select Home display type"
sensor fault (88)". 1. Select "List of data" or "Graphical illustration" with or .
"Internal fault (157)" 2. Press [OK] to save.
"Enable" To specify the contents, go to "Define Home display contents".
"Disable" "Define Home display contents"
If the real-time clock is out of order, for example due to a dead 1. To set "List of data", press [OK]. A list of parameters appears
battery, a warning is shown. You can disable the warning. in the display.
"Delete history" 2. Select or deselect with [OK].
The selected parameters are shown below. The arrow indicates
that the parameter links to the "Settings" menu and works as a
shortcut for quick settings.
3.1.19.5.0.0 Delete history
Navigation
"Home" > "Settings" > "General settings" > "Delete history"
37
"Display brightness" 8.8 "Assist" menu
English (GB)
3.1.19.7.1.0 Brightness
Assist
Navigation Navigation
"Home" > "Settings" > "General settings" > "Display brightness" "Home" > "Assist"
"Brightness" Press and go to the "Assist" menu with .
1. Press [OK]. "Assist" menu
2. Set brightness with and . This menu offers the following:
3. Press [OK] to save. "Assisted pump setup"
"Return to factory settings" "Setting of date and time"
"Multi-pump setup"
3.1.19.10.1.0 Return to factory settings
"Setup, analog input"
"Description of control mode"
"Assisted fault advice".
The "Assist" menu guides the user through the setting of the
pump. In each submenu, there is a guide that guides the user
through the setting of the pump.
8.8.1 "Assisted pump setup"
This menu guides you through a complete pump setup, starting
with a presentation of the control modes and ending with the
setpoint setting.
Navigation 8.8.2 "Setting of date and time"
"Home" > "Settings" > "General settings" > "Return to factory See section "Set date and time".
settings"
"Return to factory settings"
You can recall the factory settings and overwrite the current
settings. All user settings in the "Settings" and "Assist" menus are
set back to the factory settings. This also includes language,
units, setup of analog input, multipump function, etc.
To overwrite the current settings with the factory settings, select
"Yes" with or and press [OK].
"Run start-up guide"
3.1.19.11.0.0 Run start-up guide
Navigation
"Home" > "Settings" > "General settings" > "Run start-up guide"
"Run start-up guide"
The startup guide automatically starts when you start the pump
for the first time.
You can always run the startup guide later via this menu. The
startup guide guides the user through the general settings of the
pump, such as language, date and time.
To run the startup guide, select "Yes" with or and press
[OK].
38
8.8.3 "Multi-pump setup" Check the nameplate to identify the master pump. See fig. 52.
English (GB)
Undef-083 Select multi pump function
XXXXXXXXXXXXXXXXXXXXXXXX
P/N: XXXXXXXX IP XXX TF XXX I1 [A] P1 [W] MPa
S/N: XXXXXXXX
((,;;;3DUW; 0LQ ;;; XXXX
PC: XXXX
Model: X Made in Germany 0D[ ;;; XXXX ;;
Grundfos Holding A/S, DK - 8850 Bjerringbro, Denmark
39
"Cascade operation" 8.8.5 "Setup, analog input"
English (GB)
This menu guides you through the setup of the analog inputs, for
example a temperature sensor input to a heat energy monitor.
undef-147
Fig. 56 "No multi-pump function"
tF
TM05 5367 3612
tR
Fig. 57 MAGNA3 with built-in heat energy monitor
40
"Heat energy" Example:
English (GB)
H
Max.
Q
Fig. 60 Hydraulic difference between the two pump heads
41
The table below shows the flow accuracy of the complete
MAGNA3 range. The typical accuracy is displayed along with the
English (GB)
worst-case value.
42
9. Servicing the product
English (GB)
Before dismantling
WARNING
Electric shock
Death or serious personal injury.
- Make sure that other pumps or sources do not
force flow through the pump even if the pump is
stopped. This will cause the motor to act like a
generator, resulting in voltage on the pump.
WARNING
Electric shock
Death or serious personal injury.
- Switch off the power supply for at least 3 minutes
before you start any work on the product.
- Lock the main switch in position 0. Type and
requirements as specified in EN 60204-1, 5.3.2.
43
10. Fault finding the product
English (GB)
Two opposite green indicator lights running in the The power is on.
direction of rotation of the pump. The pump is running.
Warning.
One yellow indicator light is permanently on.
