0% found this document useful (0 votes)
940 views62 pages

Grundfosliterature 4359522 MAGNA3

magna 3

Uploaded by

rpufita
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
940 views62 pages

Grundfosliterature 4359522 MAGNA3

magna 3

Uploaded by

rpufita
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 62

GRUNDFOS INSTRUCTIONS

MAGNA3
Installation and operating instructions
English (GB) Installation and operating instructions
English (GB)

Original installation and operating instructions 11.3 Counterflanges 52


11.4 External sensors 52
CONTENTS 11.5 Cable for sensors 52
11.6 Blanking flange 53
These installation and operating instructions describe MAGNA3.
11.7 Insulating kits for air-conditioning and cooling systems 53
Sections 1-5 give the information necessary to be able to unpack,
12. Technical data 53
install and start up the product in a safe way.
12.1 Sensor specifications 54
Sections 6-13 give important information about the product, as
well as information on service, fault finding and disposal of the 13. Disposing of the product 54
product.
Page Prior to installation, read this document and the quick
guide. Installation and operation must comply with
1. General information 2 local regulations and accepted codes of good
1.1 Symbols used in this document 2 practice.
1.2 Safety symbols on the pump 3
2. Receiving the product 3 This appliance can be used by children aged from 8
2.1 Inspecting the product 3 years and above and persons with reduced physical,
2.2 Scope of delivery 3 sensory or mental capabilities or lack of experience
2.3 Lifting the pump 4 and knowledge if they have been given supervision
3. Installing the product 4 or instruction concerning use of the appliance in a
3.1 Location 4 safe way and understand the hazards involved.
3.2 Tools 4 Children shall not play with the appliance. Cleaning
3.3 Mechanical installation 5 and user maintenance shall not be made by children
3.4 Positioning the pump 5 without supervision.
3.5 Control box positions 6
3.6 Pump head position 6 1. General information
3.7 Changing the control box position 7
3.8 Electrical installation 8 1.1 Symbols used in this document
3.9 Connecting the power supply 9
4. Starting up the product 12 DANGER
4.1 Single-head pump 12 Indicates a hazardous situation which, if not avoided,
4.2 Twin-head pump 13 will result in death or serious personal injury.
5. Storing and handling the product 13
5.1 Frost protection 13 WARNING
6. Product introduction 13 Indicates a hazardous situation which, if not avoided,
6.1 Applications 13 could result in death or serious personal injury.
6.2 Pumped liquids 13
6.3 Identification 14
6.4 Model type 15 CAUTION
6.5 Radio communication 15 Indicates a hazardous situation which, if not avoided,
6.6 Insulating shells 15 could result in minor or moderate personal injury.
6.7 Non-return valve 15
7. Control functions 16 The text accompanying the three hazard symbols DANGER,
7.1 Overview of settings 16 WARNING and CAUTION is structured in the following way:
7.2 External connections 17
7.3 Input and output communication 18 SIGNAL WORD
7.4 Priority of settings 18 Description of hazard
8. Setting the product 21 Consequence of ignoring the warning.
8.1 Operating the product 23 - Action to avoid the hazard.
8.2 "Home" menu 23
8.3 Menu overview 24
8.4 Status menu 26 A blue or grey circle with a white graphical symbol
8.5 "Operating status" 26 indicates that an action must be taken.
8.6 "Settings" menu 26
8.7 Setting values for control modes 33
8.8 "Assist" menu 38 A red or grey circle with a diagonal bar, possibly with
8.9 External setpoint influence 41 a black graphical symbol, indicates that an action
8.10 Flow estimation accuracy 41 must not be taken or must be stopped.
8.11 Pump heads in twin-head pumps 41
8.12 "Description of control mode" 42
8.13 "Assisted fault advice" 42
8.14 Wireless GENIair 42 If these instructions are not observed, it may result in
malfunction or damage to the equipment.
9. Servicing the product 43
9.1 Differential-pressure and temperature sensor 43
9.2 External sensor condition 43
10. Fault finding the product 44 Notes or instructions that make the work easier and
10.1 Grundfos Eye operating indications 44 ensure safe operation.
10.2 Fault finding 45
11. Accessories 47
11.1 Grundfos GO 47
11.2 Communication interface module, CIM 47

2
1.2 Safety symbols on the pump 2.2.2 Plug-connected twin-head pump

English (GB)
Check the position of the clamp before you tighten
the clamp. Incorrect position of the clamp will cause
leakage from the pump and damage the hydraulic
parts in the pump head.

TM06 7225 3216


Fit and tighten the screw that holds the clamp to 8
Nm 1 Nm.
8Nm!
Do not apply more torque than specified even though
water is dripping from the clamp. The condensed Fig. 2 Plug-connected twin-head pump
water is most likely coming from the drain hole under
the clamp. The box contains the following items:
MAGNA3 pump
2. Receiving the product gaskets
2.1 Inspecting the product quick guide
safety instructions
Check that the product received is in accordance with the order.
two ALPHA plugs.
Check that the voltage and frequency of the product match the
voltage and frequency of the installation site. See section 2.2.3 Terminal-connected single-head pump
6.3.1 Nameplate.

Pumps tested with water containing anticorrosive


additives are taped on the inlet and outlet ports to
prevent residual test water from leaking into the
packaging. Remove the tape before installing the
pump.

2.2 Scope of delivery


2.2.1 Plug-connected single-head pump

TM05 8159 2013


Fig. 3 Terminal-connected single-head pump

The box contains the following items:


MAGNA3 pump
TM06 7224 3216

insulating shells
gaskets
quick guide
safety instructions
Fig. 1 Plug-connected single-head pump
box with terminal and cable glands.
The box contains the following items: 2.2.4 Terminal-connected twin-head pump
MAGNA3 pump
insulating shells
gaskets
quick guide
safety instructions
one ALPHA plug.
TM06 6791 2316

Fig. 4 Terminal-connected twin-head pump

The box contains the following items:


MAGNA3 pump
gaskets
quick guide
safety instructions
two boxes with terminals and cable glands.

3
2.3 Lifting the pump 3. Installing the product
English (GB)

Observe local regulations concerning limits for


manual lifting or handling.

Always lift directly on the pump head or the cooling fins when
handling the pump. See fig. 5.
For large pumps, it may be necessary to use lifting equipment.
3.1 Location
Position the lifting straps as illustrated in fig. 5. The pump is designed for indoor installation.

3.2 Tools

1 0.6 x 3.5

2 1.2 x 8.0

3 TX10

4 TX20
TM05 5820 3216

5 5.0

Fig. 5 Correct lifting of pump

6
Do not lift the pump head by the control box, i.e. the
red area of the pump. See fig. 6.

TM05 6472 4712


8

Fig. 7 Recommended tools

Pos. Tool Size


1 Screwdriver, straight slot 0.6 x 3.5 mm
2 Screwdriver, straight slot 1.2 x 8.0 mm
3 Screwdriver, torx bit TX10
TM05 5821 3216

4 Screwdriver, torx bit TX20


5 Hexagon key 5.0 mm
6 Side cutter
Fig. 6 Incorrect lifting of pump 7 Open-end spanner Depending on DN size
Only used for pumps
8 Pipe wrench
with unions

4
3.3 Mechanical installation 3.4 Positioning the pump

English (GB)
The pump range includes both flanged and threaded versions. Always install the pump with horizontal motor shaft.
These installation and operating instructions apply to both Pump installed correctly in a vertical pipe. See fig. 8, pos. A.
versions, but give a general description of flanged versions. If the
Pump installed correctly in a horizontal pipe. See fig. 8, pos. B.
versions differ, the threaded version will be described separately.
Do not install the pump with vertical motor shaft. See fig. 8,
Install the pump so that it is not stressed by the pipes. For
pos. C and D.
maximum permissible forces and moments for pipe connections
acting on the pump flanges or threaded connections, see page
59. A B

You can suspend the pump directly in the pipes, provided that the
pipes support the pump.
Twin-head pumps are prepared for installation on a mounting
bracket or base plate. The pump housing has a M12 thread.
To ensure adequate cooling of motor and electronics, observe the
following requirements:
Position the pump in such a way that sufficient cooling is C D
ensured.
The ambient temperature must not exceed 40 C.

TM05 2866 3216


Step Action Illustration

Fig. 8 Pump installed with horizontal motor shaft

Arrows on the pump housing


TM05 2862 3216 - TM05 8456 3216

indicate the flow direction


through the pump. The flow
1
direction can be horizontal or
vertical, depending on the
control box position.

Close the isolating valves


and make sure that the
2 system is not pressurised
TM05 2863 3216

during the installation of the


pump.

Mount the pump with gaskets


TM05 2864 3216

3
in the pipes.

Flanged version:
Fit bolts and nuts. Use the
right size of bolts according
TM05 2865 3216 - TM05 8455 3216

to system pressure.
4 For further information about
torques, see page 59.

Threaded version:
Tighten the union nuts.

5
3.5 Control box positions 3.6 Pump head position
English (GB)

To ensure adequate cooling, make sure that the control box is in If you remove the pump head before installing the pump in the
horizontal position with the Grundfos logo in vertical position. See pipes, pay special attention when fitting the pump head to the
fig. 9. pump housing:
1. Visually check that the floating ring in the sealing system is
centred. See figures 11 and 12.
2. Gently lower the pump head with rotor shaft and impeller into
the pump housing.
3. Make sure that the contact face of the pump housing and that
of the pump head are in contact before you tighten the clamp.
See fig. 13.

TM05 6650 3216


TM05 2915 3216

Fig. 11 Correctly centred sealing system

Fig. 9 Pump with control box in horizontal position

Fit twin-head pumps installed in horizontal pipes


with an automatic vent, Rp 1/4, in the upper part of
the pump housing. See fig. 10.

Fig. 12 Incorrectly centred sealing system TM05 665132162


TM05 6061 3216

Observe the position of the clamp before you


tighten it. Incorrect position of the clamp will cause
leakage from the pump and damage the hydraulic
parts in the pump head. See fig. 13.

Fig. 10 Automatic vent


TM05 5837 3216

Fig. 13 Fitting the pump head to the pump housing

6
3.7 Changing the control box position Step Action Illustration

English (GB)
The warning symbol on the clamp holding the pump
head and pump housing together indicates that there
is a risk of personal injury. See specific warnings
below.

CAUTION
Crushing of feet
Minor or moderate personal injury Single-head pump.
- Do not drop the pump head when loosening the Position the clamp so that the
clamp. 4a gap points towards the arrow.
It can be in position 3, 6, 9 or
CAUTION 12 o'clock.
Pressurised system
Minor or moderate personal injury
- Pay special attention to any escaping vapour

TM05 2918 3216


when loosening the clamp.

Fit and tighten the screw that holds the clamp to 8


8Nm!
Nm 1 Nm. Do not apply more torque than specified
even though water is dripping from the clamp. The
condensed water is most likely coming from the drain
hole under the clamp.

Check the position of the clamp before you tighten


the clamp. Incorrect position of the clamp will cause Twin-head pump.
leakage from the pump and damage the hydraulic Position the clamps so that
parts in the pump head. the gaps point towards the
4b
arrows.
They can be in position 3, 6,
9 or 12 o'clock.
Step Action Illustration
Loosen the screw in the
clamp that holds the pump

TM05 2917 3216


5.0

head and pump housing


together.
TM05 2867 3216

1
If you loosen the screw too
much, the pump head will be
completely disconnected
from the pump housing. Fit and tighten the screw that 5.0 8 Nm
holds the clamp to 8 Nm 1
Carefully turn the pump head
TM05 2868 3216

TM05 2872 0612


Nm.
to the desired position. 5
Do not retighten the screw if
2 If the pump head is stuck,
condensed water is dripping
loosen it with a light blow of a
from the clamp.
rubber mallet.

Place the control box in


Fit the insulating shells.
horizontal position so that the TM05 2874 3216
The insulating shells for
TM05 2869 3216

Grundfos logo is in vertical


3 6 pumps in air-conditioning and
position. The motor shaft
cooling systems must be
must be in horizontal
ordered separately.
position.

Due to the drain hole in the


stator housing, position the
4
TM05 2870 0612

gap of the clamp as shown in


step 4a or 4b.

7
As an alternative to insulating shells, you can insulate the pump 3.8 Electrical installation
housing and pipes as illustrated in fig. 14.
English (GB)

Do not insulate the control box or cover the control


panel.

Carry out the electrical connection and protection according to


local regulations.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.

WARNING
Electric shock
Death or serious personal injury
- Before starting any work on the product, make
sure that the power supply has been switched off.
Lock the main switch in position 0. Type and
requirements as specified in EN 60204-1, 5.3.2.

TM05 2889 3216


WARNING
Electric shock
Death or serious personal injury
Fig. 14 Insulating the pump housing and pipe - Connect the pump to an external main switch
with a minimum contact gap of 3 mm in all poles.
- Use earthing or neutralisation for protection
against indirect contact.
- If the pump is connected to an electric
installation where an electrical circuit breaker
(voltage sensing ELCB, residual-current device
RCD or residual-current circuit device RCCB) is
used as an additional protection, this circuit
breaker must be marked with the first or both of
the symbols shown below:

Make sure that the pump is connected to an external main


switch.
The pump requires no external motor protection.
The motor incorporates thermal protection against slow
overloading and blocking (IEC 34-11: TP 211).
When switched on via the power supply, the pump starts after
approximately 5 seconds.
3.8.1 Supply voltage
1 x 230 V 10 %, 50/60 Hz, PE.
The voltage tolerances are intended for mains-voltage variations.
Do not use the voltage tolerances for running pumps at other
voltages than those stated on the nameplate.

8
3.9 Connecting the power supply
Step Action Illustration

English (GB)
Terminal-connected versions

Step Action Illustration

Remove the front Insert the power


cover from the supply plug into the
7

TM05 2875 3416


control box. male plug in the
1
Do not remove the

TM05 2881 3416


pump control box.
screws from the
cover.

Locate the power


supply plug and
cable gland in the
2

TM05 2876 3416


small cardboard box
supplied with the Tighten the cable
pump. 8 gland.
Fit the front cover.

TM05 2882 3416


Connect the cable
3 gland to the control
box.
TM05 2877 3416

Pull the power


4 supply cable through
the cable gland.
TM05 2878 3416

Strip the cable


5 conductors as
illustrated.
TM05 2879 3416

7 mm
20 mm

Min. 7 mm
Max. 14 mm

Connect the cable


6 conductors to the
power supply plug.
TM05 2880 3416

9
Plug-connected versions
Step Action Illustration
English (GB)

Assembling the plug

Step Action Illustration

Max. 1.5 mm2


Fit the cable gland Insert the power
and plug cover to 12 mm supply plug into
1 the cable. Strip the 7 the male plug in

TM05 5538 3216


5.5 - 10 mm
cable conductors the pump control
as illustrated. 7 mm box.
17 mm

TM05 8454 2313


Click

Disassembling the plug

Connect the cable Step Action Illustration


2 conductors to the
power supply plug.

TM05 5539 3812


Loosen the cable
1 gland and remove
it from the plug.

TM05 5545 3812


Bend the cable
with the cable
3
conductors
pointing upwards.
TM05 5540 3812

Pull off the plug


cover while
2
pressing on both

TM05 5546 3812


sides.

Pull out the


conductor guide
4
plate and throw it
Max 0.8 x 4
away.
TM05 5541 3812

Loosen the cable


conductors one by
one by pressing a
3
screwdriver gently
into the terminal
ck
Cli clip.
TM05 5547 3812

Click the plug


5 cover onto the ck x3
Cli
TM05 5542 3812

power supply plug.

The plug has now


been removed
Screw the cable 4
from the power
6 gland onto the supply plug.
TM05 5543 3812

power supply plug.


TM05 5548 3812

10
3.9.1 Connection diagram

English (GB)
External switch

Fuse

RCD/RCCB

TM03 2397 3216


Fig. 15 Example of terminal-connected motor with main switch, backup fuse and additional protection

External switch

Fuse

RCD/RCCB

TM05 5277 3712


Fig. 16 Example of plug-connected motor with main switch, backup fuse and additional protection

Make sure that the fuse is dimensioned according to


the nameplate and local legislation.

Connect all cables in accordance with local


regulations.

