Introductions
Introductions
The FireNET 2127/4127 is an analog addressable fire alarm system that meets the
requirements of UL 864 9th Edition.
The basic FireNET 2127/4127 control panel includes two SLC (Signaling Line
Circuit) loops. Each loop is capable of supporting 127 analog addressable points
(can be any combination of sensors and modules) for a total of 254 analog
addressable points on the basic panel. Two additional SLC loops can be added to
the panel increasing the analog addressable point capacity to 508. When analog
sounder bases are used, the upper addresses 128 – 254 are allocated to increase
loop capacity to 254 analog addressable points. This doubles the analog
addressable point capacity of the panel. The combination of analog addressable
points derived from sensors, modules, and sounder bases cannot exceed 800
addresses and sub-addresses maximum.
Up to 4.0 amps of power is available to drive the system, SLC loops, notification
appliances, and auxiliary equipment.
Four Class B notification appliance circuits rated at 2.5 amps each (see Section 2.7
and 2.8 for additional details regarding NAC circuit ratings).
Auto-Learn utility identifies system devices, which makes initial system start-up
easier.
8 line by 40 character graphic display provides the most intuitive operator interface
in the industry (320 characters total).
Help screens are available from the front panel and annunciator user interface to
assist in programming and operation.
512 additional points can be added to the system using the FN4127-IO 16 channel
input/output boards. Each of these points can be programmed individually to be an
input or low current output. These points are for secondary use only.
7
FireNET 4127 I & O Manual v2.03UL
1.2 System Devices and Equipment
The following boards, expanders and devices are available from Hochiki America
Corp. to be used with the FireNET 2127/4127 analog addressable fire alarm system.
For a complete description and installation instructions of each product, please see the
appropriate section of this manual and the literature supplied with the device itself.
Model Description
Control Panels
Analog/Addressable Fire Alarm Control Panel
FN-4127
(4 SLC Loop)
Analog/Addressable Fire Alarm Control Panel
FN-2127
(2 SLC Loop)
NOTE: There are several ordering models (i.e. 2 loop, 4 loop, network options,
120/240VAC, colors, etc.). Hochiki America’s order entry department will establish
exact model and configuration at time of order. Different ordering models are also
reflected on the FireNET product datasheets.
Control Panel Expanders
FN-4127-NIC Network Interface Card
FN-4127-SLC Dual SLC Loop Expander Card
FN-4127-IO 16 Channel Input Output Board
FN-CTM City-Tie Module
FN-DAC Digital Alarm Communicator/Transmitter
Annunciators
FN-LCD-N Network LCD Annunciator
FN-LCD-S Serial LCD Annunciator
SLC Loop Devices
ALK-V Analog Photoelectric Smoke Sensor
ALK-V2 Analog Photoelectric Smoke Sensor
ALG-V Analog Photoelectric Smoke Sensor
AIE-EA Analog Ionization Smoke Sensor
ATG-EA Analog Heat Sensor
ACA-V Analog Photoelectric and Heat Multi Sensor
ATJ-EA Fixed Temperature and Rate of Rise Heat Detector
ALN-V Analog Photo Electric Smoke Detector
ACC-V Analog Multi Criteria Detector Photo Electric & Heat Detector
YBN-NSA-4 4” Base for Analog Sensors
HSB-NSA-6 6” Base for Analog Sensors
SCI-B4 4” Short Circuit Base for Analog Sensors
SCI-B6 6” Short Circuit Base for Analog Sensors
DH98-A Analog Duct Smoke Detector
DH98-AR Analog Duct Smoke Detector w/Relay
DH99-A Analog Duct Smoke Detector
DH99-AR Analog Duct Smoke Detector w/Relay
8
FireNET 4127 I & O Manual v2.03UL
MS-RA, MS-RA/R, MS-
Remote Test Station for DH98A & DH98AR
KA/R
FRCME-4 Input Module 4” Box Mount
FRCME-S Mini Input Module w/ Terminal Block
FRCME-P Mini Input Module w/Pigtail Leads
FRCME-M Mini Input Module w/ Terminal Block
FRCMA, FRCMA-I Class A Input Module 4” Box Mount (FRCMA-I has built-in SCI)
SOM, SOM-A, SOM-AI Supervised Output Module
R2ML, R2ML-I Dual Relay Module, 2 amp @ 30VDC (R2ML-I has built-in SCI)
R2M Dual Relay Module
R2MH, R2MH-I Dual Relay Module, 8 amp @ 30VDC (R2MH-I has built-in SCI)
SCI Short Circuit Isolator Module
DIMM Dual Input Monitor Module
CZM Conventional Zone Module
ASB Analog Sounder Base
ASBL Analog Sounder Base – Low Frequency
AMS/KL/LP Addressable Manual Pull-Station
Accessories
TCH-B100-NS Hand-held Programmer
FN-ACC Battery/Accessory Enclosure (houses up to 33AH size batteries)
FN-ETR Enclosure Trim Ring for Panel Flush Mount
9
FireNET 4127 I & O Manual v2.03UL