0 ratings0% found this document useful (0 votes) 38 views9 pagesCode Req6
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
318 SEISMIC DESIGN OF REINFORCED-CONCRETE STRUCTURES,
walls and openings in walls equal to twice the
‘cross-sectional area of the minimum shear reinforce
‘ment required per lineal foot of wall.
(b) Shear strength of walls (and diaphragms): For walls
with a height-to-width ratio Ay/l, > 2.0, the shear
strength is to be determined using the expression:
a= GA 20K + Poly)
where
= 0.60, unless the nominal shear strength
provided exceeds the shear correspond-
Ing to development of nominal flexural
capacity of the wall
Aq, = net area as defined earlier
iy = height of entire wall or of segment of
wall considered
width of wall (or segment of wall) in
direction of shear force
For walls with y/ly < 2.0, the shear may be deter-
mined from
y= On al + Pof,)
where the coelicent a, varies linearly from a value
OF 30 For hy/ly = 130 20 for he/ly = 20.
Where a Wallis divided into several segments by
‘opening, the value of the ratio h,/Ly to Be used in
aleulating V, for any segment i hott be less than
the corresponding ratio forthe eaie wal
"The nominal shear strength V, of all wall sg-
rents or pies resting a common lateral force is
not to exceed 84." where A i the total ross
sectional area of the walls. The nominal shear
Strength of uny individual segment of wall or pit is
iff where A, is the crosssee-
tional area of the per considered
(©) Development length and splices: All continuous re-
inforeement is to be anchored or spiced in accor-
ance with provisions governing reinforcement in
tension, as dscused for flexural members
Where boundary elements are present, the tran:
verse reinforcement in wall is to be anchored within
the confined core of the boundary element to de-
velop the yield stress in tension of the transverse
reinforcement.
SEAOC-86 (UBC-88) further requires that splices
in transverse reinforement be siaggered in bars of
the same layer as well ax with respect to adjacent
bars in another layer, where two curtains oF ein-
forcement are used.
For sheaf walls with minimum edge reinforce
ment, both NEHRP-SS and SEAOC-86 (UBC-88)
require that transverse reinforcement terminating at
the edges of the walls be provided with standard
hooks enclosing the edge reinforcement. Otherwise,
the edge reinforcement is 10 be enclosed in U-stir-
rups of the same size and spacing as the transverse
reinforcement.
(4) Boundary elements: Boundary elements are to be
provided, both along the vertical boundaries of walls
8nd around the edges of openings, if any, when the
maximum extremecfber stress in the wall due to
factored forces including earthquake effects exceeds
0.2f/. The boundary members may be discontinued
‘when the calculated compressive stress becomes less
than 0415/2
Boundary elements need not be provided if the
entire wall is reinforced in accordance with the
Provisions governing transverse reinforcement for
members subjected to axial load and bending, as
given by Equations 9-6 and 9-7
Boundary elements of structural walls are to be
designed to carry all the factored vertical loads on
the wall, including self-weight and gravity loads
tributary to the wall, as well as the vertical forces
required to resist the overturning moment due to
factored earthquake loads. Such boundary elements
are to be provided with confinement reinforcement
in accordance with Equations 9-6 and 8-7.
Discussion:
(a) The use of two curtains of reinforcement in walls
subjected to significant shears (ie, > 24,)/f")
serves to reduce fragmentation and premature dete-
Floration of the concrete under load reversals into
the inelastic range. Distributing the reinforcement
uniformly across the height and width of the wall
helps control the width of inclined cracks.
(b) ACI Appendix A allows calculation of the shear
strength of structural walls using a coeficient a, =
20. However, advantage can be taken of the greater
“observed shear strength of walls with low height-to-
width ratios Ay/l, by using an a, value of up to
30 for walls with h,/ly = 15 oF less.
‘The upper bound’ on’ the average nominal shear
stress that may be developed in any individual
segment of wall (10/f") is intended to limit the
degree of shear redistribution among, several con-
nected wall segments. A wall segment refers to a
part of a wall bounded by openings or by an open-
ing and an edge.
