Open Delta Purpose in EF

The document discusses the broken delta configuration used for earth fault protection. It consists of a delta connected secondary on a potential transformer with one point left open. During a ground fault, a voltage is induced at the open point that can be measured by a relay to trip the system. A resistor is added across the open point to prevent ferroresonance. Broken delta transformers are rated so the secondary voltage during a ground fault will be 110V.

Uploaded by

nmanikandan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
249 views

Open Delta Purpose in EF

The document discusses the broken delta configuration used for earth fault protection. It consists of a delta connected secondary on a potential transformer with one point left open. During a ground fault, a voltage is induced at the open point that can be measured by a relay to trip the system. A resistor is added across the open point to prevent ferroresonance. Broken delta transformers are rated so the secondary voltage during a ground fault will be 110V.

Uploaded by

nmanikandan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

ElectroTechnik

Using Broken Delta Protection for Earth Faults


The Broken Delta configuration is used to protect against earth faults. It is a
configuration that works by monitoring the vector sum of the phase voltages.

It consists of a delta connection on the secondary of a potential transformer that is


open at one point as in the figure. In such a construction, when a balanced three
phase voltage is present in the star connected primary, the voltage across the
broken point of the delta connection would be zero, as it would be a vector sum of all
three voltages.

In the event of a ground fault in one phase, the phase-to-


ground voltage in the remaining two phases is now equal to the phase-to-phase
voltage with a displacement of 60 degrees. The voltage at the broken delta becomes
3Voor three times the phase-to-ground voltage.

This voltage can be measured by a relay and can be used to trip the power system.
A resistor is usually connected across the broken delta connection to
prevent Ferro resonance, a condition that occurs when the line capacitance and the
inductance in the potential transformers reach a state of resonance.

Broken delta transformers are usually marked as 11kV/3:110 volts. It means that
the transformer is designed that in the event of a ground fault in the primary side, the
secondary output will be 110 V.
OPEN DELTA VS BROKEN DELTA

Posted by Phil Corso, PE on 14 August, 2007 - 12:06 am


Responding to GY's 23-Jul (20:16) query about potential transformer (PT) connections for
generator E/F stator protection:The broken-delta connection uses three single-phase PTs. All
three primaries are connected between line and earth (ground!)Their secondaries are delta-
connected, except that one corner of the delta is left open-circuited. This arrangement is also
calleda residually-connected circuit. Its principle benefit is that the residual voltage is
much higher than that of the open-deltaconnection (described in next paragraph!) Thus, it is
more sensitive to earth-faults.The open-delta connection uses two single-phase PTs. They, too,
provide 3-phase transformation, but the resultant secondaryvoltage magnitude is about 1/3 that of
the broken-delta arrangement. Furthermore, secondary-circuit failures that could negateproper
fault detection are virtually ignored!