0% found this document useful (0 votes)
125 views5 pages

Structured Cabling Specifications

This document provides guidelines for contractors installing structured cabling systems at the University of Cape Town. It outlines mandatory requirements for acceptance of cabling work, including contractor certification. The cabling must be Category 6 and tested according to specifications. Installation must follow best practices for pulling, terminating, and labeling cable. Ducting and cable supports are also specified. The project will be completed and signed off in five phases.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
125 views5 pages

Structured Cabling Specifications

This document provides guidelines for contractors installing structured cabling systems at the University of Cape Town. It outlines mandatory requirements for acceptance of cabling work, including contractor certification. The cabling must be Category 6 and tested according to specifications. Installation must follow best practices for pulling, terminating, and labeling cable. Ducting and cable supports are also specified. The project will be completed and signed off in five phases.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

GENERIC PREMISE STRUCTURED CABLING REQUIREMENTS GUIDELINE

FOREWORD

The University of Cape Town Structured Cabling guideline, as outlined in the pages to follow, is mandatory in
terms of the acceptance of work done in or on University premises and facilities. Compliance therefore
determines whether or not the University will take acceptance of installed Structured Cabling Systems (SCS) or
subsystems.

The contractor is to note that despite the Structured Cabling System’s vendor warranty requirements (which
must be met), work done has been commissioned by the University of Cape Town and as owners of the
supplied Structured Cabling System, it is expected that the Requirements and Technical directives of the
University take precedence at all times.

The acceptance requirements as outlined in this document are mandatory. No variation will be tolerated nor
accepted.

DOCUMENT SCOPE

This document is intended as a guideline and therefore does not supersede the International Standards on
which it is based. The purpose of the document is to provide the contractor with information specific to the
implementation of Standards based generic structured cabling as per the requirements of the University
Network environment and the support/maintenance thereof.

CONTRACTOR REQUIREMENTS

1. The contractor shall be certified by the Structured Cabling Vendor in order that the final installation be
certified in accordance with the Vendors warranty requirements.

2. The contractor shall provide only skilled labour to complete work within the agreed upon time frame.

3. The contractor is responsible for the provision of all tools required to fulfil his installation obligations in
accordance with task at hand at his cost. This includes specialist tools such as core drills etc.

4. By means of the submittal of a quotation and the acceptance of the relevant order number, the contractor
is solely responsible for the successful delivery of all documentation pertaining to installed components
e.g. Floor plans, excel sheets and test results to the University ICTS Networks staff member responsible
for the project and NO OTHER person, unless such an agreement has been made with the
aforementioned responsible person.

5. In the event that work has been commissioned by University departments other than ICTS Networks,
contractors are reminded that the technical requirements of ICTS Networks still apply and that contractors
will be required to conform irrespective of whether other Departments or their representatives have
accepted work as completed.

6. The contractor is solely responsible for the thorough pre-quotation inspection and installation evaluation
of any given project for which a quotation is submitted. Any over-sites on the part of the contractor are for
his account.

Page 1 of 5
University of Cape Town
Integrated Data Communications Cabling System
GENERIC PREMISE STRUCTURED CABLING REQUIREMENTS GUIDELINE

100 OHM UTP STRUCTURED CABLING SYSTEMS (SCS)

GENERAL PRODUCT CONFORMANCE REQUIREMENTS

1. The minimum acceptable cable performance category to be installed on University premises shall be
ANSI/TIA/EIA-568-B Category 6 / ISO 11801 Class E (2002) compliant.
2. Only cable and connecting hardware specified for a given Vendor Structured Cabling Solution shall be
used.
3. All installed components shall be new, complete, in good condition and unused albeit for demonstration
purposes.
4. All cable reels are to be visually inspected for damage incurred during shipping and transit prior to
installation.
5. Cable and connecting components found to be damaged or defective prior and during the installation
process are to be removed immediately and returned to the supplier at no additional cost to the
University.

GENERAL PRODUCT PERFORMANCE REQUIREMENTS

The supplied product shall, once installed, conform to ISO 11801 Class E – 2002 electrical characteristics for
the purposes of Vendor warranty.

It is expected that installed products be capable of supporting voice and data communications applications and
protocols from baseline 56Kbps to ISDN PRI for Analog and Digital Voice and 10Base T to 1000 Base T for data
as per the supported applications of ISO 11801 Class E (2002).

