DESIGN OF A CANTILEVER WA
this color shows the data entry cell
DATA
bearing capacity 4.2 ksf
Fc' 3 ksi
Fy 60 ksi
wall height 4.1 f
µ 0.55
γ 110 lb/f3
ϕ 30 0.524 rad
γconcrete 150 lb/f 3
DIMENSION OF WALL
wall height 4.1 f
base width 9.8 f 3000 mm
toe width 2.2 f 675 mm
heel width 6.8 f 2075 mm
stem thickness 0.8 f 250 mm
base thickness 2.5 f 760 mm
ACTIVE COEEFFICIENT
Ka 0.333
PRESSURE
P 148.867 lb/f2
FOR LATERAL SOIL PRESSURE
P1 0.302 Kips
MOMENT
Mot 0.409 kips-f
TYPE LOAD (lb/ft) X(A) ft MOMENT(A)
W1 (stem) 192.7364235 2.624672 505.869894115
W2 (foundation 3681.257598 4.92126 18116.4257673
load
W3 (soil load) 1173.122364 6.4386485 7553.32255129
ƩW ƩM
5047.116386 26175.6182127
SLIDING:
FOS 9.186 WALL DESIGN IS SAFE
OVERTURNING MOMENT
FOS 64.003 WALL DESIGN IS SAFE
BEARING CAPACITY
X 5.105220449 f
CHECK FOR PURE COMPRESSION
B/2 4.92126
B/6 1.64042
eccetricity -0.183960449 < B/6
PURE
COMPRESSION
Pmax 0.455
Pmin 0.570
Pmax <
CANTILEVER WALL
0.82
W3
W1
4.06
2.21 6.81
W2 2.49
9.84
Pmin
Pmax 0.570 ksf
0.455
ksf
ksf
ksf
bearing capacity WALL DESIGN IS SAFE
STEM DESIGN:
0.82021
1.566562 W1 W1
2.214567
2.493438 W2
from check sheet 9.84252
Ka 0.333333
Pa 148.8667 lb/f at base of footing PMAX
0.455282
max Pa for stem
Pa 57.44059 lb/f
lateral pressure
Ha 0.044992 kips
shear force
Vu 0.071987 kips
check for one way shear
ΦVc 40.87555 Kips > 0.071987 kips
the section is adequate in one way shear
MOMENT
Ma 0.023494 kip-f
factored moment
Mu 0.037591 kip-f
for As
on solvinig quadratic equation for As
a 0.052941
b -1615.75
c 0.451091
As1 30519.69 in2
As2 0.000279 in2
from table A14 of nadeem hassoun
use #4 bar spaced at 8" (0.29 in2)
Vc
2.214567
DESIGN OF TOE:
2.493438
Critical section exist at a distance "d" from the face of stem
d= 26.92126 in
at "d" the soil pressure would become 0.455282
p= 0.454945 ksf
Vsoil
for Vc
Vc -0.00433 kips
for Vsoil
Vsoil -0.0131 kips
for factored shear
Vu -0.0088 kips
DESIGN STRENGTH
ΦVc 31.85002 kips > -0.0088 kips
the section is adequate and no shear r/f is required
MOMENT
Mc -0.0048 kip-f
Ms 1.116145 kip-f
FACTORED MOMENT
MU 1.78871 kip-f
for As
a 0.052941
b -1453.75
c 21.46452
As1 27459.67 in2
As2 0.014765 in2
use As= 0.014765 in2
from table A14 of nadeem hassoun
use #3 spaced at 6.5" (0.20 in2)
Vsoil
VC
DESIGN OF HEEL: 5
For Vc
VC 0.75 kips
For Vsoil pressure
Vsoil pressure 6.00275 kips
1.5261
For Vsoil Vsoil pressure
Vsoil 0.861609 kips
For factored shear
Vu -2.52363 kips
DESIGN STRENGTH
ΦVc 6.83052 kips > -2.52363 kips
the section is adequate
MOMENT
MC 1.875 k-f
Msoil 2.154022 k-f
Msoil pressure 13.65042 k-f
FACTORED MOMENT
MU -5.2239 k-f
for As
a 0.635294
b -270
c -62.6868
As1 425.232 in2
As2 -0.23205 in2
use As= -0.23205 in2
from table A14 of nadeem hassoun
use #6 spaced at 7.5" (0.71 in2)
4.06
6.807743
W2
9.84252
Pmin
0.570292
26.92126 in
0.481159 ksf
0.454945 ksf
5
0.875