Customer: Project N.
: aeroport Cluj
Street: Drawing: 2
City: Position:
WGK vers. 2.0.3.O.0024
Lic.0019D11FD456 Build: Arrange.:
Refree: i.f. Street:
Date: 06.07.2017 City: Pieces: 1 Page 1 of 5
model box data
Thermal transmittance U T3 (M) Classification of the leakage L1 (M)
Thermal bridging factor kb TB3 (M) Classification of mechanical strength D2 (M)
Certification Diploma N° : 13.02.003
Unit Type: Combined supply and exhaust air unit, one above the other arranged
Range : Eurevo
Execution of supply air unit: DIWER KOMBI 99 WF weatherproof galv./galv./galv. V1
supply air volume: 5000 m³/h air velocity: 1.59 m/s
Execution or exhaust air unit: DIWER KOMBI 99 WF weatherproof galv./galv./galv. V1
exhaust air volume: 5000 m³/h air velocity: 1.59 m/s
technical data of supply air unit
SW Front panel [ss.fr.] galvanized/galvanized 48 mm 2 Pa
Opening: full Damper: ALU class 2 DIN-EN 1751 mounted external
KF Flat filter section [ss.fr.] galvanized/galvanized 95 mm 82 Pa
Make: WEGER Ini.dp: 14 Pa Filters: 1 pcs. 592 x 592 x 48 2 pcs. 287 x 592 x 48
Type: FOE / G 4 / 1.5 m² End dp: 150 Pa 1 pcs. 287 x 287 x 48
Access.: pressure measurement points fitted differential pressure switch
filter frames made of galvanized metal sheet removable panel (K)
PT Plate heat exchanger galvanized/galvanized 1830 mm 170 Pa
Type: FI AL 12 N 0910 U 1 AE NS SM AABP100 plate material: Alu
Winter data: Power: 51.89 kW Efficiency dry/wet: 75 / 83.8 %
Supply air: 5000 m³/h Pressure drop: 170 Pa Return air: 5000 m³/h Pressure drop: 179 Pa
Inlet: -15 °C 90 % Inlet: 22 °C 50 %
Outlet: 16 °C 8% ER-class: H1 Outlet: 1.4 °C 100 %
Summer data: Power: 11.29 kW Efficiency dry/wet: 75 / 75%
Supply air: 5000 m³/h Pressure drop: 170 Pa Return air: 5000 m³/h Pressure drop: 179 Pa
Inlet: 35 °C 35 % Inlet: 26 °C 50 %
Outlet: 28.3 °C 74 % Outlet: 32.8 °C 34 %
freezing temperature: -8.3 °C
Access.: drain pan made of stainless steel bypass on supply air
EH Heating coil section [ss.fr.] galvanized/galvanized 180 mm 56 Pa
P4016 AC 21T 3R 755A 2PA 4NA CU/AL [11.2 l] Media: H2O Connections on/off:1 / 1 (GAS)
Air volume: 5000 m³/h 2.19 m/s Press.drop: 56 Pa Quantity.: 3330 l/h 1.21 m/s Press.drop: 31.5 kPa
Inlet temp.: -15 °C Power: 75.7 kW Inlet temp.: 80 °C
Outlet temp: 30 °C Outlet temp: 60 °C
Access.: galvanized guide rails
KH Cooling coil section [ss.fr.] galvanized/galvanized 425 mm 70 Pa
P6016 AF 14T 5R 750A 2.5PA 6NA CU/AL [12.8 l] Media: H2O Connections on/off:1 1/4 / 1 1/4 (GAS)
Air volume: 5000 m³/h 2.2 m/s Press.drop: 54 Pa Quantity.: 5070 l/h 1.23 m/s Press.drop: 31.75 kPa
Inlet temp.: 28.7 °C 51 % Power: 29.5 kW Inlet temp.: 7 °C
Outlet temp: 17 °C 85 % SHR: .66 Outlet temp: 12 °C
Access.: stainless steel guide rails drain pan made of stainless steel
moisture eliminator Alu/PPT (1) coil frame made of stainless steel
L Empty section [ss.fr.] galvanized/galvanized 300 mm 0 Pa
Customer: Project N.: aeroport Cluj
Street: Drawing: 2
City: Position:
WGK vers. 2.0.3.O.0024
Lic.0019D11FD456 Build: Arrange.:
Refree: i.f. Street:
Date: 06.07.2017 City: Pieces: 1 Page 2 of 5
model box data
Thermal transmittance U T3 (M) Classification of the leakage L1 (M)
Thermal bridging factor kb TB3 (M) Classification of mechanical strength D2 (M)
Certification Diploma N° : 13.02.003
Unit Type: Combined supply and exhaust air unit, one above the other arranged
Range : Eurevo
Execution of supply air unit: DIWER KOMBI 99 WF weatherproof galv./galv./galv. V1
supply air volume: 5000 m³/h air velocity: 1.59 m/s
Execution or exhaust air unit: DIWER KOMBI 99 WF weatherproof galv./galv./galv. V1
exhaust air volume: 5000 m³/h air velocity: 1.59 m/s
V Supply fan section [ss.fr.] galvanized/galvanized 1047 mm 14 Pa
Fan: ER45C-4DN.E7.CR / Ziehl-Abegg Motor: inc. , IP55, THCL155 IE3 / 400/3/50
Air volume: 5000 m³/h dp dyn.: 32 Pa Nom. power: 2.2 kW
dp external: 300 Pa dp stat.tot.: 695 Pa Nom. RPM: 1465 1/min
RPM: 1709.17 1/min shaft power: 1.31 kW Nom. current: 4.4 A [+/- 5%]
Noise: 82 dB(A) Efficiency: 73.7 % absorbed power: 1.58 kW (P1 (P m,ref=2.1))
SFPv: 1031 W/m³/s (SFP 2) Vibration isolators: 4x 30x30 /h.u.w.: 30 mm
K-factor: 197 (eff.pressure 644 Pa at 5000 m³/h) Remarks: Working point at 58 Hz
Frg.Hz 63 125 250 500 1000 2000 4000 8000 max. RPM: 2020 1/min
dB(A) ss 36.1 50.1 63.1 66.2 69.3 66.2 62.3 55.1 Limit the regulator at 69 Hz !
