The document contains a power flow report for a 5 bus system with 6 lines and 2 generators. It provides network statistics, solution statistics from power flow analysis, voltage and power outputs for each bus, line flows, and total power generated and loaded in the system.

Uploaded by

Anand
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
84 views4 pages

Power Flow Report (P S A T 2.1.7)

The document contains a power flow report for a 5 bus system with 6 lines and 2 generators. It provides network statistics, solution statistics from power flow analysis, voltage and power outputs for each bus, line flows, and total power generated and loaded in the system.

Uploaded by

Anand
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 4

POWER FLOW REPORT (P S A T 2.1.

7)

NETWORK STATISTICS

Buses: 5

Lines: 6

Generators: 2

Loads: 4

SOLUTION STATISTICS

Number of Iterations: 4

Maximum P mismatch [p.u.] 0

Maximum Q mismatch [p.u.] 0

Power rate [MVA] 100

POWER FLOW RESULTS

Bus V phase P gen Q gen P load Q load

[p.u.] [rad] [p.u.] [p.u.] [p.u.] [p.u.]

Bus1 1.03 0 1 -0.4641 0 0

Bus2 1.05 -0.01096 0.5 0.65373 0.15 0

Bus3 1.0332 -0.1304 0 0 0.45 0

Bus4 1.0309 -0.14106 0 0 0.4 0

Bus5 1.0295 -0.13311 0 0 0.5 0


LINE FLOWS

From Bus To Bus Line P Flow Q Flow P Loss Q Loss

[p.u.] [p.u.] [p.u.] [p.u.]

Bus4 Bus5 1 -0.21088 0.03696 0 0.00173

Bus5 Bus3 2 -0.0072 -0.00929 0 5e-05

Bus3 Bus4 3 0.18912 0.03906 0 0.0021

Bus1 Bus2 4 0.29632 -0.51338 0 0.01325

Bus1 Bus5 5 0.70368 0.04928 0 0.09381

Bus2 Bus3 6 0.64632 0.12711 0 0.07871

LINE FLOWS

From Bus To Bus Line P Flow Q Flow P Loss Q Loss

[p.u.] [p.u.] [p.u.] [p.u.]

Bus5 Bus4 1 0.21088 -0.03524 0 0.00173

Bus3 Bus5 2 0.0072 0.00934 0 5e-05

Bus4 Bus3 3 -0.18912 -0.03696 0 0.0021

Bus2 Bus1 4 -0.29632 0.52662 0 0.01325

Bus5 Bus1 5 -0.70368 0.04453 0 0.09381

Bus3 Bus2 6 -0.64632 -0.0484 0 0.07871

GLOBAL SUMMARY REPORT

TOTAL GENERATION TOTAL LOAD TOTAL LOSSES

REAL POWER [p.u.] 1.5 1.5 0

REACTIVE POWER [p.u.] 0.18964 0 0.18964


OUTPUT

Enter the number of branches :

Bus Admittance Matrix

0.0000 +30.0000i 0.0000 -25.0000i 0.0000 + 0.0000i 0.0000 + 0.0000i 0.0000 - 5.0000i

0.0000 -25.0000i 0.0000 +30.0000i 0.0000 - 5.0000i 0.0000 + 0.0000i 0.0000 + 0.0000i

0.0000 + 0.0000i 0.0000 - 5.0000i 0.0000 +24.1667i 0.0000 -16.6667i 0.0000 - 2.5000i

0.0000 + 0.0000i 0.0000 + 0.0000i 0.0000 -16.6667i 0.0000 +41.6667i 0.0000 -25.0000i

0.0000 - 5.0000i 0.0000 + 0.0000i 0.0000 - 2.5000i 0.0000 -25.0000i 0.0000 +32.5000i

Impedance Matrix for buses other than Slack Bus

0.0369 0.0215 0.0178 0.0154

0.0215 0.1292 0.1071 0.0923

0.0178 0.1071 0.1333 0.1108

0.0154 0.0923 0.1108 0.1231

Sensitivity factor matrix

0 0 0 0 0

0 0.0369 0.0215 0.0178 0.0154

0 0.0215 0.1292 0.1071 0.0923

0 0.0178 0.1071 0.1333 0.1108

0 0.0154 0.0923 0.1108 0.1231

Line outage distribution factor Matrix

0 1.0000 -1.0000 -0.4762 -0.1852 -0.4762

1.0000 0 1.0000 0.4762 0.1852 0.4762

-1.0000 1.0000 0 -0.4762 -0.1852 -0.4762

-0.8000 0.8000 -0.8000 0 0.8148 -1.0000

-0.2000 0.2000 -0.2000 0.5238 0 0.5238

-0.8000 0.8000 -0.8000 -1.0000 0.8148 0


Enter the bus number of outage :

Enter the bus number of outage :

1.0000

enter the line number in which flow is to be found out :2

enter the line no .on outage: 1

enter the base flow on outage line 1to 2: 29.63

enter the base flow on outage line 1to 5 :to 5:70.36

the flow on line 1 to 5with line 1 to 2 on outage = 99.990000

enter the base flow on outage line 2to 3 :64.63

the flow on line 2 to 3with line 1 to 2 on outage = 35.30000

enter the base flow on outage line 3to 4 :to 4:18.91

the flow on line 3 to 4with line 1 to 2 on outage = -4.79

enter the base flow on outage line 3to 5 : 0.72

the flow on line 3 to 5with line 1 to 2 on outage = -5.206000

enter the base flow on outage line 4to 5 ::21.08

the flow on line 4 to 5with line 1 to 2 on outage = -2.61