The project will be completed and signed off in 5 different phases by the Contractor and UCT ICTS
Project Manager:

Phase 1: Ducting and Supporting structures:


Remove old Metal 3 compartment trunking and replace with new PVC 2 compartment White
Execuduct or similar.
Phase 2: Cat6 Data cable Installation:
The new cable will be pulled into the outlets and terminated at the floor outlet and Netframe sides.
Phase 3: Testing and Labeling:
All outlets will be tested and labeled as per specifications in this tender document.
Phase 4: Warranties:
All test results and floor plans will be submitted to Panduit (South Africa) for Warranty purposes.
The contractor must hand over a signed letter confirming that this has been done to the UCT ICTS
Project Manager.
Phase 5: Final Handover:
The contractor will hand over all documentation, including, updated floor plans (as installed), test
results and installation warranties (Panduit and contractor) to the UCT ICTS Project Manager, who will
then sign off the installation.

GENERAL INSTALLATION PRACTICE REQUIREMENTS

1. Cable is not to be pulled in under excessive load. At all times during any given “pull”, the cable under load
should easily react and feed to pulling tension.

2. Cable being pulled in should be handled by no less than 2 individuals at all times in order to avoid
damage to the cable by means of kinks, twisting along its own axis, getting snagged etc. It is
recommended that 3 installers co-operate in the pulling in of any given cable run, 1 on each end and
another in the middle or positioned near any obstructions to feed slack and thus avoid undue stress on
the cable.

3. Whenever possible cable should be placed into pathways as apposed to pulled in under tension.
Page 2 of 5
University of Cape Town
Integrated Data Communications Cabling System
GENERIC PREMISE STRUCTURED CABLING REQUIREMENTS GUIDELINE

4. Care should be taken not to score conductors during the removal of the outer insulating sleeve of the
cable when preparing to terminate pairs.

5. Cable bends are to be kept to 25mm at minimum at all times (installed).

6. During the installation process, installers are required to visually inspect cable and connecting hardware
components for damage. If such damage is found, e.g. tears in the outer jacket of the cable, severe kinks
as identified by white/grey bands of discoloration on cable jacket, these components are to be replaced
immediately.

7. The installer is to make use of best practices when handling unjacketed conductors. Care is to be taken
as not to create pair spread, pair wrapping, pair separation and the re-twisting of pairs.

8. No more than 13mm of wire may be exposed for the purposes of termination, the only acceptable
exception being Highband modules where such practices are dictated by the design of the module.

9. All cabling shall be clearly labelled at both ends to the rear of the point of termination no more than
100mm from such a termination point.

10. All patch panel ports and workstation outlets shall be clearly labelled by means of appropriately secured
printed labels (hand written labels are not acceptable).

11. All patch and workstation outlet cables shall be clearly labelled by means of an appropriately secured
printed label.

12. All labelling schemes shall be confirmed with the appropriate representative of ICTS Networks before
being applied.

13. The maximum number of screws or bolts as provided for by the design of connecting hardware or SCS
components and accessories are to be used without exception.

DUCTING AND SUPPORTING STRUCTURES

1. Where support structures are used, such structures are to provide support at a maximum of 1.5 meters
along the length of the run as to avoid cable tension as a result of the cumulative weight of such cable
acting upon itself at the next point of support.

2. The surface of such support structures e.g. Cable hangers will not pose a risk of damaging cable due to
sharp edges or angular surfaces which would act against the symmetry of wire pairs within the cable or a
risk to installers e.g. Cuts.

3. Where cable ties are used, they are to be securely fastened but still permit for cable movement if tugged
upon making use of reasonable force.

4. Cable ties are to be used at set intervals of 300mm for all cable bundles thus presenting a uniform
appearance.

5. Under no circumstances shall any cable/s hang unsupported, vertical runs are to be supported are no
greater than 300mm intervals.

6. When cable ties are cut; once appropriately fastened around cable bundles, in order to remove
protrusions beyond the buckle, the installer will ensure that such a cut is clean and that no sharp edges
are created which would damage other cable being pulled past it or injure installers and support staff.