Make sure that all cables are heat-resistant up to 75


C.
Install all cables in accordance with EN 60204-1 and
EN 50174-2:2000.

11
4. Starting up the product
English (GB)

4.1 Single-head pump

The number of starts and stops via the power


supply must not exceed four times per hour.

Do not start the pump until the system has been filled with liquid
and vented. Furthermore, the required minimum inlet pressure
must be available at the pump inlet. See section 12. Technical
data.
The pump is self-venting through the system, and the system
must be vented at the highest point.

Step Action Illustration

1/On
Switch on the power supply to the pump.
1 The pump starts in "AUTOADAPT" mode after
approximately 5 seconds.

TM05 2884 0612


0/Off

Control panel at first startup.


2 After a few seconds, the pump display changes to the
startup guide.

TM05 2885 3216


The startup guide guides you through the general settings
of the pump, such as language, date and time.
3
If you do not touch the buttons on the control panel for 15

TM05 2886 3216


minutes, the display goes into sleep mode. When you
touch a button, the "Home" display appears.

When you have made the general settings, select the


desired control mode or let the pump run in AUTOADAPT
4
mode.
TM05 2887 3216

For additional settings, see section 7. Control functions.

12
4.2 Twin-head pump 6. Product introduction

English (GB)
TM05 8894 2813
MAGNA3 is a complete range of circulator pumps with integrated
controller enabling adjustment of pump performance to the actual
system requirements. In many systems, this reduces the power
consumption considerably, reduces noise from thermostatic
Fig. 17 MAGNA3 D
radiator valves and similar fittings and improves the control of the
system.
You can set the desired head on the control panel.
Check that the second pump head is connected to
the power supply. 6.1 Applications
The pump is designed for circulating liquids in the following
If you have not connected the second pump head to the power systems:
supply, warning 77 appears in the display. See fig. 18.
heating systems
Connect the second pump head, and restart the pump.
domestic hot-water systems
air-conditioning and cooling systems.
You can also use the pump in the following systems:
ground-source heat-pump systems
solar-heating systems.

6.2 Pumped liquids


The pump is suitable for thin, clean, non-aggressive and
non-explosive liquids, not containing solid particles or fibres that
2.1.5.1.0.0 Status

may attack the pump mechanically or chemically.


In heating systems, the water must meet the requirements of
accepted standards on water quality in heating systems, for
example the German standard VDI 2035.
The pumps are also suitable for domestic hot-water systems.
Fig. 18 Warning 77

5. Storing and handling the product Observe local legislation regarding pump housing
material.
5.1 Frost protection
We strongly recommend that you use stainless-steel pumps in
domestic hot-water applications to avoid corrosion.
If the pump is not used during periods of frost, take In domestic hot-water systems, we recommend that you use the
the necessary steps to prevent frost bursts. pump only for water with a degree of hardness lower than
approximately 14 dH.
In domestic hot-water systems, we recommend that you keep the
liquid temperature below 65 C to eliminate the risk of lime
precipitation.

Do not pump aggressive liquids.

Do not pump flammable, combustible or explosive


liquids.

13
6.2.1 Glycol 6.3 Identification
English (GB)

You can use the pump for pumping water-ethylene-glycol 6.3.1 Nameplate
mixtures up to 50 %.
Example of a water-ethylene-glycol mixture:
Maximum viscosity: 50 cSt ~ 50 % water / 50 % ethylene-glycol
mixture at -10 C.
The pump has a power-limiting function that protects it against
overload.

TM05 5981 4312


The pumping of water-ethylene-glycol mixtures affects the
maximum curve and reduces the performance, depending on the
water-ethylene-glycol mixture and the liquid temperature.
To prevent the ethylene-glycol mixture from degrading, avoid
temperatures exceeding the rated liquid temperature and
minimise the operating time at high temperatures. Fig. 20 Example of nameplate
Clean and flush the system before you add the ethylene-glycol
mixture. Pos. Description
To prevent corrosion or lime precipitation, check and maintain the
1 Product name
ethylene-glycol mixture regularly. If further dilution of the supplied
ethylene-glycol is required, follow the glycol supplier's 2 Model
instructions. 3 Production code, PC, year and week*
4 Serial number
Additives with a density and/or kinematic viscosity
higher than those/that of water reduce the hydraulic 5 Product number
performance 6 Country of manufacture
7 Enclosure class
8 Energy Efficiency Index, EEI
9 Part, according to EEI
10 Temperature class
11 Minimum current [A]
12 Maximum current [A]
13 Minimum power [W]
14 Maximum power [W]
15 Maximum system pressure
16 Voltage [V] and frequency [Hz]
TM05 8457 2313

17 QR code
18 CE mark and approvals
19 Manufacturer's name and address

* Example of production code: 1326. The pump was produced in


Fig. 19 Pumped liquids, threaded version week 26, 2013.

TM06 6692 3216

Fig. 21 Production code on packaging

14
6.4 Model type 6.6 Insulating shells

English (GB)
These installation and operating instructions cover all models. Insulating shells are available for single-head pumps only.
The model version is stated on the nameplate. See fig. 22.

Limit the heat loss from the pump housing and


pipes.

Reduce the heat loss by insulating the pump housing and the
pipes. See figures 23 and 14.
Insulating shells for pumps in heating systems are supplied
with the pump.
Insulating shells for pumps in air-conditioning and cooling
systems, down to -10 C, must be ordered separately. See
section 11.7 Insulating kits for air-conditioning and cooling
systems.
The fitting of insulating shells increases the pump dimensions.

TM05 8798 3216

TM05 2859 3216


Fig. 22 Model type on the product

You can see the different model versions in the MAGNA3 data
booklet.

6.5 Radio communication Fig. 23 Insulating shells


The radio part of this product is a class 1 device and can be used Pumps for heating systems are factory-fitted with insulating
anywhere in the EU member states without restrictions. shells. Remove the insulating shells before installing the pump.
Intended use
This pump incorporates a radio for remote control. 6.7 Non-return valve
The pump can communicate with Grundfos GO and with other If a non-return valve is fitted in the pipe system, make sure that
MAGNA3 pumps of the same type via the built-in radio. the set minimum outlet pressure of the pump is always higher
than the closing pressure of the valve. See fig. 24. This is
especially important in proportional-pressure control mode with
reduced head at low flow.

TM05 3055 0912

Fig. 24 Non-return valve

15
7. Control functions
English (GB)

7.1 Overview of settings


You can make all settings on the pump control panel or with Grundfos GO.

Menu Submenu Further information


"Setpoint" See section 8.6.1 "Setpoint".
"Operating mode" See section 8.6.2 "Operating mode".
"Normal"
"Stop"
"Min."
"Max."
"Control mode" See section 8.6.3 "Control mode".
"AUTOADAPT" See section "AUTOADAPT".
"FLOWADAPT" See section "FLOWADAPT".
"Prop. press." See section "Prop. press.".
"Const. press." See section "Const. press.".
"Const. temp." See section "Const. temp.".
"Differential temp." See section "Differential temp.".
"Constant curve" See section "Constant curve".
"Controller settings" "Controller gain Kp" See section 8.6.4 "Controller settings".
"Control. integr. action time Ti"

"FLOWLIMIT" See section 8.6.5 "FLOWLIMIT".


"Set FLOWLIMIT"
"Automatic Night Setback" See section 8.6.6 "Automatic Night Setback".
"Not active"
"Active"
"Analog Input" See section 8.6.7 "Analog Input".
"Function of analog input" See section "Function of analog input".
"Unit"
"Sensor range, min. value"
"Sensor range, max. value"
"Electrical signal"
"Relay outputs" See section 8.6.8 "Relay outputs".
"Relay output 1"
"Relay output 2"
"Setpoint influence" See section 8.7 Setting values for control modes.
"External setpoint function" See section "External setpoint function".
"Temperature influence" See section "Temperature influence".
"Bus communication" See section 8.7.2 "Bus communication".
"Pump number" See section "Pump number".
"Forced local mode" See section "Forced local mode"
"Enable"
"Disable"
"General settings" See section 8.7.3 "General settings".
"Language" See section "Language".
"Multi-pump system" "Set date and time" See section "Set date and time".
"Units" See section "Units".
"Enable/disable settings" See section "Enable/disable settings".
"Alarm and warning settings" See section "Alarm and warning settings"
"Delete history" See section "Delete history".
"Define Home display" See section "Define Home display".
"Display brightness" See section "Display brightness".
"Return to factory settings" See section "Return to factory settings".
"Run start-up guide" See section "Run start-up guide".

16
7.2 External connections

English (GB)
Pos. 3
Max. Max.
24 V DC 250 V AC
24V IN
22 mA 2 A AC1
Vcc Signal

0 - 10 V DC Min.
5 V DC
20 mA
Vcc Signal

4 - 20 mA
I

Pos. 2
M M
A I S/S NC N0 C

Pos. 1

TM05 6060 2313 - TM05 3343 2313


L N

Fig. 25 Wiring diagram, terminal-connected versions

TM05 8539 2413

Fig. 26 Wiring diagram, plug-connected versions

17
The connection terminals of plug-connected versions differ from 7.4 Priority of settings
those of terminal-connected versions, but they have the same
English (GB)

The external forced-control signals influence the settings


function and connection options.
available on the pump control panel or with Grundfos GO.
Concerning demands on signal wires and signal transmitters, see However, you can always set the pump to maximum-curve duty or
section 12. Technical data. stop the pump on the control panel or with Grundfos GO.
Use screened cables for external on-off switch, digital input, If two or more functions are enabled at the same time, the pump
sensor and setpoint signals. operates according to the setting with the highest priority.
Connect screened cables to the earth connection as follows: The priority of the settings is as shown in the table below.
Terminal-connected versions: Example: If the pump has been forced to stop via an external
Connect the cable screen to earth via the digital-input signal, the control panel or Grundfos GO can only set the pump to
terminal. See fig. 25. maximum curve.
Plug-connected versions:
Connect the cable screen to earth via cable clamp. See fig. Possible settings
26.
Priority Control panel
External
WARNING or Grundfos Bus signal
signals
Electric shock GO
Minor or moderate personal injury 1 "Stop"
- Separate wires connected to supply terminals,
2 "Max. curve"
outputs NC, NO, C and start-stop input from each
other and from the supply by reinforced insulation. 3 "Stop"
4 "Stop"
Make sure that all cables are heat-resistant up to
5 "Max. curve"
75 C.
6 "Min. curve"
Install all cables in accordance with EN 60204-1
and EN 50174-2:2000. 7 "Start"
8 "Max. curve"
9 "Min. curve"
Connect all cables in accordance with local 10 "Min. curve"
regulations.
11 "Start"
7.4.1 Relay outputs
7.3 Input and output communication
See fig. 25, pos. 1.
Relay outputs The pump has two signal relays with a potential-free changeover
Alarm, ready and operating indication via signal relay. contact for external fault indication.
Digital input You can set the function of the signal relay to "Alarm", "Ready" or
Start and stop (S/S) "Operation" on the control panel or with Grundfos GO.
Minimum curve (MI) The relays can be used for outputs up to 250 V and 2 A.
Maximum curve (MA).
Analog input
0-10 V or 4-20 mA control signal. Warnings do not activate the alarm relay.
To be used for external control of the pump or as sensor input
for the control of the external setpoint.
The 24-V supply from pump to sensor is optional and is
normally used when an external supply is not available. Use C and NC for fault signals as this enables serial
connections of more relays and detection of signal
WARNING cable defects.
Electric shock
Death or serious personal injury
- Separate input voltages from external equipment
from live parts by reinforced insulation.

18
7.4.2 Digital inputs
Relay 1 Relay 2

English (GB)
See fig. 25, pos. 2.
NC NO C NC NO C You can use the digital input for external control of start-stop or
forced maximum or minimum curve.
If no external on-off switch is connected, the jumper between
terminals start-stop (S/S) and frame ( ) must be maintained. This
connection is the factory setting.

M M
A I S/S
Operation

TM05 3338 1212


Alarm

Fig. 27 Relay output

Contact symbol Function


NC Normally closed
NO Normally open
C Common On-off timer

The functions of the signal relays appear from the table below:

Signal relay Alarm signal


Not activated: Start-stop
1 2 3
The power supply has been switched off.

TM05 3339 1212


NC NO C
1 2 3
NC NO C The pump has not registered a fault.

Activated:
1 2 3 The pump has registered a fault.
NC NO C

Signal relay Ready signal Fig. 28 Digital input

Not activated:
The pump has registered a fault and is Contact symbol Function
1 2 3
NC NO C
1 2 3 unable to run. M Maximum curve
NC NO C
The power supply has been switched off. A 100 % speed
Activated: M
Minimum curve
The pump has been set to stop, but is ready I
1 2 3 to run. S/S Start-stop
NC NO C
The pump is running.
Frame connection
Signal relay Operating signal
External start-stop
Not activated: You can start and stop the pump via the digital input.
1 2
1NC NO
2 C3
3
The power supply has been switched off.
NC NO C
Start-stop
Activated: S/S H Normal duty
1 2 3 The pump is running.
NC NO C Factory setting with jumper
between start-stop and .
Factory settings of relays: Q

Relay Function S/S H


1 Operating signal Stop
2 Alarm signal Q

19
Externally forced maximum or minimum curve In order to optimise the pump performance, you can use external
sensors in the following cases:
English (GB)

You can force the pump to operate on the maximum or minimum


curve via the digital input.
Function or control mode Sensor type
Maximum curve Heat energy monitor Temperature sensor
M H Constant temperature Temperature sensor
A
Normal duty Proportional pressure Pressure sensor

Q
1
M H
A
Maximum curve
24V IN
Q Vcc Signal

Minimum curve

M H 2
I
Normal duty

TMTM06 7237 3416


Q

M H
I
Minimum curve
Q
Fig. 31 Examples of external sensors
Select the function of the digital input on the pump control panel
or with Grundfos GO.
Pos. Sensor type
7.4.3 Analog input
Combined temperature and pressure sensor,
See fig. 25, pos. 3. 1 Grundfos type RPI T2.
You can use the analog input for the connection of an external 1/2" connection and 4-20 mA signal.
sensor for measuring temperature or pressure. See fig. 31. Pressure sensor, Grundfos type RPI.
You can use sensor types with 0-10 V or 4-20 mA signal. 2
1/2" connection and 4-20 mA signal.
You can also use the analog input for an external signal for the
For further details, see section 11.4 External sensors.
control from a building management system or similar control
system. See fig. 32.
When the input is used for the heat energy monitor, install a
temperature sensor in the return pipe. BMS
If the pump is installed in the return pipe of the system, install PLC
the sensor in the flow pipe.
If the constant-temperature control mode has been enabled 24V
and the pump is installed in the flow pipe of the system, install
the sensor in the return pipe.
If the pump is installed in the return pipe of the system, you

TM05 2888 0612


can use the internal temperature sensor.
You can change the sensor type, 0-10 V or 4-20 mA, on the
control panel or with Grundfos GO.