It is important to note that Section A231 of
ACI Appendix A requires the use of a strength-
reduction factor $ for shear of 0.6 for all members
(except joints) where the nominal shear strength is
less than the shear corresponding to the develop-
‘ment of the nominal flexural strength of the mem-
ber. In the case of beams, the design shears are
obtained by assuming plastic end moments corre-
sponding to a tensile steel stress of 1.25f, (see
Figure 9-15). Similarly, for a column the design
shears are determined not by applying load factors
to shears obtained from a lateral load analysis, but
from consideration of the maximum developablemoments at the column ends consistent with the
axial force on the column, This approach to shear
design is intended to insure that even when flexural
hhinging occurs at member ends due to earthquake-
induced deformations, no shear failure would de-
velop. Under the above conditions, ACI Appendix
A allows the use of the normal strength-reduction
factor for shear of 0.85. When design shears are not
based on the condition of flexural strength being,
developed at member ends, the code requires the
use of a lower shear strength-reduction factor to
achieve the same result, that is, prevention of pre-
‘mature shear failure
‘As pointed out earlier, in the case of multistory
structural walls, a condition similar to that used for
the shear design of beams and columns is not so
readily established. This is so primarily because the
magnitude of the shear at the base of a (vertical
cantilever) wall, or at any level above, is influenced
significantly by the forces and deformations beyond
the particular level considered. Unlike the flexural
behavior of beams and columns in a frame, which
can be considered as close-coupled systems (i.e,
‘with the forces in the members determined by the
forces and displacements within and at the ends of
the member), the state of flexural deformation at
any section of a structural wall (a far-coupled sys-
tem) is influenced significantly by the displacements
Cf points far removed from the section considered.
Results of dynamic inelastic analyses of isolated
structural walls under earthquake excitation”? also
indicate that the base shear in such walls is strongly
influenced by the higher modes of response.
‘A distribution of static lateral forces along the
hheight of the wall essentially corresponding to the
fundamental mode response, such as is assumed by
‘most codes," will produce flexural yielding at the
base if the section at the base is designed for such a
set of forces. Other distributions of lateral forces,
‘with a resultant acting closer to the base of the wall,
ccan produce yielding at the base only if the magni-
tude of the resultant horizontal force, and hence the
base shear, is increased, Results of the study of
isolated walls referred to above, which would
also apply to frame-shear-wall systems in which the
frame is flexible relative to the wall, in fact indicate
that for a wide range of wall properties and input
‘motion characteristics, the resultant of the dynamic
horizontal forces producing yielding at the base of
the wall generally occurs well below the tworthirds-
of-total-height level associated with the fundamen-
tal-mode response (see Figure 9-23). This would
imply significantly larger base shears than those due
to lateral forces distributed according to the funda-
‘mental mode response. The study of isolated walls
‘mentioned above indicates ratios of maximum dy-
namic shears to “fundamental-mode shears” (i.e.
shears associated with horizontal forces distributed
according to the fundamental-mode response, as
(CODE PROVISIONS FOR EARTHQUAKE-RESISTANT DESIGN 397.
used in codes) ranging from 1.3 to 40, the valve
the ratio increasing with increasing fundamental
period (see Figure 9-22).
(©) Since multistory structural walls behave essentially
as vertical cantilever beams, the horizontal trans
verse reinforcement is called upon to act as web
reinforcement. As such, these bars have to be fully
anchored in the boundary elements, using standard
90° hooks whenever possible
(@) ACI Appendix A uses an extreme-fiber compressive
stress of 0.2/’, calculated using a linearly elastic
‘model based on gross sections of structural mem-
bers and factored forces, as indicative of significant
compression, Structural walls subjected to compres-
sive stresses exceeding this value are generally re-
‘quired to have boundary elements
Figure 9-43 illustrates the condition assumed as
basis for requiring that boundary elements of walls.
be designed for all the gravity loads (W7) as well as
the vertical forces associated with overturning of the
wall due to earthquake forces (#1). This require
ment assumes that the boundary element alone may
hhave to carry all the vertical (compressive) forces at
the critical wall section when the maximum horizon-
tal earthquake force acts on the wall. Under load
reversals, such a loading condition imposes severe
‘demands on the conerete in the boundary elements.
Hence the requirement for confinement reinforce-
‘ment similar to those for frame members subjected
to axial load and bending.
Diaphragms of reinforced concrete, such as floor slabs,
that are called upon to transmit’ horizontal forces
through bending and shear in their own plane, are
treated in much the same manner as structural walls.
