Load Schedule Apartment

The document provides information on two sub panelboards for a home electrical system. Sub panelboard 1 is located near the living room and feeds various lighting circuits, convenience outlets, and appliances like a refrigerator in the kitchen. It has a total connected load of 6,630VA. Sub panelboard 2 is located on the 2nd floor and feeds lighting, outlets, and an air conditioning unit in the master bedroom. It has a total connected load of 7,482VA. Both panelboards receive power from the main distribution panel on the ground floor and have circuit breakers and conductor sizes specified to safely distribute power to circuits in their respective areas.

Uploaded by

shaito
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
3K views3 pages

Load Schedule Apartment

The document provides information on two sub panelboards for a home electrical system. Sub panelboard 1 is located near the living room and feeds various lighting circuits, convenience outlets, and appliances like a refrigerator in the kitchen. It has a total connected load of 6,630VA. Sub panelboard 2 is located on the 2nd floor and feeds lighting, outlets, and an air conditioning unit in the master bedroom. It has a total connected load of 7,482VA. Both panelboards receive power from the main distribution panel on the ground floor and have circuit breakers and conductor sizes specified to safely distribute power to circuits in their respective areas.

Uploaded by

shaito
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

PANEL NAME : SUB PANELBOARD 1

LOCATION : MAIN DOOR (NEAR LIVING ROOM)


FED FROM : MAIN DISTRIBUTION (GROUND FLOOR)
MAIN PROTECTION :100 A 2P ISOLATOR
FEEDER CONDUCTOR : 2 - 22mm² THHN + 1 - 14mm² TW Earth Conductor in 32mmΦ NMC

# of Current
Ckt. # Load Description Location Connected Load (in VA) Circuit Breaker Conductor/Conduit
outlet (A)

1 Lighting (7 Pin Light at 50W, 3 Fluorescent 36W) Carpark, Library/Study Area, Guest Room 10 458 1.991304 15AT/100AF 2P, 1Φ, 230-V 2 - 2mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC

2 Lighting (10 Pinlight at 50W, 2 x 36W Fluorescent Lamp ) Stairs, Living Room, Dining Area, Kitchen 12 572 2.486957 15AT/100AF 2P, 1Φ, 230-V 2 - 2mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC

Carpark, Storage Room, Guest Room, Kitchen,


3 Convenience Outlet (10 Double Outlet at 180VA) 20 3,600 15.65 15AT/100AF 2P, 1Φ, 230-V 2 - 2mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
Living Room

4 Refrigerator Kitchen 1 2,000 8.70 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC

5 BOOSTER PUMP 30AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC

6 SPARE 30AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC

7 SPARE 30AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC
8 SPARE 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
9 SPARE 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
10 SPARE 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
11 SPARE 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
12 SPARE 20AT/100AF 2P, 1Φ, 230-V 2- 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
TOTAL CONNECTED LOAD 6,630

Service Entrance Conductor Rating:


Total Lighting and Convenience Outlet Load 4,630
First 3,000VA at 100% DF
Rem at 35% DF 1,621
Lighting and Convenience Outlet Load After application of Demand Factor = 1,621 VA
Washing Machine and Cooking Range at 80%DF = VA
Refrigerator, ACU and Water Pump at 100% DF = 0 VA
TOTAL = 1,620.5 VA
Total Ampere 7.045652174 A

Use 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 32mmΦ NMC


Use 100 A 2P ISOLATOR ( subpanel disconnectin switch)

PANEL NAME : SUB PANELBOARD 2


LOCATION :2nd FLOOR (INSIDE WALK-IN CLOSET)
FED FROM : MAIN DISTRIBUTION (GROUND FLOOR)
MAIN PROTECTION :100 A 2P ISOLATOR
FEEDER CONDUCTOR : 2 - 22mm² THHN + 1 - 14mm² TW Earth Conductor in 32mmΦ NMC

# of Current
Ckt. # Load Description Location Connected Load (in VA) Circuit Breaker Conductor/Conduit
outlet (A)

1 Lighting (5 Pinlight at 50W, 2 Fluorescent Lamp at 36W) Terrace, Study Room, Bedroom 1, T&B 1, T&B 2 7 322 1.4 15AT/100AF 2P, 1Φ, 230-V 2 - 2mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC

2 Lighting (8 Pinlight at 50W, 1 Chandelier at 600W) Living Room, Master's Bedroom 9 1,000 4.347826 15AT/100AF 2P, 1Φ, 230-V 2 - 2mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC

3 Convenience Outlet (5 Double Outlet at 180VA per receptacle) Terrace, Closet, Bedroom 1 10 1,800 7.83 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC

4 Convenience Outlet (7 Double Outlet at 180VA per receptacle) Living Room, Master's Bedroom 14 2,520 10.96 30AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC

5 ACU at 1HP Master's Bedroom 1 1,840 8.00 30AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC
6 SPARE 30AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC
7 SPARE 30AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC
8 SPARE 30AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
9 SPARE 30AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
10 SPARE 30AT/100AF 2P, 1Φ, 230-V 2- 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
TOTAL CONNECTED LOAD 7,482

Service Entrance Conductor Rating:


Total Lighting and Convenience Outlet Load 5,642
First 3,000VA at 100% DF 3,000
Rem at 35% DF 925
Lighting and Convenience Outlet Load After application of Demand Factor 3,925 = 3,925 VA
Washing Machine and Cooking Range at 80%DF = 0 VA
Refrigerator, ACU and Water Pump at 100% DF = 1,840 VA
TOTAL = 5,764.7 VA
Total Ampere 25.06391304 A

Use 2 - 14mm² THHN + 1 - 8mm² TW Earth Conductor in 32mmΦ IMC


Use 100 A 2P ISOLATOR ( subpanel disconnectin switch)

PANEL NAME : SUB PANELBOARD 3


LOCATION :3rd FLOOR (NEAR POOL AREA)
FED FROM : MAIN DISTRIBUTION (GROUND FLOOR)
MAIN PROTECTION :100 A 2P ISOLATOR
SERVICE ENTRANCE CONDUCTOR : 2 - 22mm² THHN + 1 - 14mm² TW Earth Conductor in 32mmΦ NMC

# of Current
Ckt. # Load Description Location Connected Load (in VA) Circuit Breaker Conductor/Conduit
outlet (A)

1 Lighting (6 Pinlight at 50W, 4 LED Dim at 10W, 2 Fluorescent at 36W) Entertainment Room 12 412 1.791304 15AT/100AF 2P, 1Φ, 230-V 2 - 2mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC

2 Lighting (3 Pinlight at 50W, 2 Fluorescent at 36W) Playing Area,Stairs 5 222 0.965217 15AT/100AF 2P, 1Φ, 230-V 2 - 2mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC

3 Convenience Outlet (5 Double Outlet per receptacle) Mini Bar, Entertainment Room 10 1,800 7.83 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
4 Convenience Outlet (5 Double Outlet per receptacle) Entertainment Room, Playing Area 10 1,800 7.83 30AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC
5 SPARE 20AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC
6 SPARE 20AT/100AF 2P, 1Φ, 230-V 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 20mmΦ NMC
7 SPARE 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
8 SPARE 20AT/100AF 2P, 1Φ, 230-V 2 - 3.5mm² THHN + 1 - 2mm² TW Earth Conductor in 20mmΦ NMC
TOTAL CONNECTED LOAD 4,234

Service Entrance Conductor Rating:


Total Lighting and Convenience Outlet Load 4,234
First 3,000VA at 100% DF
Rem at 35% DF
Lighting and Convenience Outlet Load After application of Demand Factor = 2,760 VA
Washing Machine and Cooking Range at 80%DF = 0 VA
Refrigerator, ACU and Water Pump at 100% DF = VA
TOTAL = 2,760.0 VA
Total Ampere 12 A

Use 2 - 5.5mm² THHN + 1 - 3.5mm² TW Earth Conductor in 31mmΦ NMC


Use 100 A 2P ISOLATOR ( subpanel disconnectin switch)

PANEL NAME :MAIN DISTRIBUTION PANELBOARD


LOCATION :MAIN DOOR (NEAR LIVING ROOM)
FED FROM : SERVICE ENTRANCE (MERALCO 2-WIRE , 1Φ, 230-V SUPPLY)
MAIN PROTECTION :200AT/400AF 2P MCCB
SERVICE ENTRANCE CONDUCTOR : 2 - 80mm² THHN + 1 - 60mm² TW Earth Conductor in 50mmΦ IMC

Current
Ckt. # Load Description Location Connected Load (in VA) Circuit Breaker Conductor/Conduit
(A)
1 SUB PANELBOARD 1 Ground Floor 1,621 7.045652 100AT/200AF 2P, 1Φ, 230-V 2 - 22mm² THHN + 1 - 14mm² TW Earth Conductor in 32mmΦ NMC
2 SUB PANELBOARD 2 2nd Floor 5,765 25.06391 100AT/200AF 2P, 1Φ, 230-V 2 - 22mm² THHN + 1 - 14mm² TW Earth Conductor in 32mmΦ NMC
3 SUB PANELBOARD 3 3rd Floor 2,760 12.00 100AT/200AF 2P, 1Φ, 230-V 2 - 22mm² THHN + 1 - 14mm² TW Earth Conductor in 32mmΦ NMC
4 SPARE 100AT/200AF 2P, 1Φ, 230-V 2 - 22mm² THHN + 1 - 14mm² TW Earth Conductor in 32mmΦ NMC
TOTAL CONNECTED LOAD 10,145

Service Entrance Conductor Rating:


Total Lighting and Convenience Outlet Load 14,506
First 3,000VA at 100% DF 3,000
Rem at 35% DF 4,027
Lighting and Convenience Outlet Load After application of Demand Factor 7,027 = 7,027 VA
Washing Machine and Cooking Range at 80%DF = 0 VA
At 25%DF Highest Connected Motor = 460 VA
Refrigerator, ACU and Water Pump at 100% DF = 6,160 VA
TOTAL = 13,187.1 VA
29,388 / 230 = 127.77 A
Safety Factor : 127.77 * 1.25 = 159.71

Use 2 - 80mm² THWN + 1 - 60mm² TW Earth Conductor in 50mmΦ IMC


Use 200AT/400AF 2P, 1ɸ, 230-V Molded Case Circuit as Main Protection