The pump has stopped.
Remote-controlled.
One green indicator light in the middle is
The pump is currently being accessed by
permanently on in addition to another indication.
Grundfos GO.
44
10.2 Fault finding
English (GB)
Reset a fault indication in one of the following ways:
When you have eliminated the fault cause, the pump reverts to
normal duty.
If the fault disappears by itself, the fault indication is
automatically reset.
The fault cause is stored in the pump alarm log.
CAUTION
Pressurised system
Minor or moderate personal injury
- Before dismantling the pump, drain the system or
close the isolating valve on either side of the
pump. The pumped liquid may be scalding hot and
under high pressure
WARNING
Electric shock
Death or serious personal injury.
- Switch off the power supply for at least 3 minutes
before you start any work on the product. Lock the
main switch in position 0. Type and requirements
as specified in EN 60204-1, 5.3.2.
WARNING
Electric shock
Death or serious personal injury.
- Make sure that other pumps or sources do not
force flow through the pump even if the pump is
stopped.
45
Automatic reset
English (GB)
46
11. Accessories 11.2 Communication interface module, CIM
English (GB)
The pump can communicate via the wireless GENIair connection
or a communication module.
This enables the pump to communicate with other pumps and
with different types of network solutions.
The Grundfos communication interface modules enable the pump
to connect to standard fieldbus networks.
11.1 Grundfos GO
The pump is designed for wireless radio or infrared
communication with Grundfos GO. Grundfos GO enables setting
of functions and gives access to status overviews, technical
product information and actual operating parameters.
47
11.2.1 Description of communication interface modules
English (GB)
Fieldbus
Module Description Functions
protocol
CIM 050
CIM 100
CIM 100 has terminals for the LonWorks
connection.
CIM 100 is a Grundfos communication Two LEDs are used to indicate the actual
interface module used for status of the CIM 100 communication.
LonWorks
communication with a LonWorks One LED is used for indication of correct
TM06 7279 3416
48
Fieldbus
English (GB)
Module Description Functions
protocol
49
11.2.2 Installing a communication interface module
English (GB)
WARNING WARNING
Electric shock Electric shock
Death or serious personal injury. Death or serious personal injury.
- Make sure that other pumps or sources do not - Switch off the power supply for at least 3 minutes
force flow through the pump even if the pump is before you start any work on the product. Make
stopped. This will cause the motor to act like a sure that the power supply cannot be accidentally
generator, resulting in voltage on the pump. switched on.
- It must be possible to lock the main switch in
position 0. Type and requirements as specified in
EN 60204-1, 5.3.2.
Terminal-connected versions:
1
Remove the front cover from the control box.
50
Step Action Illustration
English (GB)
Tighten the screw holding the communication interface
5
module and secure the earth connection.
51
11.3 Counterflanges
English (GB)
Measuring
Sensor output Power supply Product
Sensor Type Supplier range Process connection
[mA] [VDC] number
[bar]
0 - 0.6 97748907
0 - 1.0 97748908
0 - 1.6 97748909
0 - 2.5 97748910
Pressure sensor RPI Grundfos 4-20 12-30 G 1/2
0 - 4.0 97748921
0 - 6.0 97748922
0-12 97748923
0-16 97748924
Length
Description Product number
[m]
Screened cable 2.0 98374260
Screened cable 5.0 98374271
52
11.6 Blanking flange 12. Technical data
English (GB)
A blanking flange is used to blank off the opening when one of the Supply voltage
pump heads of a twin-head pump is removed for service to 1 x 230 V 10 %, 50/60 Hz, PE.
enable uninterrupted operation of the other pump. See fig. 63.
Motor protection
The pump requires no external motor protection.
Enclosure class
IPX4D (EN 60529).
Insulation class
F.
Relative air humidity
Maximum 95 %.
Ambient temperature
0 to +40 C.
During transport: -40 to +70 C.
53
Minimum inlet pressure Power factor
English (GB)
The following relative minimum inlet pressure must be available The terminal-connected versions have built-in an active power
at the pump inlet during operation to avoid cavitation noise and factor correction which gives a cos from 0.98 to 0.99.
damage to the pump bearings. The plug-connected versions have built-in passive PFC, with coil
and resistors which ensures that the current drawn from the grid
The values in the table below apply to single-head is in phase with the voltage. The current is approximately
pumps and twin-head pumps in single-head sinusoidal which gives a cos from 0.55 to 0.98.
operation.