6. Frame members not forming part of lateral-force-
resisting system. Frame members that are not relied on
Swi2 Has
Wy &
Figure 8-48 Loading condition assumed for design of boundary
‘alements of stuctural walls,318 SEISMIC DESIGN OF REINFORCED-CONGRETE STRUCTURES
to resist carthquake-induced forces need not satisfy the
stringent requirements. governing lateral-load-resisting
clements. These relate particularly to the transverse
reinforcement requirements for confinement and shear.
Non-lateral-load-resisting elements, whose primary
function is the transmission of vertical loads to the
foundation, need comply only with the reinforcement
requirements of ACI Appendix A, in addition to those
found in the main body of the code.
A special requirement for non-lateral-load-resisting
clements is that they be checked for adequacy with
respect to a lateral displacement representing the ex
ppected actual displacement of the structure under the
‘design earthquake. For the purpose of this check, ACI
‘Appendix A uses a value of twice the displacement
calculated under the factored lateral loads, or 2 X 1.7
= 344 times the displacement due to the code-specitied
loads. UBC.85 specifies a lateral displacement equal to
3/K times the displacement due to the code forces (K
is the horizontal force factor that enters the expression
for the design base shear V). With K varying from 0.67
to 2.0, the factor 3/K takes on values ranging from 4.5
to 1.5, NEHRP-85 calls for checking non-lateral-load-
resisting elements using a lateral displacement equal to
Cy (the deflection amplification factor) times the dis-
placement calculated under the code-prescribed forces.
For concrete structures in regions of high seismicity, C,
varies from 4 to 6.5, depending on the type of structure.
‘The corresponding’ value in SEAOC-86 (UBC-88) is
3R,/8 (Ry, is a coefficient analogous to 1/K in UBC-
85)'times the displacements due to the code-specified
lateral forces. For regions of high seismicity, R, varies
from 6 to 12, depending on the type of structure. Thus,
the factor 3R,,/8 ranges from 2.25 to 4.5. These factors
reflect the maximum displacements that may be ex
pected under a major earthquake which are generally
larger than those produced by the code-specified
“equivalent lateral forces.” Under this requirement, the
gravity-load system should be capable of maintaining
its vertical-load-carrying capacity, without reduction,
lunder the specified lateral displacement. Where plastic
hhinging can occur under the specified displacement,
confinement reinforcement complying with Equation
9-6 or 9-7 has to be provided. These elements, however,
are not required to be designed for the moments associ
ated with the lateral forces.
For gravity-load frame members subjected to fac-
tored axial compressive forces exceeding A, f'/10, the
following requirements relating to transverse reinforce-
‘ment have to be satisfied: The maximum tie spacing
(over the length /, from the face of the joint),
X (diameter of smallest
longitudinal bar)
Sp < | 24 tie diameters
‘(least cross-sectional
dimension of column)
where
2 (clear height of column)
1, > | maximum cross-seetional
. dimension of column
18 in
‘The first tie is to be located within a distance of s,/2
from the face of the joint, The maximum tie spacing in
any part of the colun is 25
7. Frames in regions of moderate seismic risk. Al-
though ACI Appendix A does not define “moderate
seismic risk” in terms of a commonly accepted quantita-
measure, it assumes that the probable ground-
‘motion intensity in such regions would be a fraction of
that expected in a high-seismic-risk zone, to which the
major part of Appendix A is addressed. By the above
description, an area of moderate seismic risk would
‘correspond roughly to zone 2 as defined in ANSI-82.°-*
For regions of moderate seismic risk, the provisions for
the design of structural walls given in the main body of
the ACT Code are considered sufficient to provide the
necessary ductility. The requirements in ACI Appendix
AA for structures in moderate-risk areas relate mainly to
frames,
The same axial compressive force (A,f’/10) used to
distinguish flexural members from columns in high-
seismic-risk areas also applies in regions of moderate
seismicity.
