PANEL NAME : SUB PANELBOARD 1
LOCATION : MAIN DOOR (NEAR LIVING ROOM)
FED FROM : MAIN DISTRIBUTION (GROUND FLOOR)
MAIN PROTECTION :100 A 2P ISOLATOR
FEEDER CONDUCTOR : 2 - 22mm² THHN + 1 - 14mm² TW Earth Conductor in 32mmΦ NMC
# of Current
Ckt. # Load Description Location Connected Load (in VA) Circuit Breaker Conductor/Conduit
outlet (A)
1 Lighting (7 Pin Light at 50W, 3 Fluorescent 36W) Carpark, Library/Study Area, Guest Room 10 458 1.991304 15AT/100AF 2P, 1Φ, 230-V 2 - 2mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
2 Lighting (10 Pinlight at 50W, 2 x 36W Fluorescent Lamp ) Stairs, Living Room, Dining Area, Kitchen 12 572 2.486957 15AT/100AF 2P, 1Φ, 230-V 2 - 2mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
Carpark, Storage Room, Guest Room, Kitchen,
3 Convenience Outlet (10 Double Outlet at 180VA) 20 3,600 15.65 15AT/100AF 2P, 1Φ, 230-V 2 - 2mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
Living Room
4 Refrigerator Kitchen 1 2,000 8.70 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
5 BOOSTER PUMP 30AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC
6 SPARE 30AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC
7 SPARE 30AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC
8 SPARE 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
9 SPARE 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
10 SPARE 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
11 SPARE 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
12 SPARE 20AT/100AF 2P, 1Φ, 230-V 2- 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
TOTAL CONNECTED LOAD 6,630
Service Entrance Conductor Rating:
Total Lighting and Convenience Outlet Load 4,630
First 3,000VA at 100% DF
Rem at 35% DF 1,621
Lighting and Convenience Outlet Load After application of Demand Factor = 1,621 VA
Washing Machine and Cooking Range at 80%DF = VA
Refrigerator, ACU and Water Pump at 100% DF = 0 VA
TOTAL = 1,620.5 VA
Total Ampere 7.045652174 A
Use 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 32mmΦ NMC
Use 100 A 2P ISOLATOR ( subpanel disconnectin switch)
PANEL NAME : SUB PANELBOARD 2
LOCATION :2nd FLOOR (INSIDE WALK-IN CLOSET)
FED FROM : MAIN DISTRIBUTION (GROUND FLOOR)
MAIN PROTECTION :100 A 2P ISOLATOR
FEEDER CONDUCTOR : 2 - 22mm² THHN + 1 - 14mm² TW Earth Conductor in 32mmΦ NMC
# of Current
Ckt. # Load Description Location Connected Load (in VA) Circuit Breaker Conductor/Conduit
outlet (A)
1 Lighting (5 Pinlight at 50W, 2 Fluorescent Lamp at 36W) Terrace, Study Room, Bedroom 1, T&B 1, T&B 2 7 322 1.4 15AT/100AF 2P, 1Φ, 230-V 2 - 2mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
2 Lighting (8 Pinlight at 50W, 1 Chandelier at 600W) Living Room, Master's Bedroom 9 1,000 4.347826 15AT/100AF 2P, 1Φ, 230-V 2 - 2mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
3 Convenience Outlet (5 Double Outlet at 180VA per receptacle) Terrace, Closet, Bedroom 1 10 1,800 7.83 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
4 Convenience Outlet (7 Double Outlet at 180VA per receptacle) Living Room, Master's Bedroom 14 2,520 10.96 30AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
5 ACU at 1HP Master's Bedroom 1 1,840 8.00 30AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC
6 SPARE 30AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC
7 SPARE 30AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC
8 SPARE 30AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
9 SPARE 30AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
10 SPARE 30AT/100AF 2P, 1Φ, 230-V 2- 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
TOTAL CONNECTED LOAD 7,482
Service Entrance Conductor Rating:
Total Lighting and Convenience Outlet Load 5,642
First 3,000VA at 100% DF 3,000
Rem at 35% DF 925
Lighting and Convenience Outlet Load After application of Demand Factor 3,925 = 3,925 VA
Washing Machine and Cooking Range at 80%DF = 0 VA
Refrigerator, ACU and Water Pump at 100% DF = 1,840 VA
TOTAL = 5,764.7 VA
Total Ampere 25.06391304 A
Use 2 - 14mm² THHN + 1 - 8mm² TW Earth Conductor in 32mmΦ IMC
Use 100 A 2P ISOLATOR ( subpanel disconnectin switch)
PANEL NAME : SUB PANELBOARD 3
LOCATION :3rd FLOOR (NEAR POOL AREA)
FED FROM : MAIN DISTRIBUTION (GROUND FLOOR)
MAIN PROTECTION :100 A 2P ISOLATOR
SERVICE ENTRANCE CONDUCTOR : 2 - 22mm² THHN + 1 - 14mm² TW Earth Conductor in 32mmΦ NMC
# of Current
Ckt. # Load Description Location Connected Load (in VA) Circuit Breaker Conductor/Conduit
outlet (A)
1 Lighting (6 Pinlight at 50W, 4 LED Dim at 10W, 2 Fluorescent at 36W) Entertainment Room 12 412 1.791304 15AT/100AF 2P, 1Φ, 230-V 2 - 2mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
2 Lighting (3 Pinlight at 50W, 2 Fluorescent at 36W) Playing Area,Stairs 5 222 0.965217 15AT/100AF 2P, 1Φ, 230-V 2 - 2mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
3 Convenience Outlet (5 Double Outlet per receptacle) Mini Bar, Entertainment Room 10 1,800 7.83 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
4 Convenience Outlet (5 Double Outlet per receptacle) Entertainment Room, Playing Area 10 1,800 7.83 30AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC
5 SPARE 20AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC
6 SPARE 20AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC
7 SPARE 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
8 SPARE 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
TOTAL CONNECTED LOAD 4,234
Service Entrance Conductor Rating:
Total Lighting and Convenience Outlet Load 4,234
First 3,000VA at 100% DF
Rem at 35% DF
Lighting and Convenience Outlet Load After application of Demand Factor = 2,760 VA
Washing Machine and Cooking Range at 80%DF = 0 VA
Refrigerator, ACU and Water Pump at 100% DF = VA
TOTAL = 2,760.0 VA
Total Ampere 12 A
Use 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 31mmΦ NMC
Use 100 A 2P ISOLATOR ( subpanel disconnectin switch)
PANEL NAME :MAIN DISTRIBUTION PANELBOARD
LOCATION :MAIN DOOR (NEAR LIVING ROOM)
FED FROM : SERVICE ENTRANCE (MERALCO 2-WIRE , 1Φ, 230-V SUPPLY)
MAIN PROTECTION :200AT/400AF 2P MCCB
SERVICE ENTRANCE CONDUCTOR : 2 - 80mm² THHN + 1 - 60mm² TW Earth Conductor in 50mmΦ IMC
Current
Ckt. # Load Description Location Connected Load (in VA) Circuit Breaker Conductor/Conduit
(A)
1 SUB PANELBOARD 1 Ground Floor 1,621 7.045652 100AT/200AF 2P, 1Φ, 230-V 2 - 22mm² THHN + 1 - 14mm² TW Earth Conductor in 32mmΦ NMC
2 SUB PANELBOARD 2 2nd Floor 5,765 25.06391 100AT/200AF 2P, 1Φ, 230-V 2 - 22mm² THHN + 1 - 14mm² TW Earth Conductor in 32mmΦ NMC
3 SUB PANELBOARD 3 3rd Floor 2,760 12.00 100AT/200AF 2P, 1Φ, 230-V 2 - 22mm² THHN + 1 - 14mm² TW Earth Conductor in 32mmΦ NMC
4 SPARE 100AT/200AF 2P, 1Φ, 230-V 2 - 22mm² THHN + 1 - 14mm² TW Earth Conductor in 32mmΦ NMC
TOTAL CONNECTED LOAD 10,145
Service Entrance Conductor Rating:
Total Lighting and Convenience Outlet Load 14,506
First 3,000VA at 100% DF 3,000
Rem at 35% DF 4,027
Lighting and Convenience Outlet Load After application of Demand Factor 7,027 = 7,027 VA
Washing Machine and Cooking Range at 80%DF = 0 VA
At 25%DF Highest Connected Motor = 460 VA
Refrigerator, ACU and Water Pump at 100% DF = 6,160 VA
TOTAL = 13,187.1 VA
29,388 / 230 = 127.77 A
Safety Factor : 127.77 * 1.25 = 159.71
Use 2 - 80mm² THWN + 1 - 60mm² TW Earth Conductor in 50mmΦ IMC
Use 200AT/400AF 2P, 1ɸ, 230-V Molded Case Circuit as Main Protection