12.1 Sensor specifications
12.1.1 Temperature
Liquid temperature
54
Appendix 1
Appendix
Dimensions
Dimensions [mm]
Pump type
L1 L5 L6 B1 B2 B4 B6 B7 H1 H2 H3 H4 D1 G
MAGNA3 25-40 (N) 180 158 190 58 111 69 90 113 54 185 239 71 25 1 1/2
MAGNA3 25-60 (N) 180 158 190 58 111 69 90 113 54 185 239 71 25 1 1/2
MAGNA3 25-80 (N) 180 158 190 58 111 69 90 113 54 185 239 71 25 1 1/2
MAGNA3 25-100 (N) 180 158 190 58 111 69 90 113 54 185 239 71 25 1 1/2
MAGNA3 25-120 (N) 180 158 190 58 111 69 90 113 54 185 239 71 25 1 1/2
MAGNA3 32-40 (N) 180 158 190 58 111 69 90 113 54 185 239 71 32 2
MAGNA3 32-60 (N) 180 158 190 58 111 69 90 113 54 185 239 71 32 2
MAGNA3 32-80 (N) 180 158 190 58 111 69 90 113 54 185 239 71 32 2
MAGNA3 32-100 (N) 180 158 190 58 111 69 90 113 54 185 239 71 32 2
MAGNA3 32-120 (N) 180 158 190 58 111 69 90 113 54 185 239 71 32 2
Dimensions [mm]
Pump type
L1 L5 L6 B1 B2 B4 B6 B7 H1 H2 H3 H4 D1 D2 D3 D4 D5
MAGNA3 32-40 F (N) 220 158 220 58 111 69 100 110 65 185 250 82 32 76 90/100 140 14/19
MAGNA3 32-60 F (N) 220 158 220 58 111 69 100 110 65 185 250 82 32 76 90/100 140 14/19
MAGNA3 32-80 F (N) 220 158 220 58 111 69 100 110 65 185 250 82 32 76 90/100 140 14/19
MAGNA3 32-100 F (N) 220 158 220 58 111 69 100 110 65 185 250 82 32 76 90/100 140 14/19
MAGNA3 40-40 F (N) 220 158 220 58 111 69 105 105 65 199 264 83 40 84 100/110 150 14/19
MAGNA3 40-60 F (N) 220 158 220 58 111 69 105 105 65 199 264 83 40 84 100/110 150 14/19
55
Appendix
Dimensions [mm]
Pump type
L1 L5 B1 B2 B4 B6 B7 H1 H2 H3 H4 D1 D2 D3 D4 D5
MAGNA3 32-120 F (N) 220 204 84 164 73 106 116 65 301 366 86 32 76 90/100 140 14/19
MAGNA3 40-80 F (N) 220 204 84 164 73 106 128 65 304 369 83 40 84 100/110 150 14/19
MAGNA3 40-100 F (N) 220 204 84 164 73 106 128 65 304 369 83 40 84 100/110 150 14/19
MAGNA3 40-120 F (N) 250 204 84 164 73 106 128 65 304 369 83 40 84 100/110 150 14/19
MAGNA3 40-150 F (N) 250 204 84 164 73 106 128 65 304 369 83 40 84 100/110 150 14/19
MAGNA3 40-180 F (N) 250 204 84 164 73 106 128 65 304 369 83 40 84 100/110 150 14/19
MAGNA3 50-40 F (N) 240 204 84 164 73 127 127 71 304 374 97 50 102 110/125 165 14/19
MAGNA3 50-60 F (N) 240 204 84 164 73 127 127 71 304 374 97 50 102 110/125 165 14/19
MAGNA3 50-80 F (N) 240 204 84 164 73 127 127 71 304 374 97 50 102 110/125 165 14/19
MAGNA3 50-100 F (N) 280 204 84 164 73 127 127 72 304 376 97 50 102 110/125 165 14/19
MAGNA3 50-120 F (N) 280 204 84 164 73 127 127 72 304 376 97 50 102 110/125 165 14/19
MAGNA3 50-150 F (N) 280 204 84 164 73 127 127 72 304 376 97 50 102 110/125 165 14/19
MAGNA3 50-180 F (N) 280 204 84 164 73 127 127 72 304 376 97 50 102 110/125 165 14/19
MAGNA3 65-40 F (N) 340 204 84 164 73 133 133 74 312 386 94 65 119 130/145 185 14/19
MAGNA3 65-60 F (N) 340 204 84 164 73 133 133 74 312 386 94 65 119 130/145 185 14/19