(@) Shear design of beams, columns, or two-way slabs
resisting earthquake effects: The magnitude of the
design shear is not to be less than either of the
following:
(1) The sum of the shear associated with the devel-
‘opment of the nominal moment strength at each
restrained end and that due to factored gravity
loads, if any, acting on the member. This is
similar to the corresponding requirement for
high-risk zones and illustrated in Figure 9-15,
except that the stress in the flexural tensile
reinforcement is taken as f, rather than 1.25f,
@) The maximum factored shear corresponding to
the design gravity and earthquake forces, but
with the earthquake forces taken as twice the
value normally specified by codes. Thus, if the
critical load combination consists of dead Toad
(D) + live load (L) + earthquake effects (E))
then the design shear isto be computed from
U = 0.75(1.4D + 1.71 + 2(1.876)]
(b) Detailing requirements for beams: The positive mo-
‘ment strength at the face of a joint must be at least
one-third the negative moment capacity at the same
section. (This compares with one-half for high-
seismic-risk areas.) The moment strength— positive
‘or negative—at any section is to be no less thanDESIGN EXAMPLES — REPRESENTATIVE ELEMENTS OF A 12.STORY FRAME —SHEARSWALL SURONG 338
‘one-fifth the maximum moment strength at either
end of a member. Stirrup spacing requirements are
identical to those for beams in high-seismicerisk
areas.
(©) Detailing requirements for columns: The tie spacing
requirements for columns are identical to those for
‘gravity-load-carrying members, as given above un-
der item 6, with the additional minimum spacing of
Dis
(@) Detailing requirements for two-way slabs without
‘beams: As mentioned earlier, requirements for flat
plates in ACI Appendix A appear only in the sec-
tion relating to areas of moderate seismic risk. This
suggests that ACI Appendix A considers the use of
flat plates as acceptable components of the lateral-
load-resisting system only for areas of moderate
seismicity.
Specific requirements relating to flat-plate and
flatslab reinforcement for frames in moderate-risk
zones are given in ACI Appendix A and illustrated
in the Commentary to the Appendix.
‘$5 DESIGN EXAMPLES — REPRESENTATIVE
ELEMENTS OF A 12-STORY FRAME - SHEAR WALL
A significant part of the damage observed in engineered
aldings during earthquakes has resulted from the ef-
‘ets of major structural discontinuities that were inade-
‘quately provided for. The message here is clear. Unless
‘proper provision is made for the effects of major discon-
nuities in geometry, mass, stiffness, or strength,
‘Fould be prudent on the part of the engineer to avoid
conditions, which are associated with force con-
Load ® Load
Deformation
Usetul
Deformation
(a)
‘centrations and large ductility demands
areas of the structure. Where such
unavoidable or desirable from the archi
aan analysis to obtain estimates of
associated with the discontinuity is
SEAOC-86 (UBC-88) provides guidelines for
design forces in structures with various types of vertical
and plan irregularities.
In addition to discontinuities, major asymmetry, with
Particular regard to the disposition in plan of the lat-
ceral-load-resisting elements, should be avoided when-
ever possible, Such asymmetry, which can result in a
significant eccentricity between the center of stiffness
and the center of mass (and hence of the resultant
inertial force), can produce appreciable torsional forces
in the structure. Torsional effects can be critical for
corner columns or end walls, i¢., elements located far
from the center of stiffness.
Another important point to consider in the prelimi-
nary design of a structure relates to the effectiveness of
the various lateral-load-resisting components, particu-
larly where these differ significantly in deformation ca-
pacity. Efficient use of structural components would
Suggest that the useful range of deformation of the
principal lateral-load-resisting elements in a structure
be of about the same magnitude whenever practicable,
‘This is illustrated in Figure 9-442, which shows
Joad-deformation curves of representative elements (1)
and (2) in a structure. Such a design allows all the
resisting elements to participate in carrying the induced
forces over the entire range of deformation. In Figure
{9-44b, the resisting elements (1) and (2) not only possess
different initial stiffnesses but, more importantly, ex-
hibit different ductilities (not ductility ratios) or defor-
Deformation
(b)
Figure 9-44 Relative deformation capaciy in lateral-loac-resisting elements in structure,$20 SEISMIC DESIGN OF REINFORCED-CONCRETE STRUCTURES
‘mation capacities. In such a case, which is typical of a
frame-shear-wall structure, the design should be aimed.
at insuring that the maximum probable deformation or
lateral displacement under dynamic conditions does not
exceed the deformation capacity A. of element (2); o, if
the maximum expected deformation could exceed A,
then clement (1) should be so designed that it can
support the additional load that may come upon it
when element (2) loses a considerable part of its load-
carrying capacity. It is worth noting that, generally, the
lateral displacements associated with full mobilization
of the ductility of rigid (open) frames are such that
significant nonstructural damage can be expected (un-
less such movement is anticipated and provided for).