Fig. 32 Examples of external signal for the control via BMS or


PLC
24V
24V ININ
TM05 3221 0612

Vcc
Vcc signal
signal

sensor
sensor

Fig. 29 Analog input for external sensor, 0-10 V

24V IN
TM05 2948 0612

Vcc signal

sensor

Fig. 30 Analog input for external sensor, 4-20 mA

20
8. Setting the product

English (GB)
Select this control
System application
mode
Recommended for most heating systems, especially in systems with relatively large pressure losses in the AUTOADAPT
distribution pipes. See the description under proportional pressure.
H
In replacement situations where the proportional-pressure duty point is unknown.
The duty point has to be within the AUTOADAPT operating range. During operation, the pump automatically
adjusts to the actual system characteristic.
This setting ensures minimum energy consumption and noise level from valves, which reduces operating costs Q
and increases comfort.
The FLOWADAPT control mode is a combination of AUTOADAPT and FLOWLIMIT.
This control mode is suitable for systems where you want a maximum flow limit, FLOWLIMIT. The pump
continuously monitors and adjusts the flow, thus ensuring that the selected FLOWLIMIT is not exceeded.
Recommended for main pumps in boiler applications where a steady flow through the boiler is required. No extra
FLOWADAPT
energy is used for pumping too much liquid into the system.
H
In systems with mixing loops, you can use the control mode to control the flow in each loop.
Benefits:
Enough water for all loops at peak load conditions if you have set each loop to the right maximum flow.
The dimensioned flow for each zone, required heat energy, is determined by the flow from the pump. You can Q

set this value in the FLOWADAPT control mode without the use of throttling valves.
When the flow is set lower than the balancing valve setting, the pump ramps down instead of losing energy by
pumping against a balancing valve.
Cooling surfaces in air-conditioning systems can operate at high pressure and low flow.
Recommended in systems with relatively large pressure losses in the distribution pipes and in air-conditioning
and cooling systems.
Two-pipe heating systems with thermostatic valves and the following:
very long distribution pipes Proportional
strongly throttled balancing valves pressure
differential-pressure regulators H

large pressure losses in those parts of the system through which the total quantity of water flows, for
example boiler, heat exchanger and distribution pipe up to the first branching. Hset

Primary circuit pumps in systems with large pressure losses in the primary circuit. Hset
2

Air-conditioning systems with the following: Q

heat exchangers, fan coils


cooling ceilings
cooling surfaces.
Recommended in systems with relatively small pressure losses in the distribution pipes.
Two-pipe heating systems with thermostatic valves and the following:
Constant pressure
sized for natural circulation
H
small pressure losses in those parts of the system through which the total quantity of water flows, for
example boiler, heat exchanger and distribution pipe up to the first branching or modified to a high
differential temperature between flow pipe and return pipe, for example district heating.
Underfloor heating systems with thermostatic valves.
Q

One-pipe heating systems with thermostatic valves or pipe balancing valves.


Primary circuit pumps in systems with small pressure losses in the primary circuit.
In heating systems with a fixed system characteristic, for example domestic hot-water systems, it may be Constant
relevant to control the pump according to a constant return-pipe temperature. temperature
You can use FLOWLIMIT with advantage to control the maximum circulation flow. H

Select this control mode if the pump performance is to be controlled according to a differential temperature in the Differential
system where the pump is installed. temperature

This control mode requires an external temperature sensor in addition to the internal one. H
t

21
Select this control
English (GB)

System application
mode
If an external controller is installed, the pump is able to change from one constant curve to another, depending Constant curve
on the value of the external signal.
H
You can also set the pump to operate according to the maximum or minimum curve, like an uncontrolled pump:
Use the maximum-curve mode in periods in which a maximum flow is required. This operating mode is for
instance suitable for hot-water priority.
Use the minimum-curve mode in periods in which a minimum flow is required. This operating mode is for
Q
instance suitable for manual night setback if you do not want automatic night setback.

In systems with pumps connected in parallel.


The multipump function enables the control of two to four single-head pumps connected in parallel and twin-head "Assist" menu
pumps without the use of external controllers. See section 8.8.3 "Multi-pump setup". The pumps in a multipump "Multi-pump setup"
system communicate with each other via the wireless GENIair connection.

22
8.1 Operating the product 8.2 "Home" menu

English (GB)
CAUTION
Hot surface
Minor or moderate personal injury
- At high liquid temperatures, the pump housing may
be so hot that only the control panel should be
touched to avoid burns.

Undef-010
Navigation
"Home"
Press to go to the "Home" menu.
"Home" menu, factory setting
Shortcut to control mode settings
Shortcut to setpoint settings
"Estimated flow rate"
"Head".
Navigate in the display with or and change between the two
shortcuts with or .
TM05 3820 1612

You can define the Home display. See section "Define Home
display".
8.2.1 "Home" display icons

Fig. 33 Control panel Symbol Description

Automatic night setback function is enabled.


Button Function
Goes to the "Home" menu. Settings are locked. You cannot adjust settings
from the display.
Returns to the previous display.
The pump is in remote mode, for example from
Navigates between main menus, displays and
fieldbus.
digits.
When the menu is changed, the display always The multipump system is active.
shows the top display of the new menu.
Navigates between submenus.
Master pump in a multipump system.
Saves changed values, resets alarms and expands
the value field. Slave pump in a multipump system.
8.1.1 Menu structure
Forced local mode is active.
The pump incorporates a startup guide which is started at the first You cannot set the pump to remote mode, for
startup. After the startup guide, the four main menus appear in example from fieldbus.
the display. See section 7. Control functions.
"Home"
This menu shows up to four user-defined parameters with
shortcuts or a graphical illustration of a performance curve. See
section 8.2 "Home" menu.
Status
This menu shows the status of the pump and system as well as
warnings and alarms. See section 8.4 Status menu.

You cannot make settings in this menu.

"Settings "
This menu gives access to all setting parameters. You can make
a detailed setting of the pump in this menu. See section
8.6 "Settings" menu.
"Assist"
This menu enables assisted pump setup, provides a short
description of the control modes and offers fault advice. See
section 8.8 "Assist" menu.

23
8.3 Menu overview
English (GB)

Status "Settings" "Assist"


"Operating status" "Setpoint" "Assisted pump setup"
"Operating mode, from" "Operating mode" "Setting of pump"
"Control mode" "Normal" "Setting of date and time"
"Pump performance" "Stop" "Date format, date and time"
"Max. curve and duty point" "Min." "Date only"
"Resulting setpoint" "Max." "Time only"
"Liquid temperature" "Control mode" "Multi-pump setup"
"Speed" "AUTOADAPT" "Setup, analog input"
"Operating hours" "FLOWADAPT" "Description of control mode"
"Power and energy consumption" "Prop. press." "AUTOADAPT"
"Power consumption" "Const. press." "FLOWADAPT"
"Energy consumption" "Const. temp." "Prop. press."
"Warning and alarm" "Diff. temp." "Const. press."
"Actual warning or alarm" "Constant curve" "Const. temp."
"Warning log" "Controller settings (not model A)" "Differential temp."
"Warning log 1 to 5" "Controller gain Kp" "Constant curve"
"Alarm log" "Control. integr. action time Ti" "Assisted fault advice"
"Alarm log 1 to 5" "FLOWLIMIT" "Blocked pump"
"Heat energy monitor" "Enable FLOWLIMIT function" "Pump communication fault"
"Heat power" "Set FLOWLIMIT" "Internal fault"
"Heat energy" "Automatic Night Setback" "Internal sensor fault"
"Estimated flow rate" "Analog Input" "Dry running"
"Volume" "Function of analog input" "Forced pumping"
"Hours counter" "Unit" "Undervoltage"
"Temperature 1" "Sensor range, min. value" "Overvoltage"
"Temperature 2" "Sensor range, max. value" "High motor temperature"
"Differential temp." "Electrical signal" "External sensor fault"
"Operating log" "Relay outputs" "High liquid temperature"
"Operating hours" "Relay output 1" "Comm. fault, twin-head pump"
"Trend data" "Relay output 2"
"Duty point over time" "Not active"
"3D showing (Q, H, t)" "Ready"
"3D showing (Q, T, t)" "Alarm"
"3D showing (Q, P, t)" "Operation"
"3D showing (T, P, t)" "Setpoint influence"
"Fitted modules" "External setpoint function"
"Date and time" "Temperature influence"
"Date" "Bus communication"
"Time" "Pump number"
"Pump identification" "Forced local mode"
"Multi-pump system" "Enable"
"Operating status" "Disable"
"Operating mode, from" "General settings"
"Control mode" "Language"
"System performance" "Set date and time"
"Duty point" "Select date format"
"Resulting setpoint" "Set date"
"System identification" "Select time format"
"Power and energy consumption" "Set time"
"Power consumption" "Units"
"Energy consumption" "SI or US units"
"Other pump 1, multi-pump sys." "Customised units"
"Other pump 1, multi-pump sys." "Pressure"
"Differential pressure"
"Head"
"Level"

24
"Flow rate"

English (GB)
"Volume"
"Temperature"
"Differential temp."
"Electrical power"
"Electrical energy"
"Heat power"
"Heat energy"
"Enable/disable settings"
"Alarm and warning settings"
"Dry running (57)"
"Internal sensor fault (88)"
"Internal fault (157)"
"Delete history"
"Delete operating log"
"Delete heat energy data"
"Delete energy consumption"
"Define Home display"
"Select Home display type"
"List of data"
"Graphical illustration"
"Define Home display contents"
"List of data"
"Graphical illustration"
"Display brightness"
"Brightness"
"Return to factory settings"
"Run start-up guide"

25
8.4 Status menu 8.6 "Settings" menu
English (GB)

3.1.0.0.0.0 Settings
2.1.0.0.0.0 Status
Navigation Navigation
"Home" > Status "Home" > "Settings"
Press and go to the Status menu with . Press and go to the "Settings" menu with .
Status menu "Settings" menu
This menu offers the following status information: This menu offers the following setting options:
"Operating status" "Setpoint"
"Pump performance" "Operating mode"
"Power and energy consumption" "Control mode"
"Warning and alarm" "Controller settings", not model A
"Heat energy monitor" "FLOWLIMIT"
"Operating log" "Automatic Night Setback"
"Fitted modules" "Analog Input"
"Date and time" "Relay outputs"
"Pump identification" "Setpoint influence"
"Multi-pump system". "Bus communication"
Navigate between the submenus with or . "General settings".
Navigate between the submenus with or .
8.5 "Operating status"
8.6.1 "Setpoint"
2.1.1.0.0.0 Operating mode

3.1.1.0.0.0 Setpoint
Navigation
"Home" > Status > "Operating status" Navigation
"Operating status" "Home" > "Settings" > "Setpoint"
"Operating mode, from" "Setpoint"
"Control mode". Set the setpoint so that it matches the system.
This example shows that the pump runs in normal operation in a Setting:
multipump system. 1. Press [OK].
The status in the submenus gives information about the pump 2. Select digit with and and adjust with or .
settings and other operational parameters. 3. Press [OK] to save.
Navigate between the submenus with or . A too high setting may result in noise in the system whereas a too
low setting may result in insufficient heating or cooling in the
system.

Control mode Measuring unit


Proportional pressure m, ft
Constant pressure m, ft
Constant temperature C, F, K
Constant curve %

26
8.6.2 "Operating mode" 8.6.3 "Control mode"

English (GB)
3.1.2.0.0.0 Operating mode

3.1.3.0.0.0 Control mode


Navigation Navigation
"Home" > "Settings" > "Operating mode" "Home" > "Settings" > "Control mode"
"Operating mode" "Control mode"
"Normal" "AUTOADAPT"
The pump runs according to the selected control mode. "FLOWADAPT"
"Stop" "Prop. press." (proportional pressure)
The pump stops.
"Const. press." (constant pressure)
"Min."
"Const. temp." (constant temperature)
Use the minimum-curve mode in periods in which a minimum
"Differential temp." (differential temperature)
flow is required. This operating mode is for instance suitable
for manual night setback if you do not want to use automatic "Constant curve".
night setback.
"Max."
Set the operating mode to "Normal" before you
Use the maximum-curve mode in periods in which a maximum
enable a control mode.
flow is required. This operating mode is for instance suitable
for systems with hot-water priority.
Setting: Setting:
1. Select operating mode with or . 1. Select control mode with or .
2. Press [OK] to save. 2. Press [OK] to enable the control mode.
You can set the pump to operate according to the maximum or You can change the setpoint for all control modes, except
AUTOADAPT and FLOWADAPT, in the "Setpoint" submenu under
minimum curve, like an uncontrolled pump. See fig. 34.
"Settings" when you have selected the desired control mode.
You can combine all control modes, except "Constant curve", with
H
automatic night setback. See section 8.6.6 "Automatic Night
Setback".
You can also combine the FLOWLIMIT function with the last five
Max. control modes mentioned above. See section
8.6.5 "FLOWLIMIT".
TM05 2446 5111

Min.

Q
Fig. 34 Maximum and minimum curves

27
"AUTOADAPT" "Prop. press."
English (GB)

The AUTOADAPT control mode continuously adapts the pump The head is reduced at decreasing flow demand and increased at
performance according to the actual system characteristic. rising flow demand. See fig. 37.
Manual setting of the setpoint is not possible. You can set the setpoint with an accuracy of 0.1 metre. The head
against a closed valve is the setpoint.
H
H

Hfac Hset1
A1
Hset

TM05 2452 1312


Hauto_min Hset2

TM05 2448 1212


A3 A2 Hset
2
Q
Fig. 35 AUTOADAPT
Q
Fig. 37 Proportional pressure
When the AUTOADAPT control mode has been enabled, the pump
starts with the factory setting, Hfac is equal to Hset1, "Const. press."
corresponding to approximately 55 % of its maximum head, and We recommend this control mode if the pump is to deliver a
then adjust its performance to A1. See fig. 35. constant pressure, independently of the flow in the system. See
When the pump registers a lower head on the maximum curve, fig. 38.
A2, the AUTOADAPT function automatically selects a
correspondingly lower control curve, H set2. If the valves in the H
system close, the pump adjusts its performance to A3.

A 1: Original duty point.


A 2: Lower registered head on the maximum curve.
A 3: New duty point after AUTOADAPT control.
Hset1: Original setpoint setting.

TM05 2449 0312


Hset2: New setpoint after AUTOADAPT control.
Hfac.: See section 8.7 Setting values for control modes.
Hauto_min: A fixed value of 1.5 m.
Q
The AUTOADAPT control mode is a form of proportional-pressure Fig. 38 Constant pressure
control where the control curves have a fixed origin, Hauto_min.
The AUTOADAPT control mode has been developed specifically
for heating systems and we do not recommended that you use it
for air-conditioning and cooling systems.
To reset AUTOADAPT, see section "Return to factory settings".
"FLOWADAPT"
When you select FLOWADAPT, the pump runs AUTOADAPT and
ensures that the flow never exceeds the entered FLOWLIMIT
value.
The setting range for the FLOWLIMIT is 25 to 90 % of the
maximum flow rate of the pump.
The factory setting of the FLOWLIMIT is the flow where the
AUTOADAPT factory setting meets the maximum curve. See fig.
36.
Do not set the FLOWLIMIT lower than the dimensioned duty point.

H 25 % Q max 90 % Q max

Setting range

Hfac

Hauto_min
TM05 3334 1212

Q
Q fac
Fig. 36 FLOWADAPT

28
"Const. temp."

English (GB)
This control mode ensures a constant temperature. Constant
temperature is a comfort control mode that you can use in
domestic hot-water systems to control the flow to maintain a fixed
temperature in the system. See fig. 39. When you use this control
mode, do not install any balancing valves in the system.
If the pump is installed in the flow pipe, install a temperature

TM05 8236 2113


sensor in the return pipe of the system. Install the sensor as close t
as possible to the consumer for example a radiator or heat
exchanger.
We recommend that you install the pump in the flow pipe.
If the pump is installed in the return pipe of the system, you can Fig. 41 Differential temperature
use the internal temperature sensor. In this case, install the pump
as close as possible to the consumer for example a radiator or The controller constants, that is the gain, Kp, and integral time,Ti,
heat exchanger. are factory-set to gain is equal to 1 and integral time is equal to 8
seconds. In some cases, you must change the settings
The constant-temperature control mode also reduces the risk of
depending on the application and controlled parameter. See
bacterial growth in the system, for example legionella.
section 8.6.4 "Controller settings".
Sensor range:
"Constant curve"
minimum -10 C
You can set the pump to operate according to a constant curve,
maximum 130 C.
like an uncontrolled pump. See fig. 42.
To ensure that the pump is able to control the temperature, we
You can set the desired speed in % of maximum speed in the
recommend that you set the sensor range between -5 and +125
range from minimum to 100 %.
C.

H
H

TM05 2446 0312


TM05 2451 5111

Q
Q
Fig. 42 Constant curve
Fig. 39 Constant temperature
If you have set the pump speed in the range between minimum
"Differential temp." and maximum, the power and pressure are limited when the
This control mode ensures a constant differential-temperature pump is running on the maximum curve. This means that the
drop across heating and cooling systems. maximum performance can be achieved at a speed lower than
The differential-temperature control mode is available from model 100 %. See fig. 43.
B. The model version is stated on the nameplate. See fig. 22.
In this control mode, the pump maintains a constant differential H
Limited maximum curve
temperature between the pump and the external sensor. See
figures 40 and 41.

H
t
70
%
50
%
30
%
Mi
n.
90%

TM05 4266 2212


TM05 2451 5111

Q
Speed setting from min. to 100 %
Q
Fig. 43 Power and pressure limitations influencing the
Fig. 40 Differential temperature maximum curve

It is necessary to install an external temperature


sensor.