dB(A) ps 43.2 56.8 69.7 73.6 80.3 72.2 67.8 59.3
Access.: hinged service door with EMKA door open holder
potential equalization cable 16 mm² connections for air volume control
converter 1xABB ACS550-01-05A4-4+B055 ACS 550IP54
wiring and mounting inverter
SW Front panel [ss.fr.] galvanized/galvanized 48 mm 1 Pa
Opening: full Damper: w/o damper
Customer: Project N.: aeroport Cluj
Street: Drawing: 2
City: Position:
WGK vers. 2.0.3.O.0024
Lic.0019D11FD456 Build: Arrange.:
Refree: i.f. Street:
Date: 06.07.2017 City: Pieces: 1 Page 3 of 5
model box data
Thermal transmittance U T3 (M) Classification of the leakage L1 (M)
Thermal bridging factor kb TB3 (M) Classification of mechanical strength D2 (M)
Certification Diploma N° : 13.02.003
Unit Type: Combined supply and exhaust air unit, one above the other arranged
Range : Eurevo
Execution of supply air unit: DIWER KOMBI 99 WF weatherproof galv./galv./galv. V1
supply air volume: 5000 m³/h air velocity: 1.59 m/s
Execution or exhaust air unit: DIWER KOMBI 99 WF weatherproof galv./galv./galv. V1
exhaust air volume: 5000 m³/h air velocity: 1.59 m/s
technical data of exhaust air unit
SW Front panel [ss.fr.] galvanized/galvanized 48 mm 1 Pa
Opening: full Damper: w/o damper
KF Flat filter section [ss.fr.] galvanized/galvanized 96 mm 82 Pa
Make: WEGER Ini.dp: 14 Pa Filters: 1 pcs. 592 x 592 x 48 2 pcs. 287 x 592 x 48
Type: FOE / G 4 / 1.5 m² End dp: 150 Pa 1 pcs. 287 x 287 x 48
Access.: pressure measurement points fitted differential pressure switch
filter frames made of galvanized metal sheet removable panel (K)
L Empty section [ss.fr.] galvanized/galvanized 300 mm 0 Pa
V Exhaust fan section [ss.fr.] galvanized/galvanized 1016 mm 14 Pa
Fan: ER45C-4DN.D7.CR / Ziehl-Abegg Motor: inc. , IP55, THCL155 IE3 / 400/3/50
Air volume: 5000 m³/h dp dyn.: 32 Pa Nom. power: 1.5 kW
dp external: 300 Pa dp stat.tot.: 578 Pa Nom. RPM: 1445 1/min
RPM: 1600.73 1/min shaft power: 1.07 kW Nom. current: 3.2 A [+/- 5%]
Noise: 80.8 dB(A) Efficiency: 75.1 % absorbed power: 1.29 kW (P1 (P m,ref=1.8))
SFPv: 825 W/m³/s (SFP 2) Vibration isolators: 4x 30x30 /h.u.w.: 30 mm
K-factor: 197 (eff.pressure 644 Pa at 5000 m³/h) Remarks: Working point at 55 Hz
Frg.Hz 63 125 250 500 1000 2000 4000 8000 max. RPM: 1760 1/min
dB(A) ss 34.5 49.9 61.8 65.2 68.9 64.2 60.2 53.4 Limit the regulator at 61 Hz !
dB(A) ps 40.8 55.4 68.7 71.8 79.4 70.1 66.1 57.3
Access.: hinged service door with EMKA door open holder
potential equalization cable 16 mm² connections for air volume control
converter 1xABB ACS550-01-04A1-4+ B055 ACS 550IP54
wiring and mounting inverter
PT Plate heat exchanger 1830 mm 1830 mm 179 Pa
for tecnical details see on supply air unit !