‘The need to tie together all the elements making up a
structure or a portion of it that is intended to act as a
unit cannot be overemphasized. This applies to the
superstructure as well as foundation elements. Where
structure is divided into different parts by expansion
joints, as when the various parts differ considerably in
height, plan size, shape, or orientation, a sufficient gap
should be provided between adjacent parts to prevent
their pounding against each other. To avoid pounding
between adjacent buildings or parts of the same build-
ing when vibrating out of phase with each other, a gap
equal to at least six times the sum of the maximum
lateral deflections of the two structures under the design
(code-specified) lateral forces, or the sum of the maxi-
‘mum deflections of the two structures as indicated by a
dynamic analysis, would be desirable,
‘A good basis for the preliminary design of an earth-
quake-resistant building is a structure proportioned to
satisfy the requirements for gravity and wind loads. The
planning and layout of the structure, however, must
bbe undertaken with due consideration of the special
requirements for earthquake-resistant design. ‘Thus,
‘modifications in both configuration and proportions to
anticipate earthquake-related requirements should be
incorporated at the outset into the basic design for
gravity and wind, Essential to the finished design is
particular attention to details that can often mean the
difference between a severely damaged structure and
‘one with only minor, repairable damage.
9.5.2 Example Designs of Elements of @ 12-Story
Frame - Shear Wall Bullding®
The application of the earthquake-resistant design pro-
visions of ANSI A38.1-1982 (ANSI-82)* with re-
spect to design loads and those of Appendix A of ACI
“Reproduced, with minor medications, from Reference 9.75, with
‘permission ftom Van Nostrand Reiold Company.
318-83° relating to proportioning and detailing of
‘members will be illustrated for representative elements
of a 12-story frame-shear wall building located in seis-
mic zone 4. Except for minor variations in local areas,
the division of the United States into different seismic
. 0, 1, 2, 3, and 4), as adopted by ANSI-82
based on ATC 3.06", is very similar to
UBC-85 (or UBC-79, on which most of the
other ANSI-82 seismic-design provisions are based). A
‘number of areas classified under zone 1 in UBC-85 are
shown as located in zone 0 in ANSI-82,
The typical framing plan and section of the structure
considered are shown in Figure 9.45a and b, respec-
tively. The columns and structural walls have constant
cross-sections throughout the height of the building.
The floor beams and slabs also have the same dimen-
sions at all floor levels. Although the dimensions of the
structural elements in this example are within the prac-
tical range, the structure itself is hypothetical and has
bbeen chosen mainly for illustrative purposes. Other per-
28°26" ner coum
27 12F tamer Came
2°12 Sol oe a and J
@
vet | 7 @26°= er ____}
1
a& Hd
o
Figure 9-45 Structure considered in design example, (8) Typ
al floor traming plan. (b) Longtucinal section.DESIGN EXAMPLES — REPRESENTATIVE ELEMENTS OF A 12.STORY FRAME-SHEARAWALL BULDING 321
tinent design data are as follows:
Service loads—vertcal
* Live load:
Basic, 50 Ib/fe?,
Additional average uniform load to allow for
heavier basic load on corridors, 25 Ib/ft?,
Total average live load, 75 Ib/ft2,
* Superimposed dead load:
Average for partitions 20 Ib/ft.
Ceiling and mechanical 10 Ib/ft?,
‘Total average superimposed dead load, 30 lb/ft?
Material properties:
* Concrete:
JE = 4000 Ib/in.?; w= 145 bt?
* Reinforcement:
f= ksi
1. Determination of design lateral forces. On the ba-
‘sis of the given data and the dimensions shown in
Figure 9-45, the weights that may be considered lumped.
‘at a floor level (including that of all elements located
‘between two imaginary parallel planes passing through
‘mid-height of the columns above and below the floor
considered) and the roof were estimated and are listed
in Tables 9-1 and 9-2. The calculation of the base shear
¥, as explained in Chapter 4, for the transverse and
longitudinal directions is shown at the bottom of Tables
9-1 and 9-2. For this example, the importance factor F
and the soil factor S have been assigned values of unity.
‘Note that a value K= 0.8 has been used in the trans-
verse direction where the structure consists of a
frame-shear wall system, while K = 0,67 in the longitu-
dinal direction, where moment-resisting frames make up
the structure.