29
8.6.4 "Controller settings" Guidelines for setting of PI controller
English (GB)

A change of the gain and integral-time values affects all control For most applications, the factory setting of the controller
modes. If you change the control mode to another control mode, constants, gain and integral time, ensures optimum pump
change the gain and integral-time values to the factory settings. operation. However, in some applications an adjustment of the
Factory settings for all other control modes: controller may be required.
The gain, Kp, is equal to 1. You find the setpoint displayed in figures 44 and 45. For further
The integral time, Ti, is equal to 8. information about setup, see the "Assist" menu in section
8.8.1 "Assisted pump setup".
The table below shows the suggested controller settings:
If you use a built-in temperature sensor as one of the sensors,
you must install the pump as close as possible to the consumer.

Kp
System/application Heating Cooling Ti
system 1) system 2)

undef-079
10 + 5
0.5 - 0.5
t (L1 + L2)
L2 [m] Fig. 44 "Controller gain Kp"

3)
10 + 5
t - 0.5 (L1 + L2)

L2 [m]

L2 [m]

t 0.5 - 0.5 30 + 5L2

undef-080
1)
In heating systems, an increase in pump performance results
in a rise in temperature at the sensor. Fig. 45 "Control. integr. action time Ti"
2)
In cooling systems, an increase in pump performance results Proceed as follows:
in a drop in temperature at the sensor.
1. Increase the gain until the motor becomes unstable. Instability
3)
Built-in temperature sensor. can be seen by observing if the measured value starts to
L1: Distance in metres between pump and consumer. fluctuate. Furthermore, instability is audible as the motor
starts hunting up and down.
L2: Distance in metres between consumer and sensor. Some systems, such as temperature controls, are
slow-reacting, meaning that it may be several minutes before
the motor becomes unstable.
2. Set the gain to half the value of the value which made the
motor unstable.
3. Reduce the integral time until the motor becomes unstable.
4. Set the integral time to twice the value which made the motor
unstable.
Rules of thumb
If the controller is too slow-reacting, increase the gain.
If the controller is hunting or unstable, dampen the system by
reducing the gain or increasing the integral time.
Model A:
Use Grundfos GO to change the controller constants, gain and
integral time. You can only set positive values.
Model B and C:
Change the control settings by means of the display or Grundfos
GO. You can set both positive and negative values.

30
8.6.5 "FLOWLIMIT" 8.6.6 "Automatic Night Setback"

English (GB)
3.1.6.0.0.0 Automatic Night Setback
3.1.5.0.0.0 FLOWLIMIT
Navigation Navigation
"Home" > "Settings" > "FLOWLIMIT" "Home" > "Settings" > "Automatic Night Setback"
"FLOWLIMIT" "Automatic Night Setback"
"Enable FLOWLIMIT function" To enable the function, select "Active" with or and press
"Set FLOWLIMIT". [OK].
Setting: Once you have enabled automatic night setback, the pump
automatically changes between normal duty and night setback,
1. To enable the function, select "Active" with or and press
i.e. duty at low demand. The changeover depends on the
[OK].
flow-pipe temperature.
2. To set the FLOWLIMIT, press [OK].
The pump automatically changes over to night setback when the
3. Select digit with and and adjust with or . built-in sensor registers a flow-pipe temperature drop of more
4. Press [OK] to save. than 10 to 15 C within approximately two hours. The temperature
drop must be at least 0.1 C/min.
H 25 % Q max 90 % Q max Changeover to normal duty takes place without a time lag when
the temperature has increased by approximately 10 C.
You cannot enable automatic night setback when the pump is in
Setting range
constant-curve mode.
TM05 2445 1212

Q
Q limit
Fig. 46 FLOWLIMIT

You can combine the FLOWLIMIT function with the following


control modes:
"Prop. press."
"Const. press."
"Const. temp."
"Constant curve".
A flow-limiting function ensures that the flow never exceeds the
entered FLOWLIMIT value.
The setting range for FLOWLIMIT is 25 to 90 % of the Qmax of the
pump.
The factory setting of the FLOWLIMIT is the flow where the
AUTOADAPT factory setting meets the maximum curve. See fig.
36.

31
8.6.7 "Analog Input" 8.6.8 "Relay outputs"
English (GB)

In this menu, you can set an analog input such as a temperature


sensor to activate the heat-energy-monitor function. See fig. 57.

3.1.12.0.0.0 Relay outputs


3.1.7.0.0.0 Analog input
Navigation
"Home" > "Settings" > "Relay outputs"
"Relay outputs"
Navigation
"Relay output 1"
"Home" > "Settings" > "Analog Input"
"Relay output 2".
"Analog Input" You can set the relay outputs to the following:
"Function of analog input" "Not active"
"Unit" "Ready"
"Sensor range, min. value" "Alarm"
"Sensor range, max. value" "Operation".
"Electrical signal". The pump incorporates two signal relays for a potential-free
"Function of analog input" alarm signal, ready signal and operating signal. For further
Choose the function of input, for example heat energy monitor as information, see section 7.4.1 Relay outputs.
in the example below. Set the function of the signal relays, alarm signal (factory setting),
ready signal and operating signal on the pump control panel.
The output is electrically separated from the rest of the controller.
The signal relay is operated as follows:
"Not active"
The signal relay is deactivated.
3.1.7.1.0.0 Function of input

"Ready"
The signal relay is active when the pump is running or has
been set to stop, but is ready to run.
"Alarm"
The signal relay is activated together with the red indicator
light on the pump.
"Operation"
The signal relay is activated together with the green indicator
Navigation light on the pump.
"Home" > "Settings" > "Analog Input" > "Function of analog input"
"Not active"
"Differential-pressure control"
"Constant-temperature control"
"Differential-pressure control"
"Heat energy monitor"
"External setpoint influence"
Setting:
1. Select function mode with or .
2. Press [OK] to enable the function mode.
When you have selected the function of the input, specify the
sensor parameters by filling in the right values in unit, sensor
range, etc.
You can also set the analog input via the "Assist" menu where a
wizard guides you through each step of the configuration. See
8.8.5 "Setup, analog input".

32
8.7 Setting values for control modes

English (GB)
The setting values for FLOWADAPT and FLOWLIMIT are indicated
as percent of maximum flow, but you must enter the value in m3/h
in the "Settings" menu.
The maximum flow is a theoretical value corresponding to H is
equal to 0. The actual maximum flow is dependent on the system
characteristics.

AUTOADAPT FLOWADAPT and FLOWLIMIT


Qmax
Pump type Hfac Qfac Qmax 90 %
3 3
[m] [m /h] [m /h] [m3/h]
MAGNA3 25-40 (N) 2.5 8 3.7 7.2
MAGNA3 25-60 (N) 3.5 10 5.0 9.0
MAGNA3 25-80 (N) 4.5 11 5.5 9.9
MAGNA3 25-100 (N) 5.5 12 6.1 10.8
MAGNA3 25-120 (N) 6.5 13 6.2 11.7
MAGNA3 (D) 32-40 (F) (N) 2.5 9 5.0 8.1
MAGNA3 (D) 32-60 (F) (N) 3.5 11 5.9 9.9
MAGNA3 (D) 32-80 (F) (N) 4.5 12 6.4 10.8
MAGNA3 (D) 32-100 (F) (N) 5.5 13 6.7 11.7
MAGNA3 32-120 (N) 6.5 13 6.2 11.7
MAGNA3 (D) 32-120 F (N) 6.5 23 12.0 20.7
MAGNA3 (D) 40-40 F (N) 2.5 16 7.5 14.4
MAGNA3 (D) 40-60 F (N) 3.5 19 10.5 17.1
MAGNA3 (D) 40-80 F (N) 4.5 22 13.0 19.8
MAGNA3 (D) 40-100 F (N) 5.5 24 15.0 21.6
MAGNA3 (D) 40-120 F (N) 6.5 29 16.0 26.1
MAGNA3 (D) 40-150 F (N) 8.0 32 18.0 28.8
MAGNA3 (D) 40-180 F (N) 9.5 32 15.0 28.8
MAGNA3 (D) 50-40 F (N) 2.5 22 13.0 19.8
MAGNA3 (D) 50-60 F (N) 3.5 29 17.0 26.1
MAGNA3 (D) 50-80 F (N) 4.5 31 17.0 27.9
MAGNA3 (D) 50-100 F (N) 5.5 34 18.0 30.6
MAGNA3 (D) 50-120 F (N) 6.5 39 19.0 35.1
MAGNA3 (D) 50-150 F (N) 8.0 42 20.0 37.8
MAGNA3 (D) 50-180 F (N) 9.5 45 19.0 40.5
MAGNA3 (D) 65-40 F (N) 2.5 33 18.0 29.7
MAGNA3 (D) 65-60 F (N) 3.5 40 24.0 36
MAGNA3 (D) 65-80 F (N) 4.5 45 25.0 40.5
MAGNA3 (D) 65-100 F (N) 5.5 48 26.0 43.2
MAGNA3 (D) 65-120 F (N) 6.5 52 30.0 46.8
MAGNA3 (D) 65-150 F (N) 8.0 61 40.0 54.9
MAGNA3 (D) 80-40 F 2.5 49 32.0 44.1
MAGNA3 (D) 80-60 F 3.5 58 37.0 52.2
MAGNA3 (D) 80-80 F 4.5 66 40.0 59.4
MAGNA3 (D) 80-100 F 5.5 69 47.0 62.1
MAGNA3 (D) 80-120 F 6.5 74 48.0 66.6
MAGNA3 (D) 100-40 F 2.5 55 40.0 49.5
MAGNA3 (D) 100-60 F 3.5 63 43.0 56.7
MAGNA3 (D) 100-80 F 4.5 73 50.0 65.7
MAGNA3 (D) 100-100 F 5.5 79 52.0 71.1
MAGNA3 (D) 100-120 F 6.5 85 57.0 76.5
The duty ranges for proportional-pressure and constant-pressure
control appear from the data sheets in the MAGNA3 data booklet.
In constant-curve duty, you can control the pump from minimum
to 100 %. The range of control depends on the minimum speed,
power and pressure limits of the pump.

33
8.7.1 "Setpoint influence" "Temperature influence"
English (GB)

When this function is enabled in proportional- or


constant-pressure control mode, the setpoint for head is reduced
according to the liquid temperature.
You can set the temperature influence to function at liquid

3.1.15.0.0.0 Setpoint influence


temperatures below 80 or 50 C. These temperature limits are
called Tmax.. The setpoint is reduced in relation to the head set
which is equal to 100 %, according to the characteristics below.

H H

Navigation 100 %
"Home" > "Settings" > "Setpoint influence" Hactual
"Setpoint influence"
"External setpoint function" 30 %

TM05 3022 1212


"Temperature influence".
"External setpoint function"
20 50 80 T [C] Q
An external 0-10 V or 4-20 mA signal controls the pump speed in Tactual
a range from minimum to 100 % in a linear function. See fig. 47.
Fig. 48 "Temperature influence"
Range
In the above example, Tmax., which is equal to 80 C, has been
4-20 mA [0-100 %]
selected. The actual liquid temperature, Tactual, causes the
0-10 V [0-100 %] setpoint for head to be reduced from 100 % to H actual.
Control The temperature influence function requires the following:
proportional-pressure, constant-pressure or constant-curve
0-20 % e.g. 0-2 V Setpoint is equal to minimum.
control mode
Setpoint is equal from
20-100 % e.g. 2-10 V pump installed in flow pipe
minimum to setpoint.
system with flow-pipe temperature control.
If the analog input is set to external setpoint influence, the Temperature influence is suitable for the following systems:
external setpoint function is automatically activated with "Linear
Systems with variable flows for example two-pipe heating
with MIN". See section 7.4.3 Analog input.
systems, in which the enabling of the temperature influence
function ensures a further reduction of the pump performance
rpm in periods with small heating demands and consequently a
Max. reduced flow-pipe temperature.
Systems with almost constant flows, for example one-pipe
heating systems and underfloor heating systems, in which
variable heating demands cannot be registered as changes in
the head as is the case with two-pipe heating systems. In such
systems, you can only adjust the pump performance by
enabling the temperature influence function.
TM05 3219 1212

Min.
Selection of maximum temperature
In systems with a dimensioned flow-pipe temperature:
V Up to and including 55 C, select a maximum temperature
0 2 10
equal to 50 C.
Fig. 47 "External setpoint function", 0-10 V
Above 55 C, select a maximum temperature equal to 80 C.
The range of control depends on the minimum speed, power and You cannot use the temperature influence function in
pressure limits of the pump. air-conditioning and cooling systems.
You can configure the analog input to an external setpoint
function in "Settings" or in the "Assist" menu. See section
7.4.3 Analog input.
3.1.15.10.0 External setpoint function

34
8.7.2 "Bus communication" 8.7.3 "General settings"

English (GB)
"Language"

3.1.18.0.0.0 Bus communication

3.1.19.1.0.0 Language
Navigation
"Home" > "Settings" > "Bus communication" Navigation
"Bus communication" "Home" > "Settings" > "General settings" > "Language"
"Pump number" "Language"
"Forced local mode" The display can be shown in any of the following languages:
"Pump number" Bulgarian
Croatian
Czech
Danish
Dutch
English
3.1.18.1.0.0 Pump number

Estonian
Finnish
French
German
Greek
Hungarian
Navigation Italian
"Home" > "Settings" > "Bus communication" > "Pump number" Japanese
"Pump number" Korean
You can allocate a unique number to the pump. This makes it Latvian
possible to distinguish between pumps in connection with bus Lithuanian
communication.
Polish
"Forced local mode" Portuguese
You can temporarily override remote commands from a building Romanian
management systems to make local settings. Once you have
Russian
disabled "Forced local mode", the pump reconnects to the
network when it receives a remote command from the building Serbian
management system. Simplified Chinese
Slovak
Slovenian
Spanish
Swedish
3.1.18.2.0.0 Forced local mode

Turkish
Ukrainian.
Measuring units are automatically changed according to the
selected language.
Setting:
1. Select language with and .
2. Press [OK] to enable the language.
Navigation
"Home" > "Settings" > "Bus communication" > "Forced local
mode"
"Forced local mode"
"Enable"
"Disable".

35
"Set date and time" In this menu you can select between SI and US units. The setting
can be made generally for all parameters or customised for each
English (GB)

individual parameter.
"Pressure"
"Differential pressure"

3.1.19.2.0.0 Set date and time


"Head"
"Level"
"Flow rate"
"Volume"
"Temperature"
"Differential temp."
"Power"
Navigation "Energy".
"Home" > "Settings" > "General settings" > "Set date and time" Setting:
"Set date and time" 1. Select parameter and press [OK].
"Select date format" 2. Select unit with or .
"Set date" 3. Press [OK].
"Select time format" If you have selected SI or US units, the customised units are
"Set time". reset.
Set the real-time clock in this menu. "Enable/disable settings"
"Select date format"
"YYYY-MM-DD"

3.1.19.4.0.0 Enable/disable settings


"DD-MM-YYYY"
"MM-DD-YYYY".
Setting:
1. Select "Set date".
2. Press [OK].
3. Select digit with and and adjust with or .
4. Press [OK] to save.
"Select time format"
"HH:MM 24-hour clock" Navigation
"HH:MM am/pm 12-hour clock". "Home" > "Settings" > "General settings" > "Enable/disable
Setting: settings"
1. Select "Set time". "Enable/disable settings"
2. Press [OK]. In this display, you can disable the possibility of making settings .
3. Select digit with and and adjust with or . Select "Disable" with or and press [OK].
4. Press [OK] to save. The pump is now locked for settings. Only the "Home" display is
"Units" available.
To unlock the pump and allow settings, press and
simultaneously for at least 5 seconds or enable the settings again
in the menu.
3.1.19.3.0.0 Units

Navigation
"Home" > "Settings" > "General settings" > "Units"
"Units"
"SI or US units"
"Customised units".