MAGNA3 65-80 F (N) 340 204 84 164 73 133 133 74 312 386 94 65 119 130/145 185 14/19
MAGNA3 65-100 F (N) 340 204 84 164 73 133 133 74 312 386 94 65 119 130/145 185 14/19
MAGNA3 65-120 F (N) 340 204 84 164 73 133 133 74 312 386 94 65 119 130/145 185 14/19
MAGNA3 65-150 F (N) 340 204 84 164 73 133 133 74 312 386 94 65 119 130/145 185 14/19
MAGNA3 80-40 F 360 204 84 164 73 163 163 96 318 413 115 80 128 150/160 200 19
MAGNA3 80-60 F 360 204 84 164 73 163 163 96 318 413 115 80 128 150/160 200 19
MAGNA3 80-80 F 360 204 84 164 73 163 163 96 318 413 115 80 128 150/160 200 19
MAGNA3 80-100 F 360 204 84 164 73 163 163 96 318 413 115 80 128 150/160 200 19
MAGNA3 80-120 F 360 204 84 164 73 163 163 96 318 413 115 80 128 150/160 200 19
MAGNA3 100-40 F 450 204 84 164 73 178 178 103 330 433 120 100 160 170 220 19
MAGNA3 100-60 F 450 204 84 164 73 178 178 103 330 433 120 100 160 170 220 19
MAGNA3 100-80 F 450 204 84 164 73 178 178 103 330 433 120 100 160 170 220 19
MAGNA3 100-100 F 450 204 84 164 73 178 178 103 330 433 120 100 160 170 220 19
MAGNA3 100-120 F 450 204 84 164 73 178 178 103 330 433 120 100 160 170 220 19
56
Appendix
TM05 7939 2013
Fig. 4 Dimensions, twin-head pumps, threaded versions
Dimensions [mm]
Pump type
L1 L5 L7 B1 B3 B4 B5 H1 H2 H3 D1 G M3
MAGNA3 D 32-40 180 158 35 58 400 179 221 54 185 239 32 2 1/4
MAGNA3 D 32-60 180 158 35 58 400 179 221 54 185 239 32 2 1/4
MAGNA3 D 32-80 180 158 35 58 400 179 221 54 185 239 32 2 1/4
MAGNA3 D 32-100 180 158 35 58 400 179 221 54 185 239 32 2 1/4
Dimensions [mm]
Pump type
L1 L2 L3 L4 L5 L7 B1 B3 B4 B5 B6 B7 H1 H2 H3 D1 D2 D3 D4 D5 M M3
MAGNA3 D 32-40 F 220 73 120 85 158 35 58 400 179 221 130 260 69 185 254 32 76 90/100 140 14/19 M12 Rp 1/4
MAGNA3 D 32-60 F 220 73 120 85 158 35 58 400 179 221 130 260 69 185 254 32 76 90/100 140 14/19 M12 Rp 1/4
MAGNA3 D 32-80 F 220 73 120 85 158 35 58 400 179 221 130 260 69 185 254 32 76 90/100 140 14/19 M12 Rp 1/4
MAGNA3 D 32-100 F 220 73 120 85 158 35 58 400 179 221 130 260 69 185 254 32 76 90/100 140 14/19 M12 Rp 1/4
MAGNA3 D 32-120 F 220 97 90 50 204 50 84 502 210 294 130 260 68 300 368 32 76 90/100 140 14/19 M12 Rp 1/4
MAGNA3 D 40-40 F 220 53 140 60 158 15 58 452 211 241 130 260 76 199 275 40 84 100/110 150 14/19 M12 Rp1/4
MAGNA3 D 40-60 F 220 53 140 60 158 15 58 452 211 241 130 260 76 199 275 40 84 100/110 150 14/19 M12 Rp1/4
MAGNA3 D 40-80 F 220 53 140 60 204 15 84 502 210 294 130 260 76 303 379 40 84 100/110 150 14/19 M12 Rp 1/4
MAGNA3 D 40-100 F 220 53 140 60 204 15 84 502 210 294 130 260 76 303 379 40 84 100/110 150 14/19 M12 Rp 1/4
MAGNA3 D 50-40 F 240 48 160 45 204 45 84 515 221 294 130 260 75 304 379 50 102 110/125 165 14/19 M12 Rp 1/4
MAGNA3 D 50-60 F 240 48 160 45 204 45 84 515 221 294 130 260 75 304 379 50 102 110/125 165 14/19 M12 Rp 1/4