L Empty section [ss.fr.] galvanized/galvanized 130 mm 0 Pa
SW Front panel [ss.fr.] galvanized/galvanized 48 mm 2 Pa
Opening: full Damper: ALU class 2 DIN-EN 1751 mounted external
Additional HRS informations
Efficiency on dry conditiones: 74.9 %
Pressure drop of HRS (sum of supply and exhaust): 362 Pa
Encrease of electrical consumtion caused by pressure drop: 837 W
indicatore performance: 29.94
energetic efficiency: 72.4 %
values calculated according to DIN EN 13053 and EN 308
Customer: Project N.: aeroport Cluj
Street: Drawing: 2
City: Position:
WGK vers. 2.0.3.O.0024
Lic.0019D11FD456 Build: Arrange.:
Refree: i.f. Street:
Date: 06.07.2017 City: Pieces: 1 Page 4 of 5
model box data
Thermal transmittance U T3 (M) Classification of the leakage L1 (M)
Thermal bridging factor kb TB3 (M) Classification of mechanical strength D2 (M)
Certification Diploma N° : 13.02.003
Unit Type: Combined supply and exhaust air unit, one above the other arranged
Range : Eurevo
Execution of supply air unit: DIWER KOMBI 99 WF weatherproof galv./galv./galv. V1
supply air volume: 5000 m³/h air velocity: 1.59 m/s
Execution or exhaust air unit: DIWER KOMBI 99 WF weatherproof galv./galv./galv. V1
exhaust air volume: 5000 m³/h air velocity: 1.59 m/s
general access.: baseframe 80 mm potential equalization cable 16 mm²
crane lugs packaging, pallet and nylon
AHU weigth approx.: 1480 kg
flexible canvas tightness class C according to EN 13180
According guidelines VDI 3803 and VDMA standard sheet 24175 AHU’s MAY NEVER take any building functions!
AHU not suitable for work on ships
AHU designed for dry conditions
SFPv values according to EN 13779, clean filters
stainless steel means V2A, Nr. 1.4301
pipe thread of coil connection as specified in EN 102262-2
References: elevation 0 metri, temperature 20 °C
Customer: Project N.: aeroport Cluj
Street: Drawing: 2
City: Position:
WGK vers. 2.0.3.O.0024
Lic.0019D11FD456 Build: Arrange.:
Refree: i.f. Street:
Date: 06.07.2017 City: Pieces: 1 Page 5 of 5
additional informations a requested by regulation 1253/2014
name of constructor or trading mark: WEGER
www.weger.de
AHU Type: combi DIWER 99 - 99 WF
AHU Type as specified on regulation: NRVU, bidirectional
present motor drive or motor drive to provide to fulfill the requirements of regulation: stepless, inverter
kind of installed heat recovery system: plate heat exchanger
HRS efficiency as specified on EN 308: 75 %
HRS efficiency on project data: 84 %
nominal air flow rate: 1.39 m³/s
air velocity: 1.59 m/s
absorbed electrical power (motors): 2.87 kW
SFPint 578 W/(m³/s)
minimum required caracteristics as specified in 1253/2014
minimum efficiency of HRS from 01.01.2016 67 %
maximum specific fan power for ventilation components from 01.01.2016 871 W/(m³/s)
efficiency bonus ErP 2016 240 W/(m³/s)
AHU corresponding to rules of regulation valid from 01.01.2016
minimum efficiency of HRS from 01.01.2018 73 %
maximum specific fan power for ventilation components from 01.01.2018 611 W/(m³/s)
efficiency bonus ErP 2018 60 W/(m³/s)
AHU corresponding to rules of regulation valid from 01.01.2018
nominal external pressure dps, ext 300+300 Pa
pressure drop of significant components dps, int 349 Pa
faculativ: pressure drop of non significant components dps, add 324 Pa
static system efficiency (327/2011) of supply air fan 65.1 %
system efficiency on working point of supply air fan 59.9 %
static system efficiency (327/2011) of exhaust air fan 64.7 %
system efficiency on working point of exhaust air fan 60.7 %
sound power level of casing (Lwa): 59 dB(A)
sound power on fresh air connection (ODA) at 63/125/250/500/1000/2000/4000/8000 Hz:
58/62/67/62/60/50/45/43 dB
A-weightet total level: 64 dB(A)
sound power on supply air connection (SUP) at 63/125/250/500/1000/2000/4000/8000 Hz:
69/72/78/76/80/70/66/60 dB
A-weightet total level: 82 dB(A)
sound power on return air connection (ETA) at 63/125/250/500/1000/2000/4000/8000 Hz:
59/64/68/66/66/59/54/46 dB
A-weightet total level: 69 dB(A)
sound power on exhaust air connection (EHA) at 63/125/250/500/1000/2000/4000/8000 Hz:
66/71/77/74/79/68/65/58 dB
A-weightet total level: 81 dB(A)
maximum air leakage of unit casing: 0.65 %
maximum internal air leakage: 0.73 %
Filters have to be replaced if the gauge indicates that the final pressure, listed in tecnical datasheet, is reached.
Dirty filters increase the energy consumption of the ventilation unit.