36
"Alarm and warning settings" "Delete history"

English (GB)
"Delete operating log"

3.1.19.12.0.0 Alarm and warning settings


"Delete heat energy data"
"Delete energy consumption".
In this menu, you can delete data from the pump, for example if
the pump is moved to another system or if new data are required
due to changes to the system.
Setting:
1. Select submenu and press [OK].
2. Select "Yes" with or and press [OK] or press to
cancel.
"Define Home display"
Navigation
"Home" > "Settings" > "General settings" > "Alarm and warning
settings"

3.1.19.6.0.0 Define Home display


"Settings"
"Dry running (57)"
"Internal sensor fault (88)"
"Internal fault (157)"
"Dry running (57)"
"Enable"
"Disable"
The dry running detection is disabled by default on all pumps Navigation
from production code 1529. The production code is on the
"Home" > "Settings" > "General settings" > "Define Home display"
nameplate. Enable the dry-running function, if there is a risk of
dry running. "Define Home display"

"Internal sensor fault (88)" "Select Home display type"

"Enable" "Define Home display contents".

"Disable" In this menu, you can set the Home display to show up to four
user-set parameters or a graphical illustration of a performance
In case of a sensor problem related to the quality of the liquid, the
curve.
pump is able to continue operation with satisfactory performance
in most situations. In such situations, you can disable "Internal "Select Home display type"
sensor fault (88)". 1. Select "List of data" or "Graphical illustration" with or .
"Internal fault (157)" 2. Press [OK] to save.
"Enable" To specify the contents, go to "Define Home display contents".
"Disable" "Define Home display contents"
If the real-time clock is out of order, for example due to a dead 1. To set "List of data", press [OK]. A list of parameters appears
battery, a warning is shown. You can disable the warning. in the display.
"Delete history" 2. Select or deselect with [OK].
The selected parameters are shown below. The arrow indicates
that the parameter links to the "Settings" menu and works as a
shortcut for quick settings.
3.1.19.5.0.0 Delete history

Define Home display contents

Navigation
"Home" > "Settings" > "General settings" > "Delete history"

1. To set "Graphical illustration", press [OK].


2. Select the desired curve.
3. Press [OK] to save.

37
"Display brightness" 8.8 "Assist" menu
English (GB)

3.1.19.7.1.0 Brightness

Assist
Navigation Navigation
"Home" > "Settings" > "General settings" > "Display brightness" "Home" > "Assist"
"Brightness" Press and go to the "Assist" menu with .
1. Press [OK]. "Assist" menu
2. Set brightness with and . This menu offers the following:
3. Press [OK] to save. "Assisted pump setup"
"Return to factory settings" "Setting of date and time"
"Multi-pump setup"
3.1.19.10.1.0 Return to factory settings
"Setup, analog input"
"Description of control mode"
"Assisted fault advice".
The "Assist" menu guides the user through the setting of the
pump. In each submenu, there is a guide that guides the user
through the setting of the pump.
8.8.1 "Assisted pump setup"
This menu guides you through a complete pump setup, starting
with a presentation of the control modes and ending with the
setpoint setting.
Navigation 8.8.2 "Setting of date and time"
"Home" > "Settings" > "General settings" > "Return to factory See section "Set date and time".
settings"
"Return to factory settings"
You can recall the factory settings and overwrite the current
settings. All user settings in the "Settings" and "Assist" menus are
set back to the factory settings. This also includes language,
units, setup of analog input, multipump function, etc.
To overwrite the current settings with the factory settings, select
"Yes" with or and press [OK].
"Run start-up guide"
3.1.19.11.0.0 Run start-up guide

Navigation
"Home" > "Settings" > "General settings" > "Run start-up guide"
"Run start-up guide"
The startup guide automatically starts when you start the pump
for the first time.
You can always run the startup guide later via this menu. The
startup guide guides the user through the general settings of the
pump, such as language, date and time.
To run the startup guide, select "Yes" with or and press
[OK].

38
8.8.3 "Multi-pump setup" Check the nameplate to identify the master pump. See fig. 52.

English (GB)
Undef-083 Select multi pump function
XXXXXXXXXXXXXXXXXXXXXXXX
P/N: XXXXXXXX IP XXX TF XXX I1 [A] P1 [W] MPa
S/N: XXXXXXXX
((,;;;3DUW; 0LQ ;;; XXXX
PC: XXXX
Model: X Made in Germany 0D[ ;;; XXXX ;;
Grundfos Holding A/S, DK - 8850 Bjerringbro, Denmark

TM06 6890 2516


Navigation
I is defined as master.
"Home" > "Assist" > "Multi-pump setup"
1. Follow the step-by-step guide to complete the multipump Fig. 52 Identify the master pump on a twin-head pump
setup.
"Alternating operation"
2. Check the entered values.
3. Press [OK] to confirm and enable the settings.
Multipump function

TM06 7501 3516


The multipump function enables the control of single-head pumps
connected in parallel and twin-head pumps without the use of
external controllers. The pumps in a multipump system
communicate with each other via the wireless GENIair
connection.
Pump system: Fig. 53 "Alternating operation"
Twin-head pump. Alternating operation functions as a duty-standby operating mode
Two single-head pumps connected in parallel. The pumps and is possible with two pumps of same size and type connected
must be of the same type and size. Each pump requires a in parallel. The main purpose of the function is to ensure an even
non-return valve in series with the pump. amount of running hours and to ensure that the standby pump
You can set a multipump system from a selected pump, which will takes over if the running pump stops due to an alarm.
then be the master pump. "Back-up operation"
TM067498 3516

TM06 7502 3516


Fig. 49 Single-head pumps connected in parallel
Fig. 54 "Back-up operation"
Check the display to identify the master pump in a multipump
system. See fig. 50 and "Home" display icons. Backup operation is possible with two pumps of same size and
type connected in parallel. Each pump requires a non-return
valve in series with the pump.
One pump is running continuously. The backup pump is operated
for a short time each day to prevent seizing up. If the duty pump
stops due to a fault, the backup pump starts automatically.
TM06 7499 3516

Fig. 50 Identify the master pump in a multipump system

A twin-head pump is set to multipump function from factory. Here


pump head I is defined as master pump.
TM06 7500 3516

Fig. 51 Twin-head pumps

39
"Cascade operation" 8.8.5 "Setup, analog input"
English (GB)

This menu guides you through the setup of the analog inputs, for
example a temperature sensor input to a heat energy monitor.

TM06 7498 3516


Fig. 55 "Cascade operation"

Heat energy monitor


Cascade operation ensures that the pump performance is
automatically adapted to the consumption by switching pumps on
or off. The system thus runs as energy-efficiently as possible with
a constant pressure and a limited number of pumps.
When a twin-head pump is running in constant-pressure control
mode, the second pump starts at 90 % of the maximum
Navigation
performance. The second pump stops automatically when it is no
longer needed to fulfil the system demand. If both pumps are "Home" > "Assist" > "Setup, analog input"
running, they run at the same speed. 1. To enable the sensor input, select "Heat energy monitor" with
Pump system: or and press [OK].
Set the control mode to "Const. press." or "Constant curve".
"No multi-pump function"

TM06 7503 3516

undef-147
Fig. 56 "No multi-pump function"

The pumps run as single-head pumps.


2. Follow the step-by-step guide to complete the sensor-input
8.8.4 External connections in a multipump systems setup. Start with the unit display and end with the summary
The following external connections need only to be fitted to the display.
master pump: 3. Check the entered values.
analog input 4. Press [OK] to confirm and enable the settings.
digital input 8.8.6 "Heat energy monitor"
communication interface module, CIM.
The heat energy monitor is a monitoring function that calculates
If you want to monitor a slave pump, mount a communication the heat energy consumption within a system. The built-in flow
interface module on the slave pump too. estimation needed for the calculation has an inaccuracy of 10 %
Set the following on both the master and slave pump: of the maximum flow. Also, the temperature measurements
Relays needed for the calculation have some inaccuracy depending on
From model B. Configure on both master and slave pump. the sensor type. Therefore, you cannot use the heat energy value
Operating mode, control mode and setpoint for billing purposes. However, the value is perfect for optimisation
These modes are system parameters and they are shared purposes in order to prevent excessive energy costs caused by
between the two pumps. system imbalances.
Heat energy monitor The heat energy monitor requires an additional temperature
The heat energy monitor works on the system level. sensor installed in the flow pipe or return pipe depending on
Therefore, both pumps display the heat energy for the system, where the pump is installed.
not for the individual pump.
kWh

tF
TM05 5367 3612

tR
Fig. 57 MAGNA3 with built-in heat energy monitor

40
"Heat energy" Example:

English (GB)
H

Max.

2.1.6.2.0.0 Heat energy


Min.

TM05 2448 5111


Q
Navigation
"Home" > Status > "Heat energy monitor" > "Heat energy"
Qmax
"Heat energy"
Fig. 58 Qmax
You can measure both heating and cooling in the same system. If
a system is used for both heating and cooling, two counters are 1. MAGNA3 65-60 has a Qmax of 40 m3/h.
automatically shown in the display. Typically 5 % accuracy means 2 m3/h inaccuracy of Qmax +/- 2
The time stamp of the date indicates the latest use of the specific m3/h.
counter. 2. This accuracy is valid for the entire QH area. If the pump
The value of "latest year (2)" represents the last 52 consecutive indicates 10 m3/h, the measurement is 10 +/- 2 m3/h.
weeks where the pump has been supplied with power. The user 3. The flow rate can be from 8-12 m3/h.
can reset the value manually.
The use of a mixture of water and ethylene-glycol mixture will
8.9 External setpoint influence decrease the accuracy.
External setpoint influence is typically used to control the speed If the flow is less than 10 % of Qmax, the display shows a low flow.
according to a setpoint by means of a 0-10 V signal.
8.11 Pump heads in twin-head pumps
Follow the step-by-step guide to complete the sensor input setup.
The twin-head pump housing has a flap valve on the outlet side.
Start with the unit display and end with the summary display.
The flap valve seals off the port of the idle pump housing to
1. Check the entered values. prevent the pumped liquid from running back to the inlet side. See
2. Press [OK] to confirm and enable the settings. fig. 59. Due to the flap valve there is a difference in the hydraulic
3. Return to the "Settings" menu and find "External setpoint between the two pump heads. See fig. 60.
function".
4. Choose "Linear with MIN" function. See section "External
setpoint function".

8.10 Flow estimation accuracy


The internal sensor estimates the difference in pressure between
the inlet and outlet port of the pump. The measurement is not a
direct differential-pressure measurement, but by knowing the

TM06 1565 2514


hydraulic design of the pump, you can estimate the differential
pressure across the pump. The speed and power give a direct
estimation of the actual duty point at which the pump is running.
The calculated flow rate has an accuracy specified as +/- xx % of
Qmax. The less flow through the pump, the less accurate the
reading will be. See also section 8.8.6 "Heat energy monitor". Fig. 59 Twin-head pump housing with flap valve

H Right pump head

Left pump head


TM06 1566 2514

Q
Fig. 60 Hydraulic difference between the two pump heads

41
The table below shows the flow accuracy of the complete
MAGNA3 range. The typical accuracy is displayed along with the
English (GB)

worst-case value.

Single-head pumps and left-side pump Right-side pump head of twin-head


Qmax head of twin-head pumps pumps
Pump type
5 % typical 10 % worst case 7 % typical 12 % worst case
3 3 3 3
[m /h] [m /h] [m /h] [m /h] [m3/h]
MAGNA3 25-40 (N) 8 0.4 0.8 - -
MAGNA3 25-60 (N) 10 0.5 1.0 - -
MAGNA3 25-80 (N) 11 0.55 1.1 - -
MAGNA3 25-100 (N) 12 0.6 1.2 - -
MAGNA3 25-120 (N) 13 0.65 1.3 - -
MAGNA3 (D) 32-40 (F) (N) 9 0.45 0.9 0.63 1.08
MAGNA3 (D) 32-60 (F) (N) 11 0.55 1.1 0.77 1.32
MAGNA3 (D) 32-80 (F) (N) 12 0.6 1.2 0.84 1.44
MAGNA3 (D) 32-100 (F) (N) 13 0.65 1.3 0.91 1.56
MAGNA3 32-120 (N) 13 0.65 1.3 - -
MAGNA3 (D) 32-120 F (N) 23 1.15 2.3 1.61 2.76
MAGNA3 (D) 40-40 F (N) 16 1.3 1.6 1.12 1.92
MAGNA3 (D) 40-60 F (N) 19 1.45 1.9 1.33 2.28
MAGNA3 (D) 40-80 F (N) 22 1.1 2.2 1.54 2.64
MAGNA3 (D) 40-100 F (N) 24 1.2 2.4 1.68 2.88
MAGNA3 (D) 40-120 F (N) 29 1.45 2.9 2.03 3.48
MAGNA3 (D) 40-150 F (N) 32 1.6 3.2 2.24 3.84
MAGNA3 (D) 40-180 F (N) 32 1.6 3.2 2.24 3.84
MAGNA3 (D) 50-40 F (N) 22 1.1 2.2 1.54 2.64
MAGNA3 (D) 50-60 F (N) 29 1.45 2.9 2.03 3.48
MAGNA3 (D) 50-80 F (N) 31 1.55 3.1 2.17 3.72
MAGNA3 (D) 50-100 F (N) 34 1.7 3.4 2.38 4.08
MAGNA3 (D) 50-120 F (N) 39 1.95 3.9 2.73 4.68
MAGNA3 (D) 50-150 F (N) 42 2.1 4.2 2.94 5.04
MAGNA3 (D) 50-180 F (N) 45 2.25 4.5 3.15 5.40
MAGNA3 (D) 65-40 F (N) 33 1.65 3.3 2.31 3.96
MAGNA3 (D) 65-60 F (N) 40 2.0 4.0 2.80 4.80
MAGNA3 (D) 65-80 F (N) 45 2.25 4.5 3.15 5.40
MAGNA3 (D) 65-100 F (N) 48 4.4 4.8 3.36 5.76
MAGNA3 (D) 65-120 F (N) 52 2.6 5.2 3.64 6.24
MAGNA3 (D) 65-150 F (N) 61 3.05 6.1 4.27 7.32
MAGNA3 (D) 80-40 F 49 2.45 4.9 3.43 5.88
MAGNA3 (D) 80-60 F 58 2.9 5.8 4.06 6.96
MAGNA3 (D) 80-80 F 66 3.3 6.6 4.62 7.92
MAGNA3 (D) 80-100 F 69 3.45 6.9 4.83 8.28
MAGNA3 (D) 80-120 F 74 3.7 7.4 5.18 8.88
MAGNA3 (D) 100-40 F 55 2.75 5.5 3.85 6.60
MAGNA3 (D) 100-60 F 63 3.15 6.3 4.41 7.56
MAGNA3 (D) 100-80 F 73 3.65 7.3 5.11 8.76
MAGNA3 (D) 100-100 F 79 3.95 7.9 5.53 9.48
MAGNA3 (D) 100-120 F 85 4.25 8.5 5.95 10.20

8.12 "Description of control mode" 8.14 Wireless GENIair


This menu describes the possible control modes. The pump is designed for multipump connection via the wireless
GENIair connection. The built-in wireless GENIair module
8.13 "Assisted fault advice" enables communication between pumps and with Grundfos GO
This menu gives guidance and corrective actions in case of pump without the use of add-on modules:
failures. Multipump function.
See section 9. Servicing the product.
Grundfos GO.
See section 11.1 Grundfos GO.

42
9. Servicing the product

English (GB)
Before dismantling

WARNING
Electric shock
Death or serious personal injury.
- Make sure that other pumps or sources do not
force flow through the pump even if the pump is
stopped. This will cause the motor to act like a
generator, resulting in voltage on the pump.

WARNING
Electric shock
Death or serious personal injury.
- Switch off the power supply for at least 3 minutes
before you start any work on the product.
- Lock the main switch in position 0. Type and
requirements as specified in EN 60204-1, 5.3.2.

9.1 Differential-pressure and temperature sensor


The pump incorporates a differential-pressure and temperature
sensor. The sensor is located in the pump housing in a channel
between the inlet and outlet ports. The sensors of twin-head
pumps are connected to the same channel and the pumps
therefore register the same differential pressure and temperature.
Via a cable, the sensor sends an electrical signal for the
differential pressure across the pump and for the liquid
temperature to the controller in the control box.
If the sensor fails, the pump continues using the last
measurement from the sensor and operate based on this. In
earlier software versions, model A, the pump runs at maximum
speed in case of a sensor fault.
When the fault has been corrected, the pump continues operating
according to the parameters set.
The differential-pressure and temperature sensor offers
substantial benefits:
direct feedback on the pump display
complete pump control
measurement of the pump load for precise and optimum
control resulting in higher energy efficiency.