MAGNA3 D 50-80 F 240 48 160 45 204 45 84 515 221 294 130 260 75 304 379 50 102 110/125 165 14/19 M12 Rp 1/4
57
Appendix
Dimensions [mm]
Pump type
L1 L2 L3 L4 L5 B1 B3 B4 B5 B6 B7 H1 H2 H3 D1 D2 D3 D4 D5 M M3
MAGNA3 D 40-120 F 250 58 155 75 204 84 512 220 294 130 260 69 303 372 40 84 100/110 150 14/19 M12 Rp 1/4
MAGNA3 D 40-150 F 250 58 155 75 204 84 512 220 294 130 260 69 303 372 40 84 100/110 150 14/19 M12 Rp 1/4
MAGNA3 D 40-180 F 250 58 155 75 204 84 512 220 294 130 260 69 303 372 40 84 100/110 150 14/19 M12 Rp 1/4
MAGNA3 D 50-100 F 280 175 75 75 204 84 517 223 294 130 260 75 304 379 50 102 110/125 165 14/19 M12 Rp 1/4
MAGNA3 D 50-120 F 280 175 75 75 204 84 517 223 294 130 260 75 304 379 50 102 110/125 165 14/19 M12 Rp 1/4
MAGNA3 D 50-150 F 280 175 75 75 204 84 517 223 294 130 260 75 304 379 50 102 110/125 165 14/19 M12 Rp 1/4
MAGNA3 D 50-180 F 280 175 75 75 204 84 517 223 294 130 260 75 304 379 50 102 110/125 165 14/19 M12 Rp 1/4
MAGNA3 D 65-40 F 340 218 92 92 204 84 522 228 294 130 260 77 312 389 65 119 130/145 185 14/19 M12 Rp 1/4
MAGNA3 D 65-60 F 340 218 92 92 204 84 522 228 294 130 260 77 312 389 65 119 130/145 185 14/19 M12 Rp 1/4
MAGNA3 D 65-80 F 340 218 92 92 204 84 522 228 294 130 260 77 312 389 65 119 130/145 185 14/19 M12 Rp 1/4
MAGNA3 D 65-100 F 340 218 92 92 204 84 522 228 294 130 260 77 312 389 65 119 130/145 185 14/19 M12 Rp 1/4
MAGNA3 D 65-120 F 340 218 92 92 204 84 522 228 294 130 260 77 312 389 65 119 130/145 185 14/19 M12 Rp 1/4
MAGNA3 D 65-150 F 340 218 92 92 204 84 522 228 294 130 260 77 312 389 65 119 130/145 185 14/19 M12 Rp 1/4
MAGNA3 D 80-40 F 360 218 102 102 204 84 538 244 294 130 260 97 318 415 80 128 150/160 200 19 M12 Rp 1/4
MAGNA3 D 80-60 F 360 218 102 102 204 84 538 244 294 130 260 97 318 415 80 128 150/160 200 19 M12 Rp 1/4
MAGNA3 D 80-80 F 360 218 102 102 204 84 538 244 294 130 260 97 318 415 80 128 150/160 200 19 M12 Rp 1/4
MAGNA3 D 80-100 F 360 218 102 102 204 84 538 244 294 130 260 97 318 415 80 128 150/160 200 19 M12 Rp 1/4
MAGNA3 D 80-120 F 360 218 102 102 204 84 538 244 294 130 260 97 318 415 80 128 150/160 200 19 M12 Rp 1/4
MAGNA3 D 100-40 F 450 243 147 147 204 84 551 252 299 135 270 103 330 434 100 160 170 220 19 M12 Rp 1/4
MAGNA3 D 100-60 F 450 243 147 147 204 84 551 252 299 135 270 103 330 434 100 160 170 220 19 M12 Rp 1/4
MAGNA3 D 100-80 F 450 243 147 147 204 84 551 252 299 135 270 103 330 434 100 160 170 220 19 M12 Rp 1/4
MAGNA3 D 100-100 F 450 243 147 147 204 84 551 252 299 135 270 103 330 434 100 160 170 220 19 M12 Rp 1/4
MAGNA3 D 100-120 F 450 243 147 147 204 84 551 252 299 135 270 103 330 434 100 160 170 220 19 M12 Rp 1/4
58
1. Flange forces and moments
Appendix
Maximum permissible forces and moments from the pipe connections acting on the pump flanges or threaded connections are indicated
in fig. 7.
