Single Line Diagram-Layout1

The document summarizes the specifications and wiring details of a new 480V panel located in an EE room. It has a 125A main breaker feeding six circuits, with the first two circuits supplying welding machine outlets at tracks 4 and 5 rated for 100A each, and the remaining circuits supplying screw jack outlets or marked as spares at 50A each. The panel has a NEMA 2 enclosure, is wall mounted, and has a minimum short circuit rating of 10kA.

Uploaded by

Lesther Sosa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
403 views1 page

Single Line Diagram-Layout1

The document summarizes the specifications and wiring details of a new 480V panel located in an EE room. It has a 125A main breaker feeding six circuits, with the first two circuits supplying welding machine outlets at tracks 4 and 5 rated for 100A each, and the remaining circuits supplying screw jack outlets or marked as spares at 50A each. The panel has a NEMA 2 enclosure, is wall mounted, and has a minimum short circuit rating of 10kA.

Uploaded by

Lesther Sosa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

PANEL : NEW PANEL VOLTAGE : 480V ENCLOSURE : NEMA 2

LOCATION : EE ROOM PHASE : 3 MIN.KAIC : 10


FEED : TOP WIRE : 3+G MOUNT : WALL MOUNTED

WIRES
CKT BREAKER CONNECTED LOAD CONDUIT (THHN/THWN)
LOAD DESCRIPTION VA
NO. P AF AT (RSC) LINE GROUND
1 3 100 100 WELDING MACHINE POWER OUTLET @TRACK 4 (2 NOS.) 5760 1920 1920 1920
2 3 100 100 WELDING MACHINE POWER OUTLET @TRACK 5 (2 NOS.) 5760 1920 1920 1920
3 3 50 30 SCREW JACK POWER OUTLET @ TRACK 4 (1 NO.) 2880 960 960 960
4 3 50 30 SCREW JACK POWER OUTLET @ TRACK 5 (1 NO.) 2880 960 960 960
5 3 50 30 SPARE 3000 1000 1000 1000 - - -
6 3 50 30 SPARE 3000 1000 1000 1000 - - -
TOTAL 23280 7760 7760 7760

FEEDER :

MAIN : 125AT, 125AF, 3P, 480V, 60Hz MCCB

TO GLSV
FEEDER NO. 34, 160 A RATING

NEW PANEL

@ EE ROOM
125 AT
125 AF

1 2 3 4 5 6

100 AT 100 AT 30 AT 30 AT 30 AT 30 AT
100 AF 100 AF 50 AF 50 AF 50 AF 50 AF
@ TRACK 4

@ TRACK 5

@ TRACK 4

@ TRACK 5
SCREW JACK POWER OUTLET

SCREW JACK POWER OUTLET

SPARE

SPARE
WELDING MACHINE POWER OUTLET

WELDING MACHINE POWER OUTLET