9.2 External sensor condition


In case of missing sensor signal:
Pumps produced before week 4, 2016: The pump runs at
maximum speed.
Pumps produced after week 4, 2016: The pump runs at 50 %
of the nominal speed.

43
10. Fault finding the product
English (GB)

10.1 Grundfos Eye operating indications

Grundfos Eye Indication Cause

The power is off.


No lights are on.
The pump is not running.

Two opposite green indicator lights running in the The power is on.
direction of rotation of the pump. The pump is running.

Two opposite green indicator lights are The power is on.


permanently on. The pump is not running.

One yellow indicator light running in the direction Warning.


of rotation of the pump. The pump is running.

Warning.
One yellow indicator light is permanently on.
The pump has stopped.

Two opposite red indicator lights flashing Alarm.


simultaneously. The pump has stopped.

Remote-controlled.
One green indicator light in the middle is
The pump is currently being accessed by
permanently on in addition to another indication.
Grundfos GO.

Signals from Grundfos Eye


The operating condition of the pump is indicated by Grundfos Eye
on the control panel when it communicates with a remote control.

Indication Description Grundfos Eye


The green indicator light in the This is a feedback signal which the pump gives in
middle flashes quickly four times. order to ensure identification of itself.
Grundfos GO or another pump is trying to
The green indicator light in the
communicate with the pump. Press [OK] on the pump
middle flashes continuously.
control panel to allow communication.
Remote control with Grundfos GO via radio. The
The green indicator light in the
pump is communicating with Grundfos GO via radio
middle is permanently on.
connection.

44
10.2 Fault finding

English (GB)
Reset a fault indication in one of the following ways:
When you have eliminated the fault cause, the pump reverts to
normal duty.
If the fault disappears by itself, the fault indication is
automatically reset.
The fault cause is stored in the pump alarm log.

CAUTION
Pressurised system
Minor or moderate personal injury
- Before dismantling the pump, drain the system or
close the isolating valve on either side of the
pump. The pumped liquid may be scalding hot and
under high pressure

If the power supply cable is damaged, it must be


replaced by the manufacturer, the manufacturer's
service partner or a similarly qualified person.

WARNING
Electric shock
Death or serious personal injury.
- Switch off the power supply for at least 3 minutes
before you start any work on the product. Lock the
main switch in position 0. Type and requirements
as specified in EN 60204-1, 5.3.2.

WARNING
Electric shock
Death or serious personal injury.
- Make sure that other pumps or sources do not
force flow through the pump even if the pump is
stopped.

45
Automatic reset
English (GB)

Warning and alarm codes Fault Corrective actions


and restart
"Pump communication fault" Communication fault between Replace the pump, or contact Grundfos Service.
(10) different parts of the Yes Check if the pump is running in turbine
"Alarm" electronics. operation. See code (29) "Forced pumping".
Switch off the pump on the main switch. If the
light in Grundfos Eye is on, the pump is running
Other pumps or sources force
in forced-pumping mode.
"Forced pumping" (29) flow through the pump even if
Yes Check the system for defective non-return
"Alarm" the pump is stopped and
valves and replace the valves, if necessary.
switched off.
Check the system for correct position of
non-return valves, etc.
"Undervoltage" (40, 75) The supply voltage to the pump Make sure that the power supply is within the
Yes
"Alarm" is too low. specified range.
Dismantle the pump, and remove any foreign
"Blocked pump" (51)
The pump is blocked. Yes matter or impurities preventing the pump from
"Alarm"
rotating.
Prime and vent the pump before a new startup.
"Dry running" (57) No water at the pump inlet or Check that the pump is operating correctly. If
No
"Alarm" the water contains too much air. not, replace the pump, or contact Grundfos
Service.
"High motor temperature" (64) The temperature in the stator
No Replace the pump, or contact Grundfos Service.
"Alarm" windings is too high.
There might be turbine flow in the application
Internal fault in the pump
that forces a flow through the pump.
"Internal fault" (72 and 155) electronics.
Yes Check if the sensor is blocked by sediments.
"Alarm" Irregularities in the voltage
This can occur if the media is impure.
supply can cause alarm 72.
Replace the pump, or contact Grundfos Service.
Check if turbine operation is present in the
"Internal fault" (84 and 157)
Fault in the pump electronics. - application.
"Warning"
Replace the pump, or contact Grundfos Service.
"Overvoltage" (74) The supply voltage to the pump Make sure that the power supply is within the
Yes
"Alarm" is too high. specified range.
"Communication fault, twin-head The communication between
Make sure that the second pump head is
pump" (77) pump heads was disturbed or -
powered on or connected to the power supply.
"Warning" broken.
Make sure that the plug and cable are
The pump is receiving a signal connected correctly in the sensor. The sensor is
"Internal sensor fault" (88)
from the internal sensor which - located on the back of the pump housing.
"Warning"
is outside the normal range. Replace the sensor, or contact Grundfos
Service.
Does the electrical signal set (0-10 V or 4-20
mA) match the sensor output signal?
If not, change the setting of the analog input, or
replace the sensor with one that matches the
setup.
Check the sensor cable for damage.
The pump is receiving a signal
"External sensor fault" (93) Check the cable connection at the pump and at
from the external sensor which -
"Warning" the sensor. Correct the connection, if required.
is outside the normal range.
See section 9.1 Differential-pressure and
temperature sensor.
The sensor has been removed, but the analog
input has not been disabled.
Replace the sensor, or contact Grundfos
Service.

Warnings do not activate the alarm relay.

46
11. Accessories 11.2 Communication interface module, CIM

English (GB)
The pump can communicate via the wireless GENIair connection
or a communication module.
This enables the pump to communicate with other pumps and
with different types of network solutions.
The Grundfos communication interface modules enable the pump
to connect to standard fieldbus networks.
11.1 Grundfos GO
The pump is designed for wireless radio or infrared
communication with Grundfos GO. Grundfos GO enables setting
of functions and gives access to status overviews, technical
product information and actual operating parameters.

The radio communication between the pump and

TM05 2710 0612


Grundfos GO is encrypted to protect against misuse.

Grundfos GO is available in Apple App Store and Google Play.


Grundfos GO replaces the Grundfos R100 remote control. This
means that all products supported by R100 are now supported by Fig. 61 Building management system, BMS, with four pumps
Grundfos GO. connected in parallel
You can use Grundfos GO for the following:
A communication interface module is an add-on communication
Reading of operating data. interface module.
Reading of warning and alarm indications. The communication interface module enables data transmission
Setting of control mode. between the pump and an external system, for example a
Setting of setpoint. building management system or SCADA system.
Selection of external setpoint signal. The communication interface module communicates via fieldbus
Allocation of pump number to distinguish between pumps that protocols.
are connected via GENIbus.
Selection of function for digital input. A gateway is a device that facilitates the transfer of
Generation of reports in PDF. data between two different networks based on
different communication protocols.
Assist function.
Multipump setup. The following communication interface modules are available:
Display of relevant documentation.
For function and connection to the pump, see separate Module Fieldbus protocol Product number
installation and operating instructions for the desired type of CIM 050 GENIbus 96824631
Grundfos GO setup.
CIM 100 LonWorks 96824797
CIM 150 PROFIBUS DP 96824793
CIM 200 Modbus RTU 96824796
CIM 250 GSM/GPRS 96824795
CIM 270 GRM 96898815
CIM 300 BACnet MS/TP 96893770
CIM 500 Ethernet 98301408

47
11.2.1 Description of communication interface modules
English (GB)

Fieldbus
Module Description Functions
protocol

CIM 050

CIM 050 is a Grundfos communication


interface module used for CIM 050 has terminals for the GENIbus
GENIbus
communication with a GENIbus connection.
TM06 7238 3416 network.

CIM 100
CIM 100 has terminals for the LonWorks
connection.
CIM 100 is a Grundfos communication Two LEDs are used to indicate the actual
interface module used for status of the CIM 100 communication.
LonWorks
communication with a LonWorks One LED is used for indication of correct
TM06 7279 3416

network. connection to the pump, and the other is


used to indicate LonWorks communication
status.

CIM 150 has terminals for the PROFIBUS


CIM 150
DP connection.
DIP switches are used to set line
termination.
CIM 150 is a Grundfos communication Two hexadecimal rotary switches are used
interface module used for to set the PROFIBUS DP address.
PROFIBUS DP
communication with a PROFIBUS Two LEDs are used to indicate the actual
network. status of the CIM 150 communication.
TM06 7280 3416

One LED is used for indication of correct


connection to the pump, and the other is
used to indicate PROFIBUS communication
status.
CIM 200 has terminals for the Modbus
CIM 200 connection.
DIP switches are used to select parity and
stop bits, to select transmission speed and
to set line termination.
CIM 200 is a Grundfos communication
Two hexadecimal rotary switches are used
interface module used for
Modbus RTU to set the Modbus address.
communication with a Modbus RTU
Two LEDs are used to indicate the actual
network.
status of the CIM 200 communication.
TM06 7281 3416

One LED is used for indication of correct


connection to the pump, and the other is
used to indicate Modbus communication
status.
CIM 250 has a SIM-card slot and an SMA
connection to the GSM antenna.
The CIM 250 also has an internal backup
CIM 250 battery. Two LEDs are used to indicate the
actual status of the CIM 250
communication. One LED is used for
CIM 250 is a Grundfos communication
indication of correct connection to the pump,
interface module used for GSM or
and the other is used to indicate
GSM/GPRS GPRS communication.
GSM/GPRS communication status.
CIM 250 is used to communicate via a
Note: The SIM card is not supplied with the
GSM network.
CIM 250. The SIM card from the service
provider must support data/fax service to
TM06 7282 3416

use call service from PC Tool or SCADA.


The SIM card from the service provider
must support GPRS service to use ethernet
service from PC Tool or SCADA.

48
Fieldbus

English (GB)
Module Description Functions
protocol

CIM 270 With CIM 270 you have wireless access to


your account anywhere, anytime when you
have an internet connection, for example via
CIM 270 is a Grundfos GSM or GPRS
a smartphone, tablet PC, laptop or
modem used for communication with a
computer. Warnings and alarms can be sent
Grundfos Remote Grundfos Remote Management
by e-mail or SMS to your mobile phone or
Management system.
computer. You will get a complete status

TM06 7282 3416


It requires a GSM antenna, a SIM card
overview of the entire Grundfos Remote
and a contract with Grundfos.
Management system. It allows you to plan
maintenance and service based on actual
operating data.
CIM 300 has terminals for the BACnet
CIM 300 MS/TP connection.
DIP switches are used to set transmission
speed and line termination and to select the
custom Device Object Instance Number.
CIM 300 is a Grundfos communication
Two hexadecimal rotary switches are used
interface module used for
BACnet MS/TP to set the BACnet address.
communication with a BACnet MS/TP
Two LEDs are used to indicate the actual
network.
status of the CIM 300 communication.
TM06 7281 3416

One LED is used for indication of correct


connection to the pump, and the other is
used to indicate BACnet communication
status.
CIM 500 CIM 500 is a Grundfos communication
interface module used for data
transmission between an industrial CIM 500 supports various industrial ethernet
ethernet network and a Grundfos protocols. CIM 500 is configured via the
product. built-in web server, using a standard web
Ethernet CIM 500 supports various industrial browser on a PC.
ethernet protocols: See the specific functional profile on the
TM06 7283 3416

PROFINET DVD-ROM supplied with the Grundfos CIM


Modbus TCP module.
BACnet/IP
EtherNet/IP

49
11.2.2 Installing a communication interface module
English (GB)

WARNING WARNING
Electric shock Electric shock
Death or serious personal injury. Death or serious personal injury.
- Make sure that other pumps or sources do not - Switch off the power supply for at least 3 minutes
force flow through the pump even if the pump is before you start any work on the product. Make
stopped. This will cause the motor to act like a sure that the power supply cannot be accidentally
generator, resulting in voltage on the pump. switched on.
- It must be possible to lock the main switch in
position 0. Type and requirements as specified in
EN 60204-1, 5.3.2.

Step Action Illustration

Terminal-connected versions:
1
Remove the front cover from the control box.

TM05 2875 3416


Plug-connected versions:
2
Open the front cover.

TM05 8458 3416


3 Unscrew the earth connection.

TM06 6907 3416

Fit the communication interface module as illustrated and


4
click it on.
TM05 2914 3416

50
Step Action Illustration

English (GB)
Tighten the screw holding the communication interface
5
module and secure the earth connection.

TM05 2912 3416


For connection to fieldbus networks, see the installation
6 and operating instructions for the desired communication
interface module.

TM05 2913 3416


11.2.3 Grundfos Remote Management 11.2.4 Reuse of communication interface modules
Grundfos Remote Management is an easy-to-install, low-cost You can reuse a communication interface module in a CIU unit
solution for wireless monitoring and management of Grundfos used together with Grundfos MAGNA Series 2000 in MAGNA3.
products. It is based on a centrally hosted database and a web Before you use the CIM module in the pump, reconfigure the
server with wireless data collection via GSM or GPRS modem. module. Contact your nearest Grundfos company.
The system only requires an internet connection, a web browser,
a Grundfos Remote Management modem and an antenna as well
as a contract with Grundfos allowing you to monitor and manage
Grundfos pump systems.

TM05 2911 1312


You have wireless access to your account anywhere, anytime
when you have an internet connection, for example via a mobile
device. Warnings and alarms can be sent by email or SMS to
your mobile device.

Product Fig. 62 Reuse of communication interface module


Application Description
number
Grundfos Remote Management
CIM 270 Requires a contract with 96898815
Grundfos and a SIM card.
Antenna for use on top of metal
cabinets.
GSM antenna for
Vandal-proof. 97631956
roof-mounting
2-metre cable.
Quad band for global use.
Antenna for general-purpose
application, for example inside
plastic cabinets.
GSM antenna for
To be fixed with the 97631957
desk-mounting
double-adhesive tape supplied.
4-metre cable.
Quad band for global use.

For Grundfos Remote Management contract, contact your local


Grundfos company.

51
11.3 Counterflanges
English (GB)

Counterflange kits consist of two flanges, two gaskets and bolts


and nuts, making it possible to install the pump in any pipework.
See MAGNA3 data booklet, Accessories section, for the right
dimension and product number.

11.4 External sensors


11.4.1 Temperature sensor

Measuring Measuring Transmitter


Power supply Process Product
Sensor Type range range output
[VDC] connection number
[bar] [C] [mA]
Combined pressure and
RPI T2 0-16 -10 to +120 4-20 0-10 G 1/2 98355521
temperature sensor
11.4.2 Pressure sensor

Measuring
Sensor output Power supply Product
Sensor Type Supplier range Process connection
[mA] [VDC] number
[bar]
0 - 0.6 97748907
0 - 1.0 97748908
0 - 1.6 97748909
0 - 2.5 97748910
Pressure sensor RPI Grundfos 4-20 12-30 G 1/2
0 - 4.0 97748921
0 - 6.0 97748922
0-12 97748923
0-16 97748924

11.5 Cable for sensors

Length
Description Product number
[m]
Screened cable 2.0 98374260
Screened cable 5.0 98374271

52
11.6 Blanking flange 12. Technical data

English (GB)
A blanking flange is used to blank off the opening when one of the Supply voltage
pump heads of a twin-head pump is removed for service to 1 x 230 V 10 %, 50/60 Hz, PE.
enable uninterrupted operation of the other pump. See fig. 63.
Motor protection
The pump requires no external motor protection.
Enclosure class
IPX4D (EN 60529).
Insulation class
F.
Relative air humidity
Maximum 95 %.
Ambient temperature
0 to +40 C.
During transport: -40 to +70 C.