Force Moment
[N] [Nm]
Diameter DN Fy Fz Fx Fb My Mz Mx Mb
25* 350 425 375 650 300 350 450 650
32* 425 525 450 825 375 425 550 800
40 500 625 550 975 450 525 650 950
50 675 825 750 1300 500 575 700 1025
65 850 1050 925 1650 550 600 750 1100
80 1025 1250 1125 1975 575 650 800 1175
100 1350 1675 1500 2625 625 725 875 1300
59
60
Argentina Denmark Latvia Slovenia
Grundfos companies
Bombas GRUNDFOS de Argentina S.A. GRUNDFOS DK A/S SIA GRUNDFOS Pumps Latvia GRUNDFOS LJUBLJANA, d.o.o.
Ruta Panamericana km. 37.500 Centro Martin Bachs Vej 3 Deglava biznesa centrs Leskokova 9e, 1122 Ljubljana
Industrial Garin DK-8850 Bjerringbro Augusta Deglava iel 60, LV-1035, Rga, Phone: +386 (0) 1 568 06 10
1619 Garn Pcia. de B.A. Tlf.: +45-87 50 50 50 Tlr.: + 371 714 9640, 7 149 641 Telefax: +386 (0)1 568 06 19
Phone: +54-3327 414 444 Telefax: +45-87 50 51 51 Fakss: + 371 914 9646 E-mail: [email protected]
Telefax: +54-3327 45 3190 E-mail: [email protected]
www.grundfos.com/DK Lithuania South Africa
Australia GRUNDFOS Pumps UAB GRUNDFOS (PTY) LTD
GRUNDFOS Pumps Pty. Ltd. Estonia Smolensko g. 6 Corner Mountjoy and George Allen Roads
P.O. Box 2040 GRUNDFOS Pumps Eesti O LT-03201 Vilnius Wilbart Ext. 2
Regency Park Peterburi tee 92G Tel: + 370 52 395 430 Bedfordview 2008
South Australia 5942 11415 Tallinn Fax: + 370 52 395 431 Phone: (+27) 11 579 4800
Phone: +61-8-8461-4611 Tel: + 372 606 1690 Fax: (+27) 11 455 6066
Telefax: +61-8-8340 0155 Fax: + 372 606 1691 Malaysia E-mail: [email protected]
GRUNDFOS Pumps Sdn. Bhd.
Austria Finland 7 Jalan Peguam U1/25 Spain
GRUNDFOS Pumpen Vertrieb Ges.m.b.H. OY GRUNDFOS Pumput AB Glenmarie Industrial Park Bombas GRUNDFOS Espaa S.A.
Grundfosstrae 2 Trukkikuja 1 40150 Shah Alam Camino de la Fuentecilla, s/n
A-5082 Grdig/Salzburg FI-01360 Vantaa Selangor E-28110 Algete (Madrid)
Tel.: +43-6246-883-0 Phone: +358-(0) 207 889 500 Phone: +60-3-5569 2922 Tel.: +34-91-848 8800
Telefax: +43-6246-883-30 Telefax: +60-3-5569 2866 Telefax: +34-91-628 0465
France
Belgium Pompes GRUNDFOS Distribution S.A. Mexico Sweden
N.V. GRUNDFOS Bellux S.A. Parc dActivits de Chesnes Bombas GRUNDFOS de Mxico S.A. de GRUNDFOS AB
Boomsesteenweg 81-83 57, rue de Malacombe C.V. Box 333 (Lunnagrdsgatan 6)
B-2630 Aartselaar F-38290 St. Quentin Fallavier (Lyon) Boulevard TLC No. 15 431 24 Mlndal
Tl.: +32-3-870 7300 Tl.: +33-4 74 82 15 15 Parque Industrial Stiva Aeropuerto Tel.: +46 31 332 23 000
Tlcopie: +32-3-870 7301 Tlcopie: +33-4 74 94 10 51 Apodaca, N.L. 66600 Telefax: +46 31 331 94 60
Phone: +52-81-8144 4000
Belarus Germany Telefax: +52-81-8144 4010 Switzerland
GRUNDFOS GMBH GRUNDFOS Pumpen AG
Schlterstr. 33 Netherlands Bruggacherstrasse 10
220125, 40699 Erkrath GRUNDFOS Netherlands CH-8117 Fllanden/ZH
. , 11, . 56, Tel.: +49-(0) 211 929 69-0 Veluwezoom 35 Tel.: +41-44-806 8111
Telefax: +49-(0) 211 929 69-3799 1326 AE Almere Telefax: +41-44-806 8115
.: +7 (375 17) 286 39 72/73 e-mail: [email protected] Postbus 22015
: +7 (375 17) 286 39 71 Service in Deutschland: 1302 CA ALMERE Taiwan
E-mail: [email protected] e-mail: [email protected] Tel.: +31-88-478 6336 GRUNDFOS Pumps (Taiwan) Ltd.