Calculation of the undamped (elastic) natural periods
of vibration of the structure in the transverse direction,
as shown in Figure 9-46, using the story weights listed
in Table 9-1 and member stifinesses based on gross
concrete sections, yielded a value for the fundamental
period of 1.34 sec (compared 10 a T value of 0.91 see
obtained by the approximate formula given in ANSI-82).
‘The mode shapes and corresponding periods of the first
five modes of vibration of the structure in the transverse
direction are shown in Figure 9-47,
The lateral seismic design forces acting at the floor
levels, resulting from the distribution of the base shear
in each principal direction, are also listed in Tables 9-1
and 9-2. For example, the seismic lateral force F, at the
10th floor level in the transverse direction is given by
(Y= F)w,h, _ (1500 - 96)(124)(2200)
SS 2,144,300
= 179 kips
Fo
Table 8-1 Design Lateral Forces in Transverse (Short Direction (Corresponding to Entire Structure)®
Seismic forces Wind forces,
Fleorlevel Height Storyweight h,, _Lateralforce Slory shear Wind pressure Lateral force Sion shear
Grombare) heft whips fekins Akos EA klps(Average),Ib/R®Hskips TH klpe
12 149 B100.——«st8,000——scos 237 259
(Poot 300 259
1 136 2200 298.000 106 24 505:
496 784
10 14 20073000179, 226 aoa
2 12 2200 246.000 181 a 220 at =
8 100 2200 zao00 ua len 214 467 138
7 e200 183,000 128 bead 206 480 ~_
6 78 2200 167,000 109 1106 198 432 =
5 oe mm oo wl ad 190 a8 bea
4 oo ee om 182 28 og
3 40220080058 to wa 373 at
2 2 on iC) 159 347 a
1 16 005080020 i 144 367 bua
1500 4988
26300 2144300 1500 4908
{Bare seer, v= Z0C3W, ware C= 1/G8/F) m8 T= 00a) YB, m vanmaree acon, p, ~vu8 Hae D>
Yo E.ONOexOan«r¥~ Dea = coseze00) = UTR eo Tabupe Fe OBTTY One SIKICOON oe os,
areentng te uFm2
‘SEIGMIC DESIGN OF REINFORCED-CONCRETE STRUCTURES
Table 9-2. Design Lateral Forces in Longitudinal Direction (Corresponding to Entire Structure)®
‘Seismic forces Wind foes
Floor level Height Sioryweight wh, Lateral force Slory shear Wind pressure Lateral force Story shear
rombase) heft skips ftkips—F,kips EA, Kips (Average), 1B/? Kips TH, Kb
72 1482100 + 208 787 78
(Foo!) 280 78
1" 136 200 + 149 193 183
388 231
10 8 200 + 138 188 149
° 112 00 + 1m = 180 143 =
8 100 2200 + 109 ue 172 136 =
7 300 i 6 = 186 132 a
6 7% 2200 a 8 =I 180 wz a
5 e200 + 0 baal 160 ne oe
4 52 2200 + sr 140 ma Ley
4 «2200 t “ ee 130 103 Uae
a 3 2200 t 30 us ne 94 ve
1 16 2200 + 6 1135; 10.4 93 ian
1180 vase
2600 2144900 1160 rr)
“ir logs recon, 7= Gy. where Gx(oncwa wanes = 0535. T= a0asiab}""— 156 see. = 1/ (inf) = 198/108) = 005. Base sre
Also listed in the tables are the story shears correspond-
ing to the distributed lateral forces
For comparison, the wind forces and story shears
corresponding to basic wind speed of 75 mi/h and
Exposure B (urban and suburban areas), computed as
prescribed in ANSI-82, are shown for each direction in
Tables 9-1 and 9.2,
YL maw crys sre amouty= Gotan = SoS 8) = 146, ny 18D pe = BO7TV = (OGTR GONE) ~ 85 Mom
Lateral-load analyses of the structure along each
principal direction, under the respective seismic and
wind loads, were carried out assuming no torsional
effects. The model shown in Figure 9-45 was used for
the analysis in the transverse direction. This model
consists of three different frames linked by hinged rigid
bars at the floor levels. (This device, which imposes
Tews
(2 Exar Frames
Figure 9-46. Analytical madel fr lateral load analysis of structure in transverse direction.DESIGN EXAMPLES — REPRESENTATIVE ELEMENTS OF A 12-STORY FRAME
a
Relative Dislacement
Figure 9-47 _Undamped natural modes and periods of vibration
‘of structure in transverse direction.