TM05 5994 4312


Temperature class
TF110 (EN 60335-2-51).
Liquid temperature
Continuously: -10 to +110 C.
Fig. 63 Position of blanking flange Stainless-steel pumps in domestic hot-water systems:
In domestic hot-water systems, we recommend that you keep the
Pump type Product number liquid temperature below 65 C to eliminate the risk of lime
precipitation.
MAGNA3 32-40/60/80/100 (F)
98159373 System pressure
MAGNA3 40-40/60 F
MAGNA3 32-120 F
MAGNA3 40-/80/100/120/150/180 F The actual inlet pressure and the pump pressure
MAGNA3 50-40/60/80/100/120/150/180 F against a closed valve must be lower than the
98159372 maximum permissible system pressure.
MAGNA3 65-40/60/80/100/120/150 F
MAGNA3 80-40/60/80/100/120 F
MAGNA3 100-40/60/80/100/120 F The maximum permissible system pressure is stated on the pump
nameplate:
11.7 Insulating kits for air-conditioning and cooling PN 6: 6 bar / 0.6 MPa
systems PN 10: 10 bar / 1.0 MPa
You can fit single-head pumps for air-conditioning and cooling PN 16: 16 bar / 1.6 MPa.
systems with insulating shells. A kit consists of two shells made Test pressure
of polyurethane and a self-adhesive seal to ensure tight
The pumps can withstand test pressures as indicated in EN
assembly.
60335-2-51. See below.
The dimensions of the insulating shells for pumps in
PN 6: 7.2 bar
air-conditioning and cooling systems differ from those of the
insulating shells for pumps in heating systems. PN 10: 12 bar
PN 6/10: 12 bar
Pump type Product number PN 16: 19.2 bar.
MAGNA3 25-40/60/80/100/120 (N) 98354534 During normal operation, do not use the pump at higher
pressures than those stated on the nameplate.
MAGNA3 32-40/60/80/100/120 (N) 98354535
The pressure test has been made with water containing
MAGNA3 32-40/60/80/100 F (N) 98354536
anticorrosive additives at a temperature of 20 C.
MAGNA3 32-120 F (N) 98063287
MAGNA3 40-40/60 F (N) 98354537
MAGNA3 40-80/100 F (N) 98063288
MAGNA3 40-120/150/180 F (N) 98145675
MAGNA3 50-40/60/80 F (N) 98063289
MAGNA3 50-100/120/150/180 F (N) 98145676
MAGNA3 65-40/60/80/100/120/150 F (N) 96913593
MAGNA3 80-40/60/80/100/120 F 98134265
MAGNA3 100-40/60/80/100/120 F 96913589

Insulating shells for single-head pumps for heating systems are


supplied with the pump.

53
Minimum inlet pressure Power factor
English (GB)

The following relative minimum inlet pressure must be available The terminal-connected versions have built-in an active power
at the pump inlet during operation to avoid cavitation noise and factor correction which gives a cos from 0.98 to 0.99.
damage to the pump bearings. The plug-connected versions have built-in passive PFC, with coil
and resistors which ensures that the current drawn from the grid
The values in the table below apply to single-head is in phase with the voltage. The current is approximately
pumps and twin-head pumps in single-head sinusoidal which gives a cos from 0.55 to 0.98.
operation.
12.1 Sensor specifications
12.1.1 Temperature
Liquid temperature

MAGNA3 75 C 95 C 110 C Temperature range during operation Accuracy


DN -10 to +35 C 4 C
Inlet pressure
[bar] / [MPa] +35 to +90 C 2 C
25-40/60/80/100/100 0.10 / 0.01 0.35 / 0.04 1.0 / 0.10 +90 to +110 C 4 C
32-40/60/80/100/120 0.10 / 0.01 0.35 / 0.04 1.0 / 0.10
13. Disposing of the product
32-120 F 0.10 / 0.01 0.50 / 0.05 1.1 / 0.11
This product has been designed with focus on the disposal and
40-40/60 F 0.10 / 0.01 0.35 / 0.04 1.0 / 0.10
recycling of materials. The following average disposal values
40-80/100 F 0.10 / 0.01 0.50 / 0.05 1.1 / 0.11 apply to all variants of pumps:
40-120/150/180 F 0.10 / 0.01 0.40 / 0.04 1.0 / 0.10 85 % recycling
50-40/60/80 F 0.10 / 0.01 0.10 / 0.01 0.7 / 0.07 10 % incineration
50-100 F 0.10 / 0.01 0.50 / 0.05 1.1 / 0.11 5 % depositing.
50-120 F 0.10 / 0.01 0.40 / 0.04 1.0 / 0.10 Dispose of this product or parts of it in an environmentally sound
way according to local regulations.
50-150/180 F 0.20 / 0.02 0.60 / 0.06 1.2 / 0.12
For further information see the end-of-life information on
65-40/60/80/100 F 0.20 / 0.02 0.60 / 0.06 1.2 / 0.12 www.Grundfos.com.
65-120 F 0.10 / 0.01 0.50 / 0.05 1.1 / 0.11
65-150 F 0.40 / 0.04 0.80 / 0.08 1.2 / 0.12
80-40/60/80/100/120 F 0.50 / 0.05 0.90 / 0.09 1.5 / 0.15 Subject to alterations.

100-40/60/80/100/120 F 0.50 / 0.05 0.90 / 0.09 1.5 / 0.15


In the case of cascade operation, the required relative inlet
pressure must be increased by 0.1 bar / 0.01 MPa compared to
the stated values for single-head pumps or twin-head pumps in
single-head operation.
The relative minimum inlet pressures apply to pumps installed up
to 300 metres above sea level. For altitudes above 300 metres,
the required relative inlet pressure must be increased by 0.01 bar
/ 0.001 MPa per 100 metres altitude. The MAGNA3 pump is only
approved for an altitude of 2000 metres above sea level.
Sound pressure level
The sound pressure level of the pump is lower than 43 dB(A).
Leakage current
The mains filter will cause a leakage current to earth during
operation. The leakage current is less than 3.5 mA.
Consumption when the pump is stopped
4 to 10 W, depending on activity, such as reading the display, use
of Grundfos GO, interaction with modules.
4 W when the pump is stopped and there is no activity.
Input and output communication

External potential-free contact.


Contact load: 5 V, 10 mA.
Two digital inputs
Screened cable.
Loop resistance: Maximum 130 .
4-20 mA, load: 150 .
Analog input
0-10 VDC, load: Greater than 10 k.
Internal potential-free changeover contact.
Maximum load: 250 V, 2 A, AC1.
Two relay outputs
Minimum load: 5 VDC, 20 mA.
Screened cable, depending on signal level.
Maximum load: 22 mA
24 VDC supply
Capacitive load: Less than 470 F

54
Appendix 1

Appendix
Dimensions

TM05 7938 2013


Fig. 1 Dimensions, single-head pumps, threaded versions

Dimensions [mm]
Pump type
L1 L5 L6 B1 B2 B4 B6 B7 H1 H2 H3 H4 D1 G
MAGNA3 25-40 (N) 180 158 190 58 111 69 90 113 54 185 239 71 25 1 1/2
MAGNA3 25-60 (N) 180 158 190 58 111 69 90 113 54 185 239 71 25 1 1/2
MAGNA3 25-80 (N) 180 158 190 58 111 69 90 113 54 185 239 71 25 1 1/2
MAGNA3 25-100 (N) 180 158 190 58 111 69 90 113 54 185 239 71 25 1 1/2
MAGNA3 25-120 (N) 180 158 190 58 111 69 90 113 54 185 239 71 25 1 1/2
MAGNA3 32-40 (N) 180 158 190 58 111 69 90 113 54 185 239 71 32 2
MAGNA3 32-60 (N) 180 158 190 58 111 69 90 113 54 185 239 71 32 2
MAGNA3 32-80 (N) 180 158 190 58 111 69 90 113 54 185 239 71 32 2
MAGNA3 32-100 (N) 180 158 190 58 111 69 90 113 54 185 239 71 32 2
MAGNA3 32-120 (N) 180 158 190 58 111 69 90 113 54 185 239 71 32 2

TM05 7938 2013


Fig. 2 Dimensions, single-head pumps, flanged versions

Dimensions [mm]
Pump type
L1 L5 L6 B1 B2 B4 B6 B7 H1 H2 H3 H4 D1 D2 D3 D4 D5
MAGNA3 32-40 F (N) 220 158 220 58 111 69 100 110 65 185 250 82 32 76 90/100 140 14/19
MAGNA3 32-60 F (N) 220 158 220 58 111 69 100 110 65 185 250 82 32 76 90/100 140 14/19
MAGNA3 32-80 F (N) 220 158 220 58 111 69 100 110 65 185 250 82 32 76 90/100 140 14/19
MAGNA3 32-100 F (N) 220 158 220 58 111 69 100 110 65 185 250 82 32 76 90/100 140 14/19
MAGNA3 40-40 F (N) 220 158 220 58 111 69 105 105 65 199 264 83 40 84 100/110 150 14/19
MAGNA3 40-60 F (N) 220 158 220 58 111 69 105 105 65 199 264 83 40 84 100/110 150 14/19

55
Appendix

TM05 5291 2013


Fig. 3 Dimensions, single-head pumps, flanged versions

Dimensions [mm]
Pump type
L1 L5 B1 B2 B4 B6 B7 H1 H2 H3 H4 D1 D2 D3 D4 D5
MAGNA3 32-120 F (N) 220 204 84 164 73 106 116 65 301 366 86 32 76 90/100 140 14/19
MAGNA3 40-80 F (N) 220 204 84 164 73 106 128 65 304 369 83 40 84 100/110 150 14/19
MAGNA3 40-100 F (N) 220 204 84 164 73 106 128 65 304 369 83 40 84 100/110 150 14/19
MAGNA3 40-120 F (N) 250 204 84 164 73 106 128 65 304 369 83 40 84 100/110 150 14/19
MAGNA3 40-150 F (N) 250 204 84 164 73 106 128 65 304 369 83 40 84 100/110 150 14/19
MAGNA3 40-180 F (N) 250 204 84 164 73 106 128 65 304 369 83 40 84 100/110 150 14/19
MAGNA3 50-40 F (N) 240 204 84 164 73 127 127 71 304 374 97 50 102 110/125 165 14/19
MAGNA3 50-60 F (N) 240 204 84 164 73 127 127 71 304 374 97 50 102 110/125 165 14/19
MAGNA3 50-80 F (N) 240 204 84 164 73 127 127 71 304 374 97 50 102 110/125 165 14/19
MAGNA3 50-100 F (N) 280 204 84 164 73 127 127 72 304 376 97 50 102 110/125 165 14/19
MAGNA3 50-120 F (N) 280 204 84 164 73 127 127 72 304 376 97 50 102 110/125 165 14/19
MAGNA3 50-150 F (N) 280 204 84 164 73 127 127 72 304 376 97 50 102 110/125 165 14/19
MAGNA3 50-180 F (N) 280 204 84 164 73 127 127 72 304 376 97 50 102 110/125 165 14/19
MAGNA3 65-40 F (N) 340 204 84 164 73 133 133 74 312 386 94 65 119 130/145 185 14/19
MAGNA3 65-60 F (N) 340 204 84 164 73 133 133 74 312 386 94 65 119 130/145 185 14/19
MAGNA3 65-80 F (N) 340 204 84 164 73 133 133 74 312 386 94 65 119 130/145 185 14/19
MAGNA3 65-100 F (N) 340 204 84 164 73 133 133 74 312 386 94 65 119 130/145 185 14/19
MAGNA3 65-120 F (N) 340 204 84 164 73 133 133 74 312 386 94 65 119 130/145 185 14/19
MAGNA3 65-150 F (N) 340 204 84 164 73 133 133 74 312 386 94 65 119 130/145 185 14/19
MAGNA3 80-40 F 360 204 84 164 73 163 163 96 318 413 115 80 128 150/160 200 19
MAGNA3 80-60 F 360 204 84 164 73 163 163 96 318 413 115 80 128 150/160 200 19
MAGNA3 80-80 F 360 204 84 164 73 163 163 96 318 413 115 80 128 150/160 200 19
MAGNA3 80-100 F 360 204 84 164 73 163 163 96 318 413 115 80 128 150/160 200 19
MAGNA3 80-120 F 360 204 84 164 73 163 163 96 318 413 115 80 128 150/160 200 19
MAGNA3 100-40 F 450 204 84 164 73 178 178 103 330 433 120 100 160 170 220 19
MAGNA3 100-60 F 450 204 84 164 73 178 178 103 330 433 120 100 160 170 220 19
MAGNA3 100-80 F 450 204 84 164 73 178 178 103 330 433 120 100 160 170 220 19
MAGNA3 100-100 F 450 204 84 164 73 178 178 103 330 433 120 100 160 170 220 19
MAGNA3 100-120 F 450 204 84 164 73 178 178 103 330 433 120 100 160 170 220 19

56
Appendix
TM05 7939 2013
Fig. 4 Dimensions, twin-head pumps, threaded versions

Dimensions [mm]
Pump type
L1 L5 L7 B1 B3 B4 B5 H1 H2 H3 D1 G M3
MAGNA3 D 32-40 180 158 35 58 400 179 221 54 185 239 32 2 1/4
MAGNA3 D 32-60 180 158 35 58 400 179 221 54 185 239 32 2 1/4
MAGNA3 D 32-80 180 158 35 58 400 179 221 54 185 239 32 2 1/4
MAGNA3 D 32-100 180 158 35 58 400 179 221 54 185 239 32 2 1/4

TM05 5294 3612


Fig. 5 Dimensions, twin-head pumps, flanged versions

Dimensions [mm]
Pump type
L1 L2 L3 L4 L5 L7 B1 B3 B4 B5 B6 B7 H1 H2 H3 D1 D2 D3 D4 D5 M M3
MAGNA3 D 32-40 F 220 73 120 85 158 35 58 400 179 221 130 260 69 185 254 32 76 90/100 140 14/19 M12 Rp 1/4
MAGNA3 D 32-60 F 220 73 120 85 158 35 58 400 179 221 130 260 69 185 254 32 76 90/100 140 14/19 M12 Rp 1/4
MAGNA3 D 32-80 F 220 73 120 85 158 35 58 400 179 221 130 260 69 185 254 32 76 90/100 140 14/19 M12 Rp 1/4
MAGNA3 D 32-100 F 220 73 120 85 158 35 58 400 179 221 130 260 69 185 254 32 76 90/100 140 14/19 M12 Rp 1/4
MAGNA3 D 32-120 F 220 97 90 50 204 50 84 502 210 294 130 260 68 300 368 32 76 90/100 140 14/19 M12 Rp 1/4
MAGNA3 D 40-40 F 220 53 140 60 158 15 58 452 211 241 130 260 76 199 275 40 84 100/110 150 14/19 M12 Rp1/4
MAGNA3 D 40-60 F 220 53 140 60 158 15 58 452 211 241 130 260 76 199 275 40 84 100/110 150 14/19 M12 Rp1/4
MAGNA3 D 40-80 F 220 53 140 60 204 15 84 502 210 294 130 260 76 303 379 40 84 100/110 150 14/19 M12 Rp 1/4
MAGNA3 D 40-100 F 220 53 140 60 204 15 84 502 210 294 130 260 76 303 379 40 84 100/110 150 14/19 M12 Rp 1/4
MAGNA3 D 50-40 F 240 48 160 45 204 45 84 515 221 294 130 260 75 304 379 50 102 110/125 165 14/19 M12 Rp 1/4
MAGNA3 D 50-60 F 240 48 160 45 204 45 84 515 221 294 130 260 75 304 379 50 102 110/125 165 14/19 M12 Rp 1/4
MAGNA3 D 50-80 F 240 48 160 45 204 45 84 515 221 294 130 260 75 304 379 50 102 110/125 165 14/19 M12 Rp 1/4