Telefax: +31-88-478 6332 7 Floor, 219 Min-Chuan Road
Bosnia and Herzegovina Greece E-mail: [email protected] Taichung, Taiwan, R.O.C.
GRUNDFOS Sarajevo GRUNDFOS Hellas A.E.B.E. Phone: +886-4-2305 0868
Zmaja od Bosne 7-7A, 20th km. Athinon-Markopoulou Av. New Zealand Telefax: +886-4-2305 0878
BH-71000 Sarajevo P.O. Box 71 GRUNDFOS Pumps NZ Ltd.
Phone: +387 33 592 480 GR-19002 Peania 17 Beatrice Tinsley Crescent Thailand
Telefax: +387 33 590 465 Phone: +0030-210-66 83 400 North Harbour Industrial Estate GRUNDFOS (Thailand) Ltd.
www.ba.grundfos.com Telefax: +0030-210-66 46 273 Albany, Auckland 92 Chaloem Phrakiat Rama 9 Road,
e-mail: [email protected] Phone: +64-9-415 3240 Dokmai, Pravej, Bangkok 10250
Hong Kong Telefax: +64-9-415 3250 Phone: +66-2-725 8999
Brazil GRUNDFOS Pumps (Hong Kong) Ltd. Telefax: +66-2-725 8998
BOMBAS GRUNDFOS DO BRASIL Unit 1, Ground floor Norway
Av. Humberto de Alencar Castelo Branco, Siu Wai Industrial Centre GRUNDFOS Pumper A/S Turkey
630 29-33 Wing Hong Street & Strmsveien 344 GRUNDFOS POMPA San. ve Tic. Ltd. Sti.
CEP 09850 - 300 68 King Lam Street, Cheung Sha Wan Postboks 235, Leirdal Gebze Organize Sanayi Blgesi
So Bernardo do Campo - SP Kowloon N-1011 Oslo Ihsan dede Caddesi,
Phone: +55-11 4393 5533 Phone: +852-27861706 / 27861741 Tlf.: +47-22 90 47 00 2. yol 200. Sokak No. 204
Telefax: +55-11 4343 5015 Telefax: +852-27858664 Telefax: +47-22 32 21 50 41490 Gebze/ Kocaeli
Phone: +90 - 262-679 7979
Bulgaria Hungary Poland Telefax: +90 - 262-679 7905
Grundfos Bulgaria EOOD GRUNDFOS Hungria Kft. GRUNDFOS Pompy Sp. z o.o. E-mail: [email protected]
Slatina District Park u. 8 ul. Klonowa 23
Iztochna Tangenta street no. 100 H-2045 Trkblint, Baranowo k. Poznania Ukraine
BG - 1592 Sofia Phone: +36-23 511 110 PL-62-081 Przemierowo
Tel. +359 2 49 22 200 Telefax: +36-23 511 111 Tel: (+48-61) 650 13 00 , 103
Fax. +359 2 49 22 201 Fax: (+48-61) 650 13 50 . , 03131,
email: [email protected] India : (+38 044) 237 04 00
GRUNDFOS Pumps India Private Limited Portugal .: (+38 044) 237 04 01
Canada 118 Old Mahabalipuram Road Bombas GRUNDFOS Portugal, S.A. E-mail: [email protected]
GRUNDFOS Canada Inc. Thoraipakkam Rua Calvet de Magalhes, 241
2941 Brighton Road Chennai 600 096 Apartado 1079 United Arab Emirates
Oakville, Ontario Phone: +91-44 2496 6800 P-2770-153 Pao de Arcos GRUNDFOS Gulf Distribution
L6H 6C9 Tel.: +351-21-440 76 00 P.O. Box 16768
Phone: +1-905 829 9533 Indonesia Telefax: +351-21-440 76 90 Jebel Ali Free Zone
Telefax: +1-905 829 9512 PT. GRUNDFOS POMPA Dubai
Graha Intirub Lt. 2 & 3 Romania Phone: +971 4 8815 166
China Jln. Cililitan Besar No.454. Makasar, GRUNDFOS Pompe Romnia SRL Telefax: +971 4 8815 136
GRUNDFOS Pumps (Shanghai) Co. Ltd. Jakarta Timur Bd. Biruintei, nr 103
10F The Hub, No. 33 Suhong Road ID-Jakarta 13650 Pantelimon county Ilfov United Kingdom
Minhang District Phone: +62 21-469-51900 Phone: +40 21 200 4100 GRUNDFOS Pumps Ltd.