‘equal horizontal displacements at each floor level, is
‘used to model the effect of the floor slabs, which gener-
ally may be assumed as very stiff in their own planes.)
Frame T-1 represents the four identical interior frames
along lines 3, 4, 5, and 6, which have been lumped
fogether in this single frame, while Frame T-2 repre-
sents the two exterior frames along lines 1 and &
‘The third frame, T-3, represents the two identical
frame-shear-wall systems along lines 2 and 7. In the
longitudinal direction, two linked frames, each similar
fo the frame shown in Figure 9-45b, were used to
represent the two identical exterior frames L-I along
fines a and d and the two identical frames L-2 along
‘ines b and c (see Figure 9-46)
The lateral displacements due to both seismic and
‘sind forces listed in Tables 9-1 and 9-2 are shown
Longitudinal
‘Wind Lose
O02 a 6 BWI 1a 18 18 202228
Lateral Displacement (in)
Figure 9-48 Lateral displacements under seismic and wing
loads.
plotted in Figure 9-48. Although the seismic forces used
to obtain the curves of Figure 9-48 are approximate, the
results shown still serve to draw the distinetion between
wind and seismic forces, that is, the fact that the former
are external forces the magnitudes of which are propor-
tional to the exposed surface, while the latter represent
inertial forces depending primarily on the mass and
stiffness. properties of the structure. Thus, while the
ratio of the total wind force in the transverse direction
Table 9-3 Distribution of Horizontal Selsmic Story Shears among the Three Transverse
Frames Shown in Figure 9-46
Frame 7-3
Frame T-1 Frame T-2 interior
(exterior Leth
‘trames) a
Story ‘Story Sot shear,
level shear total Kips
12 163 ot 300
" 115 2 496
10 297 “a 129 19 ers
9 306 36 133 16 836
a a6 2 138 14 980
7 321 29 40 13 1106
6 39 26 140 2 1215
5 307 24 134 10 1307
4 285 a 28 8 1382
3 202 7 105 7 1440
a 205 14 a8 6 1480
1 48 7 2 1 1500324 SEISMIC DESIGN OF REINFORCED-CONCRETE STRUCTURES
to that in the longitudinal direction (see Tables 9-1 and
9-2) is about 3.5, the corresponding ratio forthe seismic
forces is only 1.3. As a result of this and the smaller
lateral stiffness of the structure in the longitudinal direc-
tion, the displacement due to seismic forces in the
longitudinal direction is significantly greater than that
in the transverse direction. By comparison, the displace-
ments due to wind are about the same for both direc-
tions. The typical deflected shapes associated with pre-
dominantly cantilever or flexure structures (as in. the
transverse direction) and shear (open-frame) buildings
(as in the longitudinal direction) are evident in Figure
9-48, The average deflection indices, that i, the ratios of
the lateral displacement at the top to the total height of
the structure, are zh; for wind and 7; for seismic
loads in the transverse direction. The corresponding
values in the longitudinal direction are =f for wind
and 5 for seismic loads.
‘An idea of the distribution of lateral loads among the
different frames making up the structure in the trans-
verse direction may be obtained from Table 9-3, which
lists the portion of the total story shear at each level
resisted by each of the three lumped frames. Note that
atthe top (12th floor level), the lumped frame T-1 takes
121% of the total story shear. This reflects the fact that
in frame-shear-wall systems of average proportions,
interaction between frame and wall under lateral loads
results in the frame “supporting” the wall at the top,
while at the base most of the horizontal shear is resisted
by the wall. Table 5-3 indicates that for the structure
Table $-4 Summary of Design Moments for Typical Beams on Sixth Floor of Interior Transverse
Frames along Lines 3 through 6 (Figure 9-46)
ou [raps im (o20)
Cte ue [otetatinstee) oa
aps eae (or)
Beam AB
Deion moment pe
Tear apa
™ ora 2
oa 6 —
on
Snowy ont 28 =
nena +70 a
oe
Seevey ot a0
Sideonay tole we
Design moment pe
3 wi-sen z
oa “9 a
oe
‘Seenay'o ht +00
Seon tt +60 7
exe
See ht + -27
Siena let ”