57
Appendix

TM05 5366 2013


Fig. 6 Dimensions, twin-head pumps

Dimensions [mm]
Pump type
L1 L2 L3 L4 L5 B1 B3 B4 B5 B6 B7 H1 H2 H3 D1 D2 D3 D4 D5 M M3
MAGNA3 D 40-120 F 250 58 155 75 204 84 512 220 294 130 260 69 303 372 40 84 100/110 150 14/19 M12 Rp 1/4
MAGNA3 D 40-150 F 250 58 155 75 204 84 512 220 294 130 260 69 303 372 40 84 100/110 150 14/19 M12 Rp 1/4
MAGNA3 D 40-180 F 250 58 155 75 204 84 512 220 294 130 260 69 303 372 40 84 100/110 150 14/19 M12 Rp 1/4
MAGNA3 D 50-100 F 280 175 75 75 204 84 517 223 294 130 260 75 304 379 50 102 110/125 165 14/19 M12 Rp 1/4
MAGNA3 D 50-120 F 280 175 75 75 204 84 517 223 294 130 260 75 304 379 50 102 110/125 165 14/19 M12 Rp 1/4
MAGNA3 D 50-150 F 280 175 75 75 204 84 517 223 294 130 260 75 304 379 50 102 110/125 165 14/19 M12 Rp 1/4
MAGNA3 D 50-180 F 280 175 75 75 204 84 517 223 294 130 260 75 304 379 50 102 110/125 165 14/19 M12 Rp 1/4
MAGNA3 D 65-40 F 340 218 92 92 204 84 522 228 294 130 260 77 312 389 65 119 130/145 185 14/19 M12 Rp 1/4
MAGNA3 D 65-60 F 340 218 92 92 204 84 522 228 294 130 260 77 312 389 65 119 130/145 185 14/19 M12 Rp 1/4
MAGNA3 D 65-80 F 340 218 92 92 204 84 522 228 294 130 260 77 312 389 65 119 130/145 185 14/19 M12 Rp 1/4
MAGNA3 D 65-100 F 340 218 92 92 204 84 522 228 294 130 260 77 312 389 65 119 130/145 185 14/19 M12 Rp 1/4
MAGNA3 D 65-120 F 340 218 92 92 204 84 522 228 294 130 260 77 312 389 65 119 130/145 185 14/19 M12 Rp 1/4
MAGNA3 D 65-150 F 340 218 92 92 204 84 522 228 294 130 260 77 312 389 65 119 130/145 185 14/19 M12 Rp 1/4
MAGNA3 D 80-40 F 360 218 102 102 204 84 538 244 294 130 260 97 318 415 80 128 150/160 200 19 M12 Rp 1/4
MAGNA3 D 80-60 F 360 218 102 102 204 84 538 244 294 130 260 97 318 415 80 128 150/160 200 19 M12 Rp 1/4
MAGNA3 D 80-80 F 360 218 102 102 204 84 538 244 294 130 260 97 318 415 80 128 150/160 200 19 M12 Rp 1/4
MAGNA3 D 80-100 F 360 218 102 102 204 84 538 244 294 130 260 97 318 415 80 128 150/160 200 19 M12 Rp 1/4
MAGNA3 D 80-120 F 360 218 102 102 204 84 538 244 294 130 260 97 318 415 80 128 150/160 200 19 M12 Rp 1/4
MAGNA3 D 100-40 F 450 243 147 147 204 84 551 252 299 135 270 103 330 434 100 160 170 220 19 M12 Rp 1/4
MAGNA3 D 100-60 F 450 243 147 147 204 84 551 252 299 135 270 103 330 434 100 160 170 220 19 M12 Rp 1/4
MAGNA3 D 100-80 F 450 243 147 147 204 84 551 252 299 135 270 103 330 434 100 160 170 220 19 M12 Rp 1/4
MAGNA3 D 100-100 F 450 243 147 147 204 84 551 252 299 135 270 103 330 434 100 160 170 220 19 M12 Rp 1/4
MAGNA3 D 100-120 F 450 243 147 147 204 84 551 252 299 135 270 103 330 434 100 160 170 220 19 M12 Rp 1/4

58
1. Flange forces and moments

Appendix
Maximum permissible forces and moments from the pipe connections acting on the pump flanges or threaded connections are indicated
in fig. 7.

TM05 5639 4012


Fig. 7 Forces and moments from the pipe connections acting on the pump flanges or threaded connections

Force Moment
[N] [Nm]

Diameter DN Fy Fz Fx Fb My Mz Mx Mb
25* 350 425 375 650 300 350 450 650
32* 425 525 450 825 375 425 550 800
40 500 625 550 975 450 525 650 950
50 675 825 750 1300 500 575 700 1025
65 850 1050 925 1650 550 600 750 1100
80 1025 1250 1125 1975 575 650 800 1175
100 1350 1675 1500 2625 625 725 875 1300

* The values also apply to pumps with threaded connection.


The above values apply to cast-iron versions. For stainless-steel versions, the values can be multiplied by two according to the
ISO 5199 standard.

2. Tightening torques for bolts


Recommended tightening torques for bolts used in flanged
connections:

Bolt dimension Torque


M12 27 Nm
M16 66 Nm

59
60
Argentina Denmark Latvia Slovenia

Grundfos companies
Bombas GRUNDFOS de Argentina S.A. GRUNDFOS DK A/S SIA GRUNDFOS Pumps Latvia GRUNDFOS LJUBLJANA, d.o.o.
Ruta Panamericana km. 37.500 Centro Martin Bachs Vej 3 Deglava biznesa centrs Leskokova 9e, 1122 Ljubljana
Industrial Garin DK-8850 Bjerringbro Augusta Deglava iel 60, LV-1035, Rga, Phone: +386 (0) 1 568 06 10
1619 Garn Pcia. de B.A. Tlf.: +45-87 50 50 50 Tlr.: + 371 714 9640, 7 149 641 Telefax: +386 (0)1 568 06 19
Phone: +54-3327 414 444 Telefax: +45-87 50 51 51 Fakss: + 371 914 9646 E-mail: [email protected]
Telefax: +54-3327 45 3190 E-mail: [email protected]
www.grundfos.com/DK Lithuania South Africa
Australia GRUNDFOS Pumps UAB GRUNDFOS (PTY) LTD
GRUNDFOS Pumps Pty. Ltd. Estonia Smolensko g. 6 Corner Mountjoy and George Allen Roads
P.O. Box 2040 GRUNDFOS Pumps Eesti O LT-03201 Vilnius Wilbart Ext. 2
Regency Park Peterburi tee 92G Tel: + 370 52 395 430 Bedfordview 2008
South Australia 5942 11415 Tallinn Fax: + 370 52 395 431 Phone: (+27) 11 579 4800
Phone: +61-8-8461-4611 Tel: + 372 606 1690 Fax: (+27) 11 455 6066
Telefax: +61-8-8340 0155 Fax: + 372 606 1691 Malaysia E-mail: [email protected]
GRUNDFOS Pumps Sdn. Bhd.
Austria Finland 7 Jalan Peguam U1/25 Spain
GRUNDFOS Pumpen Vertrieb Ges.m.b.H. OY GRUNDFOS Pumput AB Glenmarie Industrial Park Bombas GRUNDFOS Espaa S.A.
Grundfosstrae 2 Trukkikuja 1 40150 Shah Alam Camino de la Fuentecilla, s/n
A-5082 Grdig/Salzburg FI-01360 Vantaa Selangor E-28110 Algete (Madrid)
Tel.: +43-6246-883-0 Phone: +358-(0) 207 889 500 Phone: +60-3-5569 2922 Tel.: +34-91-848 8800
Telefax: +43-6246-883-30 Telefax: +60-3-5569 2866 Telefax: +34-91-628 0465
France
Belgium Pompes GRUNDFOS Distribution S.A. Mexico Sweden
N.V. GRUNDFOS Bellux S.A. Parc dActivits de Chesnes Bombas GRUNDFOS de Mxico S.A. de GRUNDFOS AB
Boomsesteenweg 81-83 57, rue de Malacombe C.V. Box 333 (Lunnagrdsgatan 6)
B-2630 Aartselaar F-38290 St. Quentin Fallavier (Lyon) Boulevard TLC No. 15 431 24 Mlndal
Tl.: +32-3-870 7300 Tl.: +33-4 74 82 15 15 Parque Industrial Stiva Aeropuerto Tel.: +46 31 332 23 000
Tlcopie: +32-3-870 7301 Tlcopie: +33-4 74 94 10 51 Apodaca, N.L. 66600 Telefax: +46 31 331 94 60
Phone: +52-81-8144 4000
Belarus Germany Telefax: +52-81-8144 4010 Switzerland
GRUNDFOS GMBH GRUNDFOS Pumpen AG
Schlterstr. 33 Netherlands Bruggacherstrasse 10
220125, 40699 Erkrath GRUNDFOS Netherlands CH-8117 Fllanden/ZH
. , 11, . 56, Tel.: +49-(0) 211 929 69-0 Veluwezoom 35 Tel.: +41-44-806 8111
Telefax: +49-(0) 211 929 69-3799 1326 AE Almere Telefax: +41-44-806 8115
.: +7 (375 17) 286 39 72/73 e-mail: [email protected] Postbus 22015
: +7 (375 17) 286 39 71 Service in Deutschland: 1302 CA ALMERE Taiwan
E-mail: [email protected] e-mail: [email protected] Tel.: +31-88-478 6336 GRUNDFOS Pumps (Taiwan) Ltd.
Telefax: +31-88-478 6332 7 Floor, 219 Min-Chuan Road
Bosnia and Herzegovina Greece E-mail: [email protected] Taichung, Taiwan, R.O.C.
GRUNDFOS Sarajevo GRUNDFOS Hellas A.E.B.E. Phone: +886-4-2305 0868
Zmaja od Bosne 7-7A, 20th km. Athinon-Markopoulou Av. New Zealand Telefax: +886-4-2305 0878
BH-71000 Sarajevo P.O. Box 71 GRUNDFOS Pumps NZ Ltd.
Phone: +387 33 592 480 GR-19002 Peania 17 Beatrice Tinsley Crescent Thailand
Telefax: +387 33 590 465 Phone: +0030-210-66 83 400 North Harbour Industrial Estate GRUNDFOS (Thailand) Ltd.
www.ba.grundfos.com Telefax: +0030-210-66 46 273 Albany, Auckland 92 Chaloem Phrakiat Rama 9 Road,
e-mail: [email protected] Phone: +64-9-415 3240 Dokmai, Pravej, Bangkok 10250
Hong Kong Telefax: +64-9-415 3250 Phone: +66-2-725 8999
Brazil GRUNDFOS Pumps (Hong Kong) Ltd. Telefax: +66-2-725 8998
BOMBAS GRUNDFOS DO BRASIL Unit 1, Ground floor Norway
Av. Humberto de Alencar Castelo Branco, Siu Wai Industrial Centre GRUNDFOS Pumper A/S Turkey
630 29-33 Wing Hong Street & Strmsveien 344 GRUNDFOS POMPA San. ve Tic. Ltd. Sti.
CEP 09850 - 300 68 King Lam Street, Cheung Sha Wan Postboks 235, Leirdal Gebze Organize Sanayi Blgesi
So Bernardo do Campo - SP Kowloon N-1011 Oslo Ihsan dede Caddesi,
Phone: +55-11 4393 5533 Phone: +852-27861706 / 27861741 Tlf.: +47-22 90 47 00 2. yol 200. Sokak No. 204
Telefax: +55-11 4343 5015 Telefax: +852-27858664 Telefax: +47-22 32 21 50 41490 Gebze/ Kocaeli
Phone: +90 - 262-679 7979
Bulgaria Hungary Poland Telefax: +90 - 262-679 7905
Grundfos Bulgaria EOOD GRUNDFOS Hungria Kft. GRUNDFOS Pompy Sp. z o.o. E-mail: [email protected]
Slatina District Park u. 8 ul. Klonowa 23
Iztochna Tangenta street no. 100 H-2045 Trkblint, Baranowo k. Poznania Ukraine
BG - 1592 Sofia Phone: +36-23 511 110 PL-62-081 Przemierowo
Tel. +359 2 49 22 200 Telefax: +36-23 511 111 Tel: (+48-61) 650 13 00 , 103
Fax. +359 2 49 22 201 Fax: (+48-61) 650 13 50 . , 03131,
email: [email protected] India : (+38 044) 237 04 00
GRUNDFOS Pumps India Private Limited Portugal .: (+38 044) 237 04 01
Canada 118 Old Mahabalipuram Road Bombas GRUNDFOS Portugal, S.A. E-mail: [email protected]
GRUNDFOS Canada Inc. Thoraipakkam Rua Calvet de Magalhes, 241
2941 Brighton Road Chennai 600 096 Apartado 1079 United Arab Emirates
Oakville, Ontario Phone: +91-44 2496 6800 P-2770-153 Pao de Arcos GRUNDFOS Gulf Distribution
L6H 6C9 Tel.: +351-21-440 76 00 P.O. Box 16768
Phone: +1-905 829 9533 Indonesia Telefax: +351-21-440 76 90 Jebel Ali Free Zone
Telefax: +1-905 829 9512 PT. GRUNDFOS POMPA Dubai
Graha Intirub Lt. 2 & 3 Romania Phone: +971 4 8815 166
China Jln. Cililitan Besar No.454. Makasar, GRUNDFOS Pompe Romnia SRL Telefax: +971 4 8815 136
GRUNDFOS Pumps (Shanghai) Co. Ltd. Jakarta Timur Bd. Biruintei, nr 103
10F The Hub, No. 33 Suhong Road ID-Jakarta 13650 Pantelimon county Ilfov United Kingdom
Minhang District Phone: +62 21-469-51900 Phone: +40 21 200 4100 GRUNDFOS Pumps Ltd.
Shanghai 201106 Telefax: +62 21-460 6910 / 460 6901 Telefax: +40 21 200 4101 Grovebury Road
PRC E-mail: [email protected] Leighton Buzzard/Beds. LU7 4TL
Phone: +86 21 612 252 22 Ireland Phone: +44-1525-850000
Telefax: +86 21 612 253 33 GRUNDFOS (Ireland) Ltd. Russia Telefax: +44-1525-850011
Unit A, Merrywell Business Park
COLOMBIA Ballymount Road Lower 109544, . , . , 39-41, U.S.A.
GRUNDFOS Colombia S.A.S. Dublin 12 . 1 GRUNDFOS Pumps Corporation
Km 1.5 va Siberia-Cota Conj. Potrero Phone: +353-1-4089 800 . (+7) 495 564-88-00 (495) 737-30-00 17100 West 118th Terrace
Chico, Telefax: +353-1-4089 830 (+7) 495 564 88 11 Olathe, Kansas 66061
Parque Empresarial Arcos de Cota Bod. E-mail [email protected] Phone: +1-913-227-3400
1A. Italy Telefax: +1-913-227-3500
Cota, Cundinamarca GRUNDFOS Pompe Italia S.r.l. Serbia
Via Gran Sasso 4 Grundfos Srbija d.o.o. Uzbekistan
Phone: +57(1)-2913444
I-20060 Truccazzano (Milano) Omladinskih brigada 90b Grundfos Tashkent, Uzbekistan The
Telefax: +57(1)-8764586
Tel.: +39-02-95838112 11070 Novi Beograd Representative Office of Grundfos
Croatia Telefax: +39-02-95309290 / 95838461 Phone: +381 11 2258 740 Kazakhstan in Uzbekistan
GRUNDFOS CROATIA d.o.o. Telefax: +381 11 2281 769 38a, Oybek street, Tashkent
Buzinski prilaz 38, Buzin Japan www.rs.grundfos.com : (+998) 71 150 3290 / 71 150
HR-10010 Zagreb GRUNDFOS Pumps K.K. 3291
Phone: +385 1 6595 400 1-2-3, Shin-Miyakoda, Kita-ku, Singapore : (+998) 71 150 3292
Telefax: +385 1 6595 499 Hamamatsu GRUNDFOS (Singapore) Pte. Ltd.
www.hr.grundfos.com 431-2103 Japan 25 Jalan Tukang Addresses Revised 05.12.2016
Phone: +81 53 428 4760 Singapore 619264
GRUNDFOS Sales Czechia and Telefax: +81 53 428 5005 Phone: +65-6681 9688
Slovakia s.r.o. Telefax: +65-6681 9689
ajkovskho 21
Korea
779 00 Olomouc GRUNDFOS Pumps Korea Ltd. Slovakia
Phone: +420-585-716 111 6th Floor, Aju Building 679-5 GRUNDFOS s.r.o.
Yeoksam-dong, Kangnam-ku, 135-916 Prievozsk 4D
Seoul, Korea 821 09 BRATISLAVA
Phone: +82-2-5317 600 Phona: +421 2 5020 1426
Telefax: +82-2-5633 725 sk.grundfos.com
ECM: 1199282
98091805 1216

www.grundfos.com
The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks owned by Grundfos Holding A/S or Grundfos A/S, Denmark. All rights reserved worldwide. Copyright Grundfos Holding A/S

You might also like