Shanghai 201106 Telefax: +62 21-460 6910 / 460 6901 Telefax: +40 21 200 4101 Grovebury Road
PRC E-mail: [email protected] Leighton Buzzard/Beds. LU7 4TL
Phone: +86 21 612 252 22 Ireland Phone: +44-1525-850000
Telefax: +86 21 612 253 33 GRUNDFOS (Ireland) Ltd. Russia Telefax: +44-1525-850011
Unit A, Merrywell Business Park
COLOMBIA Ballymount Road Lower 109544, . , . , 39-41, U.S.A.
GRUNDFOS Colombia S.A.S. Dublin 12 . 1 GRUNDFOS Pumps Corporation
Km 1.5 va Siberia-Cota Conj. Potrero Phone: +353-1-4089 800 . (+7) 495 564-88-00 (495) 737-30-00 17100 West 118th Terrace
Chico, Telefax: +353-1-4089 830 (+7) 495 564 88 11 Olathe, Kansas 66061
Parque Empresarial Arcos de Cota Bod. E-mail [email protected] Phone: +1-913-227-3400
1A. Italy Telefax: +1-913-227-3500
Cota, Cundinamarca GRUNDFOS Pompe Italia S.r.l. Serbia
Via Gran Sasso 4 Grundfos Srbija d.o.o. Uzbekistan
Phone: +57(1)-2913444
I-20060 Truccazzano (Milano) Omladinskih brigada 90b Grundfos Tashkent, Uzbekistan The
Telefax: +57(1)-8764586
Tel.: +39-02-95838112 11070 Novi Beograd Representative Office of Grundfos
Croatia Telefax: +39-02-95309290 / 95838461 Phone: +381 11 2258 740 Kazakhstan in Uzbekistan
GRUNDFOS CROATIA d.o.o. Telefax: +381 11 2281 769 38a, Oybek street, Tashkent
Buzinski prilaz 38, Buzin Japan www.rs.grundfos.com : (+998) 71 150 3290 / 71 150
HR-10010 Zagreb GRUNDFOS Pumps K.K. 3291
Phone: +385 1 6595 400 1-2-3, Shin-Miyakoda, Kita-ku, Singapore : (+998) 71 150 3292
Telefax: +385 1 6595 499 Hamamatsu GRUNDFOS (Singapore) Pte. Ltd.
www.hr.grundfos.com 431-2103 Japan 25 Jalan Tukang Addresses Revised 05.12.2016
Phone: +81 53 428 4760 Singapore 619264
GRUNDFOS Sales Czechia and Telefax: +81 53 428 5005 Phone: +65-6681 9688
Slovakia s.r.o. Telefax: +65-6681 9689
ajkovskho 21
Korea
779 00 Olomouc GRUNDFOS Pumps Korea Ltd. Slovakia
Phone: +420-585-716 111 6th Floor, Aju Building 679-5 GRUNDFOS s.r.o.
Yeoksam-dong, Kangnam-ku, 135-916 Prievozsk 4D
Seoul, Korea 821 09 BRATISLAVA
Phone: +82-2-5317 600 Phona: +421 2 5020 1426
Telefax: +82-2-5633 725 sk.grundfos.com
ECM: 1199282
98091805 1216
www.grundfos.com
The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks owned by Grundfos Holding A/S or Grundfos A/S, Denmark. All rights reserved worldwide. Copyright Grundfos Holding A/S