1 2 3 4 5 6 7 8
3 CURRENT TRANSFORMERS
L1
A A
L2
G
L3
B 30 50 70 90 8 9 10 1 B
USB
PROGRAMMING
PORT
6
7
C RS
C
16 35
COMMON ALARM
44 66 77 33 4 19 W B 15
6
MC
Starter Motor
Remote start
7A 2 92
+ 6
(24 Volt)
Battery
1
_ 7
DYN 7 6
5 CLS
+ M Ref.
5 19 D03 25 CAN
_ RS Ref.
ETS
OPS
D D05 D
+VE 6 3
Ref. S S
5 D06
- VE
5
To / From Relay Box 3 W B
6 5
CAN
E E
RN : FUEL SOLENOID RELAY CLS : COOLANT LEVEL SENSOR S : SENSOR OUTGOING/INCOMING PANEL TERMINAL
F1 F2 F3 F4 F5
MPR: MAIN POWER RELAY RS : RELAY START CUSTOMER TERMINAL
7 7A 3 5 92 25
(DSE power supply)
+ve 24V - 10A
(For Emergency Stop)
+ve 24V - 20A
PHASE 1 - 4A
PHASE 2 - 4A
PHASE 3 - 4A
Common Alarm
SOLENOID
Emergency Stop
Remote Start
OPR : OIL PRESSURE READING ES :EMERGENCY STOP INTERNAL JOIN
ETR :ENGINE TEMPERATURE READING SOL : SOLENOID
GROUNDING
OPS : OIL PRESSURE SWITCH G : GENERATOR TO/From RELAY BOX
ETR :ENGINE TEMPERATURE SWITCH M : STARTER MOTOR
F F
DYN : DYNAMO (CHARGING ALTERNATOR) F : FUSE TERMINALS BLOCK
DRAWING NO. Revision No. DESCRIPTION : DATE : 26/5/14
ELE6110C3M200001 JUBAILI BROS ENG. LTD Control Wiring Diagram For P200-250KVA
SHEET NO: 1/1
SHEET Integrated electromechanical services DESIGN BY: Yasser Farhat
SIZE
A3 End User With DSE 6110 CAN Approved BY: Ahmed Dahshi
1 2 3 4 5 6 7 8