Page 3 of 5
University of Cape Town
Integrated Data Communications Cabling System
GENERIC PREMISE STRUCTURED CABLING REQUIREMENTS GUIDELINE

7. Cable shall under no circumstances be strapped to PVC electrical conduit or any structures belonging to
an unrelated functional unit such as an air conditioning drain pipe as future maintenance by associated
maintenance staff may result in damage or removal in order to facilitate work.

8. Where purpose-installed conduits are to be used for structured cabling, such conduits may never be filled
beyond 40% of capacity and should bend at a radius of no less than 6 times the outside diameter of such
conduit, nor shall more than two 90 degree bends along the total span of such a conduit.

9. Cable is at no point to be placed directly on top of suspended ceiling tiles.

10. Contractors are to ensure that cable is not installed in areas such as roof spaces or in direct sunlight
where temperature ranges might exceed the manufactures operating temperate specifications (typically
not in spaces where temperatures exceed 60 degrees Celsius.)

11. All metallic support structures, be it conduit, ducting or trays, shall be grounded in accordance with
national electric regulations.

12. Ducting systems shall be securely fastened to walls by means of the appropriate fixing hardware so as to
ensure a sound and durable installation.

13. Ducting system covers are to be fitted securely and any portion of the ducting system found to be cracked
or damaged is to be immediately replaced.

POWER AND EMI SOURCE SEPARATION

1. Cable may be laid adjacent to sources of interference such as 240V electrical branch circuits with a
minimum separation of 50.8mm where:
a. A continuous grounded metallic barrier exists between electric cable and structured cabling.

b. A durable non-metallic insulation exists, other than the insulation material of the cable.

2. At no point may data cabling cross the path of any power or broadband cable, fluorescent lighting unit
(where suspension is used as a means of separation) at an angle less or greater than 90 degrees.

3. The installer is to ensure that electrostatic devices such as photocopiers and sources of radiation such as
x-ray devices, radio transmitters, their antennae and associated broadband cables are to be avoided
when routing cable.

POST-INSTALLATION TEST AND CERTIFICATION

General Requirements

1. Every cabling link is to be tested and must meet with the requirements of ISO 11801 Class E (2002)
across the full length of the link.

2. Test requirements as per Permanent Link certification requirement for which the appropriate test
adapters are to be used.

3. The contractor will ensure that the full plot data is stored for each and every test.

4. The test results shall also be in Fluke Networks Linkware format (.flw).

5. Test results are to be stored and provided to ICTS Networks staff in electronic format in .csv and .flw file
formats.

Page 4 of 5
University of Cape Town
Integrated Data Communications Cabling System
GENERIC PREMISE STRUCTURED CABLING REQUIREMENTS GUIDELINE

6. Only Fluke DSP 4000 series testers will be used to certify University SCS’s or their subcomponents
running the current firmware revision ver 5.12.

7. The test equipment is to be well maintained and in good working order. ICTS Networks staff reserve the
right to insist on an annual factory calibration certificate for the instrument to be used for testing.

8. ICTS Networks staff further reserve the right to insist on being present during the self-calibration of the
test unit and the instruments initial configuration prior to test and during the test process itself.

9. The contractor is to advise ICTS Networks staff within 3 working days of intent to commence testing in
order that such a staff member may make himself available to attend testing procedures.

10. The contractor is required to make available the test equipment and necessary personnel at no extra cost
should a member of ICTS Networks wish to perform random acceptance testing on approximately 10% of
the installed cabling infrastructure.

11. ICTS Networks staff reserves the right to decline acceptance of marginal performing cables irrespective
of their having passed testing based on risk of future degradation over the life span of the installed
product.

12. Where it is found that the random tests do not match those presented, ICTS Networks staff reserves the
right to insist on a supervised re-test of any or all installed cables prior to acceptance.

13. It is the sole responsibility of the contractor to ensure that the appropriate Vendor test and documentation
requirements are met in order that ICTS Networks be provided with a warranty certificate issued by the
SCS Vendor.

14. Any contention regarding Vendor warranty requirements is to be resolved between the Vendor and the
contractor and has thus no bearing on the University’s requirements as outlined here.

15. Documentation is to be provided in 3 parts:


a. An excel sheet indicating cable label, location of work area and Telecommunications closet
termination points etc in electronic format.
b. Detailed test results in .flw (Fluke Networks Linkware) format inclusive of all plot data.
c. A floor plan or site diagram reflecting the routes taken to and location of all installed cables in
electronic format.

Page 5 